1. Introduction
The grounding system is a key element impacting the lightning performance of transmission lines (TLs), especially in cases of direct strikes to towers or shield wires [
1]. When lightning strikes a tower or the shield wires, the lightning current is conducted to the ground through the towers closest to the point of incidence. This current is dispersed into the ground via the tower-footing grounding electrodes, causing a ground potential rise (GPR) that propagates through the tower body, including its crossarms. Additionally, the portion of the lightning current traveling along the shield wires induces voltages in the phase conductors. The resulting overvoltages across each line insulator string are determined by the difference between the crossarm voltage and the voltage coupled to the phase conductor from the shield wires [
2]. As a result, the GPR has direct impacts on both the magnitude and rise rate of these overvoltages, making the tower-footing grounding system a key factor in the lightning performance of the line [
3,
4,
5].
In practice, the primary parameter used to qualify the performance of the TL grounding system is the tower-footing ground resistance: the lower this value, the better the grounding system performance and its ability to mitigate lightning overvoltages [
5]. The tower-footing ground resistance can be determined through simulations using computational tools, as commonly performed during the design phase, based on soil resistivity and the electrode arrangement configuration [
6,
7,
8]. However, a direct measurement of the tower-footing resistance is important for several reasons—for example, to account for seasonal variations, during routine maintenance to assess the condition of grounding electrodes, and after a transmission line outage to evaluate the grounding conditions of the faulted tower [
9].
A survey of different methods for measuring the resistance and impedance of grounding systems can be found in [
10]. Among these methods, the most widely used for measuring tower-footing ground resistance is the fall-of-potential (FOP) method [
11], whose measurement setup is illustrated in
Figure 1. The FOP method consists of injecting a current between the grounding system under test (G) and an auxiliary current-return probe (CP), while measuring the resulting voltage drop between G and a potential probe (PB). To reduce interelectrode influence caused by mutual resistance, the current-return probe is typically placed at a considerable distance from G, generally several times the largest dimension of the grounding electrodes under test [
10].
Field measurements of grounding resistance face intrinsic challenges [
10], but measuring the grounding resistance of TL structures introduces additional difficulties [
11]. When applying the FOP method, depending on the dimensions of the tower-footing grounding electrodes, the current probe must be placed at a substantial distance. This requires long test leads to inject a current into the grounding system under test and to measure the resulting ground potential rise relative to remote earth [
10]. However, many TL structures are located in areas with difficult access or dense vegetation, making the deployment of long test leads laborious or, in some cases, unfeasible. As reported in [
12], the relative positioning of the current and voltage measurement circuits may also influence the results.
An alternative to using long current and voltage test leads is proposed in [
13], where a method is introduced to measure grounding resistance using fast impulse currents and very short leads. This is achieved by replacing conventional test leads with the so-called Artificial Infinite Line (LIA), a transmission line constructed with a thin insulated wire wrapped around a non-conductive polyvinyl chloride (PVC) pipe. The propagation velocity can be adjusted by modifying the number of turns per unit length. Taking advantage of the reduced propagation velocity, this alternative lead can emulate conventional test leads several hundred meters long. Promising results from this methodology are reported in [
13,
14].
An additional challenge in measuring the tower-footing grounding system of high voltage TLs is the presence of shield wires [
11]. Since transmission line towers are interconnected via shield wires, measurements using the fall-of-potential method with a conventional earth tester (here referred to as a “low-frequency earth tester”) result in only a fraction of the instrument’s current flowing through the grounding system under test. A significant portion of the current travels up the tower, flows through the shield wires, and is dispersed into the grounding systems of adjacent structures, as schematically illustrated in
Figure 2. Consequently, the measured resistance reflects the parallel resistance of multiple interconnected grounding systems rather than the resistance of the individual structure under test.
One possible solution to the aforementioned challenge consists of directly measuring the true current injected into the tower-footing electrodes. This can be achieved using an external current transformer placed around the down conductor connected to the grounding electrode, as shown in
Figure 2 on one of the tower legs [
11]. If the tower-footing grounding system is symmetrical and the current can be assumed to be equally divided among the tower legs, this technique can be efficiently applied. Otherwise, the current should be measured individually at each leg, followed by a post-processing step to determine the grounding resistance. Alternatively, a single measurement can be performed using four current transformers, capturing the total injected current directly. The complexity of the technique increases in the case of guyed towers, where the current injected through each guy wire must also be measured. In practical applications, special attention should be given to ensuring that the diameter of the current transformer is compatible with high-voltage TL towers.
Among the techniques described, the most commonly used solution by power utilities for measuring tower-footing grounding resistance is the traditional FOP method combined with the so-called high-frequency earth meters, which eliminate the need to disconnect shield wires or grounding electrodes from the tower, enabling safer and more practical measurements. The operation of these meters is based on the principle that, at the frequency of the injected current—typically 25 kHz for commercial instruments—the inductive reactance of the shield wires is much higher than the tower-footing resistance, effectively preventing current diversion to the shield wires. However, recent studies have raised questions about the use of high-frequency earth testers, suggesting that they may lead to significant errors, with increased deterioration in the quality of measurements, particularly in cases of structures with two or more shield wires and transmission lines installed in regions with high-resistivity soils [
15].
Considering the aforementioned context, the main contribution of this work is to present a comprehensive analysis of the accuracy of the measurement results provided by high-frequency earth testers based on extensive simulation results covering various tower configurations, span lengths, and soil resistivities, as well as field measurements of a real TL tower-footing grounding system. Contrary to what has been suggested, as long as proper precautions are taken in the application of the FOP method, high-frequency earth testers can accurately characterize the tower-footing grounding impedance at the instrument’s operating frequency. This holds true for towers with adjacent span lengths of approximately 300 m to 400 m or greater, depending on the number of shield wires present in the structure under test, and for a wide range of soil resistivities. To the best of the authors’ knowledge, the presented results and analyses are novel and provide valuable guidelines for using high-frequency earth testers to evaluate the performance of tower-footing grounding systems.
This paper is organized as follows:
Section 2 describes the tower geometries analyzed in this study.
Section 3 presents the tower-footing grounding configurations and describes the electromagnetic model used in calculations.
Section 4 discusses the characterization of tower-footing grounding systems for lightning performance studies of transmission lines.
Section 5 evaluates the accuracy of high-frequency earth testers through simulations, considering line structures with one and two shield wires, a wide range of span lengths, and varying soil resistivities.
Section 6 presents experimental results of tower-footing ground resistance measurements, complementing the findings obtained from the simulations. Finally, a summary and the main conclusions are presented in
Section 7. Additionally,
Appendix A provides information on earth testers used in the measurements.
3. Tower-Footing Grounding Configurations and Electromagnetic Modeling
The tower-footing grounding system of the towers is illustrated in
Figure 4 (where
is 6 m or 7 m, and
is 20 m or 30 m for the 138 kV and 230 kV lines, respectively). It consists of four counterpoise wires of length
with a diameter of 0.9525 cm and buried at a depth of 0.5 m.
Different approaches are found in the literature for modeling grounding electrodes based on circuit theory [
16,
17], transmission line theory [
8,
18], and electromagnetic field theory [
7,
19,
20,
21,
22]. In this paper, the Hybrid Electromagnetic Model (HEM) is used to model the tower-footing grounding electrodes [
7]. The HEM is a computational method developed for the numerical analysis of lightning-related problems [
23]. The HEM follows a hybrid electromagnetic circuit approach, employing electromagnetic theory to compute the coupling among system elements through a numerical implementation of fundamental EM equations, including propagation effects, with the results expressed in circuital quantities such as voltages and currents. Computations are performed in the frequency domain, and time-domain results can be obtained through inverse Fourier or Laplace transforms.
The HEM model discretizes grounding electrodes into several filamentary segments, associating two distinct types of electromagnetic field sources with each segment: (i) transversal current and (ii) longitudinal current. The transversal current is a leakage current that crosses the segment surface and spreads into the surrounding medium—the soil in the case of grounding electrodes. It is associated with a conservative electric field, which produces a potential rise on the segment itself and on all other segments relative to remote earth. It is responsible for self and mutual conductive and capacitive coupling between the discretized segments of the grounding electrodes. The longitudinal current, which flows along the segment, is associated with a non-conservative electric field that establishes a voltage drop along the segment itself and contributes to the voltage drop in all other segments. It is responsible for self and mutual inductive coupling between the segments.
The electromagnetic couplings described above, including propagation effects, which become increasingly relevant at higher frequencies, are computed using the electric scalar potential and the magnetic vector potential. The final solution is expressed in terms of the following system of linear equations, computed for each frequency:
where
is the vector of nodal voltages,
is the vector of nodal injected currents, and
is the grounding admittance matrix, which expresses the electromagnetic coupling between the grounding system elements.
In the simulations, the injected current is assumed to be equally divided between the ends of the counterpoise wires, which are connected to the tower base. Once the system in Equation (1) is solved for each frequency, the nodal voltages are computed, and the harmonic grounding impedance is obtained as the ratio between the resulting nodal voltage and the injected current, considering a range of frequencies relevant to the phenomenon under investigation. It is worth noting that, at DC, the harmonic impedance converges to the so-called low-frequency grounding resistance,
. Additionally, the soil resistivity and permittivity were assumed to be frequency-dependent according to the model proposed by Alipio and Visacro in [
24] and recommended for lightning-related studies by CIGRE [
25].
Comprehensive details on the HEM can be found in [
7,
23], with its experimental validation—considering different grounding electrode configurations—thoroughly documented in [
26,
27,
28,
29,
30].
Although the grounding system is more appropriately represented by an impedance in lightning performance studies, in most cases, transmission line utilities determine the total length of each counterpoise leg based on a threshold value of the low-frequency grounding resistance (
) [
5]. In this context, for a given soil resistivity, the total length of grounding electrodes is typically increased until either the threshold value of grounding resistance is reached or a maximum counterpoise wire length is achieved. In this paper, the following criterion based on typical engineering practices was considered: for a given soil resistivity, the counterpoise length
increased from a minimum of 10 m in 5 m increments until the grounding resistance was equal to 20 Ω or less, or until a length of 120 m was reached. To cover a wide range of soil resistivities, ranging from low to high values, eight resistivities were considered: 250 Ωm, 500 Ωm, 1000 Ωm, 2000 Ωm, 3000 Ωm, 5000 Ωm, 7500 Ωm, and 10,000 Ωm.
Table 1 shows the lengths
defined for each soil resistivity and for both the 138 kV and 230 kV lines, along with the grounding resistance values (indicated in parentheses), which were obtained through simulations using the HEM.
According to
Table 1, the length of counterpoise wire required to achieve the 20 Ω grounding resistance criterion increases with increasing soil resistivity. Also, note that in the case of soils with higher resistivity, the value of
was greater than 20 Ω, indicating that four counterpoise wires of 120 m were not sufficient to reach the threshold value. It is also observed in
Table 1 that, for the same counterpoise wire length, the grounding resistance for the 230 kV line was slightly lower than that obtained for the 138 kV line. This occurs because, although the grounding electrode arrangement was the same, the tower base dimensions (
in
Figure 4) of the 230 kV line are larger, as well as the distance between counterpoise wires when running in parallel (
in
Figure 4). The increases in both
and
reduces the electromagnetic coupling effect between electrodes, resulting in a slightly lower grounding resistance.
4. Characterization of the Tower-Footing Grounding for Studies of the Lightning Performance of Transmission Lines
Due to the impulse nature of lightning currents, which exhibit a broad frequency range from DC to several MHz [
31], the behavior of grounding systems varies across these frequencies. Notably, capacitive and inductive effects become significant, requiring the representation of the grounding system by a frequency-dependent impedance known as harmonic impedance [
32]. Despite this, the quality of tower-footing grounding systems in practical transmission line projects is often evaluated using compact parameters, typically either the low-frequency grounding resistance or resistance measured at 25 kHz [
15]. This practice is largely justified by the commercial availability of both ordinary and high-frequency earth testers and their widespread application alongside the established fall-of- potential method.
This section outlines the differences between the harmonic grounding impedance,
, the low-frequency grounding resistance,
, and the 25 kHz resistance,
. To clarify these distinctions, the harmonic impedance of the grounding configuration depicted in
Figure 4 was calculated across a frequency spectrum from 10 Hz to 1 MHz using the electromagnetic model described in
Section 3.
4.1. Harmonic Impedance, Low-Frequency Resistance and 25-kHz Resistance
Figure 5 illustrates the harmonic grounding impedance computed in a frequency range from 10 Hz to 1 MHz, showing both the magnitude (blue line,
y-axis on the left) and phase (red line,
y-axis on the right) of the grounding system depicted in
Figure 4, and assuming soil resistivities of (a) 250 Ωm, (b) 500 Ωm, (c) 1000 Ωm, (d) 2000 Ωm, (e) 3000 Ωm, (f) 5000 Ωm, (g) 7500 Ωm, and (h) 10,000 Ωm. The results in
Figure 5 consider the dimensions of the 138 kV tower, i.e.,
m and
m, along with the lengths indicated in
Table 1. Qualitatively similar results were observed when considering the dimensions of the 230 kV tower.
According to the results, up to about 1 kHz, the harmonic impedance exhibits a nearly constant value and a zero-phase angle; that is, it behaves as a pure resistance, which corresponds to the so-called low-frequency grounding resistance,
. As the frequency increases, a decrease in the magnitude of
is observed. As detailed in [
33], such a decrease is attributed to two main effects. The first is the capacitive effect due to the dispersion of displacement currents from the electrode to the earth, as can be identified by the negative phase angle of the impedance in
Figure 5. The second is the frequency dependence of the soil parameters, notably the decrease in soil resistivity with increasing frequency. After further increasing the frequency, the inductive behavior begins to influence the grounding behavior, and in the higher frequency range, the inductive effect prevails, as indicated by the dominance of a positive phase angle of the impedance. In general, the capacitive effect is beneficial for the performance of the grounding system, while the inductive effect tends to impair it.
It is worth mentioning that, assuming typical/practical grounding configurations of transmission towers, both the capacitive effect and the decrease in soil resistivity with frequency become more pronounced as the low-frequency soil resistivity increases. This explains the more significant relative decrease in harmonic impedance for soils with higher resistivity in the frequency range where the capacitive effect dominates. Additionally, it is generally observed that the magnitude of the impedance at 25 kHz—referred to here for simplicity as the 25-kHz resistance, —is lower than the low-frequency grounding resistance, i.e., .
4.2. Comparison Between Low-Frequency Resistance and 25-kHz Resistance
Table 2 summarizes the values of
and
for both the 138 kV and 230 kV lines and percentage ratio between these quantities, computed as
. Confirming the results of
Section 4.1, for both TLs, it is observed that
, and that the percentage difference becomes more significant as the soil resistivity increases. Additionally, the ratio
decreases with increasing soil resistivity, indicating that the 25 kHz resistance becomes relatively smaller than the low-frequency resistance.
A key conclusion drawn from the results is that the resistance measured at 25 kHz using a high-frequency earth tester differs from the traditional low-frequency resistance, which is typically measured with ordinary earth testers that are commonly used to assess the grounding systems of other electrical installations, such as substations. In the case of high-voltage TLs, the low-frequency resistance can be measured using an ordinary earth tester, provided that the shield wires are disconnected from the tower or, alternatively, the grounding electrodes are disconnected from the base of the tower.
A question that may arise is why was there an expectation that using high-frequency meters would yield a value similar to the low-frequency resistance? Presumably, this expectation stems from a misunderstanding that the high-frequency behavior of grounding electrodes is dominated solely by the inductive effect, neglecting the capacitive effect. Indeed, CIGRE Technical Brochure 275—Methods for Measuring the Earth Resistance of Transmission Towers Equipped with Earth Wires—states that “the earthing can be simply described as a resistance in series with an inductance” [
11]. According to the same reference, the grounding impedance is a pure resistance and remains constant and equal to its DC resistance up to a cutoff frequency located around several tens to hundreds of kHz, after which it increases due to the inductive effect. Thus, assuming the typical frequency of 25 kHz used in commercial high-frequency earth testers, there would be an expectation that the grounding impedance would be essentially flat from low frequencies up to the range of several kHz. However, this occurs only in specific cases, notably long grounding electrodes buried in soils with low or very low resistivity [
32].
A second important point is that, contrary to the claims sometimes made by earth tester manufacturers, the value measured at 25 kHz is not necessarily more representative for lightning performance studies of the line simply because it employs a higher frequency signal. In fact, lightning currents do not present a single representative frequency but a spectrum of frequencies ranging from DC up to several MHz, depending on the rise time of the current. It is also a common belief in practice that the 25 kHz frequency is representative of the standardized 10/350 µs waveform, which several guidelines [
34,
35,
36] assume to represent the first positive lightning impulse. This idea is based on the fact that, assuming a sinusoidal waveform of 25 kHz, the time interval from zero to the maximum value would be equal to T/4 = 10 µs, where T is the period given by T = 1/25 kHz. However, it is important to stress again that actual lightning currents contain a broad frequency spectrum and not a single frequency. Moreover, for the purposes of assessing the lightning performance of transmission lines, negative lightning is much more significant than positive lightning, with the front-time of typical negative downward first strokes being on the order of 4 µs [
1,
37,
38].
6. Experimental Results
Measurements of the tower-footing ground resistance for a few towers of a 500-kV transmission line located in the northeast region of Brazil were conducted. For confidentiality reasons, not all these measurements can be disclosed, and, therefore, this section focuses on one of these measurements involving the guyed structure shown in
Figure 11a, which corresponds to the dominant structure of the mentioned transmission line. It is worth noting that, despite the difference in tower topology between the one used for measurements and those considered in the simulations, the most relevant factor in analyzing the accuracy of HF earth tester measurements is the number of shield wires, as it directly affects the current division between the tower-footing grounding system and the shield wires. Therefore, the results obtained from this measurement campaign can be considered representative of those from simulations for self-supporting towers with two shield wires. The grounding configuration of the tower, along with the dimensions of the grounding electrodes, is shown in
Figure 11b. The connections of the central mast and the guy wires to the grounding systems are depicted in
Figure 11c and
Figure 11d, respectively. The length of the spans adjacent to the tested tower were 435 m and 465 m.
To measure the tower-footing ground resistance, the fall-of-potential (FOP) method was used [
10]. As briefly described in the Introduction, this method involves applying a current to the grounding system under test through a current-return probe and recording the voltage drop between the grounding system and a potential probe. To prevent electromagnetic coupling between the grounding system under test and the current probe, the latter should be placed at a sufficiently large distance from the former. Additionally, the placement of the potential probe is critical, as it must be located in a region free from interference from both the grounding system under test and the current-return probe. A practical approach to verify whether the potential probe is unaffected by other electrodes is to take multiple resistance measurements while repositioning it between the grounding system under test and the current probe. If two or three consecutive readings show negligible variation, the mean value of these readings can be considered representative of the true grounding resistance (flat slope method).
Considering the details described for the consistent application of the FOP method, the experimental setup depicted in
Figure 12 was assembled. The current circuit was laid out perpendicular to the line axis, and the current probe—composed of four ground rods in parallel, each one meter in length—was placed 200 m away from the tower’s central mast. The voltage circuit was also laid out perpendicular to the line axis, and the potential probe was placed at three positions: 119 m, 132 m, and 145 m from the mast. For each position, the grounding resistance was measured. If the difference between the measurements did not exceed 5%, the average of the three values was assumed as the true resistance (flat slope method) [
10]. A shielded cable was used for the current lead in all measurements.
Measurements were conducted using the fall-of-potential method under two distinct conditions:
The measurement results are presented in
Table 3. Additionally, a description of the high-frequency and conventional low-frequency earth testers used is provided in the
Appendix A.
The resistivity at the location where the tower-footing grounding electrodes were buried was determined from the measured low-frequency resistance based on the relationship
, where
is a constant related to the electrode geometry, which is known since the tower-footing grounding geometry is available (
Figure 11b). The parameter
represents the so-called apparent resistivity, that is, the resistivity of a homogeneous equivalent soil in which the tower-footing grounding system would present the same low-frequency grounding resistance. Based on the measured
, the apparent soil resistivity was estimated to be approximately 7715 Ωm.
It is observed that the
value measured with the grounding electrodes disconnected is approximately 8% higher than the value measured without disconnection. This discrepancy is presumably due to a small current that is still diverted to the shield wires instead of being injected into the grounding system under test. In addition, part of the difference between the two measured values can be attributed to the fact that, when measuring with the grounding electrodes disconnected, the resistance value tends to be higher than the actual value, as the contribution of the structure’s foundations is not considered. This percentage difference of ~8% is considered acceptable in practical terms, given the uncertainties involved in tower-footing grounding measurements. These findings align with the conclusions from
Section 5 and confirm that, considering that the tested tower has two shield wires, the high-frequency earth tester provides a reliable estimate of
for the considered lengths of adjacent spans (>400 m).
Comparing the values of
and
, both measured with the grounding electrodes disconnected from the tower mast and guy wires,
is approximately 47% of
. This result aligns well, within the measurement uncertainties, with the same ratio found through simulations presented in
Table 2 for high-resistivity soils.
To further analyze the measurements,
Figure 14 shows the computed magnitude of the harmonic grounding impedance for the arrangement depicted in
Figure 11b. The harmonic grounding impedance was computed using the HEM model, considering the grounding electrode arrangement of the tested tower depicted in
Figure 11b and assuming the determined apparent soil resistivity of 7715 Ωm. Additionally, frequency-dependent soil parameters were considered according to the Alipio–Visacro model, as described in
Section 3. The diamond marker in the same figure represents the measured
value. It can be observed that the computed harmonic impedance exhibits a behavior similar to that shown in
Figure 5: it remains nearly constant up to a few kHz (equal to the low-frequency resistance,
), then decreases with increasing frequency due to capacitive effects, and finally increases at higher frequencies due to inductive behavior. Notably, an impressive outcome from
Figure 14 is the excellent agreement between the computed and measured harmonic impedance at 25 kHz.
7. Summary and Conclusions
This paper presented a comprehensive assessment of the accuracy of the results provided by widely used high-frequency earth meters for measuring the tower-footing ground resistance of transmission line structures based on both simulations and experimental results.
The simulations presented in this work, supported by experimental data, demonstrate that high-frequency earth meters consistently provide reliable estimates of the tower-footing resistance/impedance at the instrument’s operating frequency, considering typical span lengths and a wide range of soil resistivities. For the tower geometries analyzed in this study, high-frequency earth meters were shown to deliver accurate measurements for towers with adjacent span lengths of approximately 300 m and 400 m, corresponding to configurations with one and two shield wires, respectively. Furthermore, acceptable results (errors below 10%) were observed for span lengths exceeding 200 m and 300 m under the same conditions. Although the conclusions drawn cannot necessarily be considered valid for all line configurations, they provide a very good first set of guidelines.
It is worth mentioning that these conclusions were obtained under the assumption of good engineering practices in the design of the tower-footing grounding system, ensuring that the grounding resistance remains below a reasonable threshold. In cases where the tower-footing ground resistance is excessively high, poor measurement accuracy is expected when using high-frequency earth meters, particularly for structures with two shield wires. Additionally, such meters are not recommended for very short spans, as the inductive reactance of the span may be comparable to the grounding resistance of the tower under test.
As discussed, considering the frequency used by the earth tester, what is measured is not the tower-footing resistance at the industrial frequency but rather the magnitude of the harmonic impedance at the instrument’s operating frequency, typically 25 kHz when assuming commercial instruments. As demonstrated through simulations using an accurate electromagnetic model and typical grounding system conditions for transmission lines, due to the capacitive effect and the frequency dependence of soil parameters, the impedance value at 25 kHz—referred to in this paper simply as the 25-kHz resistance ()—is expected to be lower than the tower-footing resistance at the industrial frequency.
Although the value provided by high-frequency earth meters is not the resistance at the industrial frequency, its significance lies in providing an accurate measure of the grounding impedance at the instrument’s operating frequency, which can be used to evaluate the condition of the tower-footing grounding system. Additionally, measurements taken by the HF earth meter at different times of the year can help evaluate the impacts of seasonal variations through comparisons of the values measured across different periods. Furthermore, measuring the grounding system after an outage can reveal any underlying issues or damage, such as corrosion, that might have contributed to the outage itself. Finally, using an electromagnetic model and knowing the geometry of the electrode arrangement of the tower-footing grounding system, the resistance at industrial frequency can be estimated from the measured value through an inversion process if required or deemed necessary.
In general, it can be concluded that, provided that the fall-of-potential method is properly applied, high-frequency earth meters can be used to effectively assess the performance of tower-footing grounding systems in high-voltage transmission lines in most practical cases.