Next Article in Journal
Review of Concepts and Determinants of Grid Electricity Reliability
Previous Article in Journal
Investigation of the Water-Invasion Gas Efficiency in the Kela-2 Gas Field Using Multiple Experiments
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Review

Conventional Dissolved Gases Analysis in Power Transformers: Review

by
Alcebíades Rangel Bessa
,
Jussara Farias Fardin
,
Patrick Marques Ciarelli
and
Lucas Frizera Encarnação
*
Department of Electrical Engineering, Federal University of Espírito Santo, Vitoria 29075-910, Brazil
*
Author to whom correspondence should be addressed.
Energies 2023, 16(21), 7219; https://doi.org/10.3390/en16217219
Submission received: 30 August 2023 / Revised: 9 October 2023 / Accepted: 10 October 2023 / Published: 24 October 2023
(This article belongs to the Section F1: Electrical Power System)

Abstract

:
Transformers insulated with mineral oil tend to form gases, which might be caused by system faults or extended use. Based on an evaluation of the main failure analysis techniques using combustible gases, this study reviewed the conventional techniques for Dissolved Gas Analysis (DGA), present in the norms IEC 60599 and IEEE Std C57.104, and their failure analysis tendency. Furthermore, to illustrate distinct technique performances and failures, the performance of the following techniques was analyzed based on the IEC TC10 database: Dornenburg, Duval Triangle, Duval Pentagon, IEC ratio method, Key Gas, and Rogers. The objective of this work was to present relevant information to support students and professionals who work in failure analysis and/or assist in the development of new tools in the DGA field.

1. Introduction

The insulation of power transformers usually consists of solid and liquid insulation. The solid insulation is made of Kraft paper, manila, and pressboard [1,2]. Ester liquids are used in some types of power transformers, such as wind turbines or solar; however, mineral oil is still by far the liquid most widely used, and their liquid insulation is achieved using mineral oil.
The mineral oil insulation used in electrical equipment is extracted from petroleum, which is a hydrocarbon compound. Their composition and characteristics depend on the environment where the petroleum was extracted, which might be paraffinic or naphthenic [3].
Laboratory studies have shown that these elements, under normal operating conditions, present the formation of gaseous compounds of low molecular weight hydrocarbons, as well as CO and CO2. This formation is continuous in low volume during the equipment lifetime; however, in failures or other abnormal conditions, an imbalance in the chemical formation and an increase in the amount of these gases can be observed. Hotspots with temperatures above 300 °C predominantly result in the formation of unsaturated hydrocarbons. Furthermore, if the cellulosic system is reached, there is also the formation of abnormal concentrations of CO and CO2.
The analysis of dissolved gases (DGA) in power transformers is registered as the analysis of the formation of hydrocarbon gases, and the first study regarding this topic was published in February 1919 in “The Electric Journal” [4]. In this study, the first observations regarding the pattern of gas formation were reported, and the gases formed were composed of CO2 (1.17%), Heavy Hydrocarbons (4.86%), O2 (1.36%), CO (19.21%), H2 (59.10%), N2 (10.10%), and CH4 (4.2%). The author highlighted the high proportion of H2 and the influence of temperature on the growth and amount of dissolved gases.
In 1928, based on knowledge of the problem, the gas formation in equipment failure, the Buchholz relay, was developed. Figure 1 illustrates the functions and actuation mechanism of the relay, the purpose of which was to protect the equipment through its action with the passage of gases through the pipeline interconnected to the equipment with an expansion tank [4].
Analyses at that time were already possible in samples of gases and liquids, and in 1959, a field chromatography analyzer was developed by H.H. Wagner [4]; Figure 2 shows a piece of equipment in the field of chromatography.
From the 1960s onwards, gas chromatography (GC) saw its first applications in identifying dissolved gases in transformers from electrical faults.
Chromatographic analysis of gases dissolved in oil is carried out in three steps. First, the oil sample is collected, which can be collected with flexible aluminum bottles or using a syringe (Figure 3), and the collected gases can be stored in the Buchholz relay. Second, the gases are extracted from the oil sample [8,9]. Third, the gases extracted from the sample are analyzed using the gas chromatograph [10], which consists of separating the different gases from the mixture, and then identifying and quantifying them.
The advances in dissolved gas analysis equipment in regard to transformers make it possible to know the origin of the gases and understand the type of faults from the different types and levels of gases formed in each fault.
In 1978, Rogers [11] published a graph (Figure 4) showing the formation of dissolved combustible gases as the temperature increased. Figure 4 demonstrates the relationship between gas formation and temperature.
According to [13], the following individual gas components can be identified and determined: hydrogen (H2), nitrogen (N2), carbon monoxide (CO), carbon dioxide (CO2), methane (CH4), ethane (C2H6), ethylene (C2H4), acetylene (C2H2), propane (C3H8), and propylene (C3H6). With the exception of oxygen (O2) and nitrogen (N2), the other gases are formed from secondary chemical reactions, as a result of the breakdown of hydrocarbon molecules due to electrical or thermal stresses.
From the observation of this behavior, several studies have been developed with the objective of defining the type of failure in the equipment from the analysis of the composition of the gases formed.
These techniques make it possible to predict failures before the need to shut down the equipment, the oil draining process, and access for inspection, which can require days of work. Figure 5 illustrates two practical uses of DGA analysis in failures.
In Figure 5a, the monitoring of the equipment power transformer 315MVA 15.75/400 kV identified a large formation of C2H4 gas through analysis, showing a possible high-intensity thermal failure. During the inspection, two flexible windings from the bushing were found heated. Figure 5b presents another example of monitoring the equipment power transformer 55 MVA 110/11 kV, which showed a large formation of C2H2. DGA analysis indicated thermal failure coupled with the arc flash. The inspection revealed that the winding coil of a phase was burnt out.
In this article, we present the most popular DGA analysis techniques adopted among international standards and analyzed their performance in more detail. These analyses were made with a modified confusion matrix, with the data and types of failures presented in [15]. In addition to using an accessible failure database [15,16], the current study shows whether the techniques are determining the right hypothesis or not. This gives readers a clear and easy-to-interpret direction when using the analysis or developing new techniques.
Therefore, the combination of the interpretations of these techniques and the performance detailing different types of failure, with more than just a generic indicator of accuracy, makes this study an unprecedented review [17,18,19,20,21,22,23,24]. In addition, a table is provided with a combination of all of the responses to the pattern failure of the techniques adopted in [15], allowing the comparison to be more organized and more specific. Other studies have made unclear comparisons of the results of the adopted techniques that often did not have the same pattern of failures defined in [15].
The detailed analysis of the performance techniques from Rogers [11] and the IEC method [11], with the confusion matrix for standardized failures in [15], resulted in a table that grouping the incipient fault types codes for conventional DGA techniques showed in Section 3. These techniques, as presented in the results of this article, presented an overall performance superior to those seen in Rogers’ IEEE method [12] and the IEC 60599 method [25]. Therefore, this study presents a new approach to the use of these techniques that can contribute to better failure analysis performance.
It should be noted that, in this article, the techniques will not address mineral oil-insulated switching equipment; for example, load tap changers, circuit breakers, reclosers, or others. The analysis of dissolved gases in switches is not easy to interpret, as the formation of gases is very high in this equipment, normally associated with electrical arcs. Despite this, in the specific case of load tap changers, there are scientific documents such as [26] and standards such as [27], which serve as guidelines for interpreting failures.

