4.1. Validation of the Small-Signal Model
This section provides a validation of the small-signal model presented in
Section 2. Validation was performed by simulating both the small-signal and EMT models of the microgrid shown in
Figure 1 and comparing the responses of select state variables. Two cases featuring different disturbances were tested. First, the state variables were recorded in the EMT model before and after the disturbance was applied. These values were used as the small-signal model states at the pre- and post-disturbance operating points (
and
, respectively). The post-disturbance operating point was used to obtain the state matrix
. Then, the small-signal model was simulated using Matlab/Simulink with the default fixed-step solver and 50
s time step according to
The first disturbance was a reduction in the load LD1 shunt resistance, which caused a 0.2 pu (on the system base) increase in the active power consumed by load. The relevant setpoints and parameters used for this simulation are summarized in
Table 2.
The responses of the selected state variables from the EMT simulation and small-signal model simulation are compared in
Figure 5.
Higher resolution plots of the GFM IBR filter capacitor voltages are provided in
Figure 6 to illustrate the model agreement for higher-frequency modes.
A contingency where the GFL IBR was tripped offline was simulated for the second case. The relevant setpoints and parameters used for this simulation are summarized in
Table 3.
The responses of the selected state variables for the GFL IBR contingency case are compared in
Figure 7 with higher-resolution plots of the filter voltages in
Figure 8.
Note that the small-signal model cannot reproduce the behavior of an EMT breaker model, which includes an RC-snubber circuit as well as single-phase switching at the current waveform zero crossings. Therefore, the GFL IBR model was replaced with controlled current sources, which injected the pre-disturbance GFL IBR point of common coupling currents. To simulate the contingency, the current source references were instantaneously set to zero. Additionally, to reflect the GFL IBR contingency in the small-signal model, the equations and variables related to the GFL IBR dynamics were removed before forming the state matrix.
The EMT and small-signal model state variable responses in
Figure 5 through to
Figure 8 exhibit similar amplitudes and frequencies. The two test cases resulted in similar behavior, which was expected since load acceptance and generation loss both cause rapid increases in load for the grid-forming inverter and synchronous generator. The authors selected these types of disturbances as they are highly applicable to the transient load sharing problem.
4.2. Modal Analysis of Small-Signal Microgrid Model
A state matrix was formed by using the small-signal model discussed in
Section 2 and post-load acceptance operating point discussed in
Section 4.1. This matrix was used as the basis to conduct a sensitivity analysis of the eigenvalues and eigenvectors to variation in the GFM IBR P-F droop parameter
and the synchronous generator inertia
. The analysis began by identifying modes with low-to-moderate damping ratios
that were both sensitive to
and participated in the state variable
. The variable
was selected because the choice of RRF orientation caused the disturbances associated with fluctuation in the GFM IBR output active power to appear predominantly as an increase in the GFM IBR ouput current
d-axis component magnitude. This can be seen from
Figure 5. Thus, the presence of modes with low
and significant participation in
were indicative of a poorly damped GFM IBR output current response to an active power-related disturbance (such as generation trip or load acceptance) and an elevated risk of tripping overcurrent protections. The eigenvalues of the state matrix were iteratively computed using the eig() function of the Numpy linalg module in Python for a set of
values ranging from 0.002 pu/pu to 0.2 pu/pu on the GFM IBR base, and the eigenvalue trajectories are displayed in
Figure 9.
Figure 9 shows three underdamped modes (see inset at right), which responded significantly to the variation in the grid-forming inverter P-F droop
. These were designated in order of decreasing damped natural frequency
as the fast
, medium
, and slow
modes. The main trends observed were that both
and
exhibited very low damping ratios initially. Then,
experienced a significant damping improvement, while
moved toward the right hand side (RHS) of the real axis, eventually leading to instability and imposing a limit on any damping improvement to
.
exhibited a worst-case damping ratio
of 0.45, which corresponded to an overshoot of about 20% for a second-order system and therefore was not considered a problem mode. In the remaining analysis, a
maximum overshoot was used as the threshold to determine if a response was well damped. This threshold was chosen as it had been encountered in overcurrent and overload protection functions of commercially available control systems for both IBRs and SGs in the authors experience.
