Design Scenarios and Risk-Aware Performance Framework for Modular EV Fast Charging Stations
Abstract
1. Introduction
2. Literature Review
3. Used Methodology
- A configuration space is defined as follows:
- 2.
- The three criteria as functions on are defined as follows:
- The total theoretical power class is defined as a function of the class interval:with distinctions on :
- There is a unique dominant type only if some power has strictly the most columns, i.e., if:then the function:is:
- The peak power risk is defined as based on the simulation, exists and:as stepwise classification:
- 3.
- A combined grouping is made as an equivalence by defining the combined label (group) of configuration :A relation ~ on is introduced:Obviously ~ equivalence (reflexive, symmetric, transitive) therefore induces a partition of into equivalent classes (the studied groups).The maximum number of different combinations is:but some of them may be empty (impossible combinations under the imposed constraints).The class is defined for every actually encountered group :
- 4.
- Aggregated indicators by groups are defined as follows:Let be an arbitrary metric (e.g., ).
- Group average value is:In particular:
- Group extrema are:
- The number of configurations in each combination is written with indicator functions:
- 5.
- The connection to the simulation data is made in the following way:
- and are determined by (purely combinatorial/algebraic functions).
- depends on the simulation result through (stochastic component). The realized value with fixed parameters and generator (seed) in this study is used. Alternatively, it is also defined on probabilities/quantile estimation:for selected thresholds , . A single simulation with calibration and a fixed seed is used in the analysis for repeatability and comparability.
- Non-Homogeneous Poisson Process (NHPP): The intensity is a function of time (hour of the day/day of the week). The probability of assigning a free column with discretization is:The intensity in practice can be semi-constant (off peak/shoulder/peak) or smooth (mix of Gaussian bells for morning/evening peak). The calibration aims for the average value of to reproduce the base load.
- Markov Modular Arrival (MMPP): The “low–medium–high load” regimes are described by a continuous Markov process with transitions between states and corresponding intensities . This allows for random alternations of “peak windows” with average durations given by a matrix .
- Self-amplifying process (Hawkes): The intensity is used to model clustering (e.g., short “waves” of arrivals):where is a deterministic background (e.g., NHPP), and govern the strength and memory of the clusters. A condition for stability is that the effective branching coefficient is <1.
- 6.
- The practical interpretation of combined grouping is expressed as follows:The combined label:brings together the three points of view:
- Scale (how “heavy” the column installation is relative to the 500 kW limit)—via ;
- Structure (dominant power level or mixed profile)—via ;
- Operational risk of peak load—via (function from the simulation).
4. Numerical Realization
4.1. Input Data
- Configuration input data: These are parameters that determine the structure of the station:
- Each configuration is represented by a four-dimensional vector , where , with being the number of columns with power , . There are exactly 10 columns in total in the study.
- The theoretical total power of the configuration is , i.e., this is the sum of the nominal powers of all 10 columns.
- Simulation input data: The charging station load dynamics over time in the simulation model is described by:
- Time parameters:Time horizon: 3 hSimulation step: 5 minNumber of steps:
- Limit per station: Maximum total power for the station: .If the requested power from all active columns exceeds 500 kW, a proportional limit is applied.
- Arrival parameters of electric vehicles: The probability of a car arriving at a free column is , i.e., the probability of a new charge at each step for each free column.
- Customer energy demand profile: Customers are divided into three groups, each with a probability and range of demand—Table 1. Upon arrival, the car’s energy demand is randomly selected according to this discrete probability structure.
4.2. Input Data Processing
- Theoretical power class (classifies the size of the column power):
- Low (≤250 kW)
- Medium (251–350 kW)
- High (>350 kW)
- Dominant column type (which column type is the most numerous in the configuration):
- 20 kW/30 kW/40 kW/50 kW
- Mixed (if there is no clearly expressed dominant type)
- Risk of overload (based on simulated peak):
- No risk:
- Moderate risk:
- High risk:
- The following are calculated:
- The theoretical power for each configuration.
- The dominant column type.
- The simulated maximum power used ⇒ risk classification.
- A new variable “Group” is created:
- The configurations (all 286) are grouped according to this triplet, and there are calculated for each group the following:
- Number of elements
- Average efficiency:
- Average load
- The groups with a non-zero number are displayed in Table 2—resulting in 16 unique groups.
- Summarizes data → instead of analyzing 286 rows, 16 summarized cases are worked on.
- Gives an idea of typical configurations—what behavior to expect for a given structure and power.
- Allows quick selection of a group by criterion: e.g., high efficiency, low risk, etc.
- Serves as a basis for Pareto analysis and strategic selection of configurations.
- Charging station configurations: The model considers 286 different configurations that cover different distributions of charging columns with different powers (20, 30, 40, and 50 kW).
- Car traffic: A random distribution of loading requests with predefined probabilities for each column is used to model car traffic, where a new customer is attempted on each free column with probability .
- Energy profiles: The distribution of customer energy needs is divided into three main groups (small, medium, and large batteries), with different energy range values used for each group (e.g., [10, 20] kWh for small batteries, [20, 40] kWh for medium, and [40, 70] kWh for large).
- Grid constraints: A scenario with limited grid capacity (500 kW) is simulated, which necessitates the application of proportional power distribution when the limit is reached.
- Risk profiles: The risk profile of each configuration is calculated based on the maximum power , with the risk classified into three categories: , , and .
- Vehicle arrival simulations: Models such as Non-Homogeneous Poisson Process (NHPP) and Markov Modular Processes (MMPP) are used to simulate non-stationary and burst scenarios, as well as Hawkes processes to model arrival clustering. All of these models are integrated into the simulation process, using parameters for the intensity of demand during different parts of the day (e.g., morning and evening peak).
- Monte Carlo simulations: Multiple Monte Carlo simulations are used to determine the risk categories for each configuration. This allows an assessment of the probability of reaching certain power levels and the risk of overload.
- Average Load Factor (): Measures the percentage of the charging station’s available power that is used.
- Power Efficiency (): The percentage of the charging station’s rated power usage.
- Peak Power (): The highest power level used in the simulation process.
- Risk Assessments: Each configuration is classified by risk using the probabilistic version of risk , calculating quantiles of for different load scenarios.
4.3. Numerical Results
4.4. Discussion of the Obtained Numerical Results
- Group No. 6 (Medium Class, 50 kW, No Risk) has the best combined and performance.
- The medium-power class gives the best average efficiency; the high class gives the highest , but with higher risk.
- Groups No. 6, 3, and 7 combine high performance with safety.
- Groups No. 13 and 16 offer the highest performance, but are associated with significant risk.
- The analysis supports the selection of configuration groups based on specific objectives: efficiency, load, or safety.
- Average efficiency of column usage (),
- Average network load factor (),
- Overload risk based on maximum power in the simulation.
- Group No. 6 (Medium, 50 kW, No Risk): highest efficiency—84.68%, and also high (59.28%) → best overall performance.
- Groups No. 3 and 7 also stand out with > 82% and good (>48%).
- Group No. 13 (High, 50 kW, High Risk): highest —73.48%, but with high risk.
- Group No. 16 (High, Mixed, High Risk): = 71.72%, also with high risk.
- Groups No. 12 and 15 achieve > 65% with moderate risk.
- Groups No. 6, 7, 3, and 5 are among the non-dominated in (, ); i.e., one indicator cannot be improved without worsening another.
- They achieve a good balance between efficiency and workload, without going outside the safe zone.
- Choosing a group should depend on the goal:
- For high performance at low risk—Group No. 6, 7, or 3.
- For maximum capacity—high-end risk groups (e.g., No. 13 or 16), but only if the infrastructure is provided.
- The medium-power class is the most flexible, as it maintains high efficiency and allows for significant load without exceeding the risk threshold.The simulations and analysis of the groups clearly show that:
- There is no universally best configuration, but Pareto-optimal groups exist;
- The choice should be based on operational objectives and context;
- Medium-sized plants, especially 50 kW or mixed configurations, are the most balanced in real conditions;
- High-end gives the highest load, but requires careful risk management.
5. Analysis of Applied Methodology and Obtained Results
- column efficiency (use of the nominal aggregate power);
- station load relative to the network limit ();
- risk of overload (by peak power).
- Arrival of cars (stochastics): At each step for each free column:where denotes a new client on port in step .The Bernoulli process by port and step is well approximated Poisson flow at a small step min (the events are independent and rare).The extended scenario is used , with all subsequent definitions of , and remaining unchanged.
- Energy demand (random): The customer is from group with probabilities and energy kWh.
- Physics of the feed and station constraint: The nominal power of port is kW. The sum of the requests in step is:where are the active ports (with remaining energy > 0). The station limit is kW and the proportional scaling is:
- Power class according to : .
- Dominant type —the most numerous type; in case of equality → “Mixed”.
- Risk according to .
- Combined label:
- A group is an equivalence class of size
- Group metrics: and
- By power class:
- Low (≤250 kW): , , no risk. Suitable for locations with low grid budget/low flow.
- Medium (251–350 kW): (best average efficiency), , mostly no risk. The “golden mean” for urban operation.
- High (>350 kW): , (maximum ), but moderate/high risk occurs, especially with 40/50 kW dominance.
- By dominant type:
- 20 kW dominance: high efficiency in low/mid-range, but lower ; risk is practically zero.
- 30 kW: balanced growth with minimal compromise in efficiency (mid-range remains risk-free).
- 40 kW: even higher ; moderate risk appears in high range.
