Article

Experimental Evaluation of a Gray-Colored Building-Integrated Photovoltaic Facade System

1
Green Energy Technology Research Center, Kongju National University, Cheonan 31080, Republic of Korea
2
Byucksan R&BD Center, Byucksan Corporation, Seoul 04560, Republic of Korea
3
Department of Smart Green Architectural Engineering and Energy Systems Engineering, Kongju National University, Cheonan 31080, Republic of Korea
*
Author to whom correspondence should be addressed.
Energies 2025, 18(21), 5735; https://doi.org/10.3390/en18215735
Submission received: 14 September 2025 / Revised: 19 October 2025 / Accepted: 22 October 2025 / Published: 31 October 2025
(This article belongs to the Section A2: Solar Energy and Photovoltaic Systems)

Abstract

The rising operating temperature of Building-Integrated Photovoltaic (BIPV) systems is a critical factor that limits their electrical efficiency in real building applications. Addressing this issue is essential for improving both the performance and the reliability of BIPV systems under outdoor conditions. In particular, the demand for colored BIPV has been increasing due to its aesthetic integration with building façades, making it important to clarify its temperature behavior and electrical performance. However, most existing studies have focused on conventional BIPV modules, and research on the thermal and electrical characteristics of colored BIPV remains relatively limited. This study analyzes the temperature characteristics and electrical performance of conventional and colored BIPV systems installed in a full-scale mock-up building. Outdoor experiments showed that the maximum module temperature of the conventional BIPV system reached 75 °C, whereas the colored BIPV system remained lower at 68 °C. The temperature difference between the two systems ranged from 3 to 8 °C depending on solar radiation, mainly due to the retention of thermal energy in the rear insulation structure of BIPV systems and differences in incident energy conversion. These variations directly influenced the power generation and electrical efficiency of the modules. Compared with Standard Test Conditions (STCs), electrical efficiency decreased by approximately 15% in the conventional BIPV system and 10% in the colored BIPV system. The results demonstrate that colored BIPV systems not only mitigate the adverse impact of temperature rise on efficiency but also provide reliable performance and enhanced aesthetic adaptability, offering a promising solution for real building applications.

1. Introduction

Building-Integrated Photovoltaics (BIPV) integrate Photovoltaics (PV) modules into the building envelope and represent a key technology for achieving Zero Energy Building (ZEB) targets through on-site power generation [1,2,3]. BIPV systems eliminate the need for additional land for PV installation and are increasingly recognized as a high-value technology that can replace conventional building finishes. Nevertheless, their acceptance within the construction industry remains limited due to insufficient design information available to architects, low awareness among practitioners, and aesthetic concerns. To address these issues, colored PV modules in diverse colors have been developed, enabling BIPV systems to provide both power generation and architectural integration. These colored BIPV systems are gradually being adopted in the market, offering aesthetic appeal and harmony with building finishes [4,5]. However, unlike conventional BIPV systems, colored BIPV systems exhibit different performance characteristics in terms of temperature, electrical efficiency, and other factors due to the optical properties of the materials used, such as reflectance and transmittance, and thermal transfer differences based on rear insulation conditions. Therefore, a comprehensive performance evaluation considering these factors is necessary.
Tzikas et al. compared conventional PV modules with gray-colored modules and reported an efficiency reduction of approximately 8–10% for the gray modules [6]. Nicolas et al. investigated a colored BIPV system installed on the Kohlesilo building in Basel, Switzerland, employing crystalline silicon glass-to-glass modules in five colors (black, green, blue, gray, and gold). Relative to black modules, gray and gold modules yielded approximately 76% of the energy output, while green and blue modules reached about 84% [7]. Kutter et al. developed colored PV modules using ceramic-colored glass, Morpho-structure, and colored encapsulants, and evaluated their performance under Standard Test Conditions (STCs). Modules with ceramic-colored glass and colored encapsulants exhibited efficiency losses of 6–31% compared to standard PV modules, whereas Morpho-structured modules showed much smaller reductions of 3–7% regardless of color [8]. Kroyer et al. corroborated these findings, demonstrating that red, green, and blue Morpho-structured modules maintained efficiency losses below 7% [9].
Roverso et al. examined colored BIPV façades, measuring solar radiation and module temperature, and demonstrated that the Ross coefficient effectively represents the correlation between incident solar energy and internal module temperature [10]. Babin et al. conducted outdoor experiments with modules in terracotta, green, red, beige, and gray, integrated into BIPV façades. They found no direct correlation between total optical losses and module temperature. However, higher reflectance reduced absorbed energy, contributing to lower module heating. Notably, lighter-colored modules, such as gray and beige, exhibited rear-surface temperatures up to 5 K lower than standard modules [11]. Saretta et al. analyzed clear, blue, light gray, dark gray, and terracotta BIPV modules under STC and outdoor conditions. Dark gray modules exhibited the lowest maximum power (Pmax) (13.43%), whereas blue modules achieved the highest efficiency among colored types. Outdoor experiments revealed color-dependent variations in efficiency and operating temperature; terracotta modules produced the lowest efficiency (~9.0%) but exhibited operating temperatures similar to clear modules (~45 °C) [12]. Pelle et al. further highlighted that color layers induce distinct thermal behaviors, with Ross coefficients ranging from 0.0242 K·m2/W (white) to 0.0456 K·m2/W (mahogany brown), underscoring the significant role of color in thermal sensitivity [13].
Zhihao et al. investigated crystalline silicon colored BIPV modules incorporating dielectric multilayer coatings and showed that optimized optical interference designs can achieve conversion efficiencies above 21% with photocurrent losses below 5% [14]. Yuning et al. developed high-efficiency colored crystalline silicon PV modules in red, yellow, blue, green, and white using pearlescent pigments via screen printing. Their analysis indicated that efficiency losses were consistently below 20%, with green modules exhibiting the highest photocurrent density and lowest loss rates [15]. Mahamoud et al. studied monocrystalline solar cells with colored filters under real climate conditions and found that relative power production strongly depended on filter color, yielding approximately 73% for yellow, 64% for red, and 54% for blue [16]. Babin et al. also evaluated the long-term Direct Current (DC) Performance Ratio (PR) of colored PV modules. Their results revealed that reference and green modules exhibited the lowest annual PR (~0.86), while gray, beige, and terracotta modules achieved slightly higher values (0.88–0.89). Interestingly, red modules demonstrated the highest PR (~0.95), partly attributed to spectral mismatch gains during afternoon hours [17]. Røyset et al. analyzed the application of optical interference coatings and provided design guidelines for balancing high color lightness, low efficiency losses, color performance, and angular dependence [18].
Recent studies on colored BIPV indicate that architectural coloration—ceramic printing, pigment interlayers, colored encapsulants, and interference coatings—inevitably introduces optical-efficiency penalties, with the magnitude governed by color, technique, and angular response [17,18,19,20,21,22,23,24]. Field and modeling evidence further shows that high-reflectance (lighter) colors can moderate operating temperature at the façade by reducing effective absorptance, whereas darker tones increase thermal sensitivity often captured by the Ross coefficient (k) [17,18,25,26]. Despite the growing literature across theory/experiment/numerics, controlled, side-by-side façade experiments under identical boundary conditions remain scarce; reporting practices also vary in irradiance, sensor calibration, and Heating Ventilation and Air Conditioning (HVAC)/insulation configuration, complicating cross-study comparisons [20,22,27].
Overall, prior studies consistently demonstrate that colored BIPV systems provide enhanced architectural integration but typically incur efficiency penalties due to optical and thermal effects. However, the magnitude of these penalties depends strongly on the coloration technique, the overall system configuration with the chosen building materials, and the environmental conditions. In particular, experimental evidence on Glass-to-Glass (G/G) crystalline silicon modules with gray coloration under practical building-like conditions remains limited. Against this backdrop, we provide a full-scale, façade-integrated comparison of gray vs. non-colored G/G c-Si modules, linking STC expectations to outdoor behavior with co-planar plane-of-array (POA) measurements.
This study aims to analyze the temperature characteristics and electrical performance of BIPV systems equipped with gray-colored G/G crystalline-silicon modules installed on a full-scale, façade-integrated mock-up building operated outdoors with an HVAC-controlled interior. To evaluate the impact of coloration, the results are compared with those of a conventional non-colored BIPV system. An air layer and rear insulation material were incorporated to replicate practical installation conditions. The gray coloration of the PV modules was selected considering aesthetics, harmony with surrounding buildings, and electrical efficiency. The modules were manufactured by digital printing, which provides high color fidelity while minimizing coloration-induced power losses.