In the next step, the inertia constant of the SG
varied from 0.368 s to 3.312 s. The objective was to determine how the mode trends respond to the changes in the system inertia. This was deemed an important consideration as there was consensus from the power systems research community that the integration of renewables would lead to lower-inertia power systems [
4,
5,
12,
21,
22]. At a more local level, islanded microgrids may feature groups of smaller SGs [
1] that perform load-dependent start/stop operations to ensure that individual units operate at minimum loads, thus causing the amount of physical inertia to vary depending on the microgrid load and renewables’ profiles. For this reason, a simultaneous sensitivity of the modes
–
to the GFM IBR P-F droop
and
is presented in
Figure 10.
The main observation from
Figure 10 was that sensitivity trends of the fast mode
and medium mode
to the GFM IBR P-F droop
were little affected by the SG inertia constant
value. The trends for the slow mode
showed that the natural frequency
was reduced by increasing
; however, the trends in damping were very similar as indicated by the constant damping ratio
lines in subplot (c). Therefore, it was predicted that the damping improvement in the GFM IBR output current magnitude determined through detailed simulation would exhibit only minor sensitivity to
. At this point, further modal analysis was performed for only
and
due to finding that
exhibited suitable damping ratios regardless of the values of
or
tested.
The participation factors are often used in modal analysis to determine how the system modes contribute to the response of the system states when perturbed away from the operating point to some initial condition, denoted as
. This is readily observed by the time domain solution of the linear system response
(assuming the system inputs are constant):
where the columns of
are the right eigenvectors (also known as mode shapes) and the columns of
are the left eigenvectors. Thus, the term containing the
mode
and the initial value of the
state
in the solution of the
state
is
and
is the participation factor.
and
were used to denote the participation of the fast mode
and the slow mode
in the GFM IBR
d-axis current
, respectively. The sensitivities of
and
to the GFM IBR P-F droop
and SG inertia constant
are given in
Figure 11.
The participation factor trends suggested that the fastest mode
would be the dominate oscillatory mode observed in the response of the GFM IBR
d-axis current
regardless of the value of the GFM IBR P-F droop
and SG inertia constant
. In contrast,
would likely not be observed at all. It was noted that there are other underdamped oscillatory modes that were not studied due to insensitivity to both
and
. However, in referring once again to
Figure 9, these modes had
greater than 4000 rad/s and a damping ratio
of at least 0.1 and so were likely to settle before contributing to an overcurrent condition.
The implications of the analysis thus far was that the smallest value of the GFM IBR P-F droop
would yield the best damping of the GFM IBR output current magnitude response to a load or generation disturbance. This prediction was tested with 198 simulations of the EMT model of the single GFM IBR microgrid performed for 22 different values of
and nine values of the SG inertia constant
. The output current magnitude of the GFM IBR was recorded for each combination of parameters in response to a 0.2 pu load increase occuring at
. The EMT simulation was carried out using built-in stationary reference frame models of passive and active components available in the Matlab/Simulink Specialized Power System toolbox. As a result, the magnitude was obtained by first applying (
7) (
can be arbitrary) to the three-phase currents and then calculating the magnitude as
The most notable observation from these figures was the prevalence of the slow mode
in response to the GFM IBR output current magnitude
when the GFM IBR P-F droop
was less than 0.05 pu/pu (on the GFM IBR’s base). This seemed to contradict the indication of mode participations by the participation factors shown in
Figure 11. This result was significant given that participation factors were traditionally used to identify dominant modes associated with specific state variables in power systems (see [
26,
36]). Additionally, the use of these metrics continued to be found in more recent works, addressing power system frequency stability improvement [
37,
38]).
It was apparent that the substantial participation of the slow mode
in the GFM IBR current magnitude
observed in the subplots of
Figure 12 and
Figure 13 may be due to the excitation of
by the initial conditions of states other than the GFM IBR
d-axis current
. This would not be reflected by the values of the participation factor
illustrated in
Figure 11. To determine if another state was exciting
, the elements of the matrix containing the left eigenvectors of the model state matrix
(henceforth referred to as the mode excitations) correlating to the fast mode
and slow mode
for the case when
= 0.01 pu/pu and
= 0.736 s are tabulated in
Table 4.
From
Table 4, the excitation of the slow mode
by the SG rotor speed
was found to be several orders of magnitude larger than the excitation of
by the GFM IBR
d-axis current
. This explained the discrepancy between the values of the participation factor
from
Figure 11 and the EMT simulation results in
Figure 12 and
Figure 13. It was proposed to use a new metric to estimate the participation of a mode
in a state
, which would be denoted
and given by
The sensitivities of
and
to
and
are plotted in
Figure 14.
In contrast to the participation factors, the metrics clearly indicated the contribution of in response to ;
The metrics predicted the inversion of the relative dominance of the slow mode and fast mode in response to the GFM IBR current magnitude as the GFM IBR P-F droop increased toward the stability limit;
exhibited almost no sensitivity to the SG inertia constant while showed some sensitivity to but the general trend was the same.
The smallest overshoot
occurring for each
value and the corresponding value of P-F droop parameter
are tabulated in
Table 5.
Table 5 shows that the optimal value of
exhibited little sensitivity to
as
decreased by 0.01 pu/pu. The total improvement to
was 16.8%. Additionally, the values of
showed diminishing returns as
increased. These results suggested that re-tuning the value of
when the physical inertia in the system changed would confer minimal benefit since even the best case scenario resulted in greater than 20% maximum overshoot.
4.3. EMT Simulation of the Multiple GFM IBR Microgrid
EMT simulations of the microgrid shown in
Figure 2 were performed to determine if the same trends obtained from analyzing the single GFM IBR microgrid (
Figure 1) would be observed. Details about the simulation platform and settings are given in
Section 3. Four case studies were developed such that the number of diesel generators in operation varied from one to four. In each case study, the GFL IBR was tripped offline, resulting in a substantial load acceptance for the remaining DER. The cases were designed to result in approximately the same pre- and post-disturbance loading of the GFM IBRs (0.55 pu and 0.9 pu, respectively) and the diesel generators (0.48 pu and 0.8 pu, respectively). This was accomplished by adjusting the pre-disturbance GFL IBR active and reactive power setpoints and connecting only a subset of the constant impedance loads. These scenarios are described in
Table 6.
For each case, several simulations were run in which the value of the P-F droop parameter shared by all three GFM IBRs
varied from 0.02 pu/pu to 0.10 pu/pu (on the GFM IBR base) to determine the effect, if any, on the magnitude of the output current of the GFM IBRs (calculated according to (
48)). The starting value of
resulted in the maximum output of the GFM IBRs occurring for a frequency of 58.8 Hz at steady state, which was the continuous operation lower limit for distributed IBRs per the IEEE Std. 1547-2018 frequency ride-through requirements [
39]. Additionally, it should be noted that the GFM IBR models were identical in structure and parameters and their output current response to the generation trip was found to be nearly the same across all cases and values of
tested, as illustrated by the traces in
Figure 15.
This was expected due to the similarity of these models and the fact that the network impedances are smaller than the GFM IBR LCL filter impedances. As a result, further figures containing simulation results will only show the response of IBR1 output current magnitude for space considerations.
A subset of the results of the Case 1 through Case 4 simulations are shown in
Figure 16 and
Figure 17. From examining the output current responses for the Multiple GFM IBR Microgrid simulations, it was observed that the response contains both fast (hundreds of rad/s) and slow (tens of rad/s) components that were easily distinguished due to their disparities in time scales.
This was similar to the distribution of modes observed in
Figure 12 and
Figure 13. For comparison with the EMT simulation results of the single GFM IBR microgrid, the same data pertaining to the smallest overshoots
of
are record in
Table 7.
From
Figure 16 and
Figure 17, and
Table 7, it was apparent that the introduction of the governor and exciter dynamics significantly affected the settling time of the IBR1 output current magnitude
and decreased the damping of the slower modes.
Table 7 shows a substantial reduction in the effectiveness of tuning the GFM IBR P-F droop
to improve the damping of the GFM IBR output current in the Multiple GFM IBR Microgrid as compared to the single GFM IBR microgrid. Interestingly,
Table 7 shows that the greatest damping improvement to
occurred for the fewest number of SG cases and that the optimal value of
exhibited significant sensitivity to the number of SGs in operation. These results revealed the importance of the detailed modeling of the governor and excitation systems despite large time constants associated with these subsystems. Overall, the damping improvement by tuning
was still limited to an unsatisfactory level and the change in the smallest overshoot
due to the variation in the number of SGs in operation was 19%. This was a similar result to the limited improvement in the damping and low sensitivity of
to the SG inertia constant in the single GFM IBR microgrid analysis.