Next Article in Journal
Impact of Bedroom Ventilation Strategy on Air Change Rates and Indoor Air Parameters in the Autumn–Winter Seasons—In Situ Study in Poland
Previous Article in Journal
Voltage Stability Challenges in a 1 kW-Class PEMFC Stack for Air-Independent Propulsion Applications
Previous Article in Special Issue
Open-Switch Fault Diagnosis for Grid-Tied HANPC Converters Using Generalized Voltage Residuals Model and Current Polarity in Flexible Distribution Networks
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A P-Q Arc Suppression Method Based on DC-Link Voltage Stability for Hybrid Multifunctional Arc Suppression Devices

1
Electric Power Research Institute, Yunnan Power Grid Co., Ltd., Kunming 650217, China
2
National Electric Power Conversion and Control Engineering Technology Research Center, Hunan University, Changsha 410082, China
*
Author to whom correspondence should be addressed.
Energies 2025, 18(16), 4278; https://doi.org/10.3390/en18164278
Submission received: 25 June 2025 / Revised: 31 July 2025 / Accepted: 6 August 2025 / Published: 11 August 2025

Abstract

The traditional arc suppression device suffers from high costs and low utilization. These problems can be effectively avoided by using a hybrid multi-function arc suppression device (HMF-ASD). However, an HMF-ASD will consume active power during arc suppression. Based on this, a P-Q arc suppression method based on DC-link voltage stability is proposed. The energy flow during a single line-to-ground (SLG) fault is analyzed to optimize operation of the HMF-ASD. The topology and principle of the HMF-ASD are introduced. Secondly, the influence mechanism of the traditional arc suppression method on the output active power and energy flow direction of the HMF-ASD is analyzed. The internal reason for the change in the DC-link voltage is clarified. Additionally, non-fault phases of the HMF-ASD are regulated to produce no active output, delivering only the reactive current required for arc suppression. This method effectively mitigates SLG faults while maintaining DC-link voltage stability. Non-fault phases exclusively supply reactive power, with the active power needed for arc suppression drawn directly from the grid. The validity of the proposed method is confirmed through both simulation and experiment.

1. Introduction

A distribution network serves as a vital component in constructing a new power system. Characterized by complex structures and frequent grounding faults, the SLG fault accounts for the highest proportion, approximately 80% [1,2,3,4]. With the massive expansion of power electronic devices and nonlinear loads on distribution networks, both active and reactive power components in grounding fault currents have significantly increased [5,6]. The reactive power component can be only compensated by traditional passive arc suppression devices. Arcs can be generated by the active component and the harmonic component [7,8]. When an SLG fault occurs in a coal mine power grid in China, the active component of the measured grounding current reaches 13.05 A [8]. The fault current of some distribution networks is still as high as tens of amperes after the compensation capacitor component of the passive arc suppression device. If the fault cannot be eliminated, it will seriously threaten the power grid.

Literature Review

The active arc suppression device can achieve full compensation of the fault current. The existing active arc suppression devices inject zero-sequence current to regulate the zero-sequence voltage to be the opposite of the fault phase voltage [9,10,11]. However, these active arc suppression devices only operate during an SLG fault in distribution networks, suffering from low equipment utilization efficiency.
To fully leverage the flexible regulation capabilities of power electronic devices, an HMF-ASD that combines power quality management and grounding fault regulation is proposed. An HMF-ASD can not only achieve arc suppression during an SLG fault in the power grid but it also performs reactive power compensation, harmonic control, and three-phase imbalance control, which significantly enhances the equipment utilization rate. In [12], an HMF-ASD based on cascaded H-bridges is proposed, which outputs arc suppression current and reactive power compensation current.
However, the voltage withstand requirement of the HMF-ASD during arc suppression reaches the line voltage. This has led to the problem of high device costs. In [13], an HMF-ASD is introduced which integrates cascaded H-bridge configurations with a passive arc suppression coil. The primary function of the arc suppression coil is to offset the predominant reactive portion of the fault current. Meanwhile, the active module is designed to compensate for the active power component, harmonic distortions, and a residual fraction of the reactive power in the fault current. Since an HMF-ASD needs to fully compensate for the reactive power demands of the load, the overall capacity tends to be large. In [14], an HMF-ASD based on cascaded H-bridges and single-phase converters is proposed, which achieves deep integration of power exchange, power quality management, and grounding fault regulation. However, when the magnitude of the active current component is considerable, a voltage shift occurs at the common point, consequently compromising the DC-link voltage.
It is crucial for realizing efficient fault current compensation to maintain stable DC-link voltage. Till now, there are two ways for an HMF-ASD to maintain the DC-link voltage. Scheme I is controlling the converter to absorb energy based on positive and negative sequence loops [15,16,17,18,19,20]. Scheme II is adding additional energy storage units [21,22,23,24,25]. As for Scheme I, the influence of a zero sequence loop is not considered. Further, the existing DC-link voltage control strategies for an arc suppression device are not applicable to the condition with ground resistance [19,20]. As for Scheme II, in [21], every H-bridge module in the HMF-ASD is linked to an energy storage unit, leading to a relatively high overall device cost. In [22], only a single energy storage device is integrated into the HMF-ASD. In [23], a method is introduced that achieves DC-link voltage stability by alternately conducting arc suppression and voltage regulation on the two non-fault phases. However, this approach falls short in simultaneously accomplishing reactive power compensation and arc suppression. The existing HMF-ASDs effectively improve equipment utilization and practicality, but additional energy supply devices are needed [24,25].
To further solve the problem of unstable DC-link voltage in HMF-ASDs, a P-Q arc suppression method is proposed. Firstly, the topological structure of the HMF-ASD is elaborated in this paper. Under normal grid conditions, the HMF-ASD provides reactive power to meet the load’s demands. When an SLG fault occurs, reactive power compensation and arc suppression are achieved simultaneously. Secondly, the energy flow characteristics during an SLG fault and the reason for the failure of the traditional DC-link voltage control method are analyzed. Further, by controlling the HMF-ASD to output only reactive power during arc suppression, the DC-link voltage is stable. Finally, the validity of the proposed method is confirmed through both simulation and experiment.

2. Topology and Working Principle of HMF-ASD

The rated voltage of the distribution network is 10 kV and the neutral point is ungrounded. A three-phase structure with symmetrical distribution among the three phases is used, and the arc suppression coil is linked to the common point. The topology of the HMF-ASD is shown in Figure 1. In Figure 1, Ig, Ix (x = a, b, c), and Iinvx are the fault current, system current, and output current of the HMF-ASD, respectively. Ex, Usx, Ug, and Udc are the system voltage, busbar voltage, fault voltage, and DC-link voltage, respectively. rx and C0x are the ground resistance and capacitance, respectively. Cdc is the DC-link capacitance. Rf is the ground-fault resistance. Lf and LN are filter inductance and arc suppression inductance, respectively.

2.1. Analysis of Reactive Power Compensation Mode

Under normal conditions of the power grid, the HMF-ASD operates in a reactive power compensation state. The HMF-ASD compensates reactive power by load, which can be regarded as a controlled current source. The equivalent circuit diagram during normal conditions of a power grid is shown in Figure 2.
The voltage at the common connection point of the HMF-ASD Uo is regulated to 0 and the arc suppression inductance branch is equivalent to an open circuit. The HMF-ASD outputs reactive power compensation current and the HMF-ASD bears the phase voltage. The current flow diagram during normal operation of a power grid is shown in Figure 3.
The reactive power compensation current output by HMF-ASD is:
I inva + I a = I loada _ Q j ω C 0 a E a I invb + I b = I loadb _ Q j ω C 0 b E b I invc + I c = I loadc _ Q j ω C 0 c E c
where Iloada_Q, Iloadb_Q, and Iloadc_Q are the reactive currents of the three-phase load.

2.2. Analysis of Arc Suppression Mode

When an SLG fault occurs, the HMF-ASD switches to arc suppression mode. The ground fault point establishes a closed loop with the grounding characteristics of the distribution network, allowing the ground current to pass through the fault location. During this process, arc suppression and reactive power compensation are carried out concurrently. The equivalent schematic diagram is shown in Figure 4 and the HMF-ASD can still be equivalently regarded as a controlled current source,
The current flow diagram during an SLG fault is shown in Figure 5 and Uo is controlled to −Ec. The HMF-ASD outputs arc suppression current to effectively reduce the current at the fault point.
In order to obtain the arc suppression current of each phase output of the HMF-ASD, the current equation is written in the zero-sequence loop of the system. The following equation is obtained by formulating KCL at node D and substituting the network parameters:
U sc ( 1 r c + 1 R f + j ω C 0 c ) + U sb ( 1 r b + j ω C 0 b ) +                 U sa ( 1 r a + j ω C 0 a ) ( I oa + I ob + I oc ) = 0
Assuming that the three-phase voltage is balanced, the ground resistance and capacitance are r0 and C0, respectively. When using the traditional arc suppression method, the three-phase output arc suppression currents Iox output by the HMF-ASD are as follows:
I oa = ( E a E c ) ( 1 r 0 + j ω C 0 ) I ob = ( E b E c ) ( 1 r 0 + j ω C 0 ) I oc = 0
The output currents of the HMF-ASD are as follows:
I inva = I loada _ Q + I oa I invb = I loadb _ Q + I ob I invc = I loadc _ Q + I oc

3. Failure Mechanism of Traditional Arc Suppression Method

This section examines how the conventional arc suppression approach affects the output active power and energy flow direction of the HMF-ASD, while also elucidating the underlying cause for variations in the DC-link voltage.

3.1. Power Characteristics of Traditional Arc Suppression Method

According to Figure 4 and Figure 5, it can be seen that the voltage borne by the active part of HMF-ASD Uinvx during arc suppression is as follows:
U inva = U sa U o = E a U invb = U sb U o = E b U invc = U sc U o = E c
According to Equations (3)–(5), the active power transmitted by HMF-ASD Pinvx during arc suppression can be obtained as follows:
P inva = 3 E 2 1 r 0 2 + ω 2 C 0 2 cos θ P invb = 3 E 2 1 r 0 2 + ω 2 C 0 2 cos ( θ + 60 ° ) P invc = 0
where θ is the angle between Ioa and Ea, which is related to rx and C0x. The specific expression is as follows:
θ = arctan ( ω C 0 r 0 ) 30 °
The specific variation is shown in Table 1. It can be seen from Equation (6) that θ can directly reflect the range of the active power absorbed and emitted by the HMF-ASD.
As can be seen from Table 1, when 0 ≤ θ ≤ 60°, Pinva > 0. Phase A consumes active power during arc suppression. When 0 ≤ θ < 30°, Pinvb > 0. Phase B consumes active power. When θ = 30°, Pinvb = 0. Phase B only transmits reactive power during arc suppression. When 30° < θ ≤ 60°, Pinvb < 0. The HMF-ASD absorbs active power during arc suppression. During arc suppression, Pinvc = 0, and phase C only outputs the load reactive current.

3.2. Control Strategy of the Traditional Arc Suppression Method

The reference value id.dc corresponding to the voltage loop is obtained by calculating the difference between the reference value Udc.ref and the actual value Udc through the voltage loop PI. The load current is sampled, and the reactive compensation reference current iq.ref is subsequently calculated following dq transformation. The grid voltage components along the D-axis and Q-axis are combined with the controller outputs to produce the corresponding D-axis and Q-axis reference signals. The total arc suppression current Iz specified in Formula (3) is utilized as the reference value. The specific expression of Iz is Iz = Ioa + Iob + Ioc. Additionally, the reference signal for the 0-axis is obtained by processing the difference in the zero-sequence current io through the current loop PI controller. Finally, the modulated signal Usum is produced by performing an inverse dq transformation. The traditional arc suppression method is shown in Figure 6.
To compensate for the active power consumed during arc suppression and sustain DC-link voltage stability in the HMF-ASD, the system absorbs active power from the grid using a conventional arc suppression strategy. The active components of both the arc suppression current and the stabilizing current exhibit equal magnitudes but opposite polarities. Based on Equations (3)–(5), the stabilizing current of the HMF-ASD Iox1 can be expressed as follows:
I oa 1 = 3 r 0 2 + 3 ω 2 C 0 2 cos θ E a I ob 1 = 3 r 0 2 + 3 ω 2 C 0 2 cos ( θ + 60 ) E b I oc 1 = 0
where Iox1 is the active component of the stabilizing current of the HMF-ASD.
The conventional arc suppression approach is limited to regulating only the active power exchanged between the HMF-ASD and the distribution network. According to Equation (8), it is known that Ioa1 + Iob1 + Ioc1 = 0. At this time, the neutral point of the grid cannot satisfy KCL. There must be reactive power exchange between the HMF-ASD and the grid. Therefore, the traditional arc suppression method is unable to stabilize DC-link side voltage.

4. P-Q Arc Suppression Method Based on DC-Link Voltage Stability

Due to the large ground resistance, the active component of the arc suppression current only accounts for 5–10%. The variation range of α is from 0° to 10°, and the specific variation trajectory is shown in Figure 7a. As shown in the figure, the solid line and the dotted line represent the phasor relationship when α = 10° and α = 0°, respectively. The change trajectory is shown in the gray line.
To address the aforementioned issues, a P-Q arc suppression method is introduced. During an SLG fault, the HMF-ASD is controlled to output only reactive power, enabling complete compensation of the fault current and stabilization of the DC-link voltage without using external power supply devices. When the SLG fault occurs, non-fault phases jointly output arc suppression current. The phasor relationship is shown in Figure 7b, where α is the angle between the rx and C0x. The specific expression is as follows:
α = arctan ( 1 ω C 0 r 0 )
According to Figure 7, the zero-sequence power output by the HMF-ASD is as follows:
P zab = 2 E I z sin α Q zab = 2 E I z cos α
where Pzab and Qzab are the zero-sequence active power and reactive power using the traditional arc suppression method, respectively.
When the traditional arc suppression method is adopted, the HMF-ASD is required to simultaneously output both active and reactive power. To stabilize the DC-link voltage, supplementary energy supply units become necessary. The P-Q arc suppression method can attain complete compensation of the fault current and ensure the stability of the DC-link voltage by regulating the HMF-ASD to output solely reactive power, thereby eliminating the need for additional energy supply devices. Since the active and reactive components of the arc suppression current are respectively provided by the power grid and the HMF-ASD, the value of the arc suppression current remains unchanged. The value of the arc suppression current will not be affected by the HMF-ASD.
The zero-sequence power of the HMF-ASD is as follows:
P zab = 0 Q zab = 2 E I z cos α
where Pzab and Qzab are the zero-sequence active power and reactive power using the P-Q arc suppression method, respectively.
Therefore, when the P-Q arc suppression method is adopted, the phase A and phase B of the HMF-ASD compensate the zero-sequence reactive power. Meanwhile, the grid side undertakes the compensation for the active power. Both active power and reactive power flow along the line. The diagram illustrating the zero-sequence power flow is shown in Figure 8.
The proposed control strategy is shown in Figure 9. The control strategy of the HMF-ASD mainly includes a power loop and a voltage stability loop. Qb* and Qa* are the reactive power reference values of phase B and A, respectively. Qb and Qa are the actual reactive power values of phase B and A, respectively. izb and iza are the current reference values corresponding to the power loops of phase B and A, respectively. idcb and idca are the current reference values corresponding to the voltage stabilizing loops of phase B and A, respectively. Ebc and Eac are the line voltage of the BC phase and the AC phase, respectively. Udcx.ref and ∑Udcxi are the reference values of the actual value of the DC-link voltage. N is the number of cascades.
(1)
Power loop
During the fault, the Qa* and Qb* needed for arc suppression in phases A and B are calculated, and the reference values of arc suppression currents iza and izb are obtained through the power loop PI using the difference between them and the actual value.
(2)
Voltage stabilizing loop
idca and idcb of the voltage stabilizing are obtained through the voltage stabilizing PI. The actual output current is regulated by calculating the deviation between the combined current references and the measured current.
(3)
Current loop
iza, izb, idca, and idcb serve as the input to the current loop PI regulator, whose output is superimposed on the busbar voltage of the HMF-ASD. The resulting signal undergoes carrier phase shift PWM (CPS-PWM) to generate the signals for the HMF-ASD.
Till now, two ways are proposed to stabilize the DC-link voltage in an HMF-ASD. Scheme I is controlling the converter to absorb energy based on positive and negative sequence loops. Scheme II is adding auxiliary DC power supply units.
(1)
As for Scheme I, the influence of a zero sequence loop is not considered. Further, the existing DC-link voltage control strategies for arc suppression devices are not applicable to the condition with ground resistance. As the DC-link voltage of the HMF-ASD progressively decreases, fault current escalates, ultimately compromising arc suppression capability.
(2)
As for Scheme II, the DC side of the HMF-ASD is connected to auxiliary DC power supplies to provide arc suppression energy. While this method enables complete fault current compensation with minimal control complexity, it incurs relatively high costs.
(3)
To achieve DC-link voltage stability and full fault current compensation without auxiliary power supplies, this paper introduces a P-Q-based arc suppression strategy. A comparative analysis with existing methods is presented in Table 2. The proposed method demonstrates superior cost-effectiveness and arc suppression performance compared to conventional approaches, though its control complexity exceeds that of Scheme II.

5. Simulation Results

To evaluate the practicality and performance of the proposed HMF-ASD topology and its operational functions, a simulation model is developed using the MATLAB 2021a/Simulink environment. Detailed simulation parameters are provided in Table 3.

5.1. Simulation of Reactive Power Compensation Mode

During 0–0.1 s, the HMF-ASD is not put into operation. During 0.1–0.5 s, the HMF-ASD operates in reactive power compensation mode. Comprehensive simulation waveforms for the reactive power compensation mode are provided in Figure 10. Ea and Ia waveforms are shown in Figure 10a. Ea = 8165 V and Ia = 173 A. The in-phase alignment of voltage and current confirms the system’s effective reactive power compensation capability. The reactive power distribution is further analyzed in Figure 10b, showing the load reactive power (Qload = 241 kVar), the reactive power of the ground capacitance (Qc = 105 kVar), and the reactive power of the HMF-ASD (Qinv = 136 kVar). The ground capacitance accounts for 43.6% of the total compensation, while the HMF-ASD contributes 56.4%.

5.2. Simulation of Arc Suppression Mode

In order to further verify the performance of the HMF-ASD using the traditional control strategy, a simulation model of a 10 kV distribution network is built. The waveforms using the traditional control strategy are shown in Figure 11a,b. The HMF-ASD operates in arc suppression mode from 0.3–0.5 s, switching to reactive power compensation mode during other times.
As shown in Figure 11a, the DC-link voltage of the CHB remains stable at 2000 V between 0.2 s and 0.3 s. At 0.3 s, non-fault phases initiate arc suppression current injection. During this period, phase B consumes active power, causing its DC-link voltage to decrease, while phase C absorbs active power, resulting in an increase in its CHB DC-link voltage. Figure 11b demonstrates that the HMF-ASD achieves effective arc suppression between 0.3 s and 0.4 s. However, as DC-link voltages continue to decline, the fault current rises, ultimately compromising the HMF-ASD arc suppression capability. These findings indicate that the conventional control strategy fails to maintain effective arc suppression under conditions involving ground resistance.
The simulated waveforms of the HMF-ASD using the P-Q arc suppression method are presented in Figure 12. For fault resistances Rf = 1 Ω and Rf = 1000 Ω, the corresponding fault current Ig waveforms are displayed in Figure 12a,b. After the HMF-ASD is switched to the arc suppression mode, the fault current Ig is reduced to zero within 100 ms. The DC-link voltages of phases B and C, as shown in Figure 12c,d, stabilize near 2 kV for each sub-module after mode transition, ensuring precise delivery of arc suppression current. The output currents (Iinva, Iinvb, and Iinvc) are illustrated in Figure 12e. During reactive power compensation mode, the system accurately injects compensation current, while in arc suppression mode, phases B and C deliver 73.7∠-30.8° A and 75.1∠-149.6° A, respectively, enabling effective SLG fault mitigation.
To assess the impact of arc suppression inductance, the HMF-ASD operates without current injection during 0.2–0.3 s. From 0.3–0.4 s, direct grounding is employed to inject arc suppression current, followed by inductance-based grounding from 0.4–0.5 s. The voltage waveforms for the HMF-ASD and arc suppression inductance are depicted in Figure 12f. Under normal grid conditions, the HMF-ASD output voltage matches the phase voltage. At 0.2 s, an SLG fault in phase A causes neutral point voltage deviation, elevating the HMF-ASD output above the phase voltage. Direct grounding at 0.3 s shifts the neutral point voltage to approximately −Ea, raising the HMF-ASD output to line voltage. At 0.4 s, inductance-based grounding reduces the inductance voltage ULN to near −Ea, restoring the HMF-ASD output to phase voltage. Simulation results confirm that inductance-based grounding significantly decreases inductor capacity requirements in arc suppression mode, thereby minimizing power device usage.

6. Experimental Results

To validate the effectiveness and precision of the proposed P-Q arc suppression method, an experimental assessment is conducted using a Control Hardware-in-the-Loop (CHIL) testbed built on the RT-LAB OP5600 platform (Opal-RT). Figure 13 illustrates the configuration of this RT-LAB-based CHIL testing system.
An SLG fault is assumed to occur in Phase A at t1. During the t0-t1, the HMF-ASD operates in reactive power compensation mode. From t1-t2, the system transitions to arc suppression mode, and after t2, it reverts to reactive power compensation. All other experimental parameters remain consistent with those used in the simulation.
Figure 14 displays the experimental waveforms of Udca, Udcb, and Udcc. Using the proposed P-Q arc suppression method, the DC-link voltage of the HMF-ASD remains stable at 2000 V during arc suppression, with voltage fluctuations constrained within 50 V. Figure 15 presents the experimental waveforms of Eb and Ib. When the HMF-ASD operates in reactive power compensation mode, it supplies the load’s reactive power demand, ensuring in-phase alignment between grid voltage and current. Figure 16 illustrates the experimental waveforms of Uo, ULN, and Ig. During arc suppression mode, the HMF-ASD reduces the fault current to 0.1 A, while the voltage across the arc suppression inductance reaches approximately 8000 V. Figure 17 shows the experimental waveforms of Iinva, Iinvb, and Iinvc. The reactive current required for reactive power compensation is delivered in compensation mode, whereas the reactive current for arc suppression is provided in suppression mode.

7. Conclusions

Aiming at the problem that HMF-ASDs need to add additional power supply units to maintain DC-link voltage, a P-Q arc suppression method based on DC-link voltage stability is proposed. The conclusions are as follows:
(1)
The working principle of the HMF-ASD is introduced and the current flow of the HMF-ASD in two modes is analyzed.
(2)
The influence mechanism of the traditional arc suppression method on the output active power and energy flow direction of the HMF-ASD is analyzed. The internal causes of DC link voltage changes are clarified.
(3)
The phase relationship between voltage and current under arc suppression mode is analyzed, and a P-Q arc suppression method is proposed. By controlling the HMF-ASD to compensate only zero-sequence reactive power, the HMF-ASD can stabilize the DC-link voltage.
(4)
Compared with existing methods, the proposed method has lower cost and better arc suppression effect, but the control complexity is relatively high.
(5)
In the future, the performance improvement of PLL under unbalanced and fault conditions will be further studied.

Author Contributions

Supervision, Q.G.; conceptualization, Z.H. and Q.G.; methodology, Z.H. and H.L.; software, H.L. and C.Z.; validation, J.Y.; project administration, Q.G.; formal analysis, H.L. and C.Z.; investigation, J.Y.; resources, C.Z.; data curation, H.L.; writing—original draft, Z.H.; writing—review and editing, Z.H. and H.L.; visualization, C.Z. and J.Y.; funding acquisition, H.L. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Science and Technology Project of China Southern Power Grid Corporation, grant number 0562002023030301PD00015.

Data Availability Statement

Data is contained within the article.

Conflicts of Interest

Authors Hongwen Liu, Chunli Zhang and Jindong Yang were employed by the Yunnan Power Grid Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Nomenclature

ParametersDefinitions
ExSystem voltage
UsxBusbar voltage
UgFault voltage
UoThe voltage at the common point of HMF-ASD
UinvxThe voltage borne by the active part of HMF-ASD
IxSystem current
IgFault current
IinvxOutput current of HMF-ASD
Iloadx_QReactive currents of the load
IoxArc suppression currents
Iox1The active component of the stabilizing current of HMF-ASD
IzTotal arc suppression current
rxThe ground resistance
C0xThe ground capacitance
CdcThe DC-link capacitance
LfFilter inductance
LNArc suppression inductance
RfThe ground-fault resistance
PinvxThe active power transmitted by HMF-ASD
PzabThe zero-sequence active power using traditional arc suppression method
PzabThe zero-sequence active power using P-Q arc suppression method
Qx*The reactive power reference values
QxThe actual reactive power values
QloadThe reactive power of the load
QcThe reactive power of the ground capacitance
QinvThe reactive power of HMF-ASD
QzabThe zero-sequence reactive power using traditional arc suppression method
QzabThe zero-sequence reactive power using P-Q arc suppression method
izxThe current reference values corresponding to power loops
idcxThe current reference values corresponding to voltage stabilizing loops
NThe number of cascades
Udcx.refThe reference value of DC-link voltage
UdcxiThe actual value of DC-link voltage
ULNThe voltage of arc suppression inductance
αThe angle between the ground resistance and capacitance

References

  1. Zhu, R.; Liserre, M. Control of Smart Transformer Under Single-Phase to Ground Fault Condition. IEEE Trans. Power Electron. 2020, 35, 2034–2043. [Google Scholar] [CrossRef]
  2. Huang, Z.; Guo, Q.; Xiao, Z.; Tu, C.; Sun, K.; Wang, L.; Zhu, D.; Hou, Y. Hybrid Multifunctional Arc Suppression Inverter With Its Steady and Transient State Operation Optimization Method. IEEE Trans. Power Electron. 2025, 40, 10313–10323. [Google Scholar] [CrossRef]
  3. Tang, J.; Xiong, B.; Li, Y.; Yuan, C.; Qiu, Y. Faulted Feeder Identification Based on Active Adjustment of Arc Suppression Coil and Similarity Measure of Zero-Sequence Currents. IEEE Trans. Power Deliv. 2021, 36, 3903–3913. [Google Scholar] [CrossRef]
  4. Liu, K.; Zhang, S.; Li, B.; Zhang, C.; Liu, B.; Jin, H.; Zhao, J. Flexible Grounding System for Single-Phase to Ground Faults in Distribution Networks: A Systematic Review of Developments. IEEE Trans. Power Deliv. 2022, 37, 1640–1649. [Google Scholar] [CrossRef]
  5. Li, L.; Zeng, X.; Bai, H.; Yu, K.; Li, J.; Peng, H.; Wang, Z.; Luo, H.; Wang, F. Analysis and Design of Flexible Arc Suppression Device Based on Proportional Series Lagging Control. Int. J. Electr. Power Energy Syst. 2022, 143, 108478. [Google Scholar] [CrossRef]
  6. Tan, L.; Wang, Y.; Yin, X.; Qiao, J.; Xu, W. Injected Current Regulation Based Stator Ground Fault Arc Suppression Method for Large Hydro-Generators. Int. J. Electr. Power Energy Syst. 2022, 143, 108513. [Google Scholar] [CrossRef]
  7. Belik, M.; Kuchanskyy, V.; Rubanenko, O. The Method of the Secondary Arc Suppression in Cycle Single-Phase Auto Reclose with High-Level Penetration Renewable Energy Sources. Energies 2023, 16, 6880. [Google Scholar] [CrossRef]
  8. Ouyang, S.; Liu, J.; Yang, Y.; Chen, X.; Song, S.; Wu, H. Control Strategy for Arc-Suppression-Coil-Grounded Star-Connected Power Electronic Transformers. IEEE Trans. Power Electron. 2019, 34, 5294–5311. [Google Scholar] [CrossRef]
  9. Wang, W.; Gao, X.; Fan, B.; Zeng, X.; Yao, G. Faulty Phase Detection Method under Single-Line-to-Ground Fault Considering Distributed Parameters Asymmetry and Line Impedance in Distribution Networks. IEEE Trans. Power Deliv. 2022, 37, 1513–1522. [Google Scholar] [CrossRef]
  10. Zeng, X.; Xu, Y.; Wang, Y. Some Novel Techniques for Insulation Parameters Measurement and Petersen-Coil Control in Distribution Systems. IEEE Trans. Ind. Electron. 2010, 57, 1445–1451. [Google Scholar] [CrossRef]
  11. Fan, B.; Yao, G.; Yu, K.; Zeng, X.; Wang, W.; Zhuo, C.; Guerrero, J. Principle of Flexible Ground-Fault Arc Suppression Device Based on Zero-Sequence Voltage Regulation. IEEE Access 2021, 9, 2382–2389. [Google Scholar] [CrossRef]
  12. Zheng, Z.; Guo, M.; Yang, N.; Jin, T. Flexible Arc-Suppression Method Based on Improved Distributed Commutations Modulation for Distribution Networks. Int. J. Electr. Power Energy Syst. 2020, 116, 105580. [Google Scholar] [CrossRef]
  13. Zhou, X.; Lu, S. An Arc-Suppression Method Based on the Coordinated Operation of the Petersen Coil and the Static Synchronous Compensator in Distribution Networks. Trans. China Electr. Soc. 2019, 34, 1251–1262. [Google Scholar]
  14. You, J.; Guo, M. Integrated Converter with Reactive Power Compensation and Fault Suppression and Its Control Strategy. Power Syst. Technol. 2022, 46, 2241–2248. [Google Scholar]
  15. Koyama, Y.; Nakazawa, Y.; Mochikawa, H.; Kuzumaki, A.; Sano, K.; Okada, N. A Transformerless 6.6-kV STATCOM Based on a Hybrid Cascade Multilevel Converter Using SiC Devices. IEEE Trans. Power Electron. 2018, 33, 7411–7423. [Google Scholar] [CrossRef]
  16. Wang, H.; Zhang, J.; Xia, X.; Gao, F.; Cheng, J. DC-Link Capacitance Design for Cascaded H-Bridge STATCOM With Sum of Squares Formulation. IEEE Trans. Power Electron. 2024, 39, 5733–5749. [Google Scholar] [CrossRef]
  17. Zhao, G.; Guo, M.; Zhang, B.; Zheng, Z.; Hong, Q. Cascaded H-Bridge Converter-Based Flexible Arc Suppression Method Adapting to Line Parameter Variations. IEEE Trans. Power Electron. 2025, 40, 11809–11819. [Google Scholar] [CrossRef]
  18. Pang, R.; Ding, W. Series Arc Fault Characteristics and Detection Method of a Photovoltaic System. Energies 2023, 16, 8016. [Google Scholar] [CrossRef]
  19. Cong, H.; Wang, Y.; Hu, X.; Zhang, X.; Su, W.; Li, Q. Simulation Study on the Suppression Effect on Secondary Arcs Based on Online Injection Power Compensation. IEEE Trans. Power Deliv. 2025, 40, 878–888. [Google Scholar] [CrossRef]
  20. Guo, C.; Guo, M. Quasi-PR Control Based Flexible Arc Suppression Method in Power Distribution Networks. In Proceedings of the 2020 IEEE 1st China International Youth Conference on Electrical Engineering (CIYCEE), Wuhan, China, 1–4 November 2020; pp. 1–7. [Google Scholar]
  21. Qiu, W.; Guo, M.; Yang, G.; Zheng, Z. Model-Predictive-Control-Based Flexible Arc-Suppression Method for Earth Fault in Distribution Networks. IEEE Access 2019, 7, 16051–16065. [Google Scholar] [CrossRef]
  22. Huang, Z.; Guo, Q.; Tu, C.; Hou, Y.; Jiang, F.; Wang, X.; Xiao, F.; Xiao, Z. A Non-neutral Alternate Arc Suppression Method for Single Phase Grounding Fault in Active Distribution Network. Int. J. Electr. Power Energy Syst. 2023, 152, 109182. [Google Scholar] [CrossRef]
  23. Chen, Y.; Lu, S.; Zhou, X.; Liang, S. Two-Phase Current Injection Method for Single Line-to-Ground Fault Arc-Suppression with Revised STATCOM. IEEE Access. 2020, 8, 188299–188308. [Google Scholar] [CrossRef]
  24. Hou, Y.; Guo, Q.; Tu, C.; Jiang, F.; Wang, L.; Wang, X. Adaptive Active Voltage-Type Arc Suppression Strategy Considering the Influence of Line Parameters in Active Distribution Network. IEEE Trans. Ind. Electron. 2023, 70, 4799–4808. [Google Scholar] [CrossRef]
  25. Bains, T.P.S.; Sidhu, T.S.; Xu, Z.; Voloh, I.; Zadeh, M.R.D. Impedance-Based Fault Location Algorithm for Ground Faults in Series-Capacitor-Compensated Transmission Lines. IEEE Trans. Power Deliv. 2018, 33, 189–199. [Google Scholar] [CrossRef]
Figure 1. Topology of the HMF-ASD.
Figure 1. Topology of the HMF-ASD.
Energies 18 04278 g001
Figure 2. Equivalent circuit diagram under normal conditions.
Figure 2. Equivalent circuit diagram under normal conditions.
Energies 18 04278 g002
Figure 3. Current flow diagram during normal operation of power grid.
Figure 3. Current flow diagram during normal operation of power grid.
Energies 18 04278 g003
Figure 4. Equivalent circuit diagram during SLG fault.
Figure 4. Equivalent circuit diagram during SLG fault.
Energies 18 04278 g004
Figure 5. Current flow diagram during SLG fault.
Figure 5. Current flow diagram during SLG fault.
Energies 18 04278 g005
Figure 6. Control strategy of the traditional arc suppression method.
Figure 6. Control strategy of the traditional arc suppression method.
Energies 18 04278 g006
Figure 7. Phasor diagram of HMF-ASD.
Figure 7. Phasor diagram of HMF-ASD.
Energies 18 04278 g007
Figure 8. Zero-sequence power flow diagram of P-Q arc suppression method.
Figure 8. Zero-sequence power flow diagram of P-Q arc suppression method.
Energies 18 04278 g008
Figure 9. Control strategy of HMF-ASD.
Figure 9. Control strategy of HMF-ASD.
Energies 18 04278 g009
Figure 10. Simulation waveforms of reactive power compensation mode.
Figure 10. Simulation waveforms of reactive power compensation mode.
Energies 18 04278 g010
Figure 11. Simulation waveforms of arc suppression mode using traditional control strategy. (a) Waveforms of Udca, Udcb, and Udcc. (b) Waveforms of Ig.
Figure 11. Simulation waveforms of arc suppression mode using traditional control strategy. (a) Waveforms of Udca, Udcb, and Udcc. (b) Waveforms of Ig.
Energies 18 04278 g011
Figure 12. Simulation waveforms of arc suppression mode using P-Q arc suppression method.
Figure 12. Simulation waveforms of arc suppression mode using P-Q arc suppression method.
Energies 18 04278 g012
Figure 13. RT-LAB based CHIL testing platform.
Figure 13. RT-LAB based CHIL testing platform.
Energies 18 04278 g013
Figure 14. Experimental waveforms of Udca, Udcb, and Udcc.
Figure 14. Experimental waveforms of Udca, Udcb, and Udcc.
Energies 18 04278 g014
Figure 15. Experimental waveforms of Eb and Ib.
Figure 15. Experimental waveforms of Eb and Ib.
Energies 18 04278 g015
Figure 16. Experimental waveforms of Uo, ULN, and Ig.
Figure 16. Experimental waveforms of Uo, ULN, and Ig.
Energies 18 04278 g016
Figure 17. Experimental waveforms of Iinva, Iinvb, and Iinvc.
Figure 17. Experimental waveforms of Iinva, Iinvb, and Iinvc.
Energies 18 04278 g017
Table 1. Variation of energy of HMF-ASD with θ.
Table 1. Variation of energy of HMF-ASD with θ.
The Range of θPinvaPinvbPinvc
0 ≤ θ < 30°++0
θ = 30°+00
30° < θ ≤ 60°+0
Table 2. The comparison between existing methods and P-Q arc suppression method.
Table 2. The comparison between existing methods and P-Q arc suppression method.
Contrast TypeScheme IScheme IIP-Q Arc Suppression Method
CostLowHighLow
The effect of arc suppressionLittleGreatGreat
ComplexityMediumLowMedium
Table 3. Simulation Parameters.
Table 3. Simulation Parameters.
ParametersValuesParametersValues
Distribution network voltage (kV)10Filter inductance (mH)5
Ground resistance (kΩ)30Active power of load (MW)1
Ground capacitance (uF)10Power factor of load0.97
Ground-fault resistance (Ω)1DC-link capacitance (mF)3
Arc suppression inductance (mH)330Number of cascaded modules5
Proportional coefficient of the power loop0.0175Integral coefficient of the power loop15
Proportional coefficient of the stabilizing loop0.2Integral coefficient of the stabilizing loop20
Proportional coefficient of the current loop5Integral coefficient of the current loop30
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Liu, H.; Huang, Z.; Zhang, C.; Guo, Q.; Yang, J. A P-Q Arc Suppression Method Based on DC-Link Voltage Stability for Hybrid Multifunctional Arc Suppression Devices. Energies 2025, 18, 4278. https://doi.org/10.3390/en18164278

AMA Style

Liu H, Huang Z, Zhang C, Guo Q, Yang J. A P-Q Arc Suppression Method Based on DC-Link Voltage Stability for Hybrid Multifunctional Arc Suppression Devices. Energies. 2025; 18(16):4278. https://doi.org/10.3390/en18164278

Chicago/Turabian Style

Liu, Hongwen, Zejun Huang, Chunli Zhang, Qi Guo, and Jindong Yang. 2025. "A P-Q Arc Suppression Method Based on DC-Link Voltage Stability for Hybrid Multifunctional Arc Suppression Devices" Energies 18, no. 16: 4278. https://doi.org/10.3390/en18164278

APA Style

Liu, H., Huang, Z., Zhang, C., Guo, Q., & Yang, J. (2025). A P-Q Arc Suppression Method Based on DC-Link Voltage Stability for Hybrid Multifunctional Arc Suppression Devices. Energies, 18(16), 4278. https://doi.org/10.3390/en18164278

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Article metric data becomes available approximately 24 hours after publication online.
Back to TopTop