2. Experiment

2.1. BIPV Full-Scale Mock-Up Building

A full-scale mock-up building with a building area of 131 m2 and a total floor area of 393 m2 was constructed in Jeollabuk-do, South Korea, to evaluate the functionality and performance of a multifunctional façade based on a post-and-beam structure. As shown in Figure 1, the mock-up building was constructed at a 1:1 scale to accurately reproduce real façade installation details and boundary conditions. This approach allows for realistic evaluation of thermal and electrical performance under actual operating conditions. The building consists of three identical, air-conditioned rooms, enabling controlled experimental environments by replacing the exterior walls with BIPV façades. This design allows for a comparative evaluation of different PV integration types, including Building Integrated Photovoltaic (BIPV) and Building Applied Photovoltaic (BAPV), under simulated real installation conditions.
The gray BIPV system was installed on the south-facing exterior wall of the two-story building, and for comparison, a conventional BIPV system was mounted under the same configuration. The test wall had dimensions of 2400 mm in width and 3000 mm in height, accommodating a total of eight modules (700 × 1150 mm each) arranged in two arrays of four modules. Table 1 summarizes the detailed specifications of the conventional and gray PV modules applied in the BIPV systems.

2.2. BIPV System Design Detail

For a comparative analysis of electrical performance between the gray-colored BIPV system and the conventional BIPV system, excluding the color elements of the front glass, the PV cell and the rear structure (BIPV layer configuration) were designed identically. The wall structure of the BIPV system mimics the spandrel part of a curtain wall structure and is designed to meet South Korea’s exterior wall insulation standards (thermal transmittance of façade element; U-value 0.24 W/m2K). The width of the internal air layer in the BIPV system is approximately 50 mm, and the insulation material has a thickness of 90 mm (Figure 2). Each façade array (per system) measures 1148 mm × 2832 mm, corresponding to 3.25 m2. Figure 3 illustrates the layout of the gray-colored BIPV system and the conventional BIPV system installed under identical experimental conditions in the mock-up buildings, as shown in Figure 4.
The temperature sensors installed in the two types of BIPV systems are presented in Figure 5, which also provides detailed positions of the sensors placed on the rear surface of the modules, within the air gap, on the surface of the insulation layer, and on the interior surface. Figure 6 shows the installation of conventional and gray-colored BIPV modules, which are integrated with specially designed mounting frames for BIPV system, as well as interior view of the mock-up building where the systems are installed.
Each system was configured as a 4-module series string (4S) and monitored at the array (string) level via an MPPT input. The STC nameplates of the strings were ≈472 Wp (conventional) and ≈406 Wp (gray). Modules employed manufacturer-integrated bypass diodes; DC cable routing was arranged symmetrically to minimize imbalance.

2.3. Monitoring Systems and Measuring Instruments

Figure 7 depicts the measurement layout for the gray and conventional BIPV façades. Both façades were connected to an I–V curve tracer operated in MPPT mode, enabling continuous logging of Pmax, Vmp, and Imp, while Voc and Isc were obtained from periodic I–V sweeps. Global plane-of-array irradiance (GPOA) was measured with a thermopile pyranometer mounted co-planar to the façade (tilt 90°, alignment within ±1°) so that irradiance was recorded on the same plane as the modules.
Ambient conditions were monitored by a rooftop weather station, which measured air temperature with a shielded sensor, relative humidity, and wind speed. Prior to the test, both façades were cleaned following the same procedure, and a visual inspection on the morning of 31 October 2021 confirmed that no visible soiling differences were present during the measurement window. The façade’s thermal behavior was captured with T-type thermocouples installed within the assembly, with four sensors placed on the rear of the PV modules, four in the internal air layer, and four on the inner and outer surfaces of the insulation.
Both façades were instrumented at the array level as four-module series strings and logged concurrently on the same multichannel data logger with a common 10-s timebase using calibrated sensors (irradiance, meteorological, temperature, and electrical channels time-synchronized). On the representative clear-sky day, the test façade had no external shading, and verification checks indicated no pronounced mismatch. Outdoor DC plane-of-array efficiency (proxy) was computed as follows (Equation (1)).
η D C ( t ) = P D C , M P P ( t ) [ G P O A ( t ) A a p e r t u r e ]
where PDC,MPP is obtained from the I–V tracker in MPPT mode. We used the aperture area (0.81 m2 per module; 3.25 m2 per 4-module string); cell area was not used. This DC metric is reported for comparative purposes only and should not be interpreted as an AC system index (e.g., PR).
Instrument models, specifications, installation details, and measurement uncertainties are summarized in Table 2. This table is newly organized for this submission. Where prior work or standards are relevant, citation markers are included. If any portion of the dataset overlaps with an earlier publication, the overlap is disclosed via [28]. The parameters and abbreviations used in this study are summarized in Table 3.