2. International Standard Developed Techniques

Since the first observations of the formation of dissolved gases in transformers, some techniques have been developed and disseminated both in the academic environment, by equipment manufacturers, and by companies in the electrical sector responsible for the maintenance and operation of this equipment.
Conventional techniques can be defined by analysis of the concentration of gases, by the relationship between the proportions of gases, or by the graphical method of classifying the faults, among which we highlighted [17]:
  • Incipient Fault Types, Frank M. Clark, 1933–1962;
  • Dörnenburg Ratios, E. Dörnenburg, 1967, 1970;
  • Potthoff’s Scheme, K. Potthoff, 1969;
  • Absolute limits, various sources, early 1970;
  • Shank’s Visual Curve method, 1970s;
  • Trilinear Plot Method, 1970;
  • Key Gas Method, David Pugh, 1974;
  • Duval’s Triangle, Michel Duval, 1974;
  • Rogers Ratios, R.R. Rogers, 1975;
  • Method MSS, 1975;
  • Glass Criterion, R.M Glass, 1977;
  • Trend Analysis, various sources, early 1980s;
  • Church Logarithmic Nomograph, J.O. Church, 1980;
  • IEEE C57.104, Limits, rates and total dissolved combustible gas (TDCG), 1978–1991;
  • IEC 60599 Ratios, Limits and gassing rates, 1999;
  • CIGRE TF 15.01.01, 1999;
  • Duval’s Pentagon, Michel Duval, 2014;
  • CIGRE TB 771-Advances in DGA interpretation, 2019;
  • IEEE EI Mag-New sub-zones for arcing in paper and in oil in Pentagons and Triangle 1, 2022;
  • IEEE EI Mag-New sub-zones for carbonization of paper C in Pentagon 2 and Triangle 5, 2023.
In addition to the techniques previously mentioned, other methodologies have been developed over time to meet regional definitions, specific demands, or due to the evolutionary process of product companies or electric energy concessionaires, among them:
  • Amount of Key Gases, California State University (CSUS);
  • RD 153-34.0-46.302-00 procedural guidelines Russian;
  • GATRON method Germany;
  • ETRA square Japan;
  • Total Combustible Gases, Doble Engineering.
The following subsections present the concepts developed by the main analysis techniques [5,12,18,19,20,21,22,23,24,25,26,28,29,30] agreed on by the IEEE [12] and IEC [25] standards.

2.1. Key Gas

The key gas method, developed by Doble Engineering [4], is based on the fact that when a fault occurs, there is the formation of gases that exceed the normal values of insulation degradation. When the gas that characterizes the incipient failure type, called the key gas, is predominant among other gases from typical formations in failure, the condition is considered abnormal. In the following subsections, failures with key gas are shown.
Failure type: Arcing. The formation of faults with arcing can reach temperatures between 2000 and 3000 °C [20], and large amounts of H2 and C2H2 and small amounts of CH4 and C2H4 are produced, as shown in Figure 6. CO and CO2 can be produced if the failure involves cellulose. Key gas: C2H2.
Failure type: Partial discharges—Low-energy electrical discharges produce H2 and CH4, with a small amount of C2H6 and C2H4, as shown in Figure 7. Comparable amounts of CO and CO2 can result from discharges into the pulp. Key gas: H2.
Failure type: Overtemperature in oil—Overtemperatures in oil with values of at least 300 °C have the characteristic formation of C2H6 and CH4. Decomposition products also include CH4. Traces of C2H2 can also form if the fault is severe or if there are electrical contacts, as shown in Figure 8. Key gas: C2H4.
Failure type: Overheated Cellulose—Overheating insulation paper produces a large amount of CO and CO2, but the latter is not a combustible gas, emphasizing that the analyses pertain to combustible gases. Gaseous hydrocarbons, such as CH4 and C2H4, are also present if the fault consists of an oil-impregnated structure, as shown in Figure 9. Key gases: CO and CO2.

2.2. Dornenburg

A report published as part of the CIGRE International Conference on Large High Tension Electric Systems in 1970 [31] was one of the first failure analysis methods based on the ratio of CH4, C2H2, C2H4, and H2 gases. Figure 10 presents an image of the early publication of the relationship between gases by Dornenburg [4].
In this methodology, if any of the gases exceed twice the value of the reference in Table 1 or if one of the CO or C2H6 gases is greater than this, it will be considered a failure and then this type of failure will be analyzed.
The types of failure are evaluated in a generic diagnosis based on the proportion between the gases, according to Table 2, which allows the identification of three types of failure: hot spot, electrical discharge (arc), and partial discharges.

2.3. Rogers

Based on the Dornenburg method, the Rogers method proposed the evaluation of failures by the relationship between the gases C2H2, C2H4, C2H6, CH4, and H2, originally published according to Table 3.
The publication of the Rogers method through the IEEE Std C57.104 standard [12] did not consider the relationship between C2H6 and CH4, reducing the amount of failure types, as shown in Table 4.

2.4. IEC

This method was published in the IEEE article in 1978 [11], differentiating from the Rogers method by removing the ratio analysis between the C2H6/CH4 gases. The purpose of removing this ratio was to simplify the analysis of failures, since the contribution of this relationship was limited to a small range in terms of the decomposition temperature and was not useful in identifying the failure.
Table 5 presents the first version of the IEC ratio method published in the article “IEE and IEC Codes to Interpret Incipient Faults in Transformers, using Gas in Oil Analysis” [11] and Table 6 shows the recent codification through the IEC 60599 standard [25].
In order to use the IEC 60599 ratio method, at least one of the gases shown in Table 1 must be above its limit, if these limits are not exceeded, the conditions of the equipment will be considered normal.
The use of the IEC 60599 ratios method on the Cartesian axis, as shown in Figure 11, allows for the visualization of fault types D1 and D2 overlapping (both related to the discharge of energy). Despite illustrating cases of lightning strikes, this intersection area can lead to the wrong interpretation of their intensity.

2.5. Duval Triangle

The Duval Triangle is currently one of the most widely used methods for interpreting the types of failures in electrical equipment. Its first publication was in 1974 [26].
In the same way as the Dornenburg criteria, the Duval criteria present generic diagnoses for identifying four types of faults: hot spots, a high-energy arc, a low-energy arc, and internal discharges.
The Duval method can indicate defects in equipment that present normal operating conditions. For this type of error to not occur, using Duval’s method, it is necessary that some of the gases exceed the limits established in Table 1, if these limits are not exceeded, the conditions of the equipment will be considered normal.
The Duval triangles are presented in seven different types, T1 to T7, with the T1 method being the classic Duval method applied to insulated transformers with insulating mineral oil, and the T4 and T5 methods being a refinement of this to deepen the interpretation of the type of failure.
The other methods are applied as follows: T2 for on-load tap changer compartments insulated with mineral oil; T3 equipment insulated with non-mineral oil, such as Bio Temp, Silicone, Midel, and FR3; T6 is used to gain further information regarding faults identified as low-temperature faults (PD, T1, or T2) by T3 for FR3 oils and T7 to gain further information regarding faults identified as thermal faults (T1, T2, or T3) and by T3 for FR3 oils [28,31].
In the initial failure analysis of equipment insulated with mineral-insulating oil, T1 is used, as shown in Figure 12, to evaluate the CH4, C2H4, and C2H2 gases [29] from Equations (1), (2), and (3).
% C H 4 = C H 4 C H 4 + C 2 H 4 + C 2 H 2
% C 2 H 4 = C 2 H 4 C H 4 + C 2 H 4 + C 2 H 2
% C 2 H 2 = C 2 H 2 C H 4 + C 2 H 4 + C 2 H 2
When low energy or temperature faults are identified from Triangle T1 (PD, T1, and T2), more information can be obtained with Triangle T4, as shown in Figure 13, and gases H2, C2H4, and C2H6 from Equations (4)–(6).
% C H 4 = C H 4 C H 4 + C 2 H 6 + H 2
% C 2 H 6 = C 2 H 6 C H 4 + C 2 H 6 + H 2
% H 2 = H 2 C H 4 + C 2 H 6 + H 2
If the analysis from Triangle T1 includes high or extremely high temperatures (T2 and T3), a more detailed analysis can be obtained with Triangle T5, as shown in Figure 14, with the analysis of CH4, C2H4, and C2H6 gases from Equations (7)–(9).
% C H 4 = C H 4 C H 4 + C 2 H 4 + C 2 H 6
% C 2 H 4 = C 2 H 4 C H 4 + C 2 H 4 + C 2 H 6
% C 2 H 6 = C 2 H 6 C H 4 + C 2 H 4 + C 2 H 6

