Experimental Study on Rheological Behavior of Firefighting Foams

1
Tianjin Key Laboratory of Fire Safety Technology, Key Laboratory of Fire Protection Technology for Industry and Public Building of Ministry of Emergency Management, Tianjin Fire Science and Technology Research Institute of MEM, Tianjin 300381, China
2
Jiangsu Suolong Fire Science and Technology Co., Ltd., Taizhou 225753, China
*
Author to whom correspondence should be addressed.
Materials 2025, 18(14), 3236; https://doi.org/10.3390/ma18143236
Submission received: 27 May 2025 / Revised: 25 June 2025 / Accepted: 5 July 2025 / Published: 9 July 2025
(This article belongs to the Section Soft Matter)

Abstract

The rheological behavior of firefighting foam is the basis for analyzing foam flow and foam spreading. This experimental study investigates the complex rheological behavior of rapidly aging firefighting foams, specifically focusing on alcohol-resistant aqueous film-forming foam. The primary objective is to characterize the time-dependent viscoelasticity, yielding, and viscous flow of firefighting foam under controlled shear conditions, addressing the significant challenge posed by its rapid structural evolution (drainage and coarsening) during measurement. Using a cylindrical Couette rheometer, conductivity measurements for the liquid fraction, and microscopy for the bubble size analysis, the study quantifies how foam aging impacts key rheological parameters. The results show that the creep and relaxation response of the firefighting foam in the linear viscoelastic region conforms to the Burgers model. The firefighting foam shows ductile yielding and significant shear thinning, and its flow curve under slow shear can be well represented by the Herschel–Bulkley model. Foam drainage and coarsening have competitive effects on the rheology of the firefighting foam, which results in monotonic and nonmonotonic variations in the rheological response in the linear and nonlinear viscoelastic regions, respectively. The work reveals that established empirical relationships between rheology, liquid fraction, and bubble size for general aqueous foams are inadequate for firefighting foams, highlighting the need for foam-specific constitutive models.

1. Introduction

Firefighting foam is the most common and practicable method for the fire protection of flammable liquids and is widely used in places where flammable liquids are produced, processed, stored, and used [1,2,3], such as oil depots, petrochemical platforms, coal chemical enterprises, and airports. In the case of fire caused by flammable liquid, firefighting foam is applied to the protected area and spreads over the liquid surface to form a foam blanket [4,5]. The foam blanket can resist the radiation of flame to flammable liquid, inhibit flammable liquid evaporation, and block the contact of flammable liquid vapor with air to achieve the purpose of fire control and extinguishing [6]. The driving force of the foam spread is due to differences in the hydrostatic pressure within the firefighting foam, whereas the dominating resisting force is due to viscous friction between the foam blanket and the flammable liquid. The friction resistance is closely related to the non-Newtonian rheological behavior of firefighting foam, and quantifying rheological properties is fundamental for modeling foam spread dynamics [7,8]. Understanding time-dependent rheological behavior is particularly crucial for rapidly aging firefighting foams, as their structural evolution impacts performance in real-world applications.
The applicable scenarios of firefighting foams generated by different foam concentrates vary significantly. Aqueous film-forming foam (AFFF) is widely recognized for its film-forming capability on flammable liquid surfaces and commendable fire suppression efficiency [9,10]. However, due to the environmental hazards posed by perfluorooctane sulfonate (PFOS) and its derivatives [11], the use of AFFF is restricted in environmentally sensitive areas (e.g., ecological reserves, drinking water sources, permanent basic farmland) and faces challenges in formula modification [12,13]. In these sensitive zones, fluoroprotein foam (FP) serves as a viable alternative. When protecting polar flammable liquids, alcohol-resistant foams such as alcohol-resistant aqueous film-forming foam (AFFF/AR) or alcohol-resistant fluoroprotein foam (FP/AR) must be employed [3]. Alcohol-resistant foam concentrates are typically formulated by incorporating high-molecular-weight polysaccharides like xanthan gum into common foam concentrates, or by appropriately increasing the concentration of fluorocarbon surfactants. These modifications can partially mitigate the dehydration effect of polar liquids on firefighting foams, though their selection must still comply with environmental protection regulations. The development of fluorine-free foam concentrate appears to be an emerging trend, though current engineering applications remain limited. A study funded by the National Fire Protection Association reveals substantial variations in the properties of fluorine-free foams currently developed by different manufacturers [14]. In terms of current engineering applications, particularly in China, AFFF and FP foams, including alcohol-resistant variants, dominate in terms of usage proportion, while fluorine-free foams remain predominantly in the research and development phase.
Firefighting foam is aqueous foam, a dispersion of a gas into a surfactant aqueous solution. From a fluid mechanics perspective, aqueous foam behaves as a complex soft material whose stress response incorporates elastic, viscous, and plastic components [15,16]. Aqueous foam exhibits the hallmark of non-Newtonian characteristics including shear-thinning viscosity, yield stress, and viscoelasticity, rendering classical Newtonian fluid mechanics inadequate. A rheological analysis provides the framework to quantify these complex behaviors through constitutive modeling [17]. Since the Nobel Prize winner Pierre-Gilles de Gennes proposed the concept of “soft matter” in 1991, with the development of soft matter rheology, scholars have carried out considerable research on the rheological behavior of aqueous foam. The related research has focused mainly on the mechanism and suppression of aqueous foam wall slip, the experimental methods of aqueous foam rheology, the factors affecting the rheological behavior of aqueous foam, and the development of constitutive models of aqueous foam [18]. At present, the mechanism of aqueous foam sliding on a solid surface has been determined, and methods for restraining wall slip in the rheological measurement of aqueous foam have been developed [19]. On the mesoscopic scale, aqueous foam aging is mainly manifested as follows: the continuous liquid phase flows downward along the bubble gap under the effect of gravity, resulting in a decrease in the local liquid fraction, that is, foam drainage occurs [20,21]; the dispersed gas phase diffuses under the effect of the pressure difference between bubbles, resulting in a decrease in the number of bubbles and an increase in the average bubble size, which is referred to as foam coarsening [22,23]. The non-Newtonian rheological behavior of aqueous foam is closely related to the foam liquid fraction and bubble size [24]. Quantitative relationships between rheological parameters such as the shear modulus, yield stress, and consistency coefficient of aqueous foam and the liquid fraction, bubble size, and liquid surface tension have been established [25,26,27].
However, the existing experimental studies on the rheological behavior of aqueous foam are almost all aimed at foams with relatively stable structures (slow aging process), and relevant models and quantitative relationships have also been established on the basis of these experimental studies. Firefighting foam shows remarkable foam drainage and foam coarsening [28,29]. The quarter drain time of commercially available firefighting foam is usually several minutes, and such rapid structural changes make it difficult to measure rheological properties. According to the literature, in the middle of the last century, scholars attempted to measure the viscosity of firefighting foam. There is no doubt that these studies are groundbreaking, but from the perspective of rheology, these measurement processes have no clear shear conditions and can only measure the viscosity of firefighting foam at a certain moment in the entire life of the foam. Elliott et al. [30] were the first to perform continuous rheological measurements of firefighting foams and measured the yield stress of various firefighting foams. Gardiner et al. [31] built a Poiseuille flow rheometer and analyzed the wall slip of compressed air firefighting foam in a pipe flow. Gao et al. [15] continuously measured the apparent viscosity of 3% aqueous film-forming firefighting foam and tried to correlate the rheological curve of firefighting foam with the liquid fraction. In general, research on the rheological behavior of firefighting foam is not very common.
To enhance the understanding of the rheological behavior of firefighting foam, in the present work, the viscoelasticity, yielding, and viscous flow of firefighting foam were experimentally studied, and the effects of foam aging on rheological behavior were analyzed. In Section 2, the foam concentrate, firefighting foam production and experimental protocol are introduced. In Section 3, the rheological response of firefighting foam under different loading modes is displayed, and the effect of foam aging on the rheological response is analyzed. Finally, the main conclusions are summarized in Section 4.