3. Results and Discussion

3.1. Temperature Distribution of the BIPV Systems

Figure 8 and Figure 9 illustrate the temperature characteristics of the gray and conventional BIPV systems installed on the building façade over the course of the representative measurement day. These figures focus on the temporal variation in temperature distributions across different layers of the BIPV assembly under real outdoor conditions. During the measurement period, the ambient conditions exhibited irradiance ranging from approximately 400 W/m2 to 780 W/m2 and outdoor temperatures fluctuated between 18 °C and 21 °C. The rear temperature of the gray BIPV modules ranged from approximately 33 °C to 68 °C, while the rear temperature of the conventional BIPV modules ranged from about 35 °C to 75 °C. The rear temperature of the gray BIPV modules was up to 7 °C lower than that of the conventional BIPV modules. The temperature in the air layer within the BIPV system was measured to be 5–6 °C lower compared to each module’s rear temperature. The temperature difference in the air layer for each BIPV system showed a similar pattern to the temperature difference in the module. The temperature of each component in the BIPV system decreased in the following order: BIPV module rear, air layer, insulation surface facing the air layer, and interior insulation surface. That is, the temperature was lower towards the interior.
All experimental data presented in Figure 8, Figure 9, Figure 10, Figure 11, Figure 12, Figure 13, Figure 14 and Figure 15 were obtained on 31 October 2021, under clear-sky conditions. The selected measurement day represents a typical autumn day with moderate irradiance levels and stable outdoor temperatures, which allows for a consistent comparative evaluation between the gray and conventional BIPV systems, and all subsequent analyses are based on this dataset.

3.2. Hourly Power and Efficiency Comparison

Figure 10 presents the irradiance-dependent thermal and electrical behavior of both systems, isolating the effect of solar input from temporal fluctuations. Both systems exhibited a distinct temperature rise with increasing irradiance, reaching their maximum values around 13:00, which coincided with near-solar-noon conditions (solar noon at 12:17 KST; solar altitude 38–39°, azimuth 195°) in Jeongeup, South Korea. These solar geometry values were obtained using the NOAA Solar Calculator provided by the National Oceanic and Atmospheric Administration (NOAA) [31], based on the site coordinates (35.56° N, 126.84° E) and the measurement date (31 October 2021).
The peak rear-surface temperature of the conventional BIPV module was approximately 73.6 °C, while that of the colored BIPV module was about 70.4 °C, indicating that the colored module consistently maintained 2–3 °C lower temperatures. This suggests that the colored BIPV system possesses slightly improved heat dissipation characteristics compared to its conventional counterpart.
Regarding electrical performance, the conventional BIPV system showed a decrease from 13.4% to 12.4% over the observation period, while the colored BIPV system declined from 11.8% to 11.0%. Although both systems demonstrated a gradual reduction in efficiency with time, the conventional BIPV module consistently outperformed the colored module by approximately 1.5–2 percentage points. This discrepancy can be attributed to optical losses, such as reflection and absorption, introduced by the surface coloring treatment. The results indicate that the colored BIPV module exhibits a thermal advantage by operating at slightly lower temperatures, but this benefit is offset by reduced optical conversion efficiency. Conversely, the conventional BIPV module achieves higher absolute efficiency but is more vulnerable to performance degradation due to elevated operating temperatures. Furthermore, both systems experienced pronounced efficiency reductions during peak irradiance hours, highlighting the importance of thermal management strategies, such as improved ventilation and heat dissipation designs, for BIPV applications.
Figure 11 presents the hourly power generation and efficiency profiles of conventional and gray-colored BIPV modules. The conventional BIPV system consistently outperformed the colored BIPV system in terms of power generation across all measured hours. At 13:00, the peak power output of the conventional BIPV module reached approximately 290 Wp, compared to 260 Wp for the colored BIPV module, representing a difference of about 10%. This discrepancy can be attributed to optical losses introduced by the module colorization (gray), such as increased reflection and absorption. This performance gap was similarly reflected in the total daily energy yield, with the conventional and colored systems producing 1528 Wh and 1371 Wh, respectively.

3.3. Statistical and Ross Coefficient Analysis

Figure 12 illustrates the statistical distribution of temperature and electrical efficiency for conventional and colored BIPV modules. The rear-surface temperature of the conventional BIPV modules exhibited a median value of approximately 64 °C, with a range between 38 °C and 76 °C, while the colored BIPV modules showed a lower median of around 61 °C and a broader variation from 37 °C to 71 °C. These results indicate that the colored BIPV modules consistently operate at slightly lower temperatures, suggesting improved heat dissipation characteristics compared to conventional BIPV modules.
In terms of efficiency, the conventional BIPV modules achieved a median value of 12.5%, with the distribution spanning from 11.6% to 13.8%. By contrast, the colored BIPV modules presented a median efficiency of 11.0%, concentrated within a narrower range of 10.1% to 12.1%. This demonstrates that, despite the thermal advantage, the colored BIPV modules suffer from reduced electrical performance due to optical losses introduced by the surface coloring treatment.
Overall, the results highlight a trade-off between thermal and electrical performance: conventional BIPV modules exhibit superior electrical efficiency but are more vulnerable to high operating temperatures, whereas colored BIPV modules demonstrate enhanced thermal stability at the expense of conversion efficiency. These findings emphasize the need for advanced coloring technologies and optimized thermal management strategies to balance aesthetics, temperature regulation, and power generation in BIPV applications.
The Ross model can be interpreted as a first-order description in which the module-to-ambient temperature difference TmTa scales linearly with GPOA (Equation (2)). The coefficient k can be attributed to combined effects of environmental conditions and module construction, and therefore exhibits system-specific values [32].
Tm = Ta + k · GPOA
As shown in Figure 13, the relationship between the module-to-ambient temperature difference (ΔTm−a) and global POA irradiance (G) was analyzed for both conventional and gray-colored BIPV systems using the Ross temperature model ΔTm−a = kG + b. For the conventional BIPV module, the Ross coefficient was determined to be k = 0.0768 K m2/W with a coefficient of determination R2 = 0.7139. In comparison, the gray-colored BIPV module exhibited a slightly lower Ross coefficient of k = 0.0710 K m2/W and a higher R2 of 0.7349, indicating a marginal reduction in temperature rise per unit irradiance and a more stable thermal response.
Both systems showed a clear linear increase in ΔTm−a with increasing global irradiance in the range of approximately 350–850 W/m2, with temperature differences exceeding 50 °C under high irradiance conditions. This reflects the limited convective cooling capacity of façade-integrated PV systems compared to free-standing PV arrays. The slightly lower Ross coefficient observed for the gray-colored module could be attributed to reduced solar absorption and increased reflectance due to surface coloration. Nevertheless, the operating temperature remained high for both systems, which may lead to reduced electrical conversion efficiency and long-term material degradation.
As shown in Figure 14, the hourly variation in the Ross coefficient k was derived from linear regression between the module-to-ambient temperature difference (ΔTm−a) and global POA irradiance (G) for both conventional and gray-colored BIPV systems. For the conventional BIPV, k ranged from approximately 0.085 to 0.088 °C·m2/W, while for the gray-colored BIPV, it remained lower, between 0.077 and 0.080 °C·m2/W during the period from 10:00 to 15:00. k value exhibited local maxima near 10:00 and 15:00, with a slight decrease toward solar noon. This systematic reduction suggests that surface coloration has a measurable influence on the thermal behavior of BIPV façades (the underlying drivers of the diurnal pattern cannot be identified from the present dataset alone).
These differences can be primarily attributed to the optical properties of the gray surface treatment, which reduce solar transmittance and mitigate heat accumulation within the module. By reflecting a larger portion of the incident radiation, the gray-colored BIPV module experiences less thermal gain under the same irradiance, leading to a lower Ross coefficient. The lower k values also indicate that gray-colored modules are less susceptible to temperature rise than conventional ones, suggesting improved thermal performance.
Furthermore, the relatively stable k profile throughout the daytime implies that this thermal advantage persists under varying solar conditions, including periods of peak irradiance. This observation supports the earlier regression results and reinforces the importance of surface optical design as a passive strategy for managing module temperature. In practice, such an approach may contribute to mitigating temperature-induced power losses and enhancing the long-term durability of colored BIPV façades.

3.4. Daily Energy Yield and STC vs. Outdoor Efficiency

Before presenting the results, we note that this study evaluates the relative power/energy reduction caused by gray colorization under real façade operating conditions. Because rated capacity and STC efficiency inherently differ due to the color layer, we report daily cumulative DC energy with simple normalizations (kWh/kWp, kWh·m−2) and focus on deviations from STC performance, rather than PR—which is a system-level AC index beyond our scope.
Figure 15 compares the daily energy yield for the conventional and gray-colored BIPV façade systems. The conventional façade produced about 1.55 kWh, whereas the gray façade generated about 1.40 kWh (≈10% lower). Over the same time window, the gray façade delivered 3.45 kWh/kWp (gray) vs. 3.28 kWh/kWp (conventional), while the area-normalized energy was 0.43 kWh·m−2 (gray) vs. 0.46 kWh·m−2 (conventional). The capacity-normalized advantage of the gray system indicates that its lower operating temperature partially offsets the optical penalty, yielding a higher relative energy per kWp under real façade operation. Conversely, when normalized by aperture area, the conventional system retains a slight advantage due to its higher nameplate per area. Taken together, gray coloration can be favorable for architecturally integrated applications where aesthetics and thermal stability are prioritized and performance is compared on a per-kWp basis, while absolute yield per unit area remains marginally lower.
Figure 16 compares the efficiencies of conventional and gray-colored BIPV modules under standard test conditions (STCs) and actual outdoor operation. Under STCs, the conventional BIPV module achieved an efficiency of 14.52%, while the colored BIPV module recorded 12.49%. Under real operating conditions, both systems showed a reduction in efficiency, with the conventional BIPV at 12.49% and the colored BIPV at 11.11%. The colored BIPV module consistently exhibited lower efficiency than the conventional module under both STC and outdoor conditions. The efficiency gap was approximately 2%p under STCs and 1.4%p under real operating conditions. The relative efficiency losses were calculated to be about 15% for the conventional BIPV and 10% for the colored BIPV. This indicates that the colored module experiences less efficiency loss under real operating conditions compared to the conventional module, reflecting the relatively higher thermal stability of the colored BIPV system.