2.6. Duval Pentagon

Graphical analysis using a pentagon shape was presented in 2012 using the Mansour Pentagon method [30], to simultaneously analyze the gases CH4, C2H6, C2H4, C2H2, and H2 (see Figure 15).
This analysis proposal aimed to overcome a failure of the Duval Triangle method in that it does not have the gases C2H6 and H2 in its analysis, which are relevant in the analysis of failure due to low overtemperature and discharge.
The Duval Pentagon method was published in 2014 [33], presenting fault boundary regions different from the proposal in [30] and divided into Duval Pentagons 1 and 2.
Figure 16 shows the Pentagon Duval 1, which is for the general analysis of fault types.
Duval Pentagon 2, as shown in Figure 17, is equivalent to the refinement presented by Duval Triangles 4 and 5 [33,34].
The Pentagon 2 method is complementary to the Pentagon 1 analysis, suggested for the refinement of the analysis if failures of type T1, T2, or T3 are identified [12].
In both methods, the calculations to map the type of failure with the collected gas data [32,33] start with one of the gases with values above the limits shown in Table 1; if these limits are not exceeded, the conditions of the equipment will be considered normal.
From the analysis that the equipment is faulty, the type of fault is evaluated with the calculation of the proportion between the gases (Equations (10) to (14)), being:
% C H 4 = C H 4 C H 4 + C 2 H 4 + C 2 H 6 + C 2 H 2 + H 2
% C 2 H 4 = C 2 H 4 C H 4 + C 2 H 4 + C 2 H 6 + C 2 H 2 + H 2
% C 2 H 6 = C 2 H 6 C H 4 + C 2 H 4 + C 2 H 6 + C 2 H 2 + H 2
% C 2 H 2 = C 2 H 2 C H 4 + C 2 H 4 + C 2 H 6 + C 2 H 2 + H 2
% H 2 = H 2 C H 4 + C 2 H 4 + C 2 H 6 + C 2 H 2 + H 2
With the percentages of gas concentration, the coordinates of each of these on the Cartesian axis are calculated [33] with Equations (15) to (19).
C o r d _ % C H 4 = ( ( % C H 4 × cos 254 ° ) ; ( % C H 4 × cos 164 ° ) )
C o r d _ % C 2 H 6 = ( % C 2 H 6 × cos 162 ° ; ( % C 2 H 6 × cos 72 ° ) )
C o r d _ % C 2 H 4 = ( ( % C 2 H 4 × cos 326 ° ) ; ( % C 2 H 4 × cos 236 ° ) )
C o r d _ % C 2 H 2 = ( ( % C 2 H 2 × cos 18 ° ) ; % C 2 H 2 × cos 72 ° )
C o r d _ % H 2 = ( ( % H 2 × cos 90 ° ) ; % H 2 × cos 0 ° )
From the coordinates of the gas concentrations, the centroid of these points is calculated with Equations (20)–(22), the location of which will indicate the type of fault.
C x = 1 6 A i = 0 n 1 ( x i + x i + 1 ) ( x i y i + 1 x i + 1 y i )
C y = 1 6 A i = 0 n 1 ( y i + y i + 1 ) ( x i y i + 1 x i + 1 y i )
A = 1 2 i = 0 n 1 ( x i y i + 1 x i + 1 y i )
In Equations (20)–(22), n is the number of coordinates of the gases under analysis.

2.7. Others Methods

The analysis of dissolved gases in electrical equipment, as it is not an exact science, is undergoing constant evolution.
Ratio analysis methods, such as IEC, Dornenburg, and Rogers, fail to identify failures in about 15 to 20% of cases, as the cases are outside the failure assessment zones. The key gas method, when applied with the aid of computational tools, presents an error in around 50% of the analyzed cases [35].
Duval Triangle and Pentagon graphic methods do not have the limitations of not identifying failures, since, as they are closed methods, they always present an answer for the type of failure. Furthermore, due to the large number of failure cases on which these methods were based, the assertiveness of these methods is very high.
The IEC method allows for the evaluation of the six basic types of faults, T1, T2, T3, PD, D1, and D2, the Duval Triangle, and Pentagon methods. Furthermore, it permits the identification of the types S, O, C, and T3-H, making the information more useful for actions regarding equipment.
Currently, several ways to improve the accuracy of the analysis have been developed using computational methods of artificial intelligence [36,37,38]. However, in addition to the search for this computational improvement, conventional methods are still debated with each new evaluation proposal.
Although the focus of this review is based on conventional methods standardized through the standards [12,25], the following subsections will briefly present some of the recently developed techniques for the conventional analysis of dissolved gases.

2.7.1. Three Rates Technique TRT

The TRT technique, published in 2018 [39], is a proposal that does not graphically operate and presents a new proposal for ratios between the gases CH4, C2H6, C2H4, C2H2, and H2. Its goal is to correct the distortions presented through other conventional analyses. The new ratios are shown in Equations (23)–(25):
R 1 = C 2 H 6 + C 2 H 4 H 2 + C 2 H 2
R 2 = C 2 H 2 + C H 4 C 2 H 4
R 3 = C 2 H 2 C 2 H 4
Based on these ratios, a new fault coding is proposed, as shown in Table 7.

2.7.2. Heptagon Graph

For a more detailed proposal of the analysis of the failure, the effects on the cellulosic insulation by the formation of CO and CO2, together with the analysis of the gases C2H6 and H2, the method Heptagon Graph (Figure 18) graphically assesses failures in equipment insulated with mineral oil from CH4, C2H6, C2H4, C2H2, H2, CO, and CO2 gases. This technique was published in 2018 [40] and included the analysis of C2H6 and H2 due to their crucial characteristics in certain types of failures.
For analysis using this method, from the collection and analysis of gas concentrations, it is evaluated if at least one of them exceeds the limits of Table 1.
If any of the gases present values above the limits in Table 1, the evaluation of the type of failure will begin with the conversion of values into proportions, using Equations (26) to (32).
% C H 4 = 2.9167 × C H 4 × 100 ( 2.9167 × C H 4 + 5.3846 × C 2 H 6 + 7 × C 2 H 4 + 116.6667 × C 2 H 2 + 3.5 × H 2 + C O + 0.14 × C O 2 )
% C 2 H 6 = 5.3846 × C 2 H 6 × 100 ( 2.9167 × C H 4 + 5.3846 × C 2 H 6 + 7 × C 2 H 4 + 116.6667 × C 2 H 2 + 3.5 × H 2 + C O + 0.14 × C O 2 )
% C 2 H 4 = 7 × C 2 H 4 × 100 ( 2.9167 × C H 4 + 5.3846 × C 2 H 6 + 7 × C 2 H 4 + 116.6667 × C 2 H 2 + 3.5 × H 2 + C O + 0.14 × C O 2 )
% C 2 H 2 = 116.6667 × C 2 H 2 × 100 ( 2.9167 × C H 4 + 5.3846 × C 2 H 6 + 7 × C 2 H 4 + 116.6667 × C 2 H 2 + 3.5 × H 2 + C O + 0.14 × C O 2 )
% H 2 = 3.5 × H 2 × 100 ( 2.9167 × C H 4 + 5.3846 × C 2 H 6 + 7 × C 2 H 4 + 116.6667 × C 2 H 2 + 3.5 × H 2 + C O + 0.14 × C O 2 )
% C O = C O × 100 ( 2.9167 × C H 4 + 5.3846 × C 2 H 6 + 7 × C 2 H 4 + 116.6667 × C 2 H 2 + 3.5 × H 2 + C O + 0.14 × C O 2 )
% C O 2 = 0.14 × C O 2 × 100 ( 2.9167 × C H 4 + 5.3846 × C 2 H 6 + 7 × C 2 H 4 + 116.6667 × C 2 H 2 + 3.5 × H 2 + C O + 0.14 × C O 2 )
With the relative percentages of gas concentrations, the point of failure in the heptagon is calculated through the center of mass of the concentrations.