2. Materials and Methods

2.1. Foam Concentrate and Firefighting Foam Production

An alcohol-resistant aqueous film-forming foam concentrate (3% AFFF/AR) provided by Jiangsu Suolong Fire Science and Technology Co., Ltd. (Taizhou, China) was used as the foaming agent. The foam concentrate contained 25 wt.% cocamidopropyl betaine, 6 wt.% alkyl glycosides, 4 wt.% fluorocarbon surfactants, and 1 wt.% xanthan gum, with a density of 1030 kg/m3 and a pour point of −40 °C. The foam concentrate was mixed with water at a volume ratio of 3:97 to form a foam solution with a surface tension of 18.7 mN/m. Firefighting foam was prepared by whipping air into 110 mL of the above solution using a mixer (HS-U-120W, Zhengzhou Dejing Instrument Equipment Co., Ltd., Zhengzhou, China) equipped with a three-blade propeller for 4 min at 2000 rpm. The expansion ratio of the firefighting foam prepared by this method was approximately 7.2.

2.2. Experimental Protocol

Firefighting foam is subjected to drainage and coarsening once it is generated. To analyze the rheology of firefighting foam quantitatively, it is necessary to measure the liquid fraction and bubble size in addition to the rheological response.
The vertical profile of the local liquid fraction in the firefighting foam was measured by electrical conductivity. A conductivity meter (DDSJ-307F, INESA Scientific Instrument Co., Ltd., Shanghai, China) with a range of 0.001 μS/cm~1000 mS/cm and a resolution of 0.001 μS/cm was used to measure the conductivity of the firefighting foam ψfoam and foam solution ψsolution. By adjusting the electrode position of the conductivity meter and repeating the test, the conductivity of the firefighting foam at different vertical positions was obtained. According to the relationship between the relative conductivity, ψ = ψfoam/ψsolution, and the liquid fraction ϕl of aqueous foam shown in Equation (1) [32], the vertical profile and time evolution of the local liquid fraction in the firefighting foam were estimated.
ϕ l = 3 ψ ( 1 + 11 ψ ) 1 + 25 ψ + 10 ψ 2
The bubble size of the firefighting foam was measured by using optical microscopy. Three autofocusing microscopes (3R-MSBTVTY, 3R Group. 3R SOLUTION Corp., Tokyo, Japan) were used to take photomicrographs of the firefighting foam through the transparent wall of the foam container. The magnification of the microscope could be manually switched between 40×, 100×, 180× and 250×. By adjusting the position of the microscope and repeating the test, photomicrographs of the firefighting foam at different vertical positions were obtained. ImageJ (v1.54f, National Institute of Health, Bethesda, MD, USA), a freely downloadable image analysis software package, was used to statistically analyze firefighting foam photomicrographs, which included the number and Feret diameter of bubbles. The experimental setup for measuring foam conductivity and bubble size is illustrated in Figure 1.
All rheological measurements were performed with a commercial rheometer (MCR92, Anton Paar, Graz, Austria). In previous rheological experiments of aqueous foams, cone-plate, parallel plate, and cylindrical Couette systems have all been successfully used as shear geometries [33]. However, considering the remarkable drainage of firefighting foam, when a cone-plate or parallel plate system is adopted, then the drained liquid accumulates at the bottom plate, which inevitably affects the measurement results. Therefore, the cylindrical Couette system is considered more suitable for rheological measurements of firefighting foam. The B-CC39/P6 inner cylinder (outer diameter of 40 mm, height of 60 mm) was paired with a custom-made outer cylinder (inner diameter of 90 mm, height of 140 mm) fixed with an Anton Paar flexible cup holder to form a cylindrical Couette system. The surfaces of the inner cylinder and outer cylinder were scored to prevent wall slip. Notably, there should be sufficient space between the bottom of the inner cylinder and the bottom of the outer cylinder, 3 cm in the present study, to contain the drained liquid. In other words, the inner cylinders were immersed in firefighting foam throughout the rheological tests.
There exists an inevitable time delay between the completion of firefighting foam preparation and the commencement of measurements. In the present study, this time delay was controlled within 30 s. To standardize experimental conditions, the moment of foam preparation completion was designated as time zero (t = 0 min), with all subsequent measurements being initiated at the 0.5 min mark.

3. Results and Discussion

3.1. Foam Aging

Figure 2 shows the time evolution and vertical profile of the local liquid fraction measured by electrical conductivity in firefighting foam with a height of 11 cm. At t = 0.5 min, the initial local liquid fraction is almost uniform and constant, ϕl,0 ≈ 0.14, which is undoubtedly equal to the reciprocal of the foam expansion ratio. Over time, the liquid drains from the firefighting foam, flows downward, and accumulates at the base of the container. The entire drainage process can be roughly divided into two stages. For approximately t < 10 min, the liquid fraction at the upper part of the foam decreases, the drainage front, referred to as the lower limit of this region, moves downward, and the width of the front increases. The lower part of the foam undergoes steady drainage, with an almost constant liquid fraction. At approximately t > 10 min, the drainage front reaches the bottom of the foam. The foam at different vertical positions continues to drain, becomes drier, and gradually develops toward the equilibrium profile.
In Figure 3, photographs at different vertical positions in the firefighting foam show the shapes and sizes of the bubbles at t = 0.5 min, 4 min, 12 min, and 20 min. All foams at different vertical positions contain wet spherical bubbles at the start of imaging, t = 0.5 min, and over time, the number of these bubbles decreases, and the bubble becomes larger and more polyhedral. In Figure 4, the bubble size distributions at different vertical positions in the firefighting foam become more discrete over time, and the bubble sizes in the upper part of the foam are more discrete than those in the lower part of the foam at a given time. The evolution of bubble size distributions is complex and difficult to quantify, and a common strategy is to analyze the average bubble size. Various average sizes, such as the arithmetic mean radius RA = <r>, the mean square radius Rrms = <r2>1/2, the cubic mean radius Ro = <r3>1/3, and the Sauter mean radius R32 = <r3>/<r2>, have been used in previous studies, but it is still not clear which average method is most appropriate for bubble size statistical analysis [28]. In conjunction with the theoretical analysis of firefighting foam rheology, the time evolution of RA and R32 was calculated, as presented in Table 1, and was used in subsequent foam rheology analysis. RA and R32 of the bubble increased over time, and the mean bubble radius in the upper part of the foam was larger than that in the lower part. R32 was larger than RA, and the ratio R32/RA ≈ 1.3~1.9.

3.2. Viscoelasticity of Firefighting Foam

Figure 5 shows the typical response of the stress amplitude τ0, shear moduli G′ and G″, and loss angle δ of the firefighting foam in the strain amplitude γ0 sweep test. There are three distinct regions: the linear region, transition region, and nonlinear region. In the linear region, the storage modulus G′ is greater than the loss modulus G″, and δ is much smaller than 45°. G′, G″, and δ are almost independent of γ0, and τ0 is proportional to γ0 ( τ 0 γ 0 ). In the nonlinear region, G″ is greater than G′, and δ is greater than 45°. Both G′ and G″ decrease with a power law ( G γ 0 a , G γ 0 b , a > b ), whereas τ0 increases with a power law ( τ 0 γ 0 c , c < 1 ). The transition region is between the linear region and the nonlinear region. In the transition region, G′ decreases monotonically, whereas G″ increases first and then decreases, and the foam yields. The stress amplitude curves in the linear and nonlinear regions are extended, and the intersection point falls in the transition region; that is, the yield point and the corresponding stress and strain are the yield stress τy and yield strain γy, respectively.
To explore the effect of foam aging on viscoelasticity, strain amplitude sweep tests were carried out after the firefighting foam was held for thold = 0.5 min, 4 min, 8 min, 12 min, 16 min, and 20 min. To ensure clarity, only partial test results are shown in Figure 6. An attempt to unify the curves under different holding times onto a single curve by normalizing the coordinate axis of Figure 6a using G′ in the linear region and γy did not succeed. The reason was that foam aging had different effects on the linear region and the nonlinear region. Figure 6 shows that in the linear region, the effect of foam aging is monotonic, and both the shear modulus and stress amplitude decrease with holding time. The time sweep test within the linear viscoelastic region (γ0 = 0.01, f = 1 Hz) shown in Figure 7 also confirms this monotonic aging effect. In the nonlinear region, the power law exponents a, b, and c are almost independent of the holding time thold, where a ≈ 1.1, b ≈ 0.63, and c ≈ 0.35. However, the curves corresponding to thold = 4 min appear at the bottom of the curve cluster, indicating that the effect of foam aging is nonmonotonic. This effect cannot be attributed to test bias, as identical nonmonotonic aging behavior is replicated in the test results of Section 3.4.
Numerous experimental results have shown that, for polydisperse aqueous foam, the variation in the shear modulus in the linear region with the liquid friction ϕl and Sauter mean radius R32 can be well described by the empirical relation shown in Equation (2) [18,27,34]. The applicability of this empirical relation to firefighting foam was examined herein. Notably, the rheological response of the firefighting foam was measured with a cylindrical Couette system with an inner cylinder height of 60 mm in this work. At this height span, the evolutions of ϕl and R32 of the foams are different, as shown in Figure 2 and Table 1. A correlation analysis was conducted between the ϕl and R32 of the foam at z = 3 cm, 5 cm, 7 cm, and 9 cm and the rheological response. In Figure 8, the normalized storage modulus shows good consistency; it is almost independent of the vertical positions of the foam but less than the calculation result of Equation (2). If the factor 1.4 in Equation (2) is changed to 0.2, then, as shown in the trend line in Figure 8, the test results are consistent with the relationship, but this treatment is a complete mathematical fit and lacks physical support.
G = 1.4 ( 1 ϕ l ) ( ϕ l ϕ l ) σ R 32             ( 0.03 < ϕ l < 0.36 )
Creep tests were also carried out to analyze the deformation response of the firefighting foam after loading and unloading stress in the linear region. The loaded creep stress was 0.5 Pa, and both the creep and relaxation processes lasted for 2 min. As shown in Figure 9a, transient deformation and continuous deformation occurred after the firefighting foam was loaded with stress, and a transient rebound, delayed recovery, and residual deformation occurred after unloading. These deformation responses conformed to the Burgers model, whose mechanical analogy and constitutive model are shown in Figure 9b and Equation (3) [35]. The Burgers model’s mechanical analogy comprises a Maxwell element (spring G1 in series with dashpot μ1) connected in series with a Kelvin–Voigt element (spring G2 parallel to dashpot μ2). This configuration captures instantaneous elastic deformation (G1), retarded viscoelastic relaxation (G2 and μ2), and viscous flow (μ1), providing a physically interpretable framework for foam viscoelasticity. The creep curve was used to fit the parameters of the Burgers model, the relaxation curve was predicted by the determined parameters, and both the fitting and prediction results were satisfactory, as shown in Figure 9b. The parameters of the Burgers model for the creep tests of the firefighting foams with different holding times are shown in Table 2, and all the parameters change monotonically.
J = 1 G 1 + 1 G 2 [ 1 e x p ( G 2 μ 2 t ) ] + 1 μ 1 t             ( c r e e p ) J = J + 1 G 2 e x p ( G 2 μ 2 t )             ( r e l a x a t i o n )

3.3. Yielding of the Firefighting Foam

In addition to the strain amplitude sweep tests shown in Figure 6, start-up flow tests and stress sweep tests were also carried out to determine the yield stress and yield strain of the firefighting foams. As shown in Figure 10a, the stress and strain corresponding to the highest point in the start-up flow test are the yield stress and yield strain, provided that the applied shear rate is small enough; it was 0.125 s−1 in this study. The determination of yield stress and yield strain in the stress sweep test also required an extension of the curve, as shown in Figure 10b, just as in the strain amplitude sweep test. The yield stress and yield strain measured by the three methods are shown in Figure 11.
Unlike classic brittle fracture yielding, the yield process of firefighting foam was relatively smooth and involved ductile yielding, as shown in Figure 10b. The results of the three test methods showed that with the foam aging, the yield strain increased monotonically, whereas the yield stress decreased slightly at first and then increased. The difference was that the yield points measured by the start-up flow and stress sweep were similar, whereas the yield stress obtained by the strain amplitude sweep was larger, and its yield strain was smaller. This inconsistency of yield values caused by different test methods, especially those involving oscillatory shear and simple shear, is a common situation in soft-material rheological measurements [36]. Exploring this general problem of rheological measurement was not the objective of this study. Previous studies have shown that the dependence of the yield stress and yield strain measured in the oscillatory mode on the bubble size, surface tension, and liquid fraction in aqueous foams can be described by the following empirical expressions [18]:
τ y = a 1 σ R A ( ϕ l ϕ l ) 2             ( 0.05 < ϕ l < 0.25 )
γ y = a 2 ( ϕ l ϕ l )
where a1 is a constant between 0.2 and 0.5, and a2 is a constant between 0.5 and 1. When combined with Figure 2a, Table 1, and Figure 11, the intermediate variable of time was eliminated, and the dependence of the normalized yield stress and yield strain on the liquid fraction could be obtained, as shown in Figure 12. The variation in the normalized yield stress with the liquid fraction of the firefighting foam seemed to fall on a trend line, which was independent of the vertical position of the firefighting foam. Within the scope of application, that is, 0.05 < ϕl < 0.25, Equation (4) was used to characterize the change in normalized yield stress with the liquid fraction of the firefighting foam, where a1 was approximately 0.38. However, the variation in yield strain with the liquid fraction at different vertical positions in the firefighting foam did not return to a trend line and far exceeded the trend and interval predicted by Equation (5).

3.4. Viscous Flow of Firefighting Foam Under Slow Shear

Viscous flow occurs after the firefighting foam yields. To measure the apparent viscosity of the firefighting foam, shear must be applied. High continuous shear inevitably affects foam drainage and coarsening, and the analysis of this coupling is difficult at present. This study focused on the viscous flow of firefighting foam under slow shear, in which the effect of shear on foam drainage and coarsening is negligible. As shown in Figure 13, continuous and intermittent shear at different constant shear rates led to differences in shear stress evolution over time. It seemed that the shear rate of 8 s−1 was tolerable. The response results of continuous and intermittent shear at shear rates above 16 s−1 were significantly different, especially in the latter part of the shear tests. Therefore, the shear rate of the viscous flow of the firefighting foam in this work was controlled within 8 s−1.
Figure 14 shows the time evolution of the stress response and viscosity of the firefighting foam under constant shear conditions ranging from 0.125 to 8 s−1. Similar to other aqueous foams, the firefighting foam also shows significant shear thinning; that is, the apparent viscosity decreases with the increasing shear rate. Under a constant shear rate, the stress response of the firefighting foam first decreases and then increases over time, and the lowest points of the curve cluster occur at t = 6 min. This nonmonotonic change is the same as the nonmonotonic effect of foam aging on the nonlinear region shown in Figure 6. By extracting the corresponding shear stress under different shear rates at a given time, as shown in Figure 14a, the flow curve of the firefighting foam under different aging times can be obtained. As shown in Figure 15, regardless of the aging time, the flow curves of the firefighting foam conform to the Herschel–Bulkley model shown in Equation (6). The fitting results of the Herschel–Bulkley model shown in Figure 16 reveal that the dynamic yield stress and flow behavior index both increase with the increasing aging time and that the consistency factor decreases, indicating that the firefighting foam becomes more plastic and shear-thinning.
τ = τ y + K γ ˙ n

3.5. Competitive Effects of Foam Drainage and Coarsening on Foam Rheology

Foam drainage and coarsening are the main manifestations of foam aging, which are coupled with each other and play different roles in affecting foam rheology. The decrease in the liquid fraction caused by foam drainage makes the foam stiffer, and the shear modulus increases. The increase in bubble polydispersity and average size caused by foam coarsening results in a decrease in shear modulus. Numerous experimental studies [33,34] and quantitative analyses, such as Equations (2) and (4), have shown the competitive effects of foam drainage and coarsening on the rheological response. Figure 6, Figure 7, and Figure 9 all show that the rheological parameters in the linear viscoelastic region change monotonically with the aging time, and the monotonic decline in the shear modulus indicates that the influence of foam coarsening on the rheological properties in this region is dominant. The variation in yield stress with the aging time almost monotonically increases, as shown in Figure 11, indicating that the influence of foam drainage on rheology appears to be dominant in the transition region. Both oscillatory shear in the nonlinear viscoelastic region (Figure 6) and viscous flow under slow shear (Figure 14) show nonmonotonic changes in rheological response with aging time, which are ultimately caused by the competition between foam drainage and coarsening.

3.6. Limitations and Prospects

Experimental investigations were conducted on the viscoelasticity, yielding, and viscous flow under slow shear of 3% AFFF/AR foam, along with analysis of competitive effects of drainage and coarsening on its rheological behavior. The selection of the 3% AFFF/AR foam as a starting point stems from its composition, which features the most complex surfactant–polysaccharide system among traditional non-fluorinated foam concentrates. Limited data indicate that classical rheological relationships for aqueous foams do not fully apply to 3% AFFF/AR foam. This discrepancy may arise from multiple factors, including the intrinsic complexity of the material and limitations in measurement techniques. As the foam ages, the local liquid fraction and bubble size exhibit top-down inhomogeneity within the foam container. However, rheological measurements inherently capture the average response within a specific region, whereas the local liquid fraction and bubble size are point-specific parameters. The combined effect of regional inhomogeneity and the relationship between local and average values may cause deviations in the constant factors of Equations (2) and (4). Alternatively, the intricate surfactant–polysaccharide composition unique to firefighting foams could be responsible. Furthermore, the qualitative conclusions from this study—such as the time-dependent decay of the local liquid fraction, time-dependent bubble growth, and the competitive influence of drainage and coarsening on rheology—are broadly applicable to other firefighting foams (e.g., fluoroprotein foams, fluorine-free foams). Nevertheless, quantitative differences are expected due to variations in foam formulation chemistry.
While this study and subsequent research on rheological behavior and structural aging focus on fundamental investigations into firefighting foams, foam fire-extinguishing numerical simulation serves as a critical conduit for applying these findings to practical fire suppression scenarios. Once the rheological properties of firefighting foams—and their variations with intrinsic factors (e.g., foam type, surfactants) and extrinsic factors (e.g., foam expansion ratio, thermal exposure)—are quantitatively characterized, they can be integrated into the governing equations of foam spread models. This integration enables the assessment of how rheologically induced changes impact real-world fire suppression, thereby establishing a quantitative framework for optimizing foam formulations. It should be noted, however, that achieving this objective requires extensive additional research.

4. Conclusions

Firefighting foam shows elasto-viscoplastic behavior. Under the oscillatory shear strain amplitude sweep mode, the firefighting foam passes through the linear viscoelastic region, transition region, and nonlinear viscoelastic region in sequence. The creep and relaxation response of firefighting foam in the linear viscoelastic region conforms to the Burgers model. In the transition zone, the foam yields are ductile and different from the classic brittle fracture yield. After entering the nonlinear viscoelastic region, the shear modulus of the firefighting foam changes significantly, and viscous deformation dominates the flow. The flow curve of the firefighting foam under slow shear can be effectively represented by the Herschel–Bulkley model.
Firefighting foam shows remarkable foam drainage and foam coarsening, which play different roles in affecting the foam rheology. Once the firefighting foam is prepared, the foam at different vertical positions continues to drain, becomes drier, the local liquid fraction decreases and gradually develops toward the equilibrium profile. Foam coarsening makes the bubbles more polyhedral, more dispersed, and larger in average size. Foam coarsening dominates the rheological response in the linear viscoelastic region, whereas foam drainage seems to dominate the foam yield change in the transition region. In the nonlinear viscoelastic region or slow shear flow, the competitive effects of foam drainage and coarsening are intense.
Although the experimental samples and data in this work are limited, some existing classical relationships among the rheological parameters, liquid fraction, and bubble size established for aqueous foam are not applicable to firefighting foam. To develop rheological relationships and constitutive models suitable for firefighting foam, a large amount of rheological test data must be accumulated. The present work provides basic protocols for measuring the rheology, drainage, and coarsening of firefighting foam. The effects of potential intrinsic factors—such as concentrate formulation, additive systems, and fluorine substitution—as well as extrinsic factors like expansion ratio and thermal exposure on firefighting foam rheology and aging will be gradually investigated in future work.

Author Contributions

Conceptualization, Y.B., H.Z. and L.W.; Methodology, H.Z. and L.W.; Investigation, Y.F.; Resources, J.W.; Writing—Original Draft, Y.B.; Writing—Review and Editing, Y.B. and H.Z.; Funding Acquisition, Y.B. and H.Z. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the National Natural Science Foundation of China [grant number 12202376] and the Natural Science Foundation of Tianjin [grant numbers 22JCYBJC01700 and 22JCZDJC00830].

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author(s).

Conflicts of Interest

Author Junqi Wang was employed by the company Jiangsu Suolong Fire Science and Technology Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Abbreviations

The following abbreviations are used in this manuscript:
Nomenclature
a, b, cpower law exponents
a1, a2empirical parameters in Equation (4) and Equation (5)
dFeFeret diameter [mm]
ffrequency [Hz]
Gstorage modulus [Pa]
Gloss modulus [Pa]
G1, G2parameters of the Burgers model (Equation (3)) [Pa]
Jcompliance [Pa−1]
Jresidual compliance [Pa−1]
Kconsistency factor [Pa.sn]
nflow behavior index
rbubble radius, equal to half the Feret diameter [mm]
R32Sauter mean radius, defined as R32 = <r3>/<r2> [mm]
RAarithmetic mean radius, defined as RA = <r> [mm]
Rocubic mean radius, defined as Ro = <r3>1/3 [mm]
Rrmsmean square radius, defined as Rrms = <r2>1/2 [mm]
ttime [min]
tholdholding time [min]
Greek symbols
γstrain
γ0strain amplitude
γyyield strain
γ ˙ shear rate [s−1]
δloss angle [°]
μ1, μ2parameters of the Burgers model (Equation (3)) [Pa.s]
σsurface tension of the foam solution [mN.m−1]
τshear stress [Pa]
τ0stress amplitude [Pa]
τyyield stress [Pa]
ϕlliquid friction (volume fraction of the liquid phase of a foam)
ϕ l critical liquid fraction
ϕl,0initial liquid friction
ψrelative conductivity of firefighting foam, defined as ψ = ψfoam/ψsolution
ψfoamconductivity of firefighting foam [mS.cm−1]
ψsolutionconductivity of the foam solution [mS.cm−1]

References

  1. NFPA 11; Standard for Low-, Medium-, and High-Expansion Foam. NFPA: Quincy, MA, USA, 2024.
  2. NFPA 30; Flammable and combustible liquids code. NFPA: Quincy, MA, USA, 2024.
  3. Zhi, H.; Bao, Y.; Wang, L.; Mi, Y. Extinguishing performance of alcohol-resistant firefighting foams on polar flammable liquid fires. J. Fire Sci. 2020, 38, 53–74. [Google Scholar] [CrossRef]
  4. Conroy, M.W.; Ananth, R. Fuel surface cooling by aqueous foam: A pool fire suppression mechanism. Fire Technol. 2015, 51, 667–689. [Google Scholar] [CrossRef]
  5. Zhang, Q.; Wang, L.; Bi, Y.; Xu, D.; Zhi, H.; Qiu, P. Experimental investigation of foam spread and extinguishment of the large-scale methanol pool fire. J. Hazard. Mater. 2015, 287, 87–92. [Google Scholar] [CrossRef]
  6. Sheng, Y.J.; Jiang, N.; Lu, S.X.; Li, C.H. Fluorinated and fluorine-free firefighting foams spread on heptane surface. Colloids Surf. A 2018, 552, 1–8. [Google Scholar] [CrossRef]
  7. Persson, B.; Lönnermark, A.; Persson, H. FOAMSPEX: Large scale foam application: Modelling of foam spread and extinguishment. Fire Technol. 2003, 3, 347–362. [Google Scholar] [CrossRef]
  8. Lattimer, B.Y.; Trelles, J. Foam spread over a liquid pool. Fire Saf. J. 2007, 42, 249–264. [Google Scholar] [CrossRef]
  9. Darwin, R.L.; Williams, F.W. A Review of the Performance of AFFF Systems Serving Helicopter Decks on U.S. Navy Surface Combatants; U.S. Naval Research Laboratory: Washington, DC, USA, 2001. [Google Scholar]
  10. Ranjbar, H.; Shahraki, B.H. Effect of aqueous film-forming foams on the evaporation rate of hydrocarbon fuels. Chem. Eng. Technol. 2013, 36, 295–299. [Google Scholar] [CrossRef]
  11. Malik, P.; Nandini, D.; Tripathi, B.P. Firefighting aqueous film forming foam composition, properties and toxicity: A review. Environ. Chem. Lett. 2024, 22, 2013–2033. [Google Scholar] [CrossRef]
  12. Mcgarr, J.; Mbonimpa, E.; Mcavoy, D.; Soltanian, M. Fate and transport of per- and polyfluoroalkyl substances (PFAS) at aqueous film forming foam (AFFF) discharge sites: A review. Soil Syst. 2023, 7, 53. [Google Scholar] [CrossRef]
  13. Mcdonough, C.A.; Choyke, S.; Barton, K.E.; Mass, S.; Higgins, C.P. Unsaturated PFOS and other PFASs in human serum and drinking water from an AFFF-impacted community. Environ. Sci. Technol. 2021, 55, 8139–8148. [Google Scholar] [CrossRef]
  14. Back, G.G.; Farley, J.P. Evaluation of the fire protection effectiveness of fluorine free firefighting foams. 2020. Available online: https://www.nfpa.org/education-and-research/research/fire-protection-research-foundation/projects-and-reports/evaluation-of-the-fire-protection-effectiveness-of-fluorine-free-firefighting-foams (accessed on 1 January 2021).
  15. Gao, H.; Zhang, M.; Xia, J.J.; Song, B.; Wang, Y.K. Time and surfactant types dependent model of foams based on the Herschel–Bulkley model. Colloids Surf. A 2016, 509, 203–213. [Google Scholar] [CrossRef]
  16. Géminard, J.C.; Pastenes, J.; Melo, F. Foam rheology at large deformation. Phys. Rev. E 2018, 97, 042601. [Google Scholar] [CrossRef] [PubMed]
  17. Fan, Y.; Wang, Y.; Gao, H.; Lin, Q.; Song, B.; Xia, J. Rheological characterization and prediction model of compressed air Class A foam. J. Dispersion Sci. Technol. 2020, 43, 978–989. [Google Scholar] [CrossRef]
  18. Cohen-Addad, S.; Höhler, R. Rheology of foams and highly concentrated emulsions. Curr. Opin. Colloid Interface Sci. 2014, 19, 536–548. [Google Scholar] [CrossRef]
  19. Le Merrer, M.; Lespiat, R.; Höhler, R.; Cohen-Addad, S. Linear and non-linear wall friction of wet foams. Soft Matter 2015, 11, 368–381. [Google Scholar] [CrossRef]
  20. Magrabi, S.A.; Dlugogorski, B.Z.; Jameson, G.J. Free drainage in aqueous foams: Model and experimental study. AIChE J. 2001, 47, 314–327. [Google Scholar] [CrossRef]
  21. Shi, Q.; Qin, B.; Xu, Y.; Hao, M.; Shao, X.; Zhuo, H. Experimental investigation of the drainage characteristic and stability mechanism of gel-stabilized foam used to extinguish coal fire. Fuel 2022, 313, 122685. [Google Scholar] [CrossRef]
  22. Khakalo, K.; Baumgarten, K.; Tighe, B.P.; Puisto, A. Coarsening and mechanics in the bubble model for wet foams. Phys. Rev. E 2017, 98, 012607. [Google Scholar] [CrossRef]
  23. Requier, A.; Guidolin, C.; Rio, E.; Galvani, N.; Cohen-Addad, S.; Pitois, O.; Salonen, A. Foam coarsening in a yield stress fluid. Soft Matter 2024, 20, 6023–6032. [Google Scholar] [CrossRef]
  24. Krzan, M. Rheology of the wet surfactant foams and biofoams—A review. Tech. Trans. 2013, 1-Ch, 9–27. [Google Scholar]
  25. Denkov, N.D.; Tcholakova, S.; Golemanov, K.; Ananthpadmanabhan, K.P.; Lips, A. The role of surfactant type and bubble surface mobility in foam rheology. Soft Matter 2009, 5, 3389–3408. [Google Scholar] [CrossRef]
  26. Gorlier, F.; Khidas, Y.; Pitois, O. Yielding of complex liquid foams. J. Rheol. 2017, 61, 919–930. [Google Scholar] [CrossRef]
  27. Lexis, M.; Willenbacher, N. Yield stress and elasticity of aqueous foams from protein and surfactant solutions—The role of continuous phase viscosity and interfacial properties. Colloids Surf. A 2014, 459, 177–185. [Google Scholar] [CrossRef]
  28. Kennedy, M.J.; Conroy, M.W.; Dougherty, J.A.; Otto, N.; Williams, B.A.; Ananth, R.; Fleming, J.W. Bubble coarsening dynamics in fluorinated and non-fluorinated firefighting foams. Colloids Surf. A 2015, 470, 268–279. [Google Scholar] [CrossRef]
  29. Magrabi, S.A.; Dlugogorski, B.Z.; Jameson, G.J. A comparative study of drainage characteristics in AFFF and FFFP compressed-air fire-fighting foams. Fire Saf. J. 2002, 37, 21–52. [Google Scholar] [CrossRef]
  30. Elliott, D.E.; Chiesa, P.J. A new foam rheometer for studying fire fighting foams. Fire Technol. 1976, 12, 66–69. [Google Scholar] [CrossRef]
  31. Gardiner, B.S.; Dlugogorski, B.Z.; G.Jameson, J. Rheology of fire-fighting foams. Fire Saf. J. 1998, 31, 61–75. [Google Scholar] [CrossRef]
  32. Feitosa, K.; Marze, S.; Saint-Jalmes, A.; Durian, D.J. Electrical conductivity of dispersions: From dry foams to dilute suspensions. J. Phys. Condens. Matter 2005, 17, 6301–6305. [Google Scholar] [CrossRef]
  33. Stevenson, P. Foam Engineering: Fundamentals and Applications; John Wiley & Sons: Hoboken, NJ, USA, 2012. [Google Scholar]
  34. Cantat, I.; Cohen-Addad, S.; Elias, F.; Graner, F.; Höhler, R.; Pitois, O.; Rouyer, F.; Saint-Jalmes, A. Foams: Structure and Dynamics; Oxford University Press: Oxford, UK, 2013. [Google Scholar]
  35. Höhler, R.; Cohenaddad, S. Rheology of liquid foam. J. Phys. Condens. Matter 2005, 17, R1041. [Google Scholar] [CrossRef]
  36. Rouyer, F.; Cohen-Addad, S.; Höhler, R. Is the yield stress of aqueous foam a well-defined quantity? Colloids Surf. A 2005, 263, 111–116. [Google Scholar] [CrossRef]
Figure 1. Schematic diagram of foam conductivity and bubble size test.
Figure 1. Schematic diagram of foam conductivity and bubble size test.
Materials 18 03236 g001
Figure 2. Free drainage of firefighting foam: (a) time evolution of the local liquid fraction at different vertical positions; (b) vertical profile of the local liquid fraction as a function of time.
Figure 2. Free drainage of firefighting foam: (a) time evolution of the local liquid fraction at different vertical positions; (b) vertical profile of the local liquid fraction as a function of time.
Materials 18 03236 g002
Figure 3. Photographs at different vertical positions in the firefighting foam at t = 0.5 min, 4 min, 12 min, and 20 min.
Figure 3. Photographs at different vertical positions in the firefighting foam at t = 0.5 min, 4 min, 12 min, and 20 min.
Materials 18 03236 g003
Figure 4. Bubble size distributions at different vertical positions in the firefighting foam.
Figure 4. Bubble size distributions at different vertical positions in the firefighting foam.
Materials 18 03236 g004
Figure 5. Typical results of the strain amplitude sweep test for firefighting foam (f = 1 Hz).
Figure 5. Typical results of the strain amplitude sweep test for firefighting foam (f = 1 Hz).
Materials 18 03236 g005
Figure 6. Strain amplitude sweep tests for the firefighting foams after different holding times: (a) shear modulus vs. strain amplitude; (b) stress amplitude and loss angle vs. strain amplitude.
Figure 6. Strain amplitude sweep tests for the firefighting foams after different holding times: (a) shear modulus vs. strain amplitude; (b) stress amplitude and loss angle vs. strain amplitude.
Materials 18 03236 g006
Figure 7. Time sweep test within the linear viscoelastic region of the firefighting foam (γ0 = 0.01, f = 1 Hz).
Figure 7. Time sweep test within the linear viscoelastic region of the firefighting foam (γ0 = 0.01, f = 1 Hz).
Materials 18 03236 g007
Figure 8. Dependence of the normalized storage modulus on the liquid fraction at different vertical positions in the firefighting foam.
Figure 8. Dependence of the normalized storage modulus on the liquid fraction at different vertical positions in the firefighting foam.
Materials 18 03236 g008
Figure 9. Creep tests for firefighting foams: (a) after different holding times; (b) fitting and prediction of the Burgers model.
Figure 9. Creep tests for firefighting foams: (a) after different holding times; (b) fitting and prediction of the Burgers model.
Materials 18 03236 g009
Figure 10. Yielding of the firefighting foams: (a) start-up flow at a constant shear rate of 0.125 s−1; (b) stress sweep test.
Figure 10. Yielding of the firefighting foams: (a) start-up flow at a constant shear rate of 0.125 s−1; (b) stress sweep test.
Materials 18 03236 g010
Figure 11. Yield stress and yield strain of the firefighting foams measured by using different methods: (a) yield stress vs. holding time; (b) yield strain vs. holding time.
Figure 11. Yield stress and yield strain of the firefighting foams measured by using different methods: (a) yield stress vs. holding time; (b) yield strain vs. holding time.
Materials 18 03236 g011
Figure 12. Dependence of the normalized yield stress and yield strain on the liquid fraction at different vertical positions in the firefighting foam: (a) normalized yield stress vs. liquid fraction; (b) yield strain vs. liquid fraction.
Figure 12. Dependence of the normalized yield stress and yield strain on the liquid fraction at different vertical positions in the firefighting foam: (a) normalized yield stress vs. liquid fraction; (b) yield strain vs. liquid fraction.
Materials 18 03236 g012
Figure 13. Stress response of firefighting foam under continuous and intermittent shear conditions of 8 s−1, 16 s−1, and 32 s−1.
Figure 13. Stress response of firefighting foam under continuous and intermittent shear conditions of 8 s−1, 16 s−1, and 32 s−1.
Materials 18 03236 g013
Figure 14. Constant shear rate tests for firefighting foams: (a) time evolution of shear stress; (b) time evolution of viscosity.
Figure 14. Constant shear rate tests for firefighting foams: (a) time evolution of shear stress; (b) time evolution of viscosity.
Materials 18 03236 g014
Figure 15. Flow curves of the firefighting foams (the symbols represent the measured data, and the solid lines represent the results fitted by the Herschel–Bulkley model).
Figure 15. Flow curves of the firefighting foams (the symbols represent the measured data, and the solid lines represent the results fitted by the Herschel–Bulkley model).
Materials 18 03236 g015
Figure 16. Evolution of the fitted parameters of the Herschel–Bulkley model with aging time.
Figure 16. Evolution of the fitted parameters of the Herschel–Bulkley model with aging time.
Materials 18 03236 g016
Table 1. Mean bubble sizes of firefighting foam at specific time points and vertical positions, including arithmetic mean radius RA (±standard deviation) and Sauter mean radius R32 (±bootstrap-estimated standard errors).
Table 1. Mean bubble sizes of firefighting foam at specific time points and vertical positions, including arithmetic mean radius RA (±standard deviation) and Sauter mean radius R32 (±bootstrap-estimated standard errors).
t/minRA/mmR32/mm
z = 3 cmz = 5 cmz = 7 cmz = 9 cmz = 11 cmz = 3 cmz = 5 cmz = 7 cmz = 9 cmz = 11 cm
0.50.0502
± 0.0213
0.0511
± 0.0243
0.0495
± 0.0257
0.0543
± 0.0250
0.0540
± 0.0253
0.0662
± 0.0006
0.0714
± 0.0007
0.0730
± 0.0007
0.0745
± 0.0007
0.0749
± 0.0008
40.0703
± 0.0339
0.0734
± 0.0345
0.0795
± 0.0353
0.0793
± 0.0361
0.0896
± 0.0414
0.0992
± 0.0016
0.1020
± 0.0016
0.1071
± 0.0016
0.1073
± 0.0015
0.1224
± 0.0020
80.0810
± 0.0437
0.0854
± 0.0453
0.0958
± 0.0499
0.1031
± 0.0552
0.1312
± 0.0670
0.1226
± 0.0028
0.1279
± 0.0027
0.1392
± 0.0025
0.1527
± 0.0030
0.1876
± 0.0043
120.0873
± 0.0521
0.1025
± 0.0582
0.1168
± 0.0665
0.1585
± 0.0668
0.1939
± 0.0790
0.1416
± 0.0039
0.1583
± 0.0037
0.1789
± 0.0039
0.2065
± 0.0050
0.2487
± 0.0067
160.0985
± 0.0634
0.1382
± 0.0768
0.1586
± 0.0847
0.1989
± 0.1003
0.2417
± 0.1064
0.1697
± 0.0053
0.2091
± 0.0057
0.2296
± 0.0059
0.2783
± 0.0075
0.3197
± 0.0104
200.1099
± 0.0774
0.1864
± 0.0830
0.2215
± 0.1073
0.2493
± 0.1055
0.3036
± 0.1220
0.2065
± 0.0110
0.2516
± 0.0088
0.2920
± 0.0119
0.3251
± 0.0122
0.3877
± 0.0152
Table 2. Fitted parameters of the Burgers model for creep curves with 95% confidence intervals and goodness-of-fit metrics (RMSE).
Table 2. Fitted parameters of the Burgers model for creep curves with 95% confidence intervals and goodness-of-fit metrics (RMSE).
thold/minG1/Paμ1/Pa·sG2/Paμ2/Pa·sRMSE
0.59.6 ± 0.262.7 ± 0.123.8 ± 1.1327.8 ± 39.40.0015
46.7 ± 0.169.5 ± 0.210.8 ± 0.4225.1 ± 13.60.0018
86.2 ± 0.184.1 ± 0.28.3 ± 0.2152.4 ± 5.80.0015
125.9 ± 0.1115.2 ± 0.74.5 ± 0.1124.0 ± 2.70.0017
165.4 ± 0.1142.3 ± 1.43.9 ± 0.1109.4 ± 2.50.0021
204.9 ± 0.1173.9 ± 3.83.2 ± 0.198.0 ± 3.00.0034
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Bao, Y.; Zhi, H.; Wang, L.; Fan, Y.; Wang, J. Experimental Study on Rheological Behavior of Firefighting Foams. Materials 2025, 18, 3236. https://doi.org/10.3390/ma18143236

AMA Style

Bao Y, Zhi H, Wang L, Fan Y, Wang J. Experimental Study on Rheological Behavior of Firefighting Foams. Materials. 2025; 18(14):3236. https://doi.org/10.3390/ma18143236

Chicago/Turabian Style

Bao, Youquan, Huiqiang Zhi, Lu Wang, Yakun Fan, and Junqi Wang. 2025. "Experimental Study on Rheological Behavior of Firefighting Foams" Materials 18, no. 14: 3236. https://doi.org/10.3390/ma18143236

APA Style

Bao, Y., Zhi, H., Wang, L., Fan, Y., & Wang, J. (2025). Experimental Study on Rheological Behavior of Firefighting Foams. Materials, 18(14), 3236. https://doi.org/10.3390/ma18143236