3.5. Discussion

Although numerous studies have investigated the performance of colored Building-Integrated Photovoltaic (BIPV) systems [6,7,8,9,10,11,12,13,14,15,16,17,18], most of them focused on laboratory-scale testing or Standard Test Condition (STC) evaluations, providing limited insight into real façade operation. These works primarily assessed the optical and electrical effects of coloration, but the complex interaction between optical, thermal, and electrical parameters under dynamic outdoor conditions has not been sufficiently addressed. Moreover, reported results are often difficult to compare because the boundary conditions differ significantly among studies, particularly in terms of rear insulation, air-gap depth, and ventilation, all of which have a strong impact on the Ross coefficient (k). Consequently, the k values presented by different authors cannot be directly compared, and their implications for façade-integrated systems remain uncertain.
In addition, most previous studies treated color as a categorical property—such as “gray,” “blue,” or “terracotta”—without quantitative colorimetric or spectral characterization (e.g., CIE Lab values or wavelength-dependent reflectance). This lack of standardized optical data has hindered a clear understanding of how reflectance and absorption govern module temperature rise and efficiency loss. Several experimental works [10,11,12,13] discussed color-dependent module temperatures, yet they often analyzed thermal and electrical behaviors separately, thereby neglecting the coupled influence of irradiance, module temperature, and instantaneous efficiency. Reported Performance Ratios (PRs) for colored BIPV systems also vary in definition, mixing DC-based and AC-based formulations without clear temperature or spectral correction, which complicates long-term performance comparison. Furthermore, many previous investigations were carried out using coupon-sized or non-integrated samples rather than full-scale building façades, limiting their representativeness for practical building applications. To overcome these limitations, the present study compared the thermal and electrical behavior of conventional and gray-colored glass-to-glass BIPV systems under identical boundary conditions, using STC results as a baseline and extending the evaluation to real façade-integrated outdoor operation. The gray-colored module exhibited a consistently lower rear-surface temperature and smaller relative efficiency loss despite a moderate optical-efficiency penalty. These results are consistent with the findings of Babin et al. [11] and Saretta et al. [12], but this work further demonstrates, under realistic building-façade configurations, that gray coloration can reduce operating temperature and maintain electrical performance stability compared with STC expectations.
Overall, the results indicate that, while coloration introduces optical losses, the gray color layer reduces effective solar absorptance, lowering heat input to the façade assembly and thereby providing a tangible thermal advantage that enhances operational stability under real building conditions. The lower temperature of the gray-colored BIPV is attributed primarily to reduced effective absorptance caused by the color layer (i.e., increased reflectance), rather than to ‘enhanced heat dissipation,’ thereby decreasing the fraction of incident POA irradiance that is absorbed and converted to heat. This underscores the importance of field-scale experiments in bridging the gap between STC-based assessments and actual façade-integrated performance.
This study intentionally focuses on a controlled, façade-integrated comparison on a single clear-sky day to isolate the coupled optical–thermal effects of gray coloration. Accordingly, the findings should be interpreted as indicative trends rather than generalized values across all climates or operating scenarios. The scope is limited to one façade configuration with fixed orientation and insulation; detailed 1D/2D thermal modeling or CFD, spectral/colorimetric measurements, and IR thermography were outside the present measurement protocol and are therefore not included. These complementary analyses lie beyond the current scope and may be explored in follow-up campaigns with multi-day/seasonal datasets and varied wind regimes.

4. Conclusions

This study experimentally evaluated the thermal and electrical performance of conventional and gray-colored glass-to-glass BIPV systems installed on a full-scale mock-up building façade, comparing their behavior under real outdoor conditions against STC-based reference performance.
The outdoor results showed that the conventional BIPV module reached a maximum rear-surface temperature of 75 °C, while the gray-colored module remained lower at 68 °C, corresponding to a temperature difference of 3–8 °C depending on irradiance. Although the colored module exhibited approximately 10% lower daily energy yield, its relative efficiency loss under real conditions was smaller (≈10%) than that of the conventional module (≈15%), confirming its superior thermal resilience and stability. These findings reveal that, while colorization inevitably causes optical losses, it mitigates excessive heat accumulation within insulated façades, thereby improving long-term reliability. The results highlight a clear trade-off between conversion efficiency and architectural aesthetics: conventional systems offer higher power output, whereas colored systems provide improved thermal stability and visual integration. Importantly, by comparing STC-based expectations with actual façade performance, this work provides experimental evidence of the electro-thermal correlation unique to real-world BIPV applications.
Future research should focus on extending the investigation to BIPV systems with various colorizations and insulation configurations, not limited to gray coloration, in order to comprehensively analyze the optical losses and thermal behavior associated with different color layers. The goal is to develop optimized BIPV technologies that minimize optical losses while ensuring adequate energy yield and stable operation for real building applications.
In addition, further studies should consider multiple weather conditions, including cloudy and partly cloudy days, to establish a more generalized relationship between thermal behavior and environmental variables. Advanced analytical approaches, such as multi-linear regression and optimization techniques, will be applied to explore the boundary conditions for optimal thermal performance. Moreover, economic feasibility assessments, including payback period analyses, will be incorporated to strengthen the practical applicability of the results.

Author Contributions

Conceptualization, J.-H.K. and J.-T.K.; methodology, J.-H.K. and J.-G.A.; validation, J.-H.K.; formal analysis, J.-H.K. and J.-G.A.; investigation, J.-H.K. and J.-G.A.; resources, J.-H.K. and J.-G.A.; data curation, J.-H.K. and J.-G.A.; writing—original draft preparation, J.-H.K.; writing—review and editing, J.-H.K. and J.-T.K.; visualization, J.-H.K.; supervision, J.-T.K.; project administration, J.-H.K. and J.-T.K.; funding acquisition, J.-T.K. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported by the Korea Institute of Energy Technology Evaluation and Planning (KETEP) through the Ministry of Trade, Industry and Energy (MOTIE), Republic of Korea (RS-2023-00266248), and by a 2022 research grant from Kongju National University.

Data Availability Statement

The original contributions presented in the study are included in the article, and further inquiries can be directed to the corresponding author.

Conflicts of Interest

Author Jong-Gwon Ahn was employed by Byucksan R&BD Center, Byucksan Corporation. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Mohammad, A.K.; Garrod, A.; Ghosh, A. Do Building Integrated Photovoltaic (BIPV) windows propose a promising solution for the transition toward zero energy buildings? A review. J. Build. Eng. 2023, 79, 107950. [Google Scholar] [CrossRef]
  2. Gholami, H.; Rostvik, H.N.; Steemers, K. The contribution of building-integrated photovoltaics (BIPV) to the concept of nearly zero-energy cities in Europe: Potential and challenges ahead. Energies 2021, 14, 6015. [Google Scholar] [CrossRef]
  3. Kylili, A.; Fokaides, P.A. Investigation of building integrated photovoltaics potential in achieving the zero energy building target. Indoor Built Environ. 2014, 23, 92–106. [Google Scholar] [CrossRef]
  4. Pelle, M.; Lucchi, E.; Maturi, L.; Astigarraga, A.; Causone, F. Coloured BIPV Technologies: Methodological and Experimental Assessment for Architecturally Sensitive Areas. Energies 2020, 13, 4506. [Google Scholar] [CrossRef]
  5. Riedel, B.; Messaoudi, P.; Assoa, Y.B.; Thony, P.; Aebi, L.E.P.; Tsanakas, J.A. Color coated glazing for next generation BIPV: Performance vs aesthetics. EPJ Photovolt. 2021, 12, 11. [Google Scholar] [CrossRef]
  6. Tzikas, C.; Valckenborg, R.; Dorenkamper, M.; Donker, M.V.D.; Lozano, L.L.; Bognar, A.; Loonen, R.; Hensen, J.; Folkerts, W. Outdoor characterization of colored and textured prototype PV facade elements. In Proceedings of the 35 European Photovoltaic Solar Energy Conference and Exhibition, Brussels, Belgium, 24–28 September 2018; pp. 1468–1471. [Google Scholar]
  7. Jolissaint, N.; Hanbali, R.; Hadorn, J.C.; Schüler, A. Colored Solar Façades for Buildings. Energy Procedia 2017, 122, 175–180. [Google Scholar] [CrossRef]
  8. Kutter, C.; Bläsi, B.; Wilson, H.R.; Kroyer, T.; Mittag, M.; Höhn, O.; Heinrich, M. Decorated Building-Integrated Photovoltaic Modules: Power Loss, Color Appearance and Cost Analysis. In Proceedings of the 35th European Photovoltaic Solar Energy Conference and Exhibition (EU PVSEC), Brussels, Belgium, 24–28 September 2018; pp. 1488–1492. [Google Scholar]
  9. Kroyer, T.; Eisenlohr, J.; Bläsi, B.; Höhn, O.; Heinrich, M.; Neuhaus, H.; Kuhn, T.E. Pilot installations of highly efficient coloured BIPV modules with anti-glare coating. In Proceedings of the Conference on Advanced Building Skins, Bern, Switzerland, 28–29 October 2019; pp. 550–555. [Google Scholar]
  10. Roverso, R.; Pelle, M.; Dallapiccola, M.; Astigarraga, A.; Lucchi, E.; Ingenhoven, P.; Maturi, L. Experimental Assessment and data analysis of colored photovoltaic in the field of BIPV technology application. In Proceedings of the 38 European Photovoltaic Solar Energy Conference and Exhibition, Online, 6–10 September 2021; pp. 1468–1471. [Google Scholar]
  11. Babin, M.; Jóhannsson, I.H.; Jakobsen, M.L.; Thorsteinsson, S. Experimental evaluation of the impact of pigment-based colored interlayers on the temperature of BIPV modules. EPJ Photovolt. 2023, 14, 34. [Google Scholar] [CrossRef]
  12. Saretta, E.; Bonomo, P.; Frontini, F. BIPV meets customizable glass: A dialogue between energy efficiency and aesthetics. In Proceedings of the 35th European Photovoltaic Solar Energy Conference and Exhibition, Brussels, Belgium, 24–28 September 2018; pp. 1472–1477. [Google Scholar]
  13. Pelle, M.; Gubert, M.; Dalla Maria, E.; Astigarraga, A.; Avesani, S.; Maturi, L. Experimental evaluation of the temperature related behaviour of pigment based colored BIPV modules integrated in a ventilated façade. Energy Build. 2024, 323, 114763. [Google Scholar] [CrossRef]
  14. Xu, Z.; Matsui, T.; Matsubara, K.; Sai, H. Effect of multilayer structure and surface texturing on optical and electric properties of structural colored photovoltaic modules for BIPV applications. Appl. Energy 2024, 367, 123347. [Google Scholar] [CrossRef]
  15. Chen, Y.; Li, Z.; Li, S.; Liu, J.; Dai, X.; Ma, S.L.; Ma, T. Colored and patterned silicon photovoltaic modules through highly transparent pearlescent pigments. Sol. Energy Mater. Sol. Cells 2024, 275, 113033. [Google Scholar] [CrossRef]
  16. Ben Amara, M.; Balghouthi, M. Colored filter’s impact on the solar cells’ electric output under real climatic conditions for application in building integrated photovoltaics. J. Build. Eng. 2023, 76, 107276. [Google Scholar] [CrossRef]
  17. Babin, M.; Andersen, N.L.; Thorning, J.K.; Thorsteinsson, S. Yield analysis of a BIPV façade prototype installation. Energy Build. 2024, 322, 114730. [Google Scholar] [CrossRef]
  18. Røyset, A.; Kolås, T.; Nordseth, Ø.; You, C.C. Optical interference coatings for colored building integrated photovoltaic modules: Predicting and optimising visual properties and efficiency. Energy Build. 2023, 298, 113517. [Google Scholar] [CrossRef]
  19. Røyset, A.K.; Kolås, T.; Jelle, B.P. Coloured Building-Integrated Photovoltaics: Influence on Energy Efficiency. Energy Build. 2020, 208, 109623. [Google Scholar] [CrossRef]
  20. Pelle, M.; Salvalai, G.; Sesana, M.M.; Vercesi, L.; Pfau, C.; Frontini, F. Opaque Coloured Building-Integrated Photovoltaic (BIPV): A Review of Models and Simulation Frameworks for Performance Optimisation. Energies 2023, 16, 1991. [Google Scholar] [CrossRef]
  21. Manwani, K.; Pawar, N.; Ghosh, A. Development of Novel Orange Coloured Photovoltaic Modules with Multilayer Interference Coatings. Sol. Energy Mater. Sol. Cells 2024, 261, 112617. [Google Scholar]
  22. Ortiz-Lizcano, J.C.; Villa, S.; Zhou, Y.; Frantzi, G.; Vattis, K.; Calcabrini, A.; Yang, G.; Zeman, M.; Isabella, O. Optimal Design of Multilayer Optical Color Filters for Coloured Photovoltaics. Sol. RRL 2023, 7, 2300256. [Google Scholar] [CrossRef]
  23. Lee, H.; Lee, R.; Kim, D.; Yoon, J.; Kim, H.; Lee, G. Performance Evaluation of Sputter-Coating-Based Colour PV Modules for BIPV Applications. Energy Rep. 2022, 8, e07995. [Google Scholar]
  24. Block, A.B.; Palou, J.E.; Courtant, M.; Virtuani, A.; Cattaneo, G.; Roten, M.; Li, H.Y.; Despeisse, M.; Hessler-Wyser, A.; Desai, U.; et al. Colouring Solutions for Building-Integrated Photovoltaic Modules: Technologies, Challenges and Advantages. Energy Build. 2024, 314, 114253. [Google Scholar] [CrossRef]
  25. Roverso, R.; Pelle, M.; Dallapiccola, M.; Astigarraga, A.; Lucchi, E.; Ingenhoven, P.; Maturi, L. Experimental Assessment and Data Analysis of Coloured BIPV Façades. In Proceedings of the 38th European Photovoltaic Solar Energy Conference and Exhibition, Online, 6–10 September 2021; Available online: https://bia.unibz.it/esploro/outputs/conferenceProceeding/991006274396901241 (accessed on 26 October 2025).
  26. Babin, M. Appearance, Performance and Reliability Assessment of Coloured PV Modules. Ph.D. Thesis, Technical University of Denmark, Kongens Lyngby, Denmark, 2024. [Google Scholar]
  27. IEA PVPS Task 15 (Subtask E). Coloured BIPV—Market, Research and Development; Report R07; IEA: Paris, France, 2020. [Google Scholar]
  28. Ahn, J.G.; Boafo, F.E.; Kim, J.H.; Kim, J.T. Performance Analysis of Grey PV Module with Optical Characteristics. Sol. Energy 2023, 264, 111995. [Google Scholar] [CrossRef]
  29. ISO 9060:2018; Solar Energy—Specification and Classification of Instruments for Measuring Hemispherical Solar and Direct Solar Radiation. International Organization for Standardization (ISO): Geneva, Switzerland, 2018.
  30. IEC 61853-1; Photovoltaic (PV) Module Performance Testing and Energy Rating—Part 1: Irradiance and Temperature Performance Measurements. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2011.
  31. National Oceanic and Atmospheric Administration (NOAA). Solar Calculator. Available online: https://gml.noaa.gov/grad/solcalc/ (accessed on 10 October 2025).
  32. Ross, R.G. Interface design considerations for terrestrial solar cell modules. In Proceedings of the IEEE Photovoltaic Specialists Conference, Baton Rouge, LA, USA, 15–18 November 1976; pp. 801–806. [Google Scholar]
Figure 1. Full-scale (1:1 scale) mock-up (real building size) building with various multifunctional prefabricated façade cladding.
Figure 1. Full-scale (1:1 scale) mock-up (real building size) building with various multifunctional prefabricated façade cladding.
Energies 18 05735 g001
Figure 2. Vertical and horizontal section views of the mock-up building with G/G BIPV system installation. The vertical section shows the installation of the G/G BIPV system on the mock-up steel structure, while the horizontal section illustrates the detailed cross-sections of the conventional and colored BIPV systems.
Figure 2. Vertical and horizontal section views of the mock-up building with G/G BIPV system installation. The vertical section shows the installation of the G/G BIPV system on the mock-up steel structure, while the horizontal section illustrates the detailed cross-sections of the conventional and colored BIPV systems.
Energies 18 05735 g002
Figure 3. Full-scale mock-up building (left) and BIPV module installation (middle) and completed BIPV system (right). Two types of BIPV systems were installed on the elevation of the air-conditioned room indicated by the red dotted line.
Figure 3. Full-scale mock-up building (left) and BIPV module installation (middle) and completed BIPV system (right). Two types of BIPV systems were installed on the elevation of the air-conditioned room indicated by the red dotted line.
Energies 18 05735 g003
Figure 4. Layout of the BIPV modules on the mock-up.
Figure 4. Layout of the BIPV modules on the mock-up.
Energies 18 05735 g004
Figure 5. Measurement points for thermocouples on the conventional and colored BIPV systems. In the left figure, the red points indicate the locations of the temperature sensors installed at the back of the BIPV systems. In the right figure, the red points indicate the positions of the thermocouples installed at the BIPV back, air layer, and insulation surface.
Figure 5. Measurement points for thermocouples on the conventional and colored BIPV systems. In the left figure, the red points indicate the locations of the temperature sensors installed at the back of the BIPV systems. In the right figure, the red points indicate the positions of the thermocouples installed at the BIPV back, air layer, and insulation surface.
Energies 18 05735 g005
Figure 6. Interior view of the mock-up building with conventional and gray-colored BIPV systems installed.
Figure 6. Interior view of the mock-up building with conventional and gray-colored BIPV systems installed.
Energies 18 05735 g006
Figure 7. Experimental setup of the BIPV systems.
Figure 7. Experimental setup of the BIPV systems.
Energies 18 05735 g007
Figure 8. Temperature distribution of the conventional BIPV system across different façade layers (module rear surface, air layer, and insulation surfaces).
Figure 8. Temperature distribution of the conventional BIPV system across different façade layers (module rear surface, air layer, and insulation surfaces).
Energies 18 05735 g008
Figure 9. Temperature distribution of the gray-colored BIPV system across different façade layers (module rear surface, air layer, and insulation surfaces).
Figure 9. Temperature distribution of the gray-colored BIPV system across different façade layers (module rear surface, air layer, and insulation surfaces).
Energies 18 05735 g009
Figure 10. Hourly temperature and electrical efficiency of conventional and gray-colored BIPV systems under identical outdoor conditions.
Figure 10. Hourly temperature and electrical efficiency of conventional and gray-colored BIPV systems under identical outdoor conditions.
Energies 18 05735 g010
Figure 11. Hourly power and efficiency of conventional and colored BIPV system.
Figure 11. Hourly power and efficiency of conventional and colored BIPV system.
Energies 18 05735 g011
Figure 12. Box plots of module temperature and efficiency for conventional and colored BIPV systems. The “×” symbol indicates the mean value of each dataset.
Figure 12. Box plots of module temperature and efficiency for conventional and colored BIPV systems. The “×” symbol indicates the mean value of each dataset.
Energies 18 05735 g012
Figure 13. Scatter plot of module-to-ambient temperature difference (ΔTm−a) versus global POA irradiance (G), with linear regression (red line) for the conventional and gray-colored BIPV. The blue and gray points indicate the measured data for the conventional and gray-colored BIPV systems, respectively.
Figure 13. Scatter plot of module-to-ambient temperature difference (ΔTm−a) versus global POA irradiance (G), with linear regression (red line) for the conventional and gray-colored BIPV. The blue and gray points indicate the measured data for the conventional and gray-colored BIPV systems, respectively.
Energies 18 05735 g013
Figure 14. Hourly Ross coefficient of conventional and colored BIPV system.
Figure 14. Hourly Ross coefficient of conventional and colored BIPV system.
Energies 18 05735 g014
Figure 15. Daily cumulative power generation (DC power of four-module string, 31 October 2021).
Figure 15. Daily cumulative power generation (DC power of four-module string, 31 October 2021).
Energies 18 05735 g015
Figure 16. Comparison of efficiency under STC and actual operation conditions of conventional and colored BIPV system. The blue and gray hatched pillars indicate the efficiency of each BIPV module under STC, and the solid pillars indicate the efficiency under actual operation conditions.
Figure 16. Comparison of efficiency under STC and actual operation conditions of conventional and colored BIPV system. The blue and gray hatched pillars indicate the efficiency of each BIPV module under STC, and the solid pillars indicate the efficiency under actual operation conditions.
Energies 18 05735 g016
Table 1. Electrical specifications at STC (rewritten; with citations [28,29,30]).
Table 1. Electrical specifications at STC (rewritten; with citations [28,29,30]).
ParameterUnitGray G/G ModuleConventional G/G Module
PmaxW101.54117.99
VmpV13.3613.18
ImpA7.608.95
VocV16.2916.32
IscA7.969.38
FF%78.3577.11
Efficiency (aperture)%12.4914.52
Module sizemm700 × 1150 (0.81 m2)
ConstructionGlass-to-glass; digital print (gray)Glass-to-glass; clear
Notes: (i) Efficiency is reported on an aperture-area basis [30]. (ii) Electrical parameters are measured under STC; methods are consistent with IEC 61853 practice [30]. (iii) If part of the dataset was used previously, this is acknowledged via [28], while the table organization and wording are newly prepared for this submission. (iv) Irradiance instrumentation and classification follow ISO 9060 [29].
Table 2. Measuring equipment used in this study [28,29,30].
Table 2. Measuring equipment used in this study [28,29,30].
Instrument (Type)Representative ModelOperating/Measurement RangeAccuracy/Class (Typ.)Installation/OrientationSampling/Notes
Plane-of-array pyranometerEKO MS-402 or equivalent (ISO 9060 first-class)Irradiance 0–4000 W·m−2; spectral 285–3000 nm; temp. compensation 10–40 °CFirst-class per ISO 9060; response time (95%) < 8 s; typical sensitivity ≈ 7 µV·(W·m−2)−1Co-planar with façade; tilt 90°; azimuth aligned within ±1°10-s interval; synchronized with electrical and thermal channels
I–V tracer/MPPT monitorLaboratory tracer (array level)Current 0–12 A; voltage 0–500 V; power up to ~1.8 kWTypical accuracy ±0.05% of setting + rangeConnected to the 4-module series string on each façadeContinuous Pmp/Vmp/Imp logging; Voc/Isc periodic sweeps
Data loggerMulti-channel DC loggerInput up to 300 V; auxiliary sensor inputs availableBasic DC voltage accuracy 0.004% (6½-digit class)Centralized rack; common time base for all channels10-s sampling; non-volatile memory ≥ 50,000 records
Thermocouples (T-type)Bare-bead probes with shielded wiringSensor −40–125 °C (probe rating up to 260 °C)±1 °C or ±0.75% (whichever is greater)PV rear × 4; air-gap × 4; insulation surfaces × 4Logged at 10-s; fixed positions and consistent mounting procedure
Weather station (rooftop weather station)Shielded ambient sensor + anemometer (cup/ultrasonic)Ambient air temperature: −40–60 °C; Wind speed: 0–60 m·s−1Air temperature: ±1 °C (shielded); Wind speed: ±0.5 m·s−1 (v < 5 m·s−1), <10% (v ≥ 5 m·s−1)Mounted on rooftop mast; temperature probe in radiation shield; free from local obstructions10-s interval; provides Ta and wind for convection analysis
Notes: (i) Sensors were time-synchronized at a 10-s cadence. (ii) Classification of the pyranometer follows ISO 9060 [29]. (iii) Electrical characterization adheres to IEC 61853 measurement practice [30]. (iv) If a subset of the dataset overlaps with our earlier article, this is disclosed via [30] and the presentation here is newly organized.
Table 3. Parameters and abbreviations used in this study.
Table 3. Parameters and abbreviations used in this study.
Symbol/AbbreviationFull TermUnitDescription
PmaxMaximum powerWMaximum output power under given irradiance
VmpVoltage at maximum power pointVVoltage corresponding to MPP
ImpCurrent at maximum power pointACurrent corresponding to MPP
VocOpen-circuit voltageVVoltage when output current is zero
IscShort-circuit currentACurrent when output voltage is zero
ηElectrical efficiency%Conversion efficiency of PV module
TmModule temperature°CRear-surface temperature of the PV module
TaAmbient temperature°COutdoor air temperature
GGlobal plane-of-array (POA) irradiance W·m−2Beam + diffuse + ground-reflected irradiance incident on the tilted plane
kRoss coefficient°C·m2/WThermal sensitivity constant in Ross model
ΔTTemperature difference°CDifference between Tm and Ta
FFFill Factor%Pmax/(Voc × Isc)
STCStandard Test Conditions1000 W/m2, 25 °C, AM 1.5
MPPTMaximum Power Point TrackingControl mode of I–V tracer/inverter
PRPerformance RatioRatio of measured energy yield to reference yield at STC
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Kim, J.-H.; Ahn, J.-G.; Kim, J.-T. Experimental Evaluation of a Gray-Colored Building-Integrated Photovoltaic Facade System. Energies 2025, 18, 5735. https://doi.org/10.3390/en18215735

AMA Style

Kim J-H, Ahn J-G, Kim J-T. Experimental Evaluation of a Gray-Colored Building-Integrated Photovoltaic Facade System. Energies. 2025; 18(21):5735. https://doi.org/10.3390/en18215735

Chicago/Turabian Style