Next Article in Journal
Fractal Characterization of Nanopore Structure in Shale, Tight Sandstone and Mudstone from the Ordos Basin of China Using Nitrogen Adsorption
Previous Article in Journal
Equivalent Circuit Model Construction and Dynamic Flow Optimization Based on Zinc–Nickel Single-Flow Battery
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Finite Control Set Model Predictive Control for Parallel Connected Online UPS System under Unbalanced and Nonlinear Loads

Department of Electrical Engineering, Bahria University, Islamabad 44000, Pakistan
*
Author to whom correspondence should be addressed.
Energies 2019, 12(4), 581; https://doi.org/10.3390/en12040581
Submission received: 11 October 2018 / Revised: 19 November 2018 / Accepted: 20 November 2018 / Published: 13 February 2019
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
In this paper, the finite control set model predictive control (FCS–MPC) technique-based controller is proposed for the inverter of the uninterrupted power supply (UPS) system. The proposed controller uses the mathematical model of the system to forecast the response of voltage for each possible switching state for every sampling instant. Following this, the cost function was used to determine the switching state, applied to the next sampling instant. First, the proposed control strategy was implemented for the single inverter of the UPS system. Finally, the droop control strategy was implemented for parallel inverters to guarantee actual power sharing among a multiple-parallel UPS system. To validate the performance of the proposed controller under steady-state conditions and dynamic-transient conditions, extensive simulations were conducted using MATLAB/Simulink. The proposed work shows a low computational burden, good steady state performance, fast transient response, and robust results against parameter disturbances as compared to linear control. The simulation results showed that total harmonic distortion (THD) for the linear load was 0.9% and THD for the nonlinear load was 1.42%.

1. Introduction

With the advancement in modern communication systems, uninterrupted power to supply lifesaving medical equipment and data centers is required for critical load in all grid conditions. In order to operate this sensitive equipment, the reliable power requirement is a major challenge for engineers and researchers. Hence, uninterrupted power supply (UPS) is attracting much attention from both industry and research, so as to find new ways to meet the demand of these devices.
Generally, UPS systems provide regulated sinusoidal output voltage, with low total harmonic distortion, and fast transient response irrespective of the change in a load connected with the system. As per international electrotechnical commission (IEC) standards for UPS systems, all types of UPS system must satisfy the following conditions.
  • THD of inverter’s output voltage is less than 4% under all loading conditions.
  • Voltage drop is not more than 5% under all loading conditions.
  • The inverter provides constant output root mean square (RMS) voltage, irrespective to disturbance or variation in system parameters such as temperature, load current, etc. [1]
The UPS system is classified into three categories, offline, line interactive, and online UPS.
Of these three categories, online UPS systems are famous for both high power and voltage applications. Online UPS systems provide strong tolerance to overcome the variations in grid frequency, system voltage, and power issues. Moreover, online UPS systems also provide isolation to load from the polluted grid. Online UPS consists of a controlled rectifier, an inverter, and a static switch as demonstrated in Figure 1 [2]. Under the normal mode of operation, the rectifier maintains regulated DC-link voltage, whilst also charging the battery bank of the UPS. The inverter converts the DC-link voltage into regulated AC to maintain the load demand. During a grid outage mode of operation, the AC grid is disconnected through the circuit breaker However, the inverter continues to supply power to load from the battery without any interruption. The inverter of the online UPS remains active in both modes of operation.
Usually, UPS systems feed critical loads that cannot afford power failure. Therefore, it is necessary to fulfill the growing demand without upgrading the existing UPS system. Thus, the parallel UPS system operation is the most effective solution to provide continuous power to load, enhance system stability, lower the maintenance cost, and increase system capacity. It is for these reasons that many control schemes have been proposed for parallel operations of the inverter in the literature, such as, centralized control [3], master–slave control [4], average load sharing [5], etc. However, the above-mentioned control schemes require an intercommunication network between the inverters for coordination.
Using a communication network decreases the reliability and increases the complexity of the system. Therefore, communication less control methods, such as droop control, are used to regulate power sharing among UPSs. Several types of droop control are reviewed in [6]. The objectives of droop control in UPS systems are power sharing between parallel-connected inverters in UPS, and stabilizing the voltage and frequency at the AC bus.
Research has been performed on linear control, deadbeat control [7,8], robust control [9,10], slide mode control [11] etc. [12]. Linear control schemes such as proportional-integral (PI), proportional-resonant (PR), and proportional-integral-derivative (PID) are frequently implemented for the inverter in UPS systems. However, this system inherits major practical limitations, such as tuning of parameters, poor transient response, and poor tracking of the sinusoidal reference. In [13], a feedback linearization control was proposed for a three-phase UPS system and the nonlinear behavior of the system was used to achieve low voltage THD. Consequently, it is not easy to implement this technique due to the computation complexities.
In nonlinear controls, The deadbeat controller has widely been implemented for UPS systems [7]. Deadbeat control puts all system poles at zero. Hence, tracking errors are equal to zero in small sampling instants, therefore giving the fastest transient response. However, one major disadvantage includes parameter variations and external disturbance. Further control schemes, based on nonlinear control theory, have been proposed in [14,15,16]. In these, the authors proposed the control scheme for cell divisions in nervous systems as asymmetry and symmetry [14]. In [15] a fuzzy based proportional-integral (PI-FC) controller was developed to control the class of a servo system. A new stable Takagi–Sugeno fuzzy control developed for the process model and matrices gain has been achieved by a swarm optimization algorithm in [16]. On the other hand, digital robust control approaches, such as hysteresis control, can handle system uncertainties and give an optimal tradeoff between performance and stability [10]. However, the mathematical modeling and implementation on digital platforms is quite complex. As compared to a classic controller, slide mode control (SMC) has optimal performance, robustness against parameter variations, and excellent dynamic response under different load operations. However, the practical limitation of SMC includes chattering phenomena, a complex mathematical approach, and high switching losses [17]. The learning based controls, such as neural network control [18], repetitive control [19], and interactive learning control [20] are able to improve the steady-state performance of the controller. Yet, these controllers have slowed dynamic response and consume a significant amount of time in learning algorithm. Therefore, the hybrid control technique is normally used for implementation, as highlighted in [18,20].
Model predictive control (MPC) is a type of non-linear, digital, and advanced control technique. Predictive controllers use the system mathematical model to envisage future responses and generate optimal control action according to predefined optimized standard. MPC has attracted the attention of researchers because it can handle a multivariable system, has a fast-dynamic response, and can incorporate system constraints into control law in a simple manner. Moreover, it can also integrate nested control loops in a single loop, has high delay controlling ability, and shows robustness against system parameter variations [21,22].
In [23] a new algorithm for model predictive direct power control has been proposed for AC/DC active rectifiers. The proposed scheme can control rectifier power and reduce its switching losses. A modified model predictive current control had been proposed in [24]. The researcher of this study attempted to reduce the spread spectrum by adding a filter to the variables that are evaluated by the cost function. The results of this highlighted that such a process helps in reducing the switching losses and lessens system harmonics. Similarly, in [25] the authors proposed predictive power control for a battery storage system and compared thus with PI linear control. MPC was shown to have good results and performance as compared to conventional PI control. In [26,27] the authors developed a tool for the analysis of predictive current control (PCC) based on the locus of a reduced set of performance indices, and highlighted the comparison between the common PCC approach. The issues that occur due to long prediction horizon in FCS–MPC has been comprehensively examined in [28], in terms of harmonic content, but the major complication with long receding horizon is computational complexity. Voltage MPC has been proposed for a four leg inverter but its THD in voltage has been shown to be more than 3%, which is above the legal limit accepted by the some European countries [29]. In [30] an observer-based voltage model predictive control (VMPC) was proposed for UPS applications in which the system cost is reduced but its performance is not adequate in terms of THD and steady-state error. In [31] an implicit MPC was developed for VSI with LC filters in an islanded mode. But this technique showed susceptibility to system external uncertainties and parametric variation. Moreover, this system required more computational burden as compared to other MPC based approaches. It measured the filter and load current instead of estimation, which may have increased the system cost due to the use of sensors. However, the MPC has not been thoroughly investigated for the parallel operation of the inverter in UPS applications.
This paper investigates the FCS–MPC control scheme for the inverter of UPS system and parallel operation of the UPS to feed a common AC load. The proposed control scheme used the system mathematical model to forecast the future behavior of the system for all possible switching states at the corresponding sampling instant. Following this, a cost function was conducted to find the optimal action, which was then applied to the next sampling instant. For the reduction of inverter switching frequency, a two-step prediction horizon-based cost function (CF) was employed. Droop control was also implemented for accurate power sharing among the inverters of the UPS system. Real-time simulation was conducted in MATLAB/Simulink to show the robustness and effectiveness of the controller so as to maintain system power quality under linear and nonlinear loading conditions.
The remaining sections of the paper are organized as follows: In Section 2, the proposed system is described and the comprehensive mathematical model of two-level voltage source inverter (VSI) with linked LC filter is proposed. Following this, a discussion of the required discretization aspects, for FCS–MPC implementation is presented. In Section 3, the operating principle of FCS–MPC and the working of the proposed controller is explained. In Section 4, for the parallel operation of inverters, droop control is proposed, and its limitations are discussed. Detailed simulation results with linear control are discussed and compared in Section 5. Finally, Section 6 provides the conclusion.