3. Results

To analyze the performance of the main techniques presented in this study, the failure database, with real cases, available in Appendix A, was used.
We adapted the type of failure of some techniques to the classification pattern of failures presented in [15], enabling the analysis of technique performances. Table 8, based on [41] and adapted according to the observations of this work, presents the summary of the adaptations developed.
One way to evaluate the results was by using confusion matrices. The confusion matrix is a very popular way to evaluate classification tasks, representing counts of predicted and actual values. For this reason, this form of analysis was selected to detail the response of the techniques to the expected result.
The actual classes (types of failures) are vertically distributed, while the predicted classes by the technique are horizontally distributed. The number in the intersection of classes with the same name (actual and predicted classes) means the number of correct identifications for that class. The numbers in the intersection of classes with different names are misclassified failures.
Due to the adaptation of the predicted or expected results presented in Table 8, it was necessary to modify the confusion matrix, since there will not always be predicted or known values in all method scenarios. For example, for the key gas method, the actual failures T1, T2, and T3 are included in the failures TD and OC. Therefore, different from the common confusion matrix, in our analysis, the confusion matrix can be not square.
In addition to using the confusion matrix to analyze the techniques within each type of failure, some performance measures were used and are detailed below:
  • Precision: This metric measures how much we can trust a model when it predicts that an example belongs to a certain class:
  P r e c i s o n = T P T P + F P
  • Recall: This metric measures the ratio of failures that were correctly identified for a specific class:
  R e c a l l = T P T P + F N
  • F1-Score: This metric is the harmonic mean between accuracy and recall:
  F 1 S c o r e = 2 × P r e c i s o n × R e c a l l P r e c i s o n + R e c a l l
  • Accuracy: This metric is the fraction of predictions that the model got right:
  A c c u r a c y = T P + T N T P + T N + F P + F N
  • Support: This will give the information of the number of cases in analysis.
To solve Equations (33) and (34), the definitions used are:
  • True Positive (TP): model correctly predicts the positive class (prediction and actual, both are positive);
  • True Negative (TN): model correctly predicts the negative class (prediction and actual, both are negative);
  • False Positive (FP): model gives the wrong prediction of the negative class (predicted-positive, actual-negative);
  • False Negative (FN): model wrongly predicts the positive class (predicted-negative, actual-positive).

3.1. Key Gas

From the analysis of the confusion matrix, as shown in Figure 19, evaluated without combining the response of the types of failures of this technique, a significant assertiveness of the failures of the T3 type is observed. It is also noteworthy that around 21%, 19 cases, were not identified (Not-F). Furthermore, PD-type failures were not identified by this technique.
To visualize the efficiency of this technique, the types of standard faults [15] were adapted according to the proposed grouping in Table 8, transforming the TD and OC faults into T, with the result of the performance analysis of this technique shown in Table 9.
The analysis of the Precision, Recall, and F1-score performances shows that the technique presents a good performance for the failures that it identifies.
It is observed that despite a high overall accuracy of 66%, the ability to discriminate the types of faults between thermal and electrical types is lost.

3.2. Dornenburg

The analysis of the Dornenburg method by the confusion matrix, as shown in Figure 20, illustrates a high assertiveness of the types of failure; however, a large number of incorrect results appear in terms of not identifying the type of failure. That is, the incorrect analysis accounts for 17% and, according to Table 10, 12.5% of the errors were due to not being able to classify the type of failure (Not-F).
However, it is important to point out that, in the same way as the Key Gas method, the combination of the type of failure to analyze the performance of this method favors the increase in this accuracy.
Despite the good performance of this technique’s accuracy, there is evidence of difficulty in the failure analysis of the PD type, with low Precision and Recall metrics, confirming, respectively, the misclassification of two PD cases and the classification of one T1_T2 case as PD.

3.3. Rogers

The analysis of the Rogers method was divided in two ways. The first one was based on the original methodology published in [11], as shown Figure 21, and adapted considering Table 8. The second stage used the new boundaries defined in [12], as shown in Figure 22, with the default failures of [15] adjusted to this model.
The general analysis between the two versions of the Rogers method highlights the increase in the number of unidentified cases from 13 to 33 cases. Most of these cases were D1 and D2 faults that were not identified by the Rogers IEEE version.
Through Table 11 and Table 12, it is possible to see the performance of the Rogers method. They show a decrease in the accuracy in relation to the original method, adapted in this article, for the grouped form in the IEEE standard.
In addition, even though the failure database was adapted to the Rogers IEEE response type, which would tend to increase accuracy, the opposite result is observed, ranging from 65% to 56%. The main reason for that is the increase in cases not classified (Not-F) and the recall index reduction.

3.4. IEC

The IEC methods were based on the methodologies published in [11,25]. The first [11] did not show the formatting of the types of failures proposed in [15], therefore, the proposed grouping in Table 8 was necessary.
The analysis of the confusion matrix for the IEC method, as shown in Figure 23, and IEC 60599 method, as shown in Figure 24, presents a balance in not identifying the type of failures from 9 to 10.
None of the faults were classified as a thermal fault of temperature < 150 °C (T0) by the IEC method.
For a comparative analysis of the performance of both methodologies, it was necessary to group the IEC methods according to Table 8, observing that both methodologies present similar accuracy, ranging from 74% to 66%.
Despite the increase in Precision in identifying D1, T1_T2, and T3 failures in IEC 60599 compared to the IEC method, a general reduction in the Recall index is also observed, which may explain the difference between the accuracies, see Table 13 and Table 14.

3.5. Duval Triangle

The Duval Triangle method adopted in the analysis was T1, as it is the base analysis of failures and refinement, as explained in Section 2.
The Duval T1 method presented the best performance with an accuracy of 83%, see Table 15, and still preserved the characteristics of the type of failure.
Through the confusion matrix, as shown in Figure 25, it is possible to identify that among the observed failures, there was an error in the classification of two failures: T1_T2 as N, three T3 as N, two T1_T2 as PD, two T3 as T2, and three T1_T2 as T3.
With the exception of the PD and T1_T2 failures, there is a balance between the values of the F1-score metric, reflecting the high precision and recall of these indicators.

3.6. Duval Pentagon

As shown in the confusion matrix, seen in Figure 26, the Duval Pentagon method 1 performed similarly to the Duval Triangle T1. The general accuracy of this method, shown in Table 16, was 82%, which is considered adequate since it still preserves the description between the failure types.

4. Discussion

The performance analysis between techniques was plotted for each kind of failure accuracy and for each technique, presented in the star graph below. Figure 27 shows the result of this comparison, based on the analysis of the response of each technique for the type of failure standardized in [15].
A comparative performance analysis of the techniques makes it clear that the Duval triangle T1 with Duval Pentagon 1 presents the best performance, and that all techniques present difficulties in identifying T1_T2 and PD failures.
Regarding T1_T2 failures, the technique that presents the best performance is the Dornenburg technique.
With regard to type D2 failures, except for the Duval Triangle T1 method, which presented excellent performance, and Rogers and Rogers IEEE, which had the worst performance, the others presented very similar performances.
The failures of types D1 and T3, in addition to the Duval Triangle and Pentagon methods, highlight the good performance of the Dornenburg and Key Gas methods.
Finally, analysis of the performance of the techniques in the PD type failure highlights the performance of the key gas method.
This kind of analysis, despite the high performance of the Duval Triangle T1 and Duval Pentagon 1 method, emphasizes the importance of analyzing the failure by combining more than one technique to increase the performance in correctly identifying the type of failure. In addition, the visualization of the techniques through a star graph may be a good tool to aid in the selection of which techniques to combine depending on the possible failures in the analysis.

5. Conclusions

Through this article, it was possible to recognize the main steps of the process that involves the science of gas analysis in power transformers insulated with mineral oil, from the knowledge of sampling to the analysis of the results found.
Emphasis was placed on the evolution of the main methods adopted in international standards with general knowledge of the evolution of research in this area. In addition, two recently published techniques, TRT and Pentagon, were presented in an illustrative way, presenting alternative forms of analysis and, in the case of TRT, with great performances.
The way of presenting the results of conventional techniques with confusion and performance matrices allows for a clearer visualization of the strengths and weaknesses of each technique depending on the type of failure.
In addition, a comparative analysis between the star graph techniques brought a form of comparative visualization to the performance of the techniques, helping to choose to combine more than one technique depending on the type of failure under analysis
From the analysis of the results of conventional techniques, it is reaffirmed that the T1 Duval Triangle technique, currently the most popular one, presents the best answers in terms of accuracy associated with discriminating the types of failure. This is crucial when professionals are trying to decide whether to stop the equipment in operation or not.
Finally, in order to support other researchers and other professionals in the field of conventional gas analysis development or even artificial intelligence tools, it is expected that this study will be a supporting document and support the comparison in the analysis of improvements or results found by such methods.

Author Contributions

Conceptualization, A.R.B. and P.M.C.; methodology, A.R.B.; software, A.R.B.; validation, A.R.B., P.M.C., J.F.F. and L.F.E.; formal analysis, A.R.B.; investigation, A.R.B.; resources, L.F.E.; data curation, A.R.B.; writing—original draft preparation, A.R.B.; writing—review and editing, A.R.B., P.M.C., J.F.F. and L.F.E.; visualization, P.M.C.; supervision, P.M.C., J.F.F. and L.F.E.; project administration, L.F.E.; funding acquisition, L.F.E. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported by the National Council for Scientific and Technological Development—CNPq (grant number 311848/2021-4) and Espírito Santo Research and Innovation Support Foundation—FAPES (grant number 1024/2022).

Data Availability Statement

The data presented in this study are openly available in A transformer Fault Diagnosis Model Based on Hybrid Grey Wolf Optimizer and LS-SVM at https://doi.org/10.3390/en12214170, reference number [12], and Interpretation of Gas-In-Oil Analysis Using New IEC Publication 60599 And IEC TC 10 Databases at https://doi.org/10.1109/57.917529, reference number [15]. The data used in the analysis are available in Appendix A.

Conflicts of Interest

The authors declare no conflict of interest.

Appendix A

Table A1. Partial Discharge fault—PD.
Table A1. Partial Discharge fault—PD.
Dissolved Gas Concentration (ppm)
H2CH4C2H6C2H4C2H2COCO2Equip.Ref.
1292.5838.393.870.840161.54523.68P[16]
2522.243.2116.731.021.01158.62251.3P[16]
3529.7558.9618.125.061.27160.52263.98P[16]
42525.3130.5514.251.530612.172687.13P[16]
53417.62131.4214.361.220428.032770.29P[16]
65869.58175.2116.451.450624.473684.56P[16]
74966.14145.6615.331.280503.423397.51P[16]
Equipment: P—Power Transformer and R—Reactor.
Table A2. Low intensity discharge fault—D1.
Table A2. Low intensity discharge fault—D1.
Dissolved Gas Concentration (ppm)
H2CH4C2H6C2H4C2H2COCO2Equip.Ref.
19620.615.415.8238.57367854P[16]
28920.016.1616.3639.4354874p[16]
378201113280784P[15]
4305100331615414403700P[15]
5123016327233692130115P[15]
6645861311031774114P[15]
760104447807600R[15]
8951001139122467P[15]
9385608531594651250R[15]
10423069051961180438791R[15]
1176001230318836156049704080R[15]
12595809892445242100P[15]
131202518405001600R[15]
1464542313121215964323628225R[15]
152177104920744070545713923R[15]
1617905803213366199564250R[15]
1713301020661822311820P[15]
Equipment: P—Power Transformer and R—Reactor.
Table A3. High intensity discharge fault—D2.
Table A3. High intensity discharge fault—D2.
Dissolved Gas Concentration (ppm)
H2CH4C2H6C2H4C2H2COCO2Equip.Ref.
1134.7834.74.540.5494.153.189.76P[16]
2207.644.143.880.913929.62331.7P[16]
344089193047572991190P[15]
4545130161532396602850P[15]
57150144097121017606082260P[15]
6120310669448271R[15]
7755229324044608455580P[15]
851001430011401010117197R[15]
91570111017517801830135602P[15]
103090502032338002540270400P[15]
1118204053536563410108610P[15]
1253516016305680172338R[15]
1382003790250462058303185R[15]
1426021535334277130416P[15]
15751571426105322P[15]
1653034585266250390020,000R[15]
17605221211882510P[15]
18902883132138011,700R[15]
192207722170240180013,800R[15]
20590015006812002300750335R[15]
21280028002343500360092718R[15]
2299170202001901401160R[15]
23150039528395323365576P[15]
2420,00013,000185029,00057,00026002430P[15]
2530585251971308138380R[15]
2619005303538343418907570R[15]
2711062901402506806470R[15]
2837001690128281032702286P[15]
292770660547127635221490P[15]
30245120181311678294250R[15]
3111702551831232551800P[15]
3244193564668286120259099082R[15]
3381058011157049011006800R[15]
34500012008310001100140265R[15]
Equipment: P—Power Transformer and R—Reactor.
Table A4. Low and medium temperature fault T1/T2.
Table A4. Low and medium temperature fault T1/T2.
Dissolved Gas Concentration (ppm)
H2CH4C2H6C2H4C2H2COCO2Equip.Ref.
16.8210.133.8174.850662.435871.86P[16]
21433.3820.10101654P[16]
387223.649.6121.1062498P[16]
478196.346.1109.3051384P[16]
522.04171.0591.29182.0401651.5716390.39P[16]
6127034505201390848344500P[15]
73420787015006990335734640P[15]
848610291001900970P[15]
912184405591710P[15]
1066602707690P[15]
111444124711282746P[15]
12203114920305563008R[15]
134801075298113204641000R[15]
Equipment: P—Power Transformer and R—Reactor.
Table A5. High temperature fault T3.
Table A5. High temperature fault T3.
Dissolved Gas Concentration (ppm)
H2CH4C2H6C2H4C2H2COCO2Equip.Ref.
182.74108.9228.06249.83.91809.042053.72P[16]
23.116.613.2336.430.26296.542367.99P[16]
33.055.843.3837.280.27256.612970.88P[16]
43.827.933.3752.680.13406.242770.54P[16]
5880064,06472,12895,650029090,300P[15]
6670910,500140017,7007502901500P[15]
729096629918105772756P[15]
8250010,500479013,50065302310P[15]
9400940210820243901700P[15]
106299029,99026,07667626P[15]
1129012602318208228826P[15]
1215502740816545018411409360R[15]
133910429062660401230180011,500R[15]
1412,70523,498604734,257518840048539R[15]
1518810063005130R[15]
163007002801700367609250R[15]
171071433422221931330P[15]
Equipment: P—Power Transformer and R—Reactor.

References

  1. ASTM D1305-99; Specification for Electrical Insulating Paper and Paperboard. The American Society for Testing and Materials (ASTM): Conshohocken, PA, USA, 2004.
  2. IEC 60554-3-3; Specification for Cellulosic Papers for Electrical Purposes. International Electrotechnical Commission (IEC): Geneva, Switzerland, 1984.
  3. ASTM D3487-16E1; Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus. The American Society for Testing and Materials (ASTM): Conshohocken, PA, USA, 2016.
  4. Meyers, S.D.; Kelly, J.J.; Parrish, E.R.H. A Guide to Transformer Maintenance; VDOC.PUB: Akron, Ohio, 1981; pp. 323–388. ISBN 0-939320-00-2. [Google Scholar]
  5. Colton, R. Combustible Gas Testing on Large Oil Filled Transformers. In Proceedings of the 9th Electrical Insulation Conference, Boston, MA, USA, 8–11 September 1969; pp. 115–118. [Google Scholar] [CrossRef]
  6. Messko Msafe Relay Buchholz, Mr Industry. Available online: https://www.reinhausen.com/productdetail/buchholz-relays/messko-msafe (accessed on 4 July 2023).
  7. Kelman TRANSPORT X. Available online: https://www.gegridsolutions.com/MD/CATALOG/TRANSPORTX.HTM (accessed on 4 July 2023).
  8. CEI EN 60475; Method of Sampling Insulating Liquids. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2011.
  9. VDE 0370-9; Oil-Filled Electrical Equipment—Sampling of Gases and Analysis of Free and Dissolved Gases—Guidance. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2011.
  10. Vahidi, B.; Teymouri, A. Quality Confirmation Tests for Power Transformer Insulation Systems; Springer: Berlin/Heidelberg, Germany, 2019; pp. 1–12. [Google Scholar]
  11. Rogers, R.R. IEEE and IEC Codes to Interpret Faults in Transformers Using Gas in Oil Analysis. IEEE Trans. Electr. Insul. 1978, 75, 349–354. [Google Scholar] [CrossRef]
  12. C57.104-1991; IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers. The Institute of Electrical and Electronics Engineers (IEEE) Standard: Piscataway, NJ, USA, 1991.
  13. ASTM D3612-02; Standard Test Method for Analysis of Gases Dissolved in Eletric Insulation Oil by Gas Chromatography. The American Society for Testing and Materials (ASTM): Conshohocken, PA, USA, 2009.
  14. Keshavamurthy, H.C.; Ravindra, D. An attempt to investigate transformer failure by Dissolved Gas Analysis. J. CPRI 2017, 13, 607–614. [Google Scholar]
  15. Duval, M.; Depablo, A. Interpretation of Gas-In-Oil Analysis Using New IEC Publication 60599 And IEC TC 10 Databases. IEEE Electr. Insul. Mag. 2001, 17, 31–41. [Google Scholar] [CrossRef]
  16. Zeng, B.; Guo, J.; Zhu, W.; Xiao, Z.; Yuan, F.; Huang, S. A transformer Fault Diagnosis Model Based on Hybrid Grey Wolf Optmizer and LS-SVM. Energies 2019, 12, 4170. [Google Scholar] [CrossRef]
  17. N’Cho, J.S.; Fofana, I.; Hadjadj, Y.; Beroual, A. Review of Physicochemical-Based Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers. Energies 2016, 9, 367. [Google Scholar] [CrossRef]
  18. Syafruddin, H.; Nugroho, H.P. Dissolved Gas Analysis (DGA) for Diagnosis of Fault in Oil-Immersed Power Transformers A Case Study. In Proceedings of the IEEE 4th International Conference on Electrical, Telecommunication and Computer Engineering (ELTICOM), Medan, Indonesia, 3–4 September 2020. [Google Scholar] [CrossRef]
  19. Ali, M.S.; Bakar, A.H.A.; Omar, A.; Jaafar, A.S.A.; Mohamed, S.H. Conventional Methods of Dissolved Gas Analysis Using Oil-Immersed Power Transformer for Fault Diagnosis: A Review. Eletr. Power Syst. Res. 2023, 216, 109064. [Google Scholar] [CrossRef]
  20. Faiz, J.; Soleimani, M. Dissolved Gas Analysis Evaluation in Eletric Power Transformers Using Conventional Methods a Review. IEEE Trans. Dielectr. Electr. Insul. 2017, 24, 1239–1248. [Google Scholar] [CrossRef]
  21. Swanasri, C.; Wannapring, E.; Swanasri, T. Dissolved Gas Analysis Methods for Distribution Transformers. In Proceedings of the 13th International Conference on Electrical Engineering/Electronics, Computer, Telecommunications and Information Technology (ECTI-CON), Chiang Mai, Thailand, 28 June–1 July 2016. [Google Scholar] [CrossRef]
  22. Wattakapaiboon, W.; Pattanadech, N. The State of the Art for Dissolved Gas Analysis Based on Interpretation Techniques. In Proceedings of the International Conference on Condition Monitoring and Diagnosis (CMD), Xi’an, China, 25–28 September 2016. [Google Scholar] [CrossRef]
  23. Junior, H.F.; Costa, J.G.S.; Olivas, J.L. A Review of Monitoring Methods for Predictive Maintenance of Electric Power Transformers Based on Dissolved Gas Analysis. Renew. Sustain. Energy Rev. 2015, 46, 201–209. [Google Scholar] [CrossRef]
  24. Sun, H.C.; Huang, Y.C.; Huang, C.M. A Review of Dissolved Gas Analysis in Power Transformers. Energy Procedia 2012, 14, 1220–1225. [Google Scholar] [CrossRef]
  25. IEC 60599 Ed. 3.0 b:2015; Mineral Oil-Impregnated Electrical Equipment in Service—Guide to the Interpretation of Dissolved and Free Gases Analysis. International Electrotechnical Commission (IEC): Geneva, Switzerland, 2015.
  26. Duval, M. Fault Gases Formed in Oil-Filled Breathing EHV Power Transformers—the Interpretation of Gas Analysis Data. IEEE PAS 1974, 1974, 1–4. [Google Scholar]
  27. C57.139-2015; IEEE Guide for Dissolved Gas Analysis in Transformer Load Tap Changers. The Institute of Electrical and Electronics Engineers (IEEE) Standard: New York, NY, USA, 2015.
  28. Duval, M. The Duval Triangle for Load Tap Changers, Non-Mineral Oils and Low Temperature Faults in Transformers. IEEE Electr. Insul. Mag. 2008, 24, 22–29. [Google Scholar] [CrossRef]
  29. Akbari, A.; Setayeshmehr, A.; Borsi, H.; Gockenbach, E. A Software Implementation of the Duval Triangle Method. In Proceedings of the Conference Record of the 2008 IEEE International Symposium on Electrical Insulation, Vancouver, BC, Canada, 9–12 June 2008. [Google Scholar] [CrossRef]
  30. Mansour, D.A. A New Graphical Technique for the Interpretation of Dissolved Gas Analysis in Power Transformers. In Proceedings of the 2012 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Montreal, QC, Canada, 14–17 October 2012; pp. 195–198. [Google Scholar] [CrossRef]
  31. Gamez, C. Dissolved Gas Analysis, Measurements and Interpretations Power Transformer Condition Monitoring and Diagnosis. In Power Transformer Condition Monitoring and Diagnosis; The Institute of Engineering and Tecnology (IET): London, UK, 2018; pp. 1–38. [Google Scholar] [CrossRef]
  32. Mansour, D.A. Development of A New Graphical Technique for Dissolved Gas Analysis in Power Transformers Based on The Five Combustible Gases. IEEE Trans. Dielectr. Electr. Insul. 2015, 22, 2507–2512. [Google Scholar] [CrossRef]
  33. Duval, M.; Lamarre, L. The Duval Pentagon—A New Complementary Tool for the Interpretation of Dissolved Gas Analysis in Transformers. IEEE Electr. Insul. Mag. 2014, 30, 9–12. [Google Scholar] [CrossRef]
  34. Cheim, L.; Duval, M.; Haider, S. Combined Duval Pentagons: A Simplified Approach. Energies 2020, 13, 2859. [Google Scholar] [CrossRef]
  35. Duval, M.; Alzieu, E.; Banovic, M.; Bhumiwat, S.; Boman, P.; Buchacz, T.; Dale, A.M.; Djurik, B.; Grisaru, M.; Heizmann, T.; et al. Advances in DGA Interpretation; CIGRE: Paris, France, 2019; ISBN 978-2-85873-473-3. [Google Scholar]
  36. Saha, T.K.; Purkait, P. Transformer Ageing—Monitoring and Estimation Techniques; Wiley-IEEE Press: Pondicherry, India, 2017; pp. 211–243. [Google Scholar] [CrossRef]
  37. Zhang, Y.; Tang, Y.; Liu, Y.; Liang, Z. Fault Diagnosis of Transformer Using Artificial Intelligence: A Review; School of Information Science, Guangdong University of Finance and Economics: Guangzhou, China; School of Electric Power, South China University of Technology: Guangzhou, China, 2022. [Google Scholar] [CrossRef]
  38. Li, Y. The State of the Art in Transformer Fault Diagnosis with Artificial Intelligence and Dissolved Gas Analysis: A Review of the Literature; School of Electrical and Electronics Engineering, North China Electric Power University: Beijing, China, 2023. [Google Scholar] [CrossRef]
  39. Gouda, O.E.; El-Hoshy, S.H.; El-Tamaly, H.E. Proposed Three Ratios Technique for the Interpretation of Mineral Oil Transformers Based Dissolved Gas Analysis. IET Gener. Transm. Distrib. 2018, 12, 2650–2661. [Google Scholar] [CrossRef]
  40. Gouda, O.E.; El-Hoshy, S.H.; El-Tamaly, H.H. Proposed Heptagon Graph for DGA Interpretation of Oil Transformers. IET Gener. Transm. Distrib. 2018, 12, 490–498. [Google Scholar] [CrossRef]
  41. Gouda, O.E.; El-Hoshy, S.H.; Ghoneim, S.S.M. Enhancing, the Diagnostic Accuracy of DGA Techniques Based on IEC-TC10 and Related Databases. IEEE Access 2021, 9, 118031–118041. [Google Scholar] [CrossRef]
Figure 1. Buchholz relay, (a) electrical schematic [5]; (b) an example of a Buchholz relay [6].
Figure 1. Buchholz relay, (a) electrical schematic [5]; (b) an example of a Buchholz relay [6].
Energies 16 07219 g001
Figure 2. Portable gas chromatograph [7].
Figure 2. Portable gas chromatograph [7].
Energies 16 07219 g002
Figure 3. Oil collection with syringe.
Figure 3. Oil collection with syringe.
Energies 16 07219 g003
Figure 4. Rate of the evolution of gases in oil as a function of temperature [12].
Figure 4. Rate of the evolution of gases in oil as a function of temperature [12].
Energies 16 07219 g004
Figure 5. Illustration of practical failure case [14]: (a) thermal fault; (b) thermal and electrical fault.
Figure 5. Illustration of practical failure case [14]: (a) thermal fault; (b) thermal and electrical fault.
Energies 16 07219 g005
Figure 6. Typical relative proportion of gases in arc type fault.
Figure 6. Typical relative proportion of gases in arc type fault.
Energies 16 07219 g006
Figure 7. Typical relative proportion of gases in partial discharge type fault.
Figure 7. Typical relative proportion of gases in partial discharge type fault.
Energies 16 07219 g007
Figure 8. Typical relative proportion of gases in overtemperature type fault.
Figure 8. Typical relative proportion of gases in overtemperature type fault.
Energies 16 07219 g008
Figure 9. Typical relative proportion of gases in cellulose heating type fault.
Figure 9. Typical relative proportion of gases in cellulose heating type fault.
Energies 16 07219 g009
Figure 10. Early Dornenburg ratio plot of the symptomatic indicator of transformers fault [4].
Figure 10. Early Dornenburg ratio plot of the symptomatic indicator of transformers fault [4].
Energies 16 07219 g010
Figure 11. Graphic representation of method IEC 60599.
Figure 11. Graphic representation of method IEC 60599.
Energies 16 07219 g011
Figure 12. Duval Triangle T1.
Figure 12. Duval Triangle T1.
Energies 16 07219 g012
Figure 13. Duval Triangle T4.
Figure 13. Duval Triangle T4.
Energies 16 07219 g013
Figure 14. Duval Triangle T5.
Figure 14. Duval Triangle T5.
Energies 16 07219 g014
Figure 15. Mansour Pentagon [32].
Figure 15. Mansour Pentagon [32].
Energies 16 07219 g015
Figure 16. Duval Pentagon 1.
Figure 16. Duval Pentagon 1.
Energies 16 07219 g016
Figure 17. Duval Pentagon 2.
Figure 17. Duval Pentagon 2.
Energies 16 07219 g017
Figure 18. Boundaries of the Heptagon graph limits. Boundaries of the Heptagon, which is expressed from 0 to 100 in a clockwise direction. HCCD, high concentration of cellulose degradation; MCCD, medium concentration of cellulose degradation; LCCD represents low concentrations of cellulose degradation; T1, thermal fault < 300 °C; T2, thermal fault from 300 to 700 °C; T3, thermal fault > 300 °C; TD, electrical and thermal faults; D1, low-energy discharges; D2, high-energy discharges; PD, partial discharge fault.
Figure 18. Boundaries of the Heptagon graph limits. Boundaries of the Heptagon, which is expressed from 0 to 100 in a clockwise direction. HCCD, high concentration of cellulose degradation; MCCD, medium concentration of cellulose degradation; LCCD represents low concentrations of cellulose degradation; T1, thermal fault < 300 °C; T2, thermal fault from 300 to 700 °C; T3, thermal fault > 300 °C; TD, electrical and thermal faults; D1, low-energy discharges; D2, high-energy discharges; PD, partial discharge fault.
Energies 16 07219 g018
Figure 19. Confusion Matrix of the Key Gas Method.
Figure 19. Confusion Matrix of the Key Gas Method.
Energies 16 07219 g019
Figure 20. Confusion Matrix of the Dornenburg method.
Figure 20. Confusion Matrix of the Dornenburg method.
Energies 16 07219 g020
Figure 21. Confusion matrix of the Rogers method.
Figure 21. Confusion matrix of the Rogers method.
Energies 16 07219 g021
Figure 22. Confusion matrix of the Rogers IEEE method.
Figure 22. Confusion matrix of the Rogers IEEE method.
Energies 16 07219 g022
Figure 23. Confusion matrix of the IEC method.
Figure 23. Confusion matrix of the IEC method.
Energies 16 07219 g023
Figure 24. Confusion matrix of the IEC 60599 method.
Figure 24. Confusion matrix of the IEC 60599 method.
Energies 16 07219 g024
Figure 25. Confusion matrix triangle of the Duval T1 method.
Figure 25. Confusion matrix triangle of the Duval T1 method.
Energies 16 07219 g025
Figure 26. Confusion matrix of the Pentagon Duval 1 method.
Figure 26. Confusion matrix of the Pentagon Duval 1 method.
Energies 16 07219 g026
Figure 27. Comparison of the performances between techniques.
Figure 27. Comparison of the performances between techniques.
Energies 16 07219 g027
Table 1. Reference value gas concentrations; values may differ according to criteria defined by standards.
Table 1. Reference value gas concentrations; values may differ according to criteria defined by standards.
Gas TypeConcetration (ppm)
Hydrogen (H2)100
Methane (CH4)120
Carbon Monoxide (CO)350
Carbon Dioxide (CO2)2500
Acetylene (C2H2)1
Ethylene (C2H4)50
Ethane (C2H6)65
Table 2. Relationships of the Dornenburg method [12].
Table 2. Relationships of the Dornenburg method [12].
Suggested Fault DiagnosisCH4
H2
C2H2
C2H4
C2H2
CH4
C2H6
C2H2
Thermal Decomposition>1<0.75<0.3>0.4
Partial Discharge (Low intensity)<0.1Not significant<0.3>0.4
Arcing (High intensity)0.1 to 1>0.75>0.3<0.4
Table 3. Rogers method relationships [11].
Table 3. Rogers method relationships [11].
FaultCH4
H2
C2H6
CH4
C2H4
C2H6
C2H2
C2H4
Normal≥0.1 and <1<1<1<0.5
Partial discharge≤0.1<1<1<0.5
Overheating < 150 °C≥1 and <3
or ≥3
<1<1<0.5
Overheating 150 °C to 200 °C≥1 and <3
or ≥3
≥1<1<0.5
Overheating 200 °C to 300 °C>0.1 and <1≥1<1<0.5
General conductor overheating>0.1 and <1<1≥1 and <3<0.5
Winding circulating currents≥1 and <3<1≥1 and <3<0.5
Core and tank circulating currents≥1 and <3<1≥3<0.5
Flashover without power follow through>0.1 and <1<1<1≥0.5 and <3
Arc with power follow through>0.1 and <1<1≥1 and <3
or ≥3
≥0.5 and <3
or ≥3
Continuous sparking to floating potential>0.1 and <1<1≥3≥3
Partial discharge with tracking≤0.1<1<1≥0.5 and <3
or ≥3
Table 4. Rogers method relationships IEEE Std C57.104.
Table 4. Rogers method relationships IEEE Std C57.104.
FaultC2H2
C2H4
CH4
H2
C2H4
C2H6
Normal<0.1≥0.1 and <1<1
Low-energy density arcing-PD<0.1<0.1<1
Arcing high-energy discharge≥1 and ≤3≥0.1 and ≤1>3
Low temperature thermal<0.1≥0.1 and ≤1≥1 and ≤3
Thermal < 700 °C<0.1>1≥1 and ≤3
Thermal > 700 °C<0.1>1>3
Table 5. IEC ratio method relations [11].
Table 5. IEC ratio method relations [11].
FaultC2H2
C2H4
CH4
H2
C2H4
C2H6
No fault<0.1≥0.1 and <1<1
Partial discharge of low-energy density<0.1<0.1≥1 and <3
Partial discharge of high-energy density≥0.1 and <3<0.1≥1 and <3
Discharge of low energy≥0.1 and <3
or ≥3
≥0.1 and <1<1
Discharge of high energy≥0.1 and <3≥0.1 and <1<1
Thermal fault of temperature < 150 °C<0.1≥0.1 and <1<1
Thermal fault of low temperature range 150 °C to 300 °C<0.1≥1>3
Thermal fault of medium temperature range 300 °C to 700 °C<0.1≥1>3
Thermal fault of high temperature range > 700 °C<0.1≥1>3
Table 6. IEC 60599 [25].
Table 6. IEC 60599 [25].
FaultC2H2
C2H4
CH4
H2
C2H4
C2H6
Partial discharges (PD)NS<0.1<0.2
Discharge of low energy (D1)>1≥0.1 and ≤0.5>1
Discharge of high energy (D2)≥0.6 and ≤2.5≥0.1 and ≤1>2
Thermal fault t < 300 °C (T1)NS≥1 but NS<1
Thermal fault 300 °C < t < 700 °C (T2)<0.1>1≥1 and ≤4
Thermal fault t > 700 °C (T3)<0.2>1>4
NS: Non significant whatever the value.
Table 7. Diagnosis coding rule of proposed TRT interpretation technique.
Table 7. Diagnosis coding rule of proposed TRT interpretation technique.
FaultR1R2R3
T3R1 > 0.05R2 ≤ 1R3 < 0.5
T2R1 > 0.051 ≤ R2 ≤ 3.5R3 < 0.5
T1R1 > 0.05R2 > 3.5R3 < 0.5
T00.05 ≤ R1 ≤ 0.9NS.R3 < 0.05
PD1R1 ≤ 0.05R2 > 1R3 < 0.5
PD2R1 ≤ 0.05R2 > 1R3 ≥ 0.5
D1  R1 ≥ 0.05R2 > 3.5R3 ≥ 0.5
D2R1 ≤ 0.9R2 ≤ 3.5R3 ≥ 0.5
DTR1 > 0.9R2 ≤ 3.5R3 ≥ 0.5
NS, non-significant whatever the value; (T3): Thermal faults of T > 700 °C; (T2): Thermal faults of 300 < T < 700 °C; (T1): Thermal faults 150 < T < 300 °C; (T0): Thermal faults T < 150 °C; (D1): Low-energy discharge; (D2): High-energy discharge; (PD1): Low-energy-corona partial discharge; (PD2): High-energy-corona partial discharge; (DT): Mix of electrical and thermal faults.
Table 8. Grouping of the incipient fault type codes for conventional DGA interpretation techniques.
Table 8. Grouping of the incipient fault type codes for conventional DGA interpretation techniques.
TechiniqueFault Types
T1T2T3PDD1D2
Duval Triangle T1Thermal fault < 300 °CThermal fault 300–700 °CThermal fault > 700 °CPartial DischargeLow-energy dischargeHigh-energy discharge
DornenburgThermal decomposition (T)Partial Discharge (PD)Energy Discharge–Arcing (D)
RogersThermal fault of low temperature < 150 °C (T1_1)Winding circulation current (T2)Core and tank circulation current (T3_1)Partial discharge with low energy (PD_1)Continuous Sparking (D1_1)Arc with power follows through (D2)
Thermal fault of temperature range 150–200 °C (T1_2)Insulated conductor overheating (T3_2)Partial discharge with tracking (PD_2)Flashover (D1_2)
Thermal fault of temperature range 200–300 °C (T1_3)
Rogers IEEELow temperature thermal (T1)Thermal < 700 °C (T2)Thermal > 700 °C (T3)Low-energy density arcing-(PD)Arcing-High-energy discharge (D)
IEC ratio methodThermal fault of temperature < 150 °C (T1_1)Thermal fault of medium temperature range 300 °C to 700 °C (T2)Thermal fault of high temperature range > 700 °C (T3)PD of low-energy density (PD_1) Discharge with low-energy density (D1)Discharge with high-energy arcing (D2)
Thermal fault of low temperature range 150 °C to 300 °C (T1_2)PD of high-energy density (PD_2)
IEC 60599 ratio methodThermal fault t < 300 °C (T1)Thermal fault 300 °C < t < 700 °C (T2)Thermal fault t > 700 °C (T3)Partial Discharge (PD)Discharge of low energy (D1)Discharge of high energy (D2)
Duval Pentagon 1Termal fault < 300 °CThermal fault 300–700 °CThermal fault > 700 °CPartial DischargeLow-energy dischargeHigh-energy discharge
Key GasThermal degradation (TD)Partial Discharge (PD)Arcing (D)
Overheat cellulose (OC)
Note: For analysis of the results, information about non-failure—N and unidentified failure—Not-F will also be used.
Table 9. Performance analysis of the Key Gas method.
Table 9. Performance analysis of the Key Gas method.
FailurePerformance Analysis
PrecisionRecallF1-ScoreSupport
D0.820.710.7651
PD0.000.000.008
T0.880.730.8030
Accuracy 0.6688
Table 10. Performance analysis of the Dornenburg method.
Table 10. Performance analysis of the Dornenburg method.
FailurePerformance Analysis
PrecisionRecallF1-ScoreSupport
D1.000.840.9151
PD0.830.710.777
T1.000.800.8930
Accuracy 0.8288
Table 11. Performance analysis of the Rogers method.
Table 11. Performance analysis of the Rogers method.
FailurePerformance Analysis
PrecisionRecallF1-ScoreSupport
D11.000.290.4517
D20.720.850.7834
PD0.830.710.777
T1_T20.880.540.6713
T30.790.650.7117
Accuracy 0.6588
Table 12. Performance analysis of the Rogers IEEE method.
Table 12. Performance analysis of the Rogers IEEE method.
FailurePerformance Analysis
PrecisionRecallF1-ScoreSupport
D1.000.530.6951
PD0.800.570.677
T1_T20.750.460.5713
T30.800.710.7517
Accuracy 0.5688
Table 13. Performance analysis of the IEC method.
Table 13. Performance analysis of the IEC method.
FailurePerformance Analysis
PrecisionRecallF1-ScoreSupport
D10.860.710.7717
D20.880.850.8734
PD0.830.710.777
T1_T20.700.540.6113
T30.800.710.7517
Accuracy 0.7488
Table 14. Performance analysis of the IEC 60599 method.
Table 14. Performance analysis of the IEC 60599 method.
FailurePerformance Analysis
PrecisionRecallF1-ScoreSupport
D11.000.470.6417
D20.870.790.8334
PD0.830.710.777
T1_T20.470.620.5313
T30.830.590.6917
Accuracy 0.6688
Table 15. Performance analysis of the Duval triangle method.
Table 15. Performance analysis of the Duval triangle method.
FailurePerformance Analysis
PrecisionRecallF1-ScoreSupport
D11.000.880.9417
D20.941.000.9734
PD0.670.570.627
T1_T20.600.460.5213
T30.820.820.8217
accuracy 0.8388
Table 16. Performance analysis of the Pentagon Duval 1 method.
Table 16. Performance analysis of the Pentagon Duval 1 method.
FailurePerformance analysis
PrecisionRecallF1-ScoreSupport
D10.840.940.8917
D21.000.880.9434
PD0.830.710.777
T1_T20.780.540.6413
T30.780.820.8017
accuracy 0.8288
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Rangel Bessa, A.; Farias Fardin, J.; Marques Ciarelli, P.; Frizera Encarnação, L. Conventional Dissolved Gases Analysis in Power Transformers: Review. Energies 2023, 16, 7219. https://doi.org/10.3390/en16217219

AMA Style

Rangel Bessa A, Farias Fardin J, Marques Ciarelli P, Frizera Encarnação L. Conventional Dissolved Gases Analysis in Power Transformers: Review. Energies. 2023; 16(21):7219. https://doi.org/10.3390/en16217219

Chicago/Turabian Style

Rangel Bessa, Alcebíades, Jussara Farias Fardin, Patrick Marques Ciarelli, and Lucas Frizera Encarnação. 2023. "Conventional Dissolved Gases Analysis in Power Transformers: Review" Energies 16, no. 21: 7219. https://doi.org/10.3390/en16217219

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop