5.2. Analysis Results
- (1)
Carbon emissions of energy sources and EH devices
According to Equations (3) and (4), the carbon emissions per unit of energy generated by energy sources in the four seasons are calculated and illustrated in
Figure 4, wherein the dotted line, dashed line and solid line denote the construction-produced, operation-produced, and life-cycle carbon emissions, respectively. In addition, the generation proportion of different energy sources is also displayed in
Figure 4. It can be seen that the operation-produced carbon emissions fluctuate with the generation trend of thermal plants because they are mainly produced by thermal power plants. Different from the operation-produced carbon emissions, the construction-produced carbon emissions of different energy resources have no significant difference over the course of the year so the dotted lines are nearly flat in four seasons. Note that as shown in
Figure 4b, the output of solar power generation increases around 12:00 in summer, so the operation-produced carbon emissions stay at the lowest level of the year and the construction-produced carbon emissions account for nearly 35% of total carbon emissions.
The carbon emissions results of various EH devices are calculated and listed in
Table 5. It can be seen that the AB has the most total construction-produced carbon emissions of 12325 t, while it does not produce the largest construction-produced carbon emissions per unit of energy generated. The EB has the most construction-produced carbon emissions per unit of energy generated at 245.7 g/kWh. The GB has the least total construction-produced carbon emissions amount of 2525 t, and the most total energy generation of 135 GW. Therefore, among EH devices, the GB produces the lowest construction-produced carbon emissions per unit of energy generated, at 18.7 g/kWh.
- (2)
Carbon emission flow of the UMES
The carbon emission flow of the test system on a summer weekday is shown in
Figure 5, in which the amount of carbon emission flow is represented by the width of the color band. In addition, the inputs and outputs of the EH in the test system on summer weekdays are presented in
Figure A2 of
Appendix A, and the results of the proposed method are compared with the operation-produced carbon emissions tracing method, as shown in
Table 6.
Figure 5 shows that the operation-produced carbon flow comes from two sources, i.e., thermal plants and gas sources, while the construction-produced carbon flow comes from more sources, including solar plants, wind plants, hydro plants, and nuclear plants. Note that in the test system, the capacity of thermal plants is much higher than that of other power plants, so the amount of the construction-produced carbon flow of thermal plants is the highest in the system. Moreover, although the gas consumption and electricity consumption are close throughout the day as shown in
Figure A2a, the operation-produced carbon emissions of the power system are higher than the gas system.
In this test system, the energy flow of electricity loads is mainly delivered from the power system directly, while that of cooling loads and heating loads are mainly delivered from the gas system through EH devices such as the GB and CHP units, as shown in
Figure 5. Therefore, the carbon emission flow of EH devices is mainly delivered to cooling loads and heating loads, while that of energy sources is mainly delivered to electricity loads.
Furthermore, the carbon emissions of the UMES during 24 h of the day are shown in
Figure 6. It can be seen that the carbon emission results vary in different periods due to changing load demands. The carbon emissions are classified by life cycle phases and energy load types as shown in
Figure 6a,b, respectively.
Figure 6a shows that the operation-produced carbon emissions generated by energy sources account for the largest proportion, while
Figure 6b indicates that the most carbon emissions are delivered to electricity loads. Additionally, the construction-produced carbon emissions of EH devices during 8:00–18:00 are larger than in other periods due to the significant increase in cooling loads, as shown in
Figure A2b.
- (3)
Evaluation indices
According to Equation (25), the DCDF indices of various EH devices are calculated and illustrated in
Figure 7. It can be seen that the DCDF indices of CHP units and GB stay at a low level, indicating the carbon emissions per unit of energy distributed in them are small. This is because the CHP units and GB are mainly powered by gas fuel. Moreover, the DCDF index of AB also stays at a low level during 7:00–22:00, because the heating to AB is provided by GB during this period and EB during other periods.
According to Equation (26), the CCDF indices of two different consumers (i.e., Consumer A and Consumer B) at two periods are calculated and shown in
Figure 8. It is assumed that Consumer A only has electricity-driven thermostatically controlled loads for cooling, while Consumer B has multi-energy-driven thermostatically controlled loads. The ratio of multi-energy consumption (i.e., electricity: heating: cooling) is 9:0:1 for Consumer A and 5:1:4 for Consumer B. In this paper, the circumstances of Consumer A and B at 00:00 are denoted as A1 and B1, respectively. Likewise, the circumstances of Consumer A and B at 12:00 are denoted as A2 and B2, respectively.
As shown in
Figure 8, the EH construction-produced CCDF value of Consumer B is larger than that of Consumer A. That is because Consumer B has more cooling loads than Consumer A, which delivered more construction-produced carbon emissions of EH devices. Meanwhile, the energy structure is different during different periods. As shown in
Figure 8, the energy source operation-produced CCDF value at A1 is larger than that at A2. That is because the energy generation of renewable energy resources (e.g., solar power plants) is small while that of thermal plants is large at 00:00 than those at 12:00, as shown in
Figure 8b.
To verify the applicability and generality of the framework proposed in this paper, a more complex UMES is used for simulation. Compared with the original test system, the number of consumers with complicated energy usage habits has increased by five times. The carbon emission flow of this more challenging case can be successfully traced by the proposed method, and the calculation results are appended in
Figure 9. The results show that the carbon emissions of the gas system in this complex network are significantly higher than the power system because the EH is mainly responsible for the user’s energy demand in the complex system. Compared with the original system, the construction-produced carbon emissions of EH devices per unit of energy in the complex system are reduced. This is due to the higher frequency of use of EH devices, as introduced in
Section 2.2. Moreover, the total carbon emissions of users in this complex system drop. This is because the dependence of this complex system on natural gas has greatly increased compared to the original network. The results show that the framework proposed in this paper is universal for complex systems.