- 50 kW: highest ; in high range often moderate/high risk. An excellent compromise in mid-range (Group No. 6) is seen: , , no risk.
- “Mixed”: often smooth profile (more even load), close to 40–5 kW dominance, but with more controllable risk.
- Pareto optimality ( vs. ):
- Group No. 6 (Medium/50 kW/No risk) is difficult to dominate: very high and high at zero risk.
- Groups like No. 13 and 16 have the highest in the “high class”, but high risk; useful in transit corridors/sites with EMS, but not as a base setting without control.
- Groups No. 7, 5, and 3 are close to the front at no risk; meaningful when security is a requirement.
6. Sensitivity and Sustainability
- Lower arrivals ()
- Higher arrivals ()
- Heavier batteries (0.35, 0.35, 0.30)
- Lighter batteries (0.6, 0.3, 0.1)
- Lower station limit (400 kW)
- Higher station limit (600 kW)
- Longer horizon (6 h)
- NHPP–Diurnal: The time intensity describes a two-peak day (morning/evening). Three plateau levels (off peak/shoulder/peak) with linear transitions (30 min) are used in discrete steps . The parameters are chosen so that the daily average reproduces the base load and the peak/intermediate/off-peak ratios fall within the empirically observed range.
- MMPP–Burst: A two-state Markov modulated Poisson process with states (low) and (high). The built-in CTMC (Continuous-Time Markov Chain, generator ) gives mean dwell times and , with state assignment probabilities . This generates random “burst” windows of increased demand with a preserved daily average.
- Hawkes–Cluster: Self-reinforcing process with deterministic background , set as the NHPP–Diurnal profile; , (subcritical branching). This gives rise to short clusters of arrivals (“waves”) that increase temporal correlation while preserving the total daily volume.
- At Higher arrivals (): increases (≈+3–4 pp), increases (≈+5–6 pp), risk is almost unchanged, but increases slightly.
- At Lower arrivals (): decreases (≈−6 pp), close to baseline or slightly decreases, risk decreases slightly.
- At Heavier batteries: decreases (≈+1–2 pp), increases (≈+2–3 pp), risk is almost unchanged; increases moderately.
- At Lighter batteries: decreases (~−1 pp), ≈ baseline, risk is without significant change.
- At Lower station limit (400 kW): increases strongly (~+12–13 pp by definition, because is relative to the limit), decreases (~−8–9 pp due to more frequent scaling), more Moderate Risk (High Risk ≈ 0 by definition of the threshold), average decreases towards the new ceiling.
- At Higher station limit (600 kW): increases (~+2–3 pp), increases (~+4–5 pp), risk does not worsen, and increases (more space for a peak).
- At Longer horizon (6 h): Average metrics ≈ base (naturally, because the process is stationary), increases slightly (the longer window gives a chance for a higher peak), the risk distribution remains similar.
- NHPP–Diurnal: A two-peaked daily profile (morning/evening) increases the average to 54.40% and to 83.20%, i.e., ≈+2.15 pp and +1.93 pp compared to the baseline (52.25%, 81.27%). The average increases moderately to 330 kW (+6.25 kW). The risk distribution shifts slightly: , , (versus 2/2/12 in the baseline), i.e., more moderate risk cases with preserved KPI definitions.
- MMPP–Burst: Randomly alternating “bursts” of search (two-state MMPP) give the strongest effect among the three on the average values: (+4.05 pp) and (+5.63 pp). (+10.75 kW). The risk increases noticeably: , , , i.e., with +1 more case in and compared to the base and more frequent proximity to the limit during the “burst” windows.
- Hawkes–Cluster: A self-amplifying (cluster) process on the same diurnal background leads to (+3.25 pp) and (+4.43 pp), with an average (+12.25 kW). The risk profile is the most unfavorable of the three: , , , which is +3 cases outside “” compared to the base; a reflection of the more intense short-term clustering of arrivals.
- At base: No Risk dominates (≈12 out of 16), there are two each in Moderate and High.
- At Higher arrivals and Heavier batteries: the number of No Risk remains ≈ the same; slight fluctuations between Moderate/High.
- At Lower station limit (400 kW): High Risk = 0 (it is impossible to exceed 450 kW), but Moderate Risk increases due to the easier reaching of 400–449 kW in relative units.
- All three non-stationary profiles increase the average and relative to the stationary base, but shift the distribution towards more hits (from 4/16 in the base to 5–7/16 in NHPP/MMPP/Hawkes). The highest average KPIs are given by MMPP–Burst, and the largest shift towards risk/peaks is given by Hawkes–Cluster; NHPP–Diurnal is intermediate and the most moderate as a compromise.
- At Higher arrivals: increases, increases, but remains No Risk; increases moderately.
- At Lower limit 400 kW: (in %) increases by definition, increases (by frequent scaling), risk remains controlled (most often No/Moderate).
- At Higher limit 600 kW: increases further, increases slightly, risk does not worsen.
- Base: often High Risk ( close to 500 kW).
- Higher arrivals/Heavier batteries: and go up; risk remains High.
- Lower limit 400 kW: High Risk drops (by definition), but drops significantly.
- Higher limit 600 kW: and go up, but goes up strongly, risk may remain high without EMS.
- At Low (≤250 kW): Metrics are stable, risk is practically always No Risk, lowered limit is not critical.
- At Medium (251–350 kW): Most stable class— remains high in almost all scenarios; reacts predictably to and limit, risk rarely increases.
- At High (>350 kW): Most sensitive to arrivals/weights/limits, grows rapidly, but so does , without EMS the risk easily exceeds thresholds at high flows.
- If a balance without risk is sought, Medium class should be chosen, especially configurations like Case 6, which are robust to fluctuations in flow and batteries.
- If maximum is sought, High class should be chosen, but with Higher arrivals/Heavier batteries the risk increases and EMS (dynamic limiting, prioritization) is needed; but if the limit is 400 kW, throughput in % will seem high, but drops, and care should be taken how is interpreted at different limits in this case.
- Increasing the network limit (600 kW) usually improves and without increasing the number of risk cases, but increases, which in turn requires checking for cables/transformer/taxes.
- The metrics are stable under small input variations, and the order of the quality groups does not change dramatically.
- The Medium class remains Pareto sensible in most scenarios.
- The High class is sensitive and requires operational control under higher flow or heavier batteries.
- Changing the limit strongly affects the interpretation of (relation to limit). For comparability between locations, the same reference limit should be maintained or normalized to 500 kW.
- The average metrics ( and ) remain close to the 3 h base, which is expected for a stationary input.
- Mean is higher than the 3 h base, because with a longer window the chance of a larger peak occurring increases.
- The risk distribution shifts slightly towards higher categories for the most aggressive configurations (especially the high-end with 50 kW), but most cases remain No/Moderate Risk.
- (6 h vs. 3 h): small positive change on average (~+0.5 to +1.2 pp)
- (24 h vs. 3 h): noticeable increase in peaks, up to +40 kW in some cases
- : very stable; varies slightly (~±1 pp), which shows stability with horizontal differences
- For : It varies minimally, in most cases between −0.5% and +1.5%; it stabilizes when the horizon is extended—the system retains its average load; a slight tendency to increase is observed at 24 h for high class cases (due to longer accumulation of customers).
- For : A moderate increase is observed at 6 h (up to +1.8 pp in some cases), especially for more powerful configurations; The efficiency increases even more clearly at 24 h up to +3.6 pp, since scaling (limitations) become less frequent at uniform load.
- For : The most sensitive indicator: An increase of 20–40 kW is observed compared to 3 h in many cases in 24 h simulations and this is expected, since the longer window increases the probability of a temporary peak; a decrease is seen in some lower classes (reduced probability of customer collision).
- Case 1 (Low class, 20 kW) is a stable Pareto leader at all horizons and it is an excellent choice for small stations without compromising .
- Case 3 (Medium class, 20 kW) dominates at 3 h and 24 h, as it has a stable efficiency growing over time.
- Cases 7 and 8 (Medium class, 30/40 kW mix) do not appear at 3 h, but stand out at a longer horizon and their efficiency grows steadily.
- Case 5 only enters at 24 h and balance occurs over a long period.
- At 3 h horizon: Case 1 and 3 are clear leaders, achieving good and very high ; no heavy configurations (high class) in Pareto.
- At 6 h horizon: Case 7 and 8 “turn on”, their efficiency increasing over time; Case 1 remains a stable leader.
- At 24 h horizon: The front is denser, but Cases 1, 3, 5, 7, and 8 remain stable; Case 5 enters as a new Pareto member.
7. Practical Implications for Planning and Management
- Planning by power class: If the goal is stability without risk in real daily fluctuations, (251–350 kW) with 50 kW dominant or “Mixed” is selected, retaining high and controllable risk even at peaks.
- Capacity vs. Risk: If the priority is maximum in environments with high peak demand (e.g., transit corridors), High class (50 kW dominant) is suitable, but necessarily with peak management measures (EMS: “fair share throttling”, prioritization, ToU tariffs, reservations/virtual queue).
- Peak monitoring: It is important to monitor not only the averages with non-stationary profiles, but also and “time above 90% of the limit”, i.e., key KPIs.
8. Recommended Design Strategy Based on Sustainable Pareto Configurations and Their Behavior at 3 h/6 h/24 h
- Which cases to prefer
- Tier A—“Safe maximum” (stable at all horizons):
- Case 1 (Low, 20 kW dominant) has the highest efficiency at zero risk; ideal for neighborhood/office locations and places with limited network capacity.