2. Description and Mathematical Modelling of System

A cluster of parallel-connected inverters in the UPS system is illustrated in Figure 2. For system modeling, a single inverter, along with its LC filter, is considered, as shown in Figure 3. Accurate mathematical modeling of both inverter and filter are required to achieve good performance of the controller. v p c is the output voltage at PCC, i 0 is output current of the inverter, L f is filter inductance, C f is filter capacitance, and v d c is capacitor DC link voltage. Similarly, S x ,   S y ,   S z are the legs of the converter. The inverter considered in this paper, is two-level voltage source inverters (2L-VSI) and its circuit diagram is demonstrated in Figure 3. However, the harmonics generated by 2L-VSI are reduced by the LC filter.
Though modeling of VSI has been shown to be realized in any frame of reference [32], VSI modeling in an αβ frame of reference was performed in this paper. In order to implement the proposed control schemes, the following assumptions were made i.e., the system conditions were balanced, and zero sequence components were neglected. By using the Clark transformation, all the state variables, such as three-phase voltages and currents were transformed into the stationary frame of reference.
v ¯ = v α + j v β = T ¯ [ v x , v y , v z ]
i ¯ = i α + j i β = T ¯ [ i x , i y , i z ]
where
T ¯ = 1 3 [ 1 e j 2 3 π 1 e j 4 3 π ]
The switching arrangements of VSI are presented in Figure 4a. S x , S y , S z are the three gating pulses given to the corresponding legs of VSI. Each leg has two possible states i.e., 0 or 1 and expressed in Equations (4) to (6):
S x = { 1 ,   if   Q 1   is   ON   and   Q 4   is   OFF 0 , if   Q 1 is   OFF   and   Q 4   is   ON }
S y = { 1 ,   if   Q 2   is   ON   and   Q 5   is   OFF 0 , if   Q 2 is   OFF   and   Q 5   is   ON }
S z = { 1 ,   if   Q 3   is   ON   and   Q 6   is   OFF 0 , if   Q 3 is   OFF   and   Q 6   is   ON }
Two level VSI has a possible eight ( 2 3 ) voltage vectors. The output voltage of inverter legs can be determined by taking the product of the state of the respective leg and dc link voltage.
v x N = S x · v d c v y N = S y · v d c v z N = S z · v d c
Common mode voltage V n N can be found by using Kirchhoff’s voltage law:
V n N = v x N + v y N + v z N 3
Inverter phase voltage can be calculated through the following equation:
v x n = v x N v n N v y n = v y N v n N v z n = v z N v n N
Table 1, explains the position of all possible voltage vectors in the αβ frame. v 0 and v 7 are zero vector and lie at the origin.

2.1. LC Filter Modelling

As shown in Figure 3, a three-phase LC filter was connected at the output terminal of VSI. As previously mentioned, the LC filter was used to attenuate the switching harmonics. Each filter consists of an inductor L f and ESR resistance R f , with current i f flowing through it. Similarly, a capacitor C f with voltage v p c is connected in parallel to the load. i f and v p c were used as the state variables in this system. The block diagram of an LC filter model is shown in Figure 4b. Filter model’s dynamics can be explained by Equations (10) and (11), one describes the inductance behavior and other explains the capacitance behavior. Filter current equation is expressed as:
L f d i f d t = v t v p c i f R f
where v t is the possible voltage vectors taken from Table 1. Dynamic response of capacitor voltage is expressed as follows:
C f d v p c d t = i f i 0
where i 0 represents output current. Equation (10) and Equation (11) can be rewritten in state space form as Equation (12):
d d [ i f v p c ] = A [ i f v p c ] + B [ v t i 0 ]
Here,
A = [ R f L f 1 C f 1 C f 0 ]
and
B = [ 1 L f 0 0 1 C f ]
Equations (12) to (14) present the complete continuous state space (CSS) model of LC filter, which has two inputs i.e., voltage vector v t ,which is defined in Table 1 and output current i 0 .

2.2. Discrete Time Domain Modelling

For the practical implementation of a CSS model on the digital control system, it is necessary to convert the CSS model into a discrete time model. Among discretization techniques, in this paper, zero-order hold (ZOH) method is deployed because it gives the precise conversion of the CSS model to discrete time state space model at sampling instants of staircase inputs.
It is assumed that the value of v d c is constant and model in the discrete time domain as expressed in Equation (15):
[ i f ( t k + 1 ) v p c ( t k + 1 ) ] = A d [ i f ( t k ) v p c ( t k ) ] + B d [ v t ( t k ) i 0 ( t k ) ]
A d = e A T s
B d = 0 T s e A τ   B   d τ
T s is the sampling instant. Equation (14) is used to calculate the voltage and current for two step receding horizons.

3. Operating Principle of FCS–MPC

FCS–MPC is proposed in this paper for the voltage control of an inverter in the UPS system as demonstrated in Figure 5. The basic principle of voltage MPC is as follows,
  • In the start of each sampling time, v p c , i f and i 0 are measured through sensors.
  • The information is sent to the algorithm, it is defined by the initial point from where the algorithm forecasts the future behavior of controlled variables using Equation (14), for all possible voltage vectors.
  • These predicted values are used to find the predefined cost functions (CF) and a voltage vector that has a minimal value of CF as applied to VSI.
A flowchart of the VMPC algorithm is shown in Figure 6. Designing a cost function (CF) in FCS–MPC is fundamental. CF permits to solve multi-objective problems and can be defined as:
g G e n = i = t k t k + N 1 v f e ( i ) 2 2 + h l i m ( i ) + λ u s w 2 ( i )
v f e ( i ) is predicted tracking error, h l i m ( i ) is current limit constraint, s w 2 ( i ) is a term used to reduce the switching frequency and can be controlled by weighting factor λ u . The term used in Equation (18) can be stated as:
v f e ( i ) = v f ( i ) v f ( i )
h l i m ( i ) = { 0 , i f | i f ( i ) | i m a x , i f | i f ( i ) | > i m a x
s w ( i ) = | u ( i ) u ( i 1 ) |
CF used in this paper is defined in Equation (22) and is a generalized form of Equation (18) with N = 2 and has no secondary objective. Its basic function is to minimize the Euclidean distance at each sampling time. In this paper, cost function defines the desired system behavior and is expressed as follows:
g v = ( v ( p c ) α ( t k + 2 ) v ( p c ) α ( t k + 2 ) ) 2 + ( v ( p c ) β ( t k + 2 ) v ( p c ) β ( t k + 2 ) ) 2
v ( p c ) α and v ( p c ) β are real and imaginary parts of output voltage reference at t k + 2 instant, taken from droop control. v ( p c ) α and v ( p c ) β are predicted output voltage at t k + 2 instant. This cost function delivers a minimum voltage error and it also reduces the switching frequency of VSI, The method used in this paper for switching frequency reduction is found in [33]. There is the possibility to add additional constraints, such as current limitations etc. However, by adding these constraints, the tuning of weight coefficients creates an issue and deteriorates the controller performance.

Switching Frequency Reduction Scheme

In a UPS system, the inverter is used to interface the battery bank with the output load in order to feed the critical load. Thus, switching frequency can play a key role in decreasing loss and is associated with low frequency and vice versa. In this case, a two-step reduction technique was employed in order to obtain the low switching frequency. In a one-step sampling case, there are eight vectors exploited for one sampling period. To evaluate the prediction horizon N = 2, two voltage vectors were considered, such as one voltage vector was applied during the first sampling period, and another vector was applied during second sampling period. The total possible sequences of the voltage vector (72) is shown in Figure 7b. It shows that the total possible voltage vector sequences are 49, which requires a large amount of calculations, hence the increase in the computational burden and control accuracy.
In order to overcome the above-mentioned issue, the two-steps prediction was accomplished. For the first and second sampling period, the same voltage vector was applied [33]. Moreover, in two-step prediction, only seven voltage vectors are employed, as shown in Figure 7c. This technique showed similar performance, but it had less switching frequency. Equation (15) can be used to predict the voltage up to ( t k + 2 ). In other words, for a two sampling instant, all eight possible voltage vector can be used sequentially. This technique also reduced the switching frequency of VSI and voltage ripple.

4. Droop Control

Generally, UPS systems are used to deliver power to sensitive loads, which cannot bear a surge or spike of voltage and power outage. Therefore, it is essential to overcome the growing load demand by upgrading the present UPS system. However, such upgrades increase system cost and the only solution to overcome the above-described problem, is to operate the UPS system in parallel. A parallel connected UPS system increases the system stability in terms of continuous power supply to load, in spite of any disruption and also fulfills system requirements, lowers the cost, and increases the system reliability. In a parallel-connected UPS system, the major task is to achieve accurate and precise active and reactive power sharing amongst the VSI’s. To connect several inverters in parallel without any intercommunication, the droop control is the best choice [34]. Fundamentally, the basic idea of droop control is based on instantaneous power theory. Active power can be calculated by phasor or power angle and reactive power Q is based on voltage amplitude difference. Normally, a droop approach is used for sharing the load among the parallel operating generators in a conventional power system based on droop curve characteristics as demonstrated in Figure 8, according to their output impedances.
Droop control uses the frequency and amplitude of inverter voltage to regulate the active and reactive power. Droop control can be expressed as follows:
V r e f = V n o m k q Q c a l
f r e f = f n o m k p P c a l
where, V r e f and f r e f are reference voltage amplitude and frequency used to synthesis the V ( r e f ) α β . V n o m and f r e f are nominal voltage amplitude and frequency at the point of common coupling. Following equations are used to calculate the P c a l and Q c a l as:
P c a l = v p c , α i 0 , α + v p c , β i 0 , β
Q c a l = v p c , β i 0 , α v p c , α i 0 , β
Power, as determined by Equations (25) and (26), is fed to low pass filter in order to mitigate the oscillations. However, it shows slow response during load transients. k q and k p are voltage and frequency droop coefficients. There is a tradeoff between droop coefficients and voltage regulation i.e., increasing the droop coefficients will result in accurate power-sharing but deprive the voltage regulation. The droop coefficients also determine the slope of droop curves. Droop coefficients are defined as:
k q = Δ V Q m a x
k p = Δ f P m a x
Δ V and Δ f are the extreme allocated divergence of voltage and frequency. Q m a x and P m a x are nominal active and reactive power delivered by the system. Usually, inductive based output impedance is considered where larger inductors filter is used. Yet, in a low-voltage system, resistive based droop is used because line impedance is resistive in nature. Comparisons between droop are expressed in the Table 2. Figure 9 shows the block diagram of droop control used in this paper.

5. Results

In order to validate the performance of the proposed controller for UPS system, extensive simulations have been performed for both single and parallel-operated inverters (VSI) using MATLAB/Simulink. Figure 10 presents the system under study in this paper. Parameters for the test system are given in Table 3.
The filter design procedure in an FCS–MPC regulated UPS system has not been clearly developed. Hence, its parameters are found in a similar way as reported in the literature [35].
Different simulation cases have been carried out to show the robustness and performance of the proposed controller. First, steady state simulation for a single inverter was conducted to verify the performance of the proposed controller under sinusoidal voltage reference. Following this, a transient response, step change of load, and system response under nonlinear load was investigated. The results showed that the system maintained high robustness and stability. Finally, two inverters were operated in parallel with the proposed controller. A proper power-sharing model was attained by using droop control and respective power-sharing was verified.

5.1. Steady State Analysis

Figure 11 demonstrates the voltage and output current waveforms of the single inverter in the UPS system under linear RL balanced load. During operation, 18 kW active and 7 kvar reactive power was supplied to the load through an inverter. The reference of voltage amplitude and frequency was set to 318 V and 60 Hz. Output voltage and current waveforms were sinusoidal with low harmonic distortions. The performance of the designed controller, in term of THD, was compared with the standard literature [31]. The output voltage THD, in case of [31], was observed as 2.93%. However, in the proposed FCS–MPC scheme, the THD of the output voltage was 0.95%, which was much less than IEC standards for the UPS system.

5.2. Load Transient Analysis

The load transient analysis was performed to examine the transient recovery time and overshoot of magnitude of current and voltage under load changing from no load to full load and vice versa. Here, an 18-kW active load and the 7 kvar reactive load were connected. Figure 12 shows the transient behavior of the system under step change in load from 100% to 0% and 0% to 100%. At time t = 0.1 s, the total load was disconnected from the system and at t = 0.12 s the full load was connected back to the system. As can be seen from the Figure 12 output current of the system varied according to load. However, output voltage of the system was slightly distorted during transients and returned to steady state within no time. Figure 13 shows the RMS output voltage graph. It shows a voltage spike at time t = 0.1 s when the load was disconnected from AC bus. The maximum value of the spike was nearly 260 V, which was under the specifications of the switches.
The proposed controller was also tested for the nonlinear loading condition as. This test was performed as a UPS system supply power to the nonlinear load in the emergency mode of operation. Figure 14 represents output voltage and load current under nonlinear load. It was observed that the voltage waveform was still sinusoidal with very small harmonic distortion despite the distorted load current. THD of output voltage waveform was 1.42%, which was under the IEC62040-3.
Figure 15 shows controller performance for a step change in load where at t = 0.12 s, the load was instantaneously doubled to the rated load. However, within no time, the voltage became stable and remained sinusoidal with low harmonic distortion.
Figure 16 and Figure 17 show the voltage and current waveform of MPC and PