The performed experiments for all test configurations are emphasized on a main parameter of the study, namely temperature. A total of 11 thermocouples were used in the experiments, of which four were used for exhaust gas temperature measurements, six for water temperatures inside the pipes with different placements and positions, and one for air ambient temperature inside the factory. It is necessary to note that the operational temperature (T5 = 79 °C) is set by the manufacturer. The press machine is ready to start functioning at this temperature. The boiler is adjusted to this temperature, and turns off automatically when reaching this value, before turning on again when the temperature decreases to increase it again.
3.1. Thermal Behavior
In this part, two samples of the tests will be discussed, and corresponding graphs will be included.
Figure 13 and
Figure 14 show the variation of gas and water temperatures for thermocouples used in “boiler only” test configuration as a function of time, respectively. The duration of the test was 123 min. This value characterizes the time that the machine plates needed to reach their operational temperature (
T5 = 79 °C). The ambient temperature was almost stable during the experiment (
T11 = 11 °C). The gas temperature inside the exhaust pipe of boiler
T9 increased from 11 to 260 °C within 4 min, and then was almost 260–270 °C during the operation of the boiler.
T10 is not calculated in this test, because the boiler tank is not yet inserted. The temperature variation between the exhaust intake and output is insignificant. Nevertheless, the three thermocouples
T5,
T1 and
T6 (water inlet of the press machine, water outlet of the press machine and water inlet of the boiler, respectively) showed similar temperature values at the beginning of the test (16.8 °C), while all the temperatures increased (after 123 min) to reach 79.9, 72.3 and 70.5 °C, respectively. This data indicates a temperature difference of around 7.5 °C between the entrance and output water in the press machine. This value represents the loss of heat that is mostly gained by the machine plates. This loss of heat only occurs in the first time operation, where the machine plates stick to each other before reaching the operating temperature. However, during the day work, this heat loss may increase due to the functioning of the machine, which will increase the surface area exposed to the space, therefore increasing convection. Yet the loss in pipes between the outlet of the press machine and the inlet of the boiler is 1.8 °C, which may be reduced to negligible values by insulating the pipes.
In summary, this part discusses two tests on gas and water temperatures in a “boiler only” configuration, showing rapid temperature changes and thermocouple readings. It also discusses heat losses during initial operation and 1.8 °C heat losses in pipes between the press machine and boiler, suggesting insulation could reduce these losses. The analysis offers insights into thermal system dynamics and suggests strategies for improving efficiency.
Alternately,
Figure 15 and
Figure 16 show the variation of gas and water temperatures for thermocouples used in the “all-in” test configuration, respectively. Although the duration of the test was 90 min, 69 min were enough for the machine plates to reach their operational temperature (
T5 = 79.2 °C). The extra 21 min after reaching the operational temperature in the test were used to observe the behavior of the test after this temperature was reached. The ambient temperature increased from
T11-initial = 13 °C to reach 19 °C at the end of the test, an increase that was due to the usage of chimney in the factory in this test configuration. However, there was a temperature differential in the gas at the input and exit of the exhaust pipe of the boiler when the water tank was installed. The inlet of the exhaust pipe in the boiler
T9 increased from 13 to 240 °C within 4 min, and then was almost 240–250 °C during the operation of the boiler. Consequently, the gas temperature at the outlet of exhaust pipe in the boiler
T10 increased from 13 to 155 °C within 4 min, and then was almost 155–165 °C during the operation of the boiler. The difference in gas temperature between
T9 and
T10 is about 85–90 °C during the operation of the boiler, when heated water passed through the boiler water tank. Nevertheless, the six thermocouples (
T1,
T4,
T5,
T6,
T7 and
T8) showed similar temperature values at the beginning of the test (13.54 °C). The readings of these thermocouples at t = 69 min and t = 90 min are specified in
Table 8. At t = 69 min,
T5 showed a maximum temperature 79.2 °C. The difference in temperature between water entering and exiting the press machine is 8.5 °C. This value represents the loss of heat, which is mostly gained by the machine plates. It is noted that the difference between temperatures
T4 and
T7 is 0.5 °C, and between
T8 and
T6 is 0.4 °C. These values represent the loss of heat at that instant, in the pipes passing from one source of energy to another one.
This part described tests conducted under an “all-in” configuration, focusing on gas and water temperature variations. The machine plates reached operational temperature (79.2 °C) after 69 min, with ambient temperature rising from 13 °C to 19 °C due to chimney usage. Gas temperatures at the boiler exhaust inlet and outlet increased rapidly, stabilizing during boiler operation. Thermocouples initially recorded similar temperatures but later diverged.
After reaching the operational temperature, the temperature behavior of thermocouples
T9 and
T10 in
Figure 15 is analyzed, showing that the boiler worked once after a few minutes for about 2 min, and was then turned off. In the boiler working mode, it has a set temperature, and turns off automatically when it is reached, and turns on again when it decreases. This happens across the working day, whenever the operating temperature
T5 decreases below its operating value. However,
T9 and
T10 (gas temperatures in the boiler exhaust pipe), will immediately increase when the boiler turns on, and vice versa. Conversely, the chimney is operating during all of the test, even when the boiler is turned off (i.e., when it is at operational temperature). This is because the chimney is initially operating for heating, and will therefore stay operational all the time. At t = 90 min, the thermocouple with the highest temperature value is (
T4 = 87.9 °C), which is placed at the outlet the of chimney water tank (the only source of heat at this instance), and the temperature value at the inlet of the press machine is (
T5 = 83 °C). The temperature difference between the output of the chimney water tank and the entrance of the press machine is therefore 4.9 °C. This value represents the loss of heat in the pipes. It is noted that
T5 is higher (by 3.8 °C) than the operational temperature, which is caused by the heating of the chimney.
The analysis reveals a dynamic operation of the boiler and chimney system, with the boiler cycling intermittently based on temperature thresholds, causing heat losses in pipes and raising temperatures that are above operational levels, emphasizing the need for efficiency optimization and pipe insulation improvements.
3.2. Energy Analysis
In order to study and analyze the energy of all test configurations, it is necessary to clarify that when the system reaches the operational temperature, employees start using the machine. However, human work cannot be considered continuous on a systematic basis. If no test then reaches the steady state, the analysis should be done in transient mode. Furthermore, some variables, such as starting ambient air temperature
T11, starting water press inlet temperature
T5, and duration of the test, are not the same in all of the 22 tests. However, water flow rate inside the system is found to be constant. Consequently, a new parameter “Rate of Temperature Difference” is defined, to analyze the test configurations and their heating behavior with respect to the different variables. It mainly depends on the temperature difference of water press inlet temperature
T5 and the test duration.
Table 9 shows a comparison between two experiments applied on the “boiler only” test configuration to inspect the ambient temperature effect on the duration of the test, and, therefore, on the rate of temperature difference.
The two experiments had similar starting operating temperature T5-A = 19.92 °C, and T5-B = 19.33 °C. The starting ambient temperature was T11-A = 8.86 °C and T11-B = 15.7 °C. Test A, with lower ambient temperature, needed 117.67 min to reach the operational temperature, while Test B, with higher ambient temperature, and needed 103 min to reach the operational temperature. Therefore the rate of temperature difference in Test B (0.586) was higher than that of Test A (0.506) which means that the same test configuration with similar initial conditions will give better results, in terms of time and energy saving.
Figure 17 illustrates the correlation between the rate of temperature difference and the initial ambient temperature in the “boiler only” test setup, which included eight distinct tests. Ambient temperature directly influences the rate of heating over time. Rising ambient temperature reduces the temperature difference between the ambient air and the water pipes, leading to a reduction in energy loss because of convection between the pipes and the air.