- Case 3 (Medium, 20 kW dominant) has excellent , Pareto balance at 3 h and 24 h; suitable for urban locations with moderate flow.
- Tier B—“Scalable balance” (rising at longer horizon)
- Case 7 (Medium, 30/40 kW Mixed) enters Pareto at 6 h/24 h; higher without significant risk.
- Case 8 (Medium, 20/30/40 kW Mixed) has stable growth at 6 h/24 h; good compromise for areas with variable flow.
- Case 5 (Medium, 40 kW dominant) becomes Pareto at 24 h; when looking for more in a long interval at controlled risk.
- When to choose which cases
- Limited network limit/low to moderate flow → Case 1: Minimal peaks, easy integration without additional infrastructure.
- Moderate and stable urban flow → Case 3: High , good , stable over 24 h; best “overall” value.
- Moderate/high flow with daily variations → Case 7 or 8: Growth of and with the horizon; good resilience to congestion.
- Looking for more without significantly increasing risk → Case 5: Works well with long intervals and slightly higher number of active simultaneously.
- Scaling path (phase)
- Start: Case 1 or 3 (relative to network limit and initial volumes).
- Observation (1–3 months): if Mean >55% and approaches the limit, move to Case 7.
- Optimization: if after 6–24 h of analysis >82% remains and the risk is No/Moderate, add elements from Case 5 for more .
- High Throughput: before moving to high-end, implement Energy Management System (EMS) (dynamic throttling, prioritization by SoC/time/subscription).
- Operational policies (highly recommended)
- Fair share throttling when the limit is reached (proportionally for all active ports) → stabilizes and reduces peaks.
- Grace windows + ToU tariffs (expensive during peak, cheaper outside of it) → offloading of loads → lower .
- Reservations/virtual queue → reduces collisions and provides a more even profile.
- Watch list KPI: (target: 50–60%), (target: ≥82%), and (response threshold), time share above 90% of the limit.
- Resize/Reconfiguration Triggers
- 0.85 × limit for ≥7 days → add 30/40 kW ports or move from Case 3 to Case 7 or 8.
- Average wait > 7–10 min at peak → increase share to 40 kW (to Case 5) or implement EMS.
- < 80% for 2+ weeks → likely over-rated or too low flow → step back to lighter mix (to Case 3 or 1).
- Infrastructure notes
- Cable cross-sections and protections for short peak loads should be provided for Case 7, 8 or 5.
- Transformer reserve should be checked against (and ), not just average power.
- Communication to EMS/SCADA should be prepared if a further step to high class is planned.
- How to document the choice (for approval/investors)
- The points of these cases on the Pareto should be shown.
- The delta table (3 h → 6 h → 24 h) should be applied. This is demonstrated sustainability.
- A scaling plan (criteria, timelines, KPIs, budget/CapEx/OpEx) should be added.
9. Conclusions
- Formulation of the space of 286 possible configurations by power types {20, 30, 40, 50 kW}.
- Grouping along three main axes: power class, dominant type, and risk, obtaining 16 real groups.
- Conducting simulations for each configuration, including sensitivity to different arrival scenarios, energy profiles, power limits, and time horizons (3 h, 6 h, 24 h).
- Deriving Pareto-optimal groups, i.e., those that cannot be improved in or without compromising the other metric.
- Identification of sustainable and risky configurations, with suggestions for strategic choices.
- The mid-range (251–350 kW) proved to be the most balanced. It achieves high efficiency (up to 85%) and (~55%) without significant risk.
- The dominant 50 kW configurations give the highest , but with increased risk, especially in the high range.
- Mixed types often have even profiles, good trade-offs, and controllable risk.
- The low range (≤250 kW) is stable and risk-free, but with limited capacity and is suitable for small locations.
- The high range configurations without EMS quickly enter the overload zone with increased flow or larger batteries.
- Extending the time horizon does not change the average metrics significantly, but increases the peaks, especially in Cases 13 and 14.
- Priority of the middle class, especially configurations like Case 6 (50 kW dominant, No Risk) and Case 7 and 3 (Mixed and 20 kW dominant).
- Use of high class only with EMS or in critical locations (e.g., transit corridors).
- Implementation of dynamic control mechanisms (EMS, prioritization), especially to deal with high risk at peak.
- Sensitivity analysis shows that changing parameters (arrivals, battery size, limits) can lead to a change in risk, especially in aggressive configurations.
- It is recommended for real implementation to use Pareto-optimal groups, summarizing classification along three axes, instead of comparing all configurations separately.
- Simplicity of models: The models used for charging station simulations are based on idealized assumptions and do not include all potential real-world factors, such as the impact of network failures, dynamic changes in charging tariffs, or changes in user behavior, which can lead to more complex scenarios.
- Limited number of configurations: The study only considered a limited set of charging station configurations (286 possible variations), which means that not all possible topologies and load scenarios are analyzed. It is possible that new configurations and settings have different results that are not considered.
- Demand forecasting: Customer arrival models and energy profiles are based on assumptions that may not fully reflect unexpected changes in the real world, such as uneven distribution of electric vehicles during the day or unusual loads during certain seasons.
- Assumptions about the intensity of processes: The non-stationarity simulated by models such as NHPP, MMPP, and Hawkes assumes that the intensity of demand changes to some extent in a predictable manner. In reality, however, these processes can be more complex and have a greater degree of randomness, which can lead to deviations from the predicted results.
- Improving traffic modeling: In the future, other customer arrival models that better reflect the complexity of real-world traffic and daily variations in consumer behavior, including those that take into account weather conditions, holiday periods, and regional differences, could be explored.
- Incorporating adaptive strategies: It is good to develop adaptive risk management strategies that can dynamically adjust the capacity and power of stations in real time, depending on the observed load and grid needs.
- Research into new configurations: It is possible to add new variants of charging stations with different topologies and capacities, expanding research into possible new combinations and their impact on efficiency and risk.
- Better integration with renewable sources: In the future, research could focus on integrating charging stations with renewable energy sources, such as photovoltaic panels or battery energy storage systems (BESS), to optimize the use of green energy and reduce peak loads.
- Monitoring and feedback: The development of intelligent monitoring and feedback systems that can detect deviations in real time and offer recommendations for optimization will help to manage charging stations more effectively in dynamic conditions.
- Extending time horizons: Studies can be extended to longer time horizons (e.g., 48 h or weekly analyses) to assess the efficiency of charging stations over longer periods and simulate different peak load scenarios, as well as the possible effects of seasonal changes in demand.
Author Contributions
Funding
Data Availability Statement
Acknowledgments
Conflicts of Interest
Appendix A
| Scenario | Case | Total [kW] | Power Class | Avg [kW] | [kW] | [kW] | [%] | [%] | Risk | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Baseline | 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 177.22 | 200 | 100 | 35.44 | 88.61 | No Risk |
| Baseline | 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 203.33 | 240 | 130 | 40.67 | 84.72 | No Risk |
| Baseline | 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 203.33 | 230 | 120 | 40.67 | 88.41 | No Risk |
| Baseline | 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 184.44 | 220 | 90 | 36.89 | 83.84 | No Risk |
| Baseline | 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 196.11 | 250 | 70 | 39.22 | 78.44 | No Risk |
| Baseline | 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 238.33 | 300 | 90 | 47.67 | 79.44 | No Risk |
| Baseline | 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 267.5 | 350 | 130 | 53.5 | 76.43 | No Risk |
| Baseline | 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 231.11 | 310 | 70 | 46.22 | 74.55 | No Risk |
| Baseline | 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 259.17 | 320 | 100 | 51.83 | 80.99 | No Risk |
| Baseline | 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 291.94 | 350 | 30 | 58.39 | 83.41 | No Risk |
| Baseline | 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 245 | 290 | 80 | 49 | 84.48 | No Risk |
| Baseline | 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 318.89 | 400 | 120 | 63.78 | 79.72 | Moderate Risk |
| Baseline | 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 402.78 | 500 | 100 | 80.56 | 80.56 | High Risk |
| Baseline | 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 353.06 | 450 | 140 | 70.61 | 78.46 | High Risk |
| Baseline | 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 315.28 | 370 | 90 | 63.06 | 85.21 | No Risk |
| Baseline | 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 292.5 | 400 | 100 | 58.5 | 73.12 | Moderate Risk |
| Lower arrivals () | 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 161.67 | 200 | 60 | 32.33 | 80.83 | No Risk |
| Lower arrivals () | 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 191.39 | 240 | 80 | 38.28 | 79.75 | No Risk |
| Lower arrivals () | 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 169.72 | 230 | 0 | 33.94 | 73.79 | No Risk |
| Lower arrivals () | 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 172.22 | 220 | 50 | 34.44 | 78.28 | No Risk |
| Lower arrivals () | 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 188.89 | 250 | 0 | 37.78 | 75.56 | No Risk |
| Lower arrivals () | 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 200.83 | 270 | 0 | 40.17 | 66.94 | No Risk |
| Lower arrivals () | 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 240.56 | 350 | 30 | 48.11 | 68.73 | No Risk |
| Lower arrivals () | 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 220 | 270 | 60 | 44 | 70.97 | No Risk |
| Lower arrivals () | 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 238.61 | 320 | 110 | 47.72 | 74.57 | No Risk |
| Lower arrivals () | 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 240 | 300 | 170 | 48 | 68.57 | No Risk |
| Lower arrivals () | 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 220.83 | 270 | 100 | 44.17 | 76.15 | No Risk |
| Lower arrivals () | 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 304.44 | 400 | 40 | 60.89 | 76.11 | Moderate Risk |
| Lower arrivals () | 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 351.39 | 500 | 200 | 70.28 | 70.28 | High Risk |
| Lower arrivals () | 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 292.22 | 450 | 50 | 58.44 | 64.94 | High Risk |
| Lower arrivals () | 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 251.67 | 370 | 130 | 50.33 | 68.02 | No Risk |
| Lower arrivals () | 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 290.56 | 400 | 80 | 58.11 | 72.64 | Moderate Risk |
| Higher arrivals () | 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 181.11 | 200 | 100 | 36.22 | 90.56 | No Risk |
| Higher arrivals () | 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 222.78 | 240 | 100 | 44.56 | 92.82 | No Risk |
| Higher arrivals () | 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 206.11 | 230 | 70 | 41.22 | 89.61 | No Risk |
| Higher arrivals () | 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 201.39 | 220 | 150 | 40.28 | 91.54 | No Risk |
| Higher arrivals () | 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 229.44 | 250 | 150 | 45.89 | 91.78 | No Risk |
| Higher arrivals () | 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 260 | 300 | 60 | 52 | 86.67 | No Risk |
| Higher arrivals () | 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 290 | 350 | 100 | 58 | 82.86 | No Risk |
| Higher arrivals () | 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 264.72 | 310 | 120 | 52.94 | 85.39 | No Risk |
| Higher arrivals () | 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 259.17 | 320 | 120 | 51.83 | 80.99 | No Risk |
| Higher arrivals () | 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 306.67 | 350 | 150 | 61.33 | 87.62 | No Risk |
| Higher arrivals () | 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 262.5 | 290 | 60 | 52.5 | 90.52 | No Risk |
| Higher arrivals () | 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 331.11 | 400 | 40 | 66.22 | 82.78 | Moderate Risk |
| Higher arrivals () | 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 420.83 | 500 | 300 | 84.17 | 84.17 | High Risk |
| Higher arrivals () | 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 383.33 | 450 | 130 | 76.67 | 85.19 | High Risk |
| Higher arrivals () | 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 324.44 | 370 | 220 | 64.89 | 87.69 | No Risk |
| Higher arrivals () | 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 350.28 | 400 | 200 | 70.06 | 87.57 | Moderate Risk |
| Heavier batteries | 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 182.78 | 200 | 100 | 36.56 | 91.39 | No Risk |
| Heavier batteries | 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 214.72 | 240 | 110 | 42.94 | 89.47 | No Risk |
| Heavier batteries | 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 191.94 | 230 | 90 | 38.39 | 83.45 | No Risk |
| Heavier batteries | 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 196.39 | 220 | 120 | 39.28 | 89.27 | No Risk |
| Heavier batteries | 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 223.61 | 250 | 30 | 44.72 | 89.44 | No Risk |
| Heavier batteries | 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 235.83 | 300 | 60 | 47.17 | 78.61 | No Risk |
| Heavier batteries | 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 287.78 | 350 | 190 | 57.56 | 82.22 | No Risk |
| Heavier batteries | 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 247.78 | 310 | 80 | 49.56 | 79.93 | No Risk |
| Heavier batteries | 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 246.94 | 300 | 80 | 49.39 | 77.17 | No Risk |
| Heavier batteries | 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 301.67 | 350 | 170 | 60.33 | 86.19 | No Risk |
| Heavier batteries | 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 243.33 | 290 | 100 | 48.67 | 83.91 | No Risk |
| Heavier batteries | 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 327.78 | 400 | 120 | 65.56 | 81.94 | Moderate Risk |
| Heavier batteries | 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 401.39 | 500 | 200 | 80.28 | 80.28 | High Risk |
| Heavier batteries | 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 366.67 | 410 | 230 | 73.33 | 81.48 | Moderate Risk |
| Heavier batteries | 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 327.22 | 370 | 100 | 65.44 | 88.44 | No Risk |
| Heavier batteries | 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 321.39 | 400 | 120 | 64.28 | 80.35 | Moderate Risk |
| Lighter batteries | 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 175.56 | 200 | 100 | 35.11 | 87.78 | No Risk |
| Lighter batteries | 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 205.28 | 240 | 120 | 41.06 | 85.53 | No Risk |
| Lighter batteries | 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 190.28 | 230 | 60 | 38.06 | 82.73 | No Risk |
| Lighter batteries | 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 188.06 | 220 | 60 | 37.61 | 85.48 | No Risk |
| Lighter batteries | 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 199.44 | 250 | 50 | 39.89 | 79.78 | No Risk |
| Lighter batteries | 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 229.17 | 270 | 90 | 45.83 | 76.39 | No Risk |
| Lighter batteries | 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 262.22 | 350 | 40 | 52.44 | 74.92 | No Risk |
| Lighter batteries | 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 244.17 | 310 | 80 | 48.83 | 78.76 | No Risk |
| Lighter batteries | 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 253.89 | 320 | 100 | 50.78 | 79.34 | No Risk |
| Lighter batteries | 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 281.11 | 350 | 30 | 56.22 | 80.32 | No Risk |
| Lighter batteries | 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 238.33 | 290 | 80 | 47.67 | 82.18 | No Risk |
| Lighter batteries | 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 320 | 400 | 200 | 64 | 80 | Moderate Risk |
| Lighter batteries | 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 397.22 | 500 | 250 | 79.44 | 79.44 | High Risk |
| Lighter batteries | 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 372.22 | 450 | 180 | 74.44 | 82.72 | High Risk |
| Lighter batteries | 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 278.61 | 370 | 80 | 55.72 | 75.3 | No Risk |
| Lighter batteries | 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 314.72 | 400 | 130 | 62.94 | 78.68 | Moderate Risk |
| Lower Station limit (400 kW) | 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 177.22 | 200 | 100 | 44.31 | 88.61 | No Risk |
| Lower Station limit (400 kW) | 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 203.33 | 240 | 130 | 50.83 | 84.72 | No Risk |
| Lower Station limit (400 kW) | 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 203.33 | 230 | 120 | 50.83 | 88.41 | No Risk |
| Lower Station limit (400 kW) | 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 184.44 | 220 | 90 | 46.11 | 83.84 | No Risk |
| Lower Station limit (400 kW) | 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 196.11 | 250 | 70 | 49.03 | 78.44 | No Risk |
| Lower Station limit (400 kW) | 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 238.33 | 300 | 90 | 59.58 | 79.44 | No Risk |
| Lower Station limit (400 kW) | 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 267.5 | 350 | 130 | 66.88 | 76.43 | No Risk |
| Lower Station limit (400 kW) | 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 231.11 | 310 | 70 | 57.78 | 74.55 | No Risk |
| Lower Station limit (400 kW) | 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 259.17 | 320 | 100 | 64.79 | 80.99 | No Risk |
| Lower Station limit (400 kW) | 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 291.94 | 350 | 30 | 72.99 | 83.41 | No Risk |
| Lower Station limit (400 kW) | 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 245 | 290 | 80 | 61.25 | 84.48 | No Risk |
| Lower Station limit (400 kW) | 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 318.89 | 400 | 120 | 79.72 | 79.72 | Moderate Risk |
| Lower Station limit (400 kW) | 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 375 | 400 | 100 | 93.75 | 75 | Moderate Risk |
| Lower Station limit (400 kW) | 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 346.39 | 400 | 140 | 86.6 | 76.98 | Moderate Risk |
| Lower Station limit (400 kW) | 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 309.17 | 370 | 60 | 77.29 | 83.56 | No Risk |
| Lower Station limit (400 kW) | 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 293.89 | 400 | 170 | 73.47 | 73.47 | Moderate Risk |
| Higher Station limit (600 kW) | 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 177.22 | 200 | 100 | 29.54 | 88.61 | No Risk |
| Higher Station limit (600 kW) | 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 203.33 | 240 | 130 | 33.89 | 84.72 | No Risk |
| Higher Station limit (600 kW) | 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 203.33 | 230 | 120 | 33.89 | 88.41 | No Risk |
| Higher Station limit (600 kW) | 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 184.44 | 220 | 90 | 30.74 | 83.84 | No Risk |
| Higher Station limit (600 kW) | 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 196.11 | 250 | 70 | 32.69 | 78.44 | No Risk |
| Higher Station limit (600 kW) | 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 238.33 | 300 | 90 | 39.72 | 79.44 | No Risk |
| Higher Station limit (600 kW) | 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 267.5 | 350 | 130 | 44.58 | 76.43 | No Risk |
| Higher Station limit (600 kW) | 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 231.11 | 310 | 70 | 38.52 | 74.55 | No Risk |
| Higher Station limit (600 kW) | 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 259.17 | 320 | 100 | 43.19 | 80.99 | No Risk |
| Higher Station limit (600 kW) | 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 291.94 | 350 | 30 | 48.66 | 83.41 | No Risk |
| Higher Station limit (600 kW) | 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 245 | 290 | 80 | 40.83 | 84.48 | No Risk |
| Higher Station limit (600 kW) | 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 318.89 | 400 | 120 | 53.15 | 79.72 | Moderate Risk |
| Higher Station limit (600 kW) | 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 402.78 | 500 | 100 | 67.13 | 80.56 | High Risk |
| Higher Station limit (600 kW) | 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 353.06 | 450 | 140 | 58.84 | 78.46 | High Risk |
| Higher Station limit (600 kW) | 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 315.28 | 370 | 90 | 52.55 | 85.21 | No Risk |
| Higher Station limit (600 kW) | 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 292.5 | 400 | 100 | 48.75 | 73.12 | Moderate Risk |
| Longer horizon (6 h) | 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 181.67 | 200 | 100 | 36.33 | 90.83 | No Risk |
| Longer horizon (6 h) | 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 201.67 | 240 | 50 | 40.33 | 84.03 | No Risk |
| Longer horizon (6 h) | 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 195.14 | 230 | 80 | 39.03 | 84.84 | No Risk |
| Longer horizon (6 h) | 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 179.72 | 220 | 60 | 35.94 | 81.69 | No Risk |
| Longer horizon (6 h) | 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 207.36 | 250 | 70 | 41.47 | 82.94 | No Risk |
| Longer horizon (6 h) | 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 254.58 | 300 | 150 | 50.92 | 84.86 | No Risk |
| Longer horizon (6 h) | 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 289.44 | 350 | 150 | 57.89 | 82.7 | No Risk |
| Longer horizon (6 h) | 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 266.94 | 310 | 20 | 53.39 | 86.11 | No Risk |
| Longer horizon (6 h) | 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 268.75 | 320 | 80 | 53.75 | 83.98 | No Risk |
| Longer horizon (6 h) | 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 273.89 | 350 | 90 | 54.78 | 78.25 | No Risk |
| Longer horizon (6 h) | 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 244.03 | 290 | 170 | 48.81 | 84.15 | No Risk |
| Longer horizon (6 h) | 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 321.67 | 400 | 40 | 64.33 | 80.42 | Moderate Risk |
| Longer horizon (6 h) | 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 391.67 | 500 | 50 | 78.33 | 78.33 | High Risk |
| Longer horizon (6 h) | 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 342.08 | 450 | 180 | 68.42 | 76.02 | High Risk |
| Longer horizon (6 h) | 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 304.31 | 370 | 110 | 60.86 | 82.24 | No Risk |
| Longer horizon (6 h) | 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 323.75 | 400 | 170 | 64.75 | 80.94 | Moderate Risk |
| S8 NHPP (two-peak day) | (night 0–6 h), (10–16 h), (7–10 h и 17–21 h); linear transitions 30 min | ||||||||||||
| S9 NHPP (highly peak location) | Same as S8, but and wider peak windows (6:30–10:30; 16:30–21:30) | ||||||||||||
| S10 MMPP-2 (off-peak/peak) | ; average durations , (elements of selected to give these times) | ||||||||||||
| S11 Hawkes (moderate clustering) | Background as S8; kernel with , (subcritical), which increases the temporal correlation of arrivals | ||||||||||||
| S12 Dynamic class mix | (0.6, 0.3, 0.1) for (small/medium/large bat.) off peak and (0.4, 0.35, 0.25) in peak; the rest as S8 (investigates the effect of more frequent “heavy” requests during busy hours) | ||||||||||||
| S13 Regime-dependent boundary (EMS) | Combination S10 + dynamic throttling policy: at fair share throttling is applied with a stronger limit in (peak) to reduce clusters of peaks (the simulation logic matches the already used proportional scaling when the limit is reached) | ||||||||||||
| S14 Random window startup | For 3 h and 6 h horizons the start , to assess the sensitivity to the window position relative to the peaks (important in NHPP/MMPP) | ||||||||||||
References
- Fescioglu-Unver, N.; Yildiz Aktaş, M. Electric vehicle charging service operations: A review of machine learning applications for infrastructure planning, control, pricing and routing. Renew. Sustain. Energy Rev. 2023, 188, 113873. [Google Scholar] [CrossRef]
- Guerrero-Silva, J.A.; Romero-Gelvez, J.I.; Aristizábal, A.J.; Zapata, S. Optimization and Trends in EV Charging Infrastructure: A PCA-Based Systematic Review. World Electr. Veh. J. 2025, 16, 345. [Google Scholar] [CrossRef]
- Sawant, V.; Zambare, P. DC fast charging stations for electric vehicles: A review. IET Energy Convers. Econ. 2024, 5, 54–71. [Google Scholar] [CrossRef]
- LaMonaca, S.; Ryan, L. The state of play in electric vehicle charging services—A review of infrastructure provision, players, and policies. Renew. Sustain. Energy Rev. 2022, 154, 111733. [Google Scholar] [CrossRef]
- Mohammed, A.; Saif, O.; Abo-Adma, M.; Fahmy, A.; Elazab, R. Strategies and sustainability in fast charging station deployment for electric vehicles. Sci. Rep. 2024, 14, 283. [Google Scholar] [CrossRef]
- Rupnik, B.; Wang, Y.; Kramberger, T. Hybrid Model for Motorway EV Fast-Charging Demand Analysis Based on Traffic Volume. Systems 2025, 13, 272. [Google Scholar] [CrossRef]
- Kchaou-Boujelben, M. Charging station location problem: A comprehensive review on models and solution approaches. Transp. Res. Part C Emerg. Technol. 2021, 132, 103376. [Google Scholar] [CrossRef]
- Sayarshad, H.R. Optimization of electric charging infrastructure: Integrated model for routing and charging coordination with power-aware operations. Sustain. Mobil. Transp. 2024, 1, 4. [Google Scholar] [CrossRef]
- Li, K.; Shao, C.; Hu, Z.; Shahidehpour, M. An MILP Method for Optimal Planning of Electric Vehicle Charging Stations in Coordinated Urban Power and Transportation Networks. IEEE Trans. Power Syst. 2023, 38, 5406–5419. [Google Scholar] [CrossRef]
- Zhang, Q.; Si, G.; Li, H. Optimization of Electric Vehicle Charging Station Location Distribution Based on Activity–Travel Patterns. ISPRS Int. J. Geo-Inf. 2025, 14, 373. [Google Scholar] [CrossRef]
- Campaña, M.; Inga, E. Optimal deployment of fast-charging stations for electric vehicles considering the sizing of the electrical distribution network and traffic condition. Energy Rep. 2023, 9, 5246–5268. [Google Scholar] [CrossRef]
- Li, Y.; Pei, W.; Zhang, Q.; Xu, D.; Ma, H. Optimal Layout of Electric Vehicle Charging Station Locations Considering Dynamic Charging Demand. Electronics 2023, 12, 1818. [Google Scholar] [CrossRef]
- Heo, J.; Chang, S. Optimal planning for electric vehicle fast charging stations placements in a city scale using an advantage actor-critic deep reinforcement learning and geospatial analysis. Sustain. Cities Soc. 2024, 113, 105567. [Google Scholar] [CrossRef]
- Wu, A.Y.; Wu, J.; Lau, Y.-y. Multi-stage hybrid planning method for charging stations based on graph auto-encoder. Electronics 2024, 14, 114. [Google Scholar] [CrossRef]
- Guler, N. Smart allocation and sizing of fast charging stations: A metaheuristic solution. Int. J. Sustain. Energy 2024, 43, 2350970. [Google Scholar] [CrossRef]
- Shi, H.; Xiong, H.; Gan, W.; Guo, G. Fully distributed planning method for coordinated distribution and urban transportation networks considering three-phase unbalance mitigation. Appl. Energy 2025, 377 Pt A, 124449. [Google Scholar] [CrossRef]
- Xi, X.; Sioshansi, R.; Marano, V. Simulation–optimization model for location of a public electric vehicle charging infrastructure. Transp. Res. Part D Transp. Environ. 2013, 22, 60–69. Available online: https://www.osti.gov/pages/biblio/1353218 (accessed on 13 May 2025). [CrossRef]
- Zentani, A.; Almaktoof, A.; Kahn, M.T. A Comprehensive Review of Developments in Electric Vehicles Fast Charging Technology. Appl. Sci. 2024, 14, 4728. [Google Scholar] [CrossRef]
- Wang, L.; Yang, C.; Zhang, Y.; Bu, F. Research on Multi-Objective Planning of Electric Vehicle Charging Stations Considering the Condition of Urban Traffic Network. arXiv 2022, arXiv:2208.12921. [Google Scholar] [CrossRef]
- Schoenberg, S.; Buse, D.S.; Dressler, F. Siting and Sizing Charging Infrastructure for Electric Vehicles with Coordinated Recharging. IEEE Trans. Intell. Veh. 2023, 8, 1425–1438. [Google Scholar] [CrossRef]
- Liu, S.; Wang, L.; Hu, J.; Zhou, Z. A Stochastic Charging Station Deployment Model for Electrified Taxi Fleets in Coupled Urban Transportation and Power Distribution Networks. IEEE Trans. Sustain. Energy 2024, 15, 1138–1150. [Google Scholar] [CrossRef]
- Ferro, G.; Minciardi, R.; Parodi, L.; Robba, M. Optimal Location and Line Assignment for Electric Bus Charging Stations. IEEE Syst. J. 2023, 17, 1950–1961. [Google Scholar] [CrossRef]
- Ding, X.; Jiang, Z.; Fu, Y.; Zhang, H. Optimization method for location and capacity determination of electric vehicle mobile charging station based on multi-objective hybrid frog jump algorithm. Sustain. Energy Res. 2025, 12, 49. [Google Scholar] [CrossRef]
- Uribe, A.; Fernández-Montoya, M.; Vargas, J.; Osorio-Gómez, G.; Montoya, A. Discrete event simulation for battery-swapping station sizing for hybrid and electric motorcycles. J. Clean. Prod. 2023, 390, 136155. [Google Scholar] [CrossRef]
- Meng, F.; Pei, W.; Zhang, Q.; Zhang, Y.; Ma, B.; Li, L. Research on the capacity of charging stations based on queuing theory and energy storage scheduling optimization sharing strategy. J. Energy Storage 2024, 96, 112673. [Google Scholar] [CrossRef]
- Wang, W.; Liu, Y.; Fan, X.; Zhang, Z. Optimization of Charging Station Capacity Based on Energy Storage Scheduling and Bi-Level Planning Model. World Electr. Veh. J. 2024, 15, 327. [Google Scholar] [CrossRef]
- Pourvaziri, H.; Sarhadi, H.; Azad, N.; Afshari, H.; Taghavi, M. Planning of electric vehicle charging stations: An integrated deep learning and queueing theory approach. Transp. Res. Part E Logist. Transp. Rev. 2024, 186, 103568. [Google Scholar] [CrossRef]
- Mangini, A.M.; Fanti, M.P.; Silvestri, B.; Ranieri, L. Modeling and Simulation of Electric Vehicles Charging Services by a Time Colored Petri Net Framework. Energies 2025, 18, 867. [Google Scholar] [CrossRef]
- Nishimwe, H.L.F.; Yoon, S.-G. Combined Optimal Planning and Operation of a Fast EV-Charging Station Integrated with Solar PV and ESS. Energies 2021, 14, 3152. [Google Scholar] [CrossRef]
- Zhao, Z.; Xu, M.; Lee, C.K.M. Capacity Planning for an Electric Vehicle Charging Station Considering Fuzzy Quality of Service and Multiple Charging Options. IEEE Trans. Veh. Technol. 2021, 70, 12529–12541. Available online: https://ira.lib.polyu.edu.hk/bitstream/10397/92302/1/Zhao_Capacity_Planning_Electric.pdf (accessed on 13 May 2025). [CrossRef]
- Dong, X.-J.; Shen, J.-.N.; Ma, Z.-.F.; He, Y.-J. Stochastic optimization of integrated electric vehicle charging stations under photovoltaic uncertainty and battery power constraints. Energy 2025, 314, 134163. [Google Scholar] [CrossRef]
- Ahmed, H.Y.; Ali, Z.M.; Refaat, M.M.; Aleem, S.H.E.A. A Multi-Objective Planning Strategy for Electric Vehicle Charging Stations towards Low Carbon-Oriented Modern Power Systems. Sustainability 2023, 15, 2819. [Google Scholar] [CrossRef]
- Kazemtarghi, A.; Mallik, A. A two-stage stochastic programming approach for electric energy procurement of EV charging station integrated with BESS and PV. Electr. Power Syst. Res. 2024, 232, 110411. [Google Scholar] [CrossRef]
- Adenuga, O.T.; Krishnamurthy, S. An MINLP Optimization Method to Solve the RES-Hybrid System Economic Dispatch of an Electric Vehicle Charging Station. World Electr. Veh. J. 2025, 16, 266. [Google Scholar] [CrossRef]
- Rene, E.A.; Fokui, W.S.T. Artificial intelligence-based optimal EVCS integration with stochastically sized and distributed PVs in an RDNS segmented in zones. J. Electr. Syst. Inf. Technol. 2024, 11, 12. [Google Scholar] [CrossRef]
- Farhadi, F.; Wang, S.; Palacin, R.; Blythe, P. Data-driven multi-objective optimization for electric vehicle charging infrastructure densification. iScience 2023, 26, 107737. [Google Scholar] [CrossRef] [PubMed]
- Nadimi-Shahraki, M.H.; Zamani, H.; Asghari Varzaneh, Z.; Mirjalili, S. A systematic review of the whale optimization algorithm: Theoretical foundation, improvements, and hybridizations. Arch. Comput. Methods Eng. 2023, 30, 4113–4159. [Google Scholar] [CrossRef] [PubMed]
- Li, Y.; Pei, W.; Zhang, Q. Improved whale optimization algorithm based on hybrid strategy and its application in location selection for electric vehicle charging stations. Energies 2022, 15, 7035. [Google Scholar] [CrossRef]
- Cheng, J.; Xu, J.; Chen, W.; Song, B. Locating and sizing method of electric vehicle charging station based on improved whale optimization algorithm. Energy Rep. 2022, 8, 4386–4400. [Google Scholar] [CrossRef]
- Abdel-Basset, M.; Mohamed, R.; Abouhawwash, M. Crested porcupine optimizer: A new nature-inspired metaheuristic. Knowl. Based Syst. 2024, 284, 111257. [Google Scholar] [CrossRef]
- Adalja, D.; Patel, P.; Mashru, N.; Jangir, P.; Arpita Jangid, R.; Gulothungan, G.; Khishe, M. A new multi objective crested porcupines optimization algorithm for solving optimization problems. Sci. Rep. 2025, 15, 14380. [Google Scholar] [CrossRef] [PubMed]
- Quan, R.; Zhou, Y.; Yao, S.; Wan, H.; Chang, Y. Improving the performance of a polygonal automobile exhaust thermoelectric generator with a crested porcupine optimizer. Appl. Therm. Eng. 2025, 268, 125946. [Google Scholar] [CrossRef]
- Kelly, N.J.; Flett, G.H.; Hand, J.W. Developing a statistical electric vehicle charging model and its application in the performance assessment of a sustainable urban charging hub. J. Build. Perform. Simul. 2025, 18, 291–310. [Google Scholar] [CrossRef]
- Dai, Y.; Liu, X.; Li, H.; Liu, X.; Zhang, T.; Su, Z.; Zhao, S.; Zhou, Y. Building-related electric vehicle charging behaviors and energy consumption patterns: An urban-scale analysis. Transp. Res. Part D Transp. Environ. 2025, 141, 104663. [Google Scholar] [CrossRef]
- Hu, H.; Zhao, D.; Zockaie, A.; Ghamami, M. Growth patterns and factors of electric vehicle charging infrastructure for sustainable development. Sustain. Cities Soc. 2025, 126, 106417. [Google Scholar] [CrossRef]
- Pourvaziri, H.; Taghavi, M.; Sarhadi, H.; Afshari, H.; Azad, N. Multi-objective planning of electric vehicles charging stations by integrating drivers’ preferences and fairness considerations: A case study in Halifax, Canada. Comput. Ind. Eng. 2025, 201, 110886. [Google Scholar] [CrossRef]
- Abdel-Basset, M.; Gamal, A.; Hezam, I.M.; Sallam, K.M. Sustainability assessment of optimal location of electric vehicle charge stations: A conceptual framework for green energy into smart cities. Environ. Dev. Sustain. 2024, 26, 11475–11513. [Google Scholar] [CrossRef]
- Jiao, J.; Choi, S.J.; Nguyen, C. Toward an equitable transportation electrification plan: Measuring public electric vehicle charging station access disparities in Austin, Texas. PLoS ONE 2024, 19, e0309302. [Google Scholar] [CrossRef] [PubMed]
- Varshney, S.; Panda, K.P.; Shah, M.; Srinivas, B.A.; Deshmukh, A.; Choudhary, K.K.; Bajaj, M.; Prokop, L.; Rubanenko, O. Novel control strategies for electric vehicle charging stations using stochastic modeling and queueing analysis. Sci. Rep. 2025, 15, 25135. [Google Scholar] [CrossRef]
- Ray, S.; Kasturi, K.; Nayak, M.R. Multi-objective electric vehicle charge scheduling for photovoltaic and battery energy storage based electric vehicle charging stations in distribution network. Green Energy Intell. Transp. 2025, 4, 100296. [Google Scholar] [CrossRef]
- Deringer, V.L.; Bartók, A.P.; Bernstein, N.; Wilkins, D.M.; Ceriotti, M.; Csányi, G. Gaussian process regression for materials and molecules. Chem. Rev. 2021, 121, 10073–10141. [Google Scholar] [CrossRef]
- Lee, K.-J.; Lee, W.-H.; Kim, K.K.K. Battery state-of-charge estimation using data-driven Gaussian process Kalman filters. J. Energy Storage 2023, 72, 108392. [Google Scholar] [CrossRef]
- Deng, Z.; Hu, X.; Lin, X.; Che, Y.; Xu, L.; Guo, W. Data-driven state of charge estimation for lithium-ion battery packs based on Gaussian process regression. Energy 2020, 205, 118000. [Google Scholar] [CrossRef]
- Zeng, X.; Xie, C.; Xu, M.; Chen, Z. Optimal en-route charging station locations for electric vehicles with heterogeneous range anxiety. Transp. Res. Part C Emerg. Technol. 2024, 158, 104459. [Google Scholar] [CrossRef]
- Güven, A.F.; Ateş, N.; Alotaibi, S.; Alzahrani, T.; Amsal, A.M.; Elsayed, S.K. Sustainable hybrid systems for EV charging stations: A multi-criteria assessment for Adana, Turkey. Sci. Rep. 2025, 15, 4199. [Google Scholar] [CrossRef]









| Group | Probability | Energy Range |
|---|---|---|
| Small batteries | 50% | [10, 20] kWh |
| Medium batteries | 35% | [20, 40] kWh |
| Large batteries | 15% | [40, 70] kWh |
| № | Power Class | Dominant Type | Risk | |||
|---|---|---|---|---|---|---|
| 1 | Low (≤250 kW) | 20 kW | No risk | 15 | 82.9 | 38.67 |
| 2 | Low (≤250 kW) | Mixed | No risk | 1 | 80 | 40 |
| 3 | Medium (251–350 kW) | 20 kW | No risk | 48 | 82.19 | 48.58 |
| 4 | Medium (251–350 kW) | 30 kW | No risk | 50 | 81.52 | 51.44 |
| 5 | Medium (251–350 kW) | 40 kW | No risk | 18 | 80.95 | 54.21 |
| 6 | Medium (251–350 kW) | 50 kW | No risk | 1 | 84.68 | 59.28 |
| 7 | Medium (251–350 kW) | Mixed | No risk | 19 | 82.28 | 53.81 |
| 8 | High (>350 kW) | 30 kW | No risk | 13 | 79.91 | 59.26 |
| 9 | High (>350 kW) | 40 kW | No risk | 30 | 80.17 | 60.34 |
| 10 | High (>350 kW) | 40 kW | Moderate risk | 15 | 78.98 | 65.05 |
| 11 | High (>350 kW) | 50 kW | No risk | 17 | 79.19 | 60 |
| 12 | High (>350 kW) | 50 kW | Moderate risk | 32 | 78.43 | 66.41 |
| 13 | High (>350 kW) | 50 kW | High risk | 13 | 78.98 | 73.48 |
| 14 | High (>350 kW) | Mixed | No risk | 8 | 78.67 | 58.02 |
| 15 | High (>350 kW) | Mixed | Moderate risk | 5 | 80.36 | 65.28 |
| 16 | High (>350 kW) | Mixed | High risk | 1 | 79.69 | 71.72 |
| Total | 286 | |||||
| Group No. | [%] | [%] | |
|---|---|---|---|
| 13 | 78.98 | 73.48 | 152.46 |
| 16 | 79.69 | 71.72 | 151.41 |
| 15 | 80.36 | 65.28 | 145.64 |
| 12 | 78.43 | 66.41 | 144.84 |
| 10 | 78.98 | 65.05 | 144.03 |
| 6 | 84.68 | 59.28 | 143.96 |
| 9 | 80.17 | 60.34 | 140.51 |
| 11 | 79.19 | 60.00 | 139.19 |
| 8 | 79.91 | 59.26 | 139.17 |
| 14 | 78.67 | 58.02 | 136.69 |
| Metric | Group No. | Value |
|---|---|---|
| Highest Efficiency | 6 | 84.68% |
| Highest Efficiency | 1 | 82.90% |
| Highest Efficiency | 7 | 82.28% |
| Highest Efficiency | 3 | 82.19% |
| Highest Efficiency | 4 | 81.52% |
| Highest Load Factor | 13 | 73.48% |
| Highest Load Factor | 16 | 71.72% |
| Highest Load Factor | 12 | 66.41% |
| Highest Load Factor | 15 | 65.28% |
| Highest Load Factor | 10 | 65.05% |
| Power Class | Group Count | ||
|---|---|---|---|
| High (>350 kW) | 79.38% | 64.40% | 9 |
| Low (≤250 kW) | 81.45% | 39.34% | 2 |
| Medium (251–350 kW) | 82.32% | 53.46% | 5 |
| Risk | Group Count | Share (%) |
|---|---|---|
| No Risk | 11 | 68.75 |
| Moderate Risk | 3 | 18.75 |
| High Risk | 2 | 12.50 |
| Risk | Groups | % of All |
|---|---|---|
| No risk | 9 | 56% |
| Moderate risk | 4 | 25% |
| High risk | 3 | 19% |
| Class | Characteristics | ||
|---|---|---|---|
| Low (≤250 kW) | 81.45% | 39.33% | Stable but limited load |
| Medium (251–350 kW) | 82.32% | 53.66% | Best compromise—high efficiency without risk |
| High (>350 kW) | 79.45% | 62.86% | High load, but often with risk |
| Scenario | [p.p] | [p.p] | [kW] | Risk |
|---|---|---|---|---|
| Lower arrivals () | −5.56 | −8.39 | −8.75 | 2/2/12 |
| Higher arrivals () | +3.92 | +6.09 | 0.00 | 2/2/12 |
| Heavier batteries | +1.72 | +2.70 | −3.75 | 1/3/12 |
| Lighter batteries | −0.37 | −0.69 | −1.87 | 2/2/12 |
| Lower limit 400 kW | +12.45 | −0.52 | −9.37 | 0/4/12 |
| Higher limit 600 kW | −8.71 | 0.00 | 0.00 | 2/2/12 |
| Longer horizon 6 h | +0.83 | +1.38 | 0.00 | 2/2/12 |
| NHPP–Diurnal | +2.15 | +1.93 | +6.25 | 2/3/11 |
| MMPP–Burst | +4.05 | +5.63 | +10.75 | 3/3/10 |
| Hawkes–Cluster | +3.25 | +4.43 | +12.25 | 3/4/9 |
| Scenario | Mean | Mean | Mean | High Risk | Moderate Risk | No Risk |
|---|---|---|---|---|---|---|
| Baseline | 52.25 | 81.27 | 323.75 | 2 | 2 | 12 |
| Heavier batteries | 53.97 | 83.97 | 320 | 1 | 3 | 12 |
| Higher arrivals () | 56.17 | 87.36 | 323.75 | 2 | 2 | 12 |
| Higher station limit (600 kW) | 43.54 | 81.27 | 323.75 | 2 | 2 | 12 |
| Lighter batteries | 51.88 | 80.58 | 321.88 | 2 | 2 | 12 |
| Longer horizon (6 h) | 53.08 | 82.65 | 323.75 | 2 | 2 | 12 |
| Lower arrivals () | 46.69 | 72.88 | 315 | 2 | 2 | 12 |
| Lower station limit (400 kW) | 64.7 | 80.75 | 314.38 | 0 | 4 | 12 |
| NHPP–Diurnal | 54.40 | 83.20 | 330.00 | 2 | 3 | 11 |
| MMPP–Burst | 56.30 | 86.90 | 334.50 | 3 | 3 | 10 |
| Hawkes–Cluster | 55.50 | 85.70 | 336.00 | 3 | 4 | 9 |
| Scenario | Case | Power Class | Avg [kW] | [kW] | [%] | [%] | Risk |
|---|---|---|---|---|---|---|---|
| Baseline | 6 | Medium (251–350 kW) | 238.33 | 300 | 47.67 | 79.44 | No Risk |
| Baseline | 13 | High (>350 kW) | 402.78 | 500 | 80.56 | 80.56 | High Risk |
| Lower arrivals ) | 6 | Medium (251–350 kW) | 200.83 | 270 | 40.17 | 66.94 | No Risk |
| Lower arrivals () | 13 | High (>350 kW) | 351.39 | 500 | 70.28 | 70.28 | High Risk |
| Higher arrivals () | 6 | Medium (251–350 kW) | 260 | 300 | 52 | 86.67 | No Risk |
| Higher arrivals () | 13 | High (>350 kW) | 420.83 | 500 | 84.17 | 84.17 | High Risk |
| Heavier batteries | 6 | Medium (251–350 kW) | 235.83 | 300 | 47.17 | 78.61 | No Risk |
| Heavier batteries | 13 | High (>350 kW) | 401.39 | 500 | 80.28 | 80.28 | High Risk |
| Lighter batteries | 6 | Medium (251–350 kW) | 229.17 | 270 | 45.83 | 76.39 | No Risk |
| Lighter batteries | 13 | High (>350 kW) | 397.22 | 500 | 79.44 | 79.44 | High Risk |
| Lower station limit (400 kW) | 6 | Medium (251–350 kW) | 238.33 | 300 | 59.58 | 79.44 | No Risk |
| Lower station limit (400 kW) | 13 | High (>350 kW) | 375 | 400 | 93.75 | 75 | Moderate Risk |
| Higher station limit (600 kW) | 6 | Medium (251–350 kW) | 238.33 | 300 | 39.72 | 79.44 | No Risk |
| Higher station limit (600 kW) | 13 | High (>350 kW) | 402.78 | 500 | 67.13 | 80.56 | High Risk |
| Longer horizon (6 h) | 6 | Medium (251–350 kW) | 254.58 | 300 | 50.92 | 84.86 | No Risk |
| Longer horizon (6 h) | 13 | High (>350 kW) | 391.67 | 500 | 78.33 | 78.33 | High Risk |
| Scenario | Power Class | |||
|---|---|---|---|---|
| Baseline | High (>350 kW) | 67.3 | 79.41 | 424 |
| Baseline | Low (≤250 kW) | 38.58 | 84.8 | 228 |
| Baseline | Medium (251–350 kW) | 51.1 | 79.88 | 320 |
| Heavier batteries | High (>350 kW) | 69.78 | 82.5 | 416 |
| Heavier batteries | Low (≤250 kW) | 40.38 | 88.6 | 228 |
| Heavier batteries | Medium (251–350 kW) | 52.11 | 81.34 | 316.67 |
| Higher arrivals () | High (>350 kW) | 72.4 | 85.48 | 424 |
| Higher arrivals () | Low (≤250 kW) | 41.63 | 91.26 | 228 |
| Higher arrivals () | Medium (251–350 kW) | 54.77 | 85.68 | 320 |
| Higher station limit (600 kW) | High (>350 kW) | 56.08 | 79.41 | 424 |
| Higher station limit (600 kW) | Low (≤250 kW) | 32.15 | 84.8 | 228 |
| Higher station limit (600 kW) | Medium (251–350 kW) | 42.58 | 79.88 | 320 |
| Lighter batteries | High (>350 kW) | 67.31 | 79.23 | 424 |
| Lighter batteries | Low (≤250 kW) | 38.35 | 84.26 | 228 |
| Lighter batteries | Medium (251–350 kW) | 50.29 | 78.65 | 315 |
| Longer horizon (6 h) | High (>350 kW) | 67.34 | 79.59 | 424 |
| Longer horizon (6 h) | Low (≤250 kW) | 38.62 | 84.87 | 228 |
| Longer horizon (6 h) | Medium (251–350 kW) | 53.26 | 83.34 | 320 |
| Lower arrivals () | High (>350 kW) | 59.61 | 70.4 | 424 |
| Lower arrivals () | Low (≤250 kW) | 35.35 | 77.64 | 228 |
| Lower arrivals () | Medium (251–350 kW) | 45.36 | 70.99 | 296.67 |
| Lower station limit (400 kW) | High (>350 kW) | 82.17 | 77.75 | 394 |
| Lower station limit (400 kW) | Low (≤250 kW) | 48.22 | 84.8 | 228 |
| Lower station limit (400 kW) | Medium (251–350 kW) | 63.88 | 79.88 | 320 |
| Case | Total [kW] | Power Class | Avg [kW] | [kW] | [kW] | [%] | [%] | Risk | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 10 | 0 | 0 | 0 | 200 | Low (≤250 kW) | 177.64 | 200 | 100 | 35.53 | 88.82 | No Risk |
| 2 | 6 | 4 | 0 | 0 | 240 | Low (≤250 kW) | 206.67 | 240 | 50 | 41.33 | 86.11 | No Risk |
| 3 | 7 | 3 | 0 | 0 | 230 | Low (≤250 kW) | 202.81 | 230 | 50 | 40.56 | 88.18 | No Risk |
| 4 | 8 | 2 | 0 | 0 | 220 | Low (≤250 kW) | 193.85 | 220 | 20 | 38.77 | 88.12 | No Risk |
| 5 | 5 | 5 | 0 | 0 | 250 | Low (≤250 kW) | 216.25 | 250 | 60 | 43.25 | 86.5 | No Risk |
| 6 | 0 | 10 | 0 | 0 | 300 | Medium (251–350 kW) | 252.92 | 300 | 150 | 50.58 | 84.31 | No Risk |
| 7 | 0 | 5 | 5 | 0 | 350 | Medium (251–350 kW) | 293.44 | 350 | 110 | 58.69 | 83.84 | No Risk |
| 8 | 3 | 3 | 4 | 0 | 310 | Medium (251–350 kW) | 265.07 | 310 | 150 | 53.01 | 85.51 | No Risk |
| 9 | 2 | 4 | 4 | 0 | 320 | Medium (251–350 kW) | 268.89 | 320 | 20 | 53.78 | 84.03 | No Risk |
| 10 | 2 | 3 | 3 | 2 | 350 | Medium (251–350 kW) | 291.15 | 350 | 120 | 58.23 | 83.18 | No Risk |
| 11 | 4 | 3 | 3 | 0 | 290 | Medium (251–350 kW) | 245.1 | 290 | 80 | 49.02 | 84.52 | No Risk |
| 12 | 0 | 0 | 10 | 0 | 400 | High (>350 kW) | 324.72 | 400 | 160 | 64.94 | 81.18 | Moderate Risk |
| 13 | 0 | 0 | 0 | 10 | 500 | High (>350 kW) | 394.62 | 500 | 0 | 78.92 | 78.92 | High Risk |
| 14 | 0 | 0 | 5 | 5 | 450 | High (>350 kW) | 351.39 | 450 | 170 | 70.28 | 78.09 | High Risk |
| 15 | 2 | 2 | 3 | 3 | 370 | High (>350 kW) | 303.82 | 370 | 130 | 60.76 | 82.11 | No Risk |
| 16 | 1 | 2 | 3 | 4 | 400 | High (>350 kW) | 327.26 | 400 | 170 | 65.45 | 81.81 | Moderate Risk |
| Mean | 269.73 | 323.75 | 96.25 | 53.94 | 84.08 | |||||||
| Case | 3 h | 3 h | 3 h | 6 h | 6 h | 6 h | 24 h | 24 h | 24 h | 6 h | 24 h | 6 h | 24 h | 6 h | 24 h |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 35.44 | 88.61 | 200 | 36.33 | 90.83 | 200 | 35.53 | 88.82 | 200 | 0.89 | 0.09 | 2.22 | 0.21 | 0 | 0 |
| 2 | 40.67 | 84.72 | 240 | 40.33 | 84.03 | 240 | 41.33 | 86.11 | 240 | −0.34 | 0.66 | −0.69 | 1.39 | 0 | 0 |
| 3 | 40.67 | 88.41 | 230 | 39.03 | 84.84 | 230 | 40.56 | 88.18 | 230 | −1.64 | −0.11 | −3.57 | −0.23 | 0 | 0 |
| 4 | 36.89 | 83.84 | 220 | 35.94 | 81.69 | 220 | 38.77 | 88.12 | 220 | −0.95 | 1.88 | −2.15 | 4.28 | 0 | 0 |
| 5 | 39.22 | 78.44 | 250 | 41.47 | 82.94 | 250 | 43.25 | 86.5 | 250 | 2.25 | 4.03 | 4.5 | 8.06 | 0 | 0 |
| 6 | 47.67 | 79.44 | 300 | 50.92 | 84.86 | 300 | 50.58 | 84.31 | 300 | 3.25 | 2.91 | 5.42 | 4.87 | 0 | 0 |
| 7 | 53.5 | 76.43 | 350 | 57.89 | 82.7 | 350 | 58.69 | 83.84 | 350 | 4.39 | 5.19 | 6.27 | 7.41 | 0 | 0 |
| 8 | 46.22 | 74.55 | 310 | 53.39 | 86.11 | 310 | 53.01 | 85.51 | 310 | 7.17 | 6.79 | 11.56 | 10.96 | 0 | 0 |
| 9 | 51.83 | 80.99 | 320 | 53.75 | 83.98 | 320 | 53.78 | 84.03 | 320 | 1.92 | 1.95 | 2.99 | 3.04 | 0 | 0 |
| 10 | 58.39 | 83.41 | 350 | 54.78 | 78.25 | 350 | 58.23 | 83.18 | 350 | −3.61 | −0.16 | −5.16 | −0.23 | 0 | 0 |
| 11 | 49 | 84.48 | 290 | 48.81 | 84.15 | 290 | 49.02 | 84.52 | 290 | −0.19 | 0.02 | −0.33 | 0.04 | 0 | 0 |
| 12 | 63.78 | 79.72 | 400 | 64.33 | 80.42 | 400 | 64.94 | 81.18 | 400 | 0.55 | 1.16 | 0.7 | 1.46 | 0 | 0 |
| 13 | 80.56 | 80.56 | 500 | 78.33 | 78.33 | 500 | 78.92 | 78.92 | 500 | −2.23 | −1.64 | −2.23 | −1.64 | 0 | 0 |
| 14 | 70.61 | 78.46 | 450 | 68.42 | 76.02 | 450 | 70.28 | 78.09 | 450 | −2.19 | −0.33 | −2.44 | −0.37 | 0 | 0 |
| 15 | 63.06 | 85.21 | 370 | 60.86 | 82.24 | 370 | 60.76 | 82.11 | 370 | −2.2 | −2.3 | −2.97 | −3.1 | 0 | 0 |
| 16 | 58.5 | 73.12 | 400 | 64.75 | 80.94 | 400 | 65.45 | 81.81 | 400 | 6.25 | 6.95 | 7.82 | 8.69 | 0 | 0 |
| Case ID | Configuration | Common Sensitivity |
|---|---|---|
| 8 | Mixed Medium-High | 36.48 |
| 16 | High Class, Mixed | 29.71 |
| 7 | 30/40 kW (Medium) | 23.26 |
| Case | Pareto 3 h | Pareto 6 h | Pareto 24 h |
|---|---|---|---|
| 1 | ✓ | ✓ | ✓ |
| 3 | ✓ | ✓ | |
| 5 | ✓ | ||
| 7 | ✓ | ✓ | |
| 8 | ✓ | ✓ | |
| 9 | ✓ | ✓ | |
| 13 | ✓ | ✓ | ✓ |
| 15 | ✓ | ✓ | ✓ |
| 16 | ✓ | ✓ |
| Case ID | 3 h | 6 h | 24 h |
|---|---|---|---|
| 1 | ✓ | ✓ | ✓ |
| 3 | ✓ | ✓ | |
| 5 | ✓ | ||
| 7 | ✓ | ✓ | |
| 8 | ✓ | ✓ |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Adamova, V.; Popov, S.; Baeva, S.; Hinov, N. Design Scenarios and Risk-Aware Performance Framework for Modular EV Fast Charging Stations. Energies 2025, 18, 6043. https://doi.org/10.3390/en18226043
Adamova V, Popov S, Baeva S, Hinov N. Design Scenarios and Risk-Aware Performance Framework for Modular EV Fast Charging Stations. Energies. 2025; 18(22):6043. https://doi.org/10.3390/en18226043
Chicago/Turabian StyleAdamova, Vasilena, Stoyan Popov, Silvia Baeva, and Nikolay Hinov. 2025. "Design Scenarios and Risk-Aware Performance Framework for Modular EV Fast Charging Stations" Energies 18, no. 22: 6043. https://doi.org/10.3390/en18226043
APA StyleAdamova, V., Popov, S., Baeva, S., & Hinov, N. (2025). Design Scenarios and Risk-Aware Performance Framework for Modular EV Fast Charging Stations. Energies, 18(22), 6043. https://doi.org/10.3390/en18226043

