After implementing the proposed exhaustive-search and multi-criteria decision framework, the algorithm was executed using a database obtained from CYME simulations. These simulations were carried out under two representative operating scenarios, namely, maximum load (100%) and minimum load (10%). For each feasible regulator-location alternative, the selected technical criteria were computed and stored for subsequent ranking using the WSM and TOPSIS. This section presents the main results obtained for each operating condition, beginning with the maximum-load scenario.
3.1. Maximum-Load Scenario
The first assessment was conducted under the maximum-load condition, which represents the most critical operating state of the feeder from the standpoint of voltage deterioration and technical losses. For this scenario, the simulation outputs associated with all feasible regulator-placement alternatives were stored in a database and used as input to the ranking algorithm. A representative excerpt of these data is presented in
Table 6, where the variables corresponding to several candidate nodes are shown. In total, 6241 data records were processed by the developed script for this scenario.
Once the database had been processed, the five best alternatives according to the Weighted Sum Method were identified. The corresponding ranking is summarized in
Table 7. These results show that node 5 achieved the best overall WSM score for the maximum-load scenario. In practical terms, this indicates that the regulator placement associated with this node provides the most favorable combined performance when all weighted technical criteria are considered simultaneously.
To better visualize the relative performance of the five best WSM alternatives,
Figure 9 presents a bar chart comparing the normalized criteria. This figure shows that, when the regulator is placed at node 5, the criteria associated with active power losses, reactive power losses, and voltage-unbalance percentage tend toward the lowest values among the top-ranked alternatives, which explains its leading position in the WSM ranking.
A complementary view of the same ranking is provided by the heatmap shown in
Figure 10. This representation allows a more direct visual identification of the relative magnitude of each normalized criterion across the best-performing alternatives. In particular, it can be observed that alternatives associated with nodes 3 to 9 exhibit comparatively larger normalized values for active and reactive power losses, whereas node 5 consistently exhibits the most favorable overall criterion distribution.
After the ranking stage, the best overall alternative identified by the WSM for the maximum-load scenario was examined in detail in order to summarize its main technical indicators.
Table 8 reports the performance metrics associated with the winning configuration. The results confirm that the preferred solution corresponds to test 5, i.e., the regulator placement at node 5 (MTS 108932). This alternative yielded the lowest overall weighted score under the adopted WSM formulation and simultaneously achieved favorable values in the principal decision criteria, including active losses, reactive losses, global voltage deviation, average voltage variation, and voltage unbalance. Particularly relevant is the fact that no nodes remained outside the admissible operating range, which further supports the technical suitability of this location under the most critical loading condition of the feeder.
Once the winning WSM alternative had been identified, the resulting nodal behavior of the evaluated criteria was analyzed in greater detail.
Figure 11 presents the criterion profiles along the feeder nodes for the selected solution. The figure shows that the voltage regulator improves the feeder response throughout the analyzed nodes, reducing the severity of the critical variables and contributing to a better technical operating condition under peak demand.
In parallel with the WSM analysis, the TOPSIS method was applied to the same maximum-load dataset in order to evaluate the consistency of the final decision under an alternative multi-criteria ranking perspective. The five best TOPSIS-ranked alternatives are listed in
Table 9. These results show that the best candidate locations according to TOPSIS are nodes 5, 10, 9, 7, and 8, respectively. Most importantly, the best-ranked alternative is again node 5, which indicates agreement between both decision methods regarding the optimal regulator location.
The comparative bar plot shown in
Figure 12 provides a visual interpretation of the TOPSIS ranking. As in the WSM case, the variables associated with active losses, reactive losses, and voltage-unbalance percentage exhibit their most favorable values when the regulator is assigned to node 5. This result reinforces the robustness of the selected solution under the maximum-load operating condition.
The corresponding TOPSIS heatmap is presented in
Figure 13. This figure shows that the alternative associated with node 5 minimizes most of the evaluated criteria, while the voltage-deviation criterion remains consistently low for all top-ranked scenarios. Consequently, the heatmap confirms that node 5 achieves the most balanced overall behavior in the TOPSIS decision space.
The final TOPSIS solution for the maximum-load scenario was examined in detail in order to verify the consistency of the multi-criteria decision process.