After calculating the average starting ambient temperature and the rate of temperature difference for each test configuration, the variation of each parameter among all configurations is illustrated in a bar graph shown in
Figure 18. The experiment obtaining the highest rate of temperature difference shows best efficiency, because the heat rate is increased; energy and fuel savings also increase. Additionally, the initial ambient temperature impacts the system’s productivity. A lower ambient temperature results in increased heat loss to the surroundings, leading to a reduction in the heat rate and efficiency of the system. This graph demonstrates that, depending on the two parameters studied, the “chimney only” test configuration shows the lower efficiency, while the “chimney + boiler only” counterpart proved to be the most efficient configuration in terms of energy. Results show that placing the boiler tank on the exhaust pipe of the boiler is not efficient, as shown by the observation of (taking into account a tiny difference in the average starting ambient temperature) a lower rate of temperature difference, compared to the “boiler only” test.
3.3. Economic Analysis
The main challenges for any heat recovery technology are social considerations, sustainability and economic factors. Thus, paybacks of any recovery system revolve around economic savings [
21,
52,
61]. To perform the economic analysis of the current study, some parameters are specified. In addition, to investigate the alteration of fuel cost among test configurations, a new parameter is defined, namely “Fuel Cost Rate”. It depends on the fuel cost of the test and the temperature difference
, which characterizes the heating amount needed for operating.
On the other hand, a test to calculate the consumption of the boiler is executed. However, based on the average daily earnings of the industry, specified by the accounting office of the industry, which takes 10 working hours in a day as an average value, the industry earns (
$134) from the daily functioning of the thermal peeling press machine. The average earnings of one working hour is then obtained by dividing the average daily earning (
$134) by the number of working hours while the machine is operating (8 h), when there is no production during the first two hours of heating before it reaches the operational temperature. The average earnings obtained in one working hour is then obtained by dividing the average daily earnings (134/8), and are found to be equal to 16.75
$/h.
Table 10 shows the parameters used for energy analysis and the corresponding expected earnings in one hour of a normal working day in the factory. However, the total fuel cost per first operation (
$) is the boiler’s fuel consumption (L) during the first-time operation multiplied by the price of fuel (
$/L), which is then taken as an average for the experiments performed in each test configuration.
Table 11 shows the fuel cost rate of each configuration with the exception of “chimney only”, as the boiler is not applied in this configuration and is turned off in this experiment, meaning there is no fuel consumption during the test. “Chimney + Boiler Only” and “All-in” configurations show a lower rate of fuel cost (0.055
$/°C), which means that the cost of heating water to 1 °C is 0.055
$. These results are more promising than those of “Boiler Only” and “Boiler + Boiler Tank” configurations, which display a rate of fuel cost (0.093
$/°C). Therefore, applying two main sources of energy (“boiler and chimney”) at the same time yields reduced fuel cost and produces money saving.
In all of the 22 tests, the initial water flow rate in the applied system was fixed. Yet, water flow rate can be changed, which is something that must be studied. Hence, a manual valve and a water flowmeter are inserted after the circulating up. The initial flow rate was 35.8 L/min, and a “boiler only” experiment was confirmed. Nonetheless, after 2 days, the valve was partially closed to reach a water flow rate of 22.8 L/min before operating the system, and the same experiment was performed. Results in
Table 12 show that both experiments had a similar starting ambient temperature
T11 = 26 °C. Test 2, with a lower flow rate than that of Test 1, had a higher rate of temperature difference (0.63 > 0.59 °C/min) and a lower rate of cost (0.079 < 0.085
$/°C). In other words, the flow rate of Test 2 (22.8 L/min) is more competent in terms of energy and money.
The difference of starting T5 between test 1 and 2, is related to the self-cooling of the press machine plates during night (heat loss to the surrounding), which is mostly affected by the ambient temperature during this period of day.
For a better comparison of all test configurations, the average of results of each configuration is used in
Table 13 to calculate the cost of fuel for first operation at the beginning of the working day, which produces the best configuration, in economic terms. However, the “chimney only” test does not have any fuel consumption, as the boiler is turned off during the experiment, which produces fuel, and therefore, money saving. However, fuel consumption is not the only factor in economic analysis, as time is likewise a very effective factor. Consequently, the duration of a test must be analyzed to estimate the time lost during the excess operation duration, thus making it possible to calculate the missing expected earnings at this excess time and the excess fuel consumption. On the contrary, if the test’s operation duration is less than the usual duration, the saved hours yield more productive working hours, and therefore, economic profit. In this study, therefore to be 150 working days (across the winter and fall seasons) when the chimney operation is needed. Nevertheless, the “boiler only” test configuration is the system initially applied on the press machine in the factory. Therefore, this configuration is considered to be a “control test” for comparing fuel consumption, fuel cost and money savings. The average starting
T11 is between 9.36 and 11.47 °C, which is an acceptable range to compare tests with each other.
In order to calculate overall money savings or losses, some terms must be clarified:
Duration of a test represents the time needed for the system to reach the operational temperature T5. Therefore, all calculations of fuel and money savings are meant to only apply to this duration, and do not include all the working hours of a day;
Heating time of a test is stated with an excess/less time, when compared to the average duration of “boiler only” tests;
An excess of heating time in a test means that there is less production due to waste of time in heating; thus, the productive functioning hours of the machine are decreased. Therefore, the expected earnings of the day are decreased, where the average of earnings is 16.75
$ for one working hour of a day (
Table 13);
A decrease of heating time in a test means that there is more production due to saving time in heating; thus, the productive functioning hours of the machine are increased. Therefore, the expected earnings of the day are increased, where the average of earnings is 16.75
$ for one working hour of a day (
Table 13);
The terminology used is illustrated in
Table 14;
However, some equations are illuminated:
Time lost or gained in Heating (h):
Expected Earnings from heating time (
$):
Results of test configurations are each demonstrated in a definite table.
For the “boiler only” test, the control test shown in
Table 15, the total fuel cost for 150 working days was
$865.01.
For the “boiler + boiler tank” test, shown in
Table 16, there was a
$129.72 loss in 150 days, compared to when the “boiler only” configuration was applied.
Where total savings (
TS) for 150 days are calculated:
- 3.
For “chimney only”, as shown in
Table 17, this test had a
$346.85 loss during 150 days, compared to when the “boiler only” configuration was applied.
Where total savings (
TS) for 150 days are calculated:
- 4.
For “chimney + boiler”, as shown in
Table 18, this test produced
$699.27 for 150 days, compared to when applying the “boiler only” configuration was applied.
Where total savings (
TS) for 150 days are calculated:
- 5.
For “all-in”, as shown in
Table 19, this test produced
$700.47 earnings during 150 days, compared to when applying the “boiler only” configuration was applied.
Where total savings (
TS) for 150 days are calculated:
After energy analysis and economic study, an overall assessment should be made of the test configurations used. Comparing “boiler only” with “boiler + boiler tank”, results showed that, under similar conditions, both configurations produced similar results for rate of temperature difference and rate of fuel cost. The money loss in 150 days was $129.72 for the “boiler + boiler tank” test, which therefore proved that this heat exchanger is not efficient in this system. Comparing “boiler only” with “chimney only”, results showed that, under similar conditions, “chimney only” had a lower rate of temperature difference. In other words, it needs more time to heat the system. Alternatively, this configuration does not consume fuel. However, it had a $346.85 loss for 150 days compared to when the “boiler only” configuration was applied, which was due to the long time needed for heating. As a result, “boiler only” is found to be better economically. Finally, when “boiler only” was compared to “chimney + boiler only” in similar conditions, “chimney + boiler only” showed a higher rate of temperature difference and lower rate of fuel cost. In addition, it verified a $2307.39 savings in 150 days. Therefore, “chimney + boiler only” is more economically efficient.