Table 10 summarizes the main technical indicators associated with the winning alternative identified by TOPSIS. The results confirm that the preferred solution again corresponds to test 5, i.e., regulator placement at node 5 (MTS 108932). This result is particularly significant because it reproduces the same winning alternative previously obtained with the WSM under the most critical loading condition. Therefore, the convergence of both ranking methods toward the same node should be interpreted as strong evidence that the selected location is not dependent on a single aggregation scheme, but instead represents a technically dominant and methodologically robust solution within the feasible decision space. In addition, the reported indicators show favorable values for all major decision criteria, including active losses, reactive losses, total voltage deviation, average voltage variation, and voltage unbalance, while also maintaining zero nodes outside the admissible operating range.
Because the WSM and TOPSIS selected the same winning alternative under the maximum-load scenario, namely node 5 (MTS 108932), the TOPSIS result confirms the nodal behavior previously observed for the WSM-based winning solution. The numerical indicators in
Table 10 show that this alternative achieves reduced active and reactive losses, limited voltage deviation, low voltage unbalance, and no nodes outside the admissible operating range.
3.2. Minimum-Load Scenario
The second operating condition considered in this study corresponds to the minimum-load scenario, defined as 10% of the installed demand. Although this condition is electrically less severe than the maximum-load case in terms of current magnitude and total losses, it remains relevant for regulator-placement analysis because the relative ranking of alternatives may change when the feeder operates far from peak demand. Therefore, the same exhaustive-search and multi-criteria evaluation procedure was applied in order to assess the consistency of the optimal regulator location under light-load conditions.
As in the previous case, the values of the selected variables were computed and stored in an Excel-based dataset for all feasible placement alternatives. A representative excerpt of these data is summarized in
Table 11. For this scenario, the developed script also processed a total of 6241 data records, thereby ensuring a complete evaluation of the feasible search space under minimum-load operation.
After processing the simulation database, the five best alternatives according to the Weighted Sum Method were identified. The resulting ranking is presented in
Table 12. Under minimum-load conditions, the best-ranked WSM alternative corresponds to node 3, followed by nodes 5, 10, 9, and 8. This result is technically important because it indicates that, unlike the maximum-load scenario, the WSM ranking under light-load operation favors node 3 as the best compromise among the selected criteria.
To facilitate the comparison among the best WSM alternatives,
Figure 14 presents the corresponding bar chart of normalized criteria. This figure shows that the alternatives associated with the smallest values of voltage deviation, active losses, and reactive losses exhibit the best overall WSM behavior. In particular, although several alternatives remain close to one another, the graphical comparison confirms that the regulator placement associated with node 3 provides the most favorable aggregate performance according to the WSM metric.
A complementary criterion-level interpretation is provided in the heatmap shown in
Figure 15. This figure shows that, for most of the top-ranked alternatives, the normalized values associated with active losses, reactive losses, and voltage deviation remain below 0.1, which confirms that the best candidate locations under minimum load exhibit relatively similar and favorable technical behavior. Nevertheless, the WSM aggregation still selects node 3 as the best overall alternative.
Once the WSM ranking for the minimum-load scenario had been completed, the winning alternative was examined in detail in order to identify the specific technical indicators associated with the selected solution.
Table 13 summarizes the main performance metrics of the best-ranked configuration. According to the WSM formulation, the preferred alternative under minimum load corresponds to test 3, i.e., regulator placement at node 3 (MTS 108404). This result differs from the one obtained under maximum-load conditions and therefore provides relevant evidence that the ranking is influenced by the feeder operating state when a weighted-sum aggregation is employed. Nevertheless, the selected solution remains technically sound, since it exhibits low active and reactive losses, a reduced global voltage deviation, a limited voltage-unbalance level, and zero nodes outside the admissible operating range. Consequently, this table formalizes the best WSM solution for the light-load regime and supports the subsequent analysis of its nodal behavior.
After identifying the winning WSM alternative, the nodal behavior of the selected criteria was analyzed in detail.
Figure 16 presents the criterion profiles for the selected solution along the feeder nodes. The obtained curves confirm a general reduction in the evaluated variables throughout the feeder, thereby indicating that the selected regulator location improves the operating condition even under light-load operation.
The same minimum-load dataset was subsequently processed using TOPSIS in order to compare the ranking behavior obtained from a different multi-criteria decision formulation. The five best alternatives according to TOPSIS are presented in
Table 14. In this case, the best-ranked alternative corresponds to node 5, followed by nodes 3, 10, 9, and 8. Therefore, under minimum-load conditions, the WSM and TOPSIS do not select the same best alternative, even though they identify a very similar group of top-performing candidate nodes.
The relative performance of the best TOPSIS alternatives is illustrated in
Figure 17. The bar chart shows that the voltage-deviation and voltage-unbalance indicators attain very low values for the best-ranked alternatives, while node 5 provides the most favorable overall balance in the weighted TOPSIS space. This explains why TOPSIS identifies node 5 as the preferred solution, even though the WSM ranking places node 3 first.
This behavior is further clarified by the heatmap shown in
Figure 18. As in the WSM case, the majority of the best-ranked alternatives exhibit normalized active-loss, reactive-loss, and voltage-deviation values below 0.1. However, the visual distribution of the criteria indicates that alternative 5 achieves the most favorable overall compromise according to the TOPSIS closeness criterion.
The winning TOPSIS alternative for the minimum-load scenario was also examined in detail in order to characterize the technical performance of the selected solution under light-load operation.
Table 15 summarizes the main indicators associated with the best-ranked configuration. According to the TOPSIS formulation, the preferred alternative corresponds to test 5, i.e., regulator placement at node 5 (MTS 108932). This result is technically significant because it shows that, even under minimum-load conditions, node 5 remains one of the strongest candidate locations in the feeder. In contrast with the WSM result obtained for the same operating scenario, the TOPSIS ranking preserves node 5 as the best solution, which reinforces its relevance as a robust placement alternative when the feeder is analyzed under different loading conditions and under different multi-criteria aggregation logics. Moreover, the reported indicators confirm that this solution maintains low active and reactive losses, a reduced total voltage deviation, limited voltage unbalance, and zero nodes outside the admissible operating range.
Under minimum-load conditions, the TOPSIS solution exhibits a nodal behavior that is technically close to the WSM-based assessment, with low active and reactive losses, limited voltage deviation, reduced voltage unbalance, and no nodes outside the admissible operating range. The detailed numerical indicators of the TOPSIS winning alternative are summarized in
Table 15.
3.3. Comparative Analysis and Sensitivity Assessment
After evaluating the maximum- and minimum-load operating conditions independently, a comparative analysis was conducted in order to quantify the improvement achieved by the winning regulator-placement alternatives with respect to the base-case condition and to assess the consistency of the proposed decision framework. This comparison was performed for both the WSM and TOPSIS, considering the most relevant technical indicators, namely, active power losses, reactive power losses, average voltage variation, and average per-unit voltage magnitude.
For the maximum-load scenario, the comparison between the base case and the winning alternatives obtained by the WSM and TOPSIS is summarized in
Table 16. These results show a clear technical improvement after regulator installation. In particular, both methods converge to the same winning solution and therefore produce identical performance values. Relative to the base case, the selected regulator placement reduces active and reactive losses, decreases the average voltage variation from 0.29% to 0.05%, and improves the average voltage magnitude from 0.985 p.u. to 1.00 p.u. This result confirms that, under the most critical operating condition, the proposed methodology yields a technically consistent and clearly beneficial solution.
In addition to the direct numerical comparison, it is relevant to examine the degree of agreement between the full WSM and TOPSIS rankings. This comparison is illustrated in
Figure 19, which presents a scatter plot of the rankings obtained under maximum load. The close concentration of the points around the main diagonal indicates a high degree of consistency between both methods over the set of evaluated alternatives. This behavior supports the robustness of the ranking process and explains why both methods identify the same best regulator location under maximum-load conditions.
To further interpret the improvement introduced by the selected regulator placement, the behavior of the total voltage variation was compared between the base case and the regulated case.
Figure 20 shows this comparison for the maximum-load scenario. The figure demonstrates that the regulator substantially attenuates the voltage-deviation profile along the feeder, especially in the downstream sections where the base case exhibits the most pronounced deterioration.
A similar comparison was performed for the main loss-related variables.
Figure 21 and
Figure 22 compare the reactive and active loss profiles, respectively, between the base case and the solution obtained with the regulator. In both figures, the regulated case exhibits systematically lower values than the base case over a significant portion of the feeder, which confirms that the selected regulator location not only improves voltage conditions but also contributes to a more efficient electrical operation.
The robustness of the maximum-load solution was further assessed through a sensitivity analysis based on systematic variations in the criterion weights. The resulting behavior is presented in
Figure 23. It is important to emphasize that, for the maximum-demand scenario, both the WSM and TOPSIS converged consistently to the same winning alternative throughout the entire range of weight perturbations considered in the analysis. Specifically, the preferred solution remained permanently associated with node 5 for all tested weighting configurations and for all evaluated criteria. Consequently, the graphical concentration of the results at node 5 should not be interpreted as a trivial or uninformative outcome; rather, it constitutes strong evidence that the selected location is structurally stable within the decision space. From a methodological standpoint, this means that the optimal placement identified under maximum load is not sensitive to moderate changes in decision-maker preferences and does not depend on a particular weighting arrangement. Instead, the persistent convergence of both multi-criteria methods to node 5 demonstrates that this alternative dominates the remaining candidates under the most critical operating condition of the feeder, thereby reinforcing its technical validity as the most robust regulator location.
A corresponding comparison was also performed for the minimum-load scenario. The numerical results are summarized in
Table 17, which compares the base case against the winning alternatives obtained from the WSM and TOPSIS. In this case, both methods again improve the feeder performance relative to the base case, although they do not select the same winning alternative. Specifically, the base-case average voltage variation decreases from 0.42% to 0.02%, while the average per-unit voltage magnitude increases from 0.965 p.u. to 1.012 p.u. The active and reactive losses are also reduced in both winning scenarios, showing that both regulator placements are technically beneficial under minimum-load operation.
The degree of agreement between the WSM and TOPSIS rankings for the minimum-load scenario is illustrated in
Figure 24. Unlike the maximum-load case, the scatter plot reveals a noticeably larger dispersion among the ranked alternatives, with only the first few positions showing strong similarity. This behavior explains why the WSM and TOPSIS identify different winning nodes under light-load operation and indicates that, in this operating regime, the ranking is more sensitive to the specific aggregation logic of each decision method.
The effect of regulator installation on the voltage profile under minimum load is shown in
Figure 25. The figure compares the total voltage variation in the base case and the regulated case, confirming that the selected regulator placement substantially improves the voltage profile even when the feeder is operating far below peak demand.
The corresponding comparisons for reactive and active losses are shown in
Figure 26 and
Figure 27, respectively. These figures indicate that the regulator also improves feeder efficiency under light-load conditions, although the relative differences between the base and regulated cases are smaller than those observed under maximum load, which is consistent with the lower current levels and reduced loss magnitude of the minimum-load operating condition.
The sensitivity analysis for the minimum-load scenario is presented in
Figure 28. In contrast to the maximum-load condition, the minimum-load case exhibits a more differentiated behavior between methods. The WSM consistently converges to solution 3 under all tested weighting variations, indicating a stable preference for that alternative. TOPSIS, however, exhibits variations in the preferred solution when the weights of active losses, reactive losses, voltage deviation, and percentage voltage variation are modified, alternating in some cases between solutions 5 and 3. This result indicates that, under minimum load, the relative ranking is more sensitive to the criterion-weight configuration, especially for TOPSIS.
Finally, after jointly examining the two operating conditions, the comparative rankings, and the sensitivity analyses, the regulator location associated with node 5 emerges as the most robust overall solution for the analyzed feeder. Although alternative solutions may appear under specific weighting configurations and under minimum-load operation, the majority of the evaluated cases, particularly those corresponding to the most critical operating condition, converge to node 5 as the preferred location. This final result is illustrated in
Figure 29, which identifies the optimal voltage-regulator placement derived from the proposed methodology.
3.4. Discussion of Results
The results obtained under maximum- and minimum-load operating conditions make it possible to identify consistent electrical behavior patterns in the analyzed feeder and, at the same time, validate the technical soundness of the implemented model. From a system-level perspective, the proposed framework proved capable of capturing the most relevant variations in feeder performance associated with demand level, regulator placement, and the weighting structure of the multi-criteria decision process. This is particularly important because the regulator-placement problem cannot be interpreted solely as a local voltage-correction task; rather, it must be understood as a planning problem involving simultaneous trade-offs among voltage quality, electrical efficiency, and operating robustness.
Under maximum-load conditions, the feeder exhibited the most critical electrical behavior, as expected. In this scenario, active and reactive power losses increased substantially, and the most severe conditions were concentrated around node MTA S 466866, which carries the highest current levels due to its position within the feeder and the amount of downstream demand it must supply. This behavior is physically coherent with the structure of radial distribution networks, where upstream sections tend to concentrate the cumulative current demanded by downstream loads and therefore experience the highest loss levels. Although the installation of a voltage regulator at or near such critical regions improves the downstream voltage profile, it does not necessarily eliminate total losses at the point of connection, since losses are fundamentally related to current magnitude and branch impedance distribution throughout the feeder.
By contrast, the minimum-load scenario exhibited a significant reduction in electrical losses, reaching values notably lower than those observed at maximum demand. Under these conditions, the feeder voltage profile remained closer to acceptable operating limits, and the electrical stress imposed on the network was considerably smaller. Consequently, the relative differences among candidate alternatives became less pronounced, which explains why the ranking dispersion between methods increased in the low-demand scenario. Even in this operating regime, however, node MTA S 466866 remained the location associated with the highest loss magnitude, confirming its dominant role in the feeder energy transfer process and reinforcing the validity of the simulated load-flow behavior.
A particularly relevant outcome of the comparative analysis is that the regulator placement at node MTS 108932, which emerged as the most robust overall alternative, is technically justified because it maximizes corrective capability precisely under the most demanding operating condition. This is a crucial planning criterion. In maximum-load operation, voltage regulation is substantially more challenging because the larger current flow causes more severe voltage drops and higher losses. Therefore, the value of a candidate regulator location should not be assessed only by its behavior under light-load conditions, but by its capacity to ensure technically reliable operation under the most stressed feeder state. From this perspective, node MTS 108932 provides the strongest overall response, especially when system performance under peak demand is prioritized, while still preserving satisfactory performance under minimum load.
The multi-criteria formulation adopted in this study was essential for reaching this conclusion. The regulator-placement problem is intrinsically multi-objective, since improvements in one indicator do not necessarily imply proportional improvements in all others. By jointly considering voltage deviation, voltage unbalance, active losses, and reactive losses, the proposed framework avoids the oversimplification that would arise from a single-criterion selection. In this context, the combined use of the WSM and TOPSIS strengthens the technical credibility of the decision process, because both methods evaluate the same solution space from different aggregation logics. The WSM performs a direct weighted aggregation of normalized criteria, whereas TOPSIS evaluates the proximity of each alternative to the ideal and anti-ideal solutions. The agreement between both methods in the maximum-load scenario therefore constitutes strong evidence that the selected solution is not an artifact of a specific ranking formulation.
The divergence observed under minimum-load conditions, where the WSM favored node 3 and TOPSIS favored node 5, should not be interpreted as a weakness of the methodology. On the contrary, it reflects the physical and decision-theoretic reality of the problem. When the feeder operates under light load, the technical differences among the best alternatives become smaller, and the relative ranking becomes more sensitive to the mathematical structure of the multi-criteria method and to the adopted weighting scheme. In such cases, it is reasonable for two robust decision methods to produce different, yet technically close, winning alternatives. What is relevant is that both methods consistently identified a very similar subset of top-performing nodes, which indicates that the feasible decision space is well characterized and that the final recommendation is not arbitrary.
This observation connects directly with the justification for using exhaustive search. In many optimization studies on distribution systems, computational efficiency is treated as a primary objective, which motivates the use of heuristics or metaheuristics. However, the present study addresses a planning problem, not an online operational-control problem. Consequently, computational time is not the dominant constraint. In planning applications, the primary requirement is to guarantee that the adopted solution is globally optimal within the feasible search space and that no technically superior alternative has been omitted due to stochastic convergence, premature stopping, or local-optimum trapping. Under this rationale, exhaustive search is particularly appropriate, because it evaluates all feasible alternatives explicitly and therefore guarantees the optimal solution over the candidate set. This advantage is especially meaningful when the number of feasible alternatives remains computationally manageable, as in the present case.
From a methodological standpoint, this exact-search strategy provides a stronger basis for technical decision-making than reduced-space or purely heuristic approaches when the objective is long-term planning. In other words, for problems such as voltage regulator placement in a real feeder, the relevant question is not whether the optimal solution can be obtained a few seconds faster, but whether the selected location can be defended as the best possible technical decision under the adopted assumptions and available network information. The present results support precisely that type of conclusion. The exhaustive-search framework guaranteed full exploration of the feasible regulator-location space, while the multi-criteria stage ensured that the final selection accounted simultaneously for voltage quality, loss reduction, and operating balance.
The sensitivity analysis further reinforces this interpretation. Under maximum load, both the WSM and TOPSIS converged repeatedly to node 5 despite changes in the criterion weights, demonstrating that the preferred solution is structurally stable under variations in decision-maker preference. This is a strong indicator of robustness, because it shows that the selected location is not the result of a narrowly tuned weighting configuration. Under minimum load, the WSM remained stable at solution 3, whereas TOPSIS alternated mainly between solutions 5 and 3 as the weights of active losses, reactive losses, voltage deviation, and percentage voltage variation were modified. Even in this case, however, the analysis remains favorable to node 5 from a planning standpoint, because it continues to appear among the dominant solutions and is the most consistently strong alternative when both loading extremes are considered together.
Therefore, the final selection should not be based solely on the isolated outcome of a single low-demand ranking, but rather on the overall robustness of the candidate solution across the full range of relevant operating conditions. This is the key argument that supports the final decision of selecting node MTS 108932 as the optimal regulator location for the analyzed feeder. Although node 3 performs competitively under minimum load and is even ranked first by the WSM in that specific scenario, node 5 presents the strongest and most defensible global behavior when the feeder is evaluated under both demand extremes, when both decision methods are considered jointly, and when ranking stability under weight perturbations is taken into account. In planning terms, this makes node 5 the most technically reliable alternative.
The obtained results are also consistent with previous studies reported in the literature. The work presented in [
6], which analyzes a real feeder in DIgSILENT for optimal voltage-regulator placement, likewise shows that strategically located nodes along the main feeder trunk exert the greatest influence on downstream voltage improvement and loss reduction. Similarly, the study in [
11], which combines on-load tap-changing transformers and exhaustive search in an IEEE test system, confirms that complete exploration of the search space allows the identification of configurations that produce global performance improvements. This is fully consistent with the robustness observed here for node MTS 108932 under the WSM and TOPSIS.
In turn, the work reported in [
12], where genetic algorithms are applied to mitigate low-voltage problems in medium-voltage networks in Ecuador, demonstrates that optimization-based approaches are capable of satisfying regulatory and technical requirements in real distribution environments. Although that study uses a metaheuristic approach and the present work employs exhaustive search, both contributions support the same fundamental conclusion: systematic optimization methods provide a substantially more reliable basis for decision-making than traditional heuristic selection. Likewise, the study in [
25], which uses mixed-integer linear programming (MILP), highlights the importance of mathematical optimization models for obtaining technically justified solutions. In this sense, the present work contributes complementary evidence showing that exact-search methods, when computationally feasible, remain highly valuable in planning problems because of their guarantee of global optimality.
Overall, the present study demonstrates that the combination of detailed feeder simulation in CYME, exhaustive evaluation of feasible alternatives, and multi-criteria ranking provides stable and technically meaningful solutions even under variations in the decision weights. This reinforces the reliability of the adopted framework and supports its applicability to real distribution-system planning problems. More importantly, the results show that the final regulator-placement decision should be based not merely on isolated numerical superiority in a single scenario, but on the overall strength, consistency, and robustness of the alternative across different operating conditions. Under this criterion, node MTS 108932 constitutes the most technically justified and operationally robust solution for the Guayacanes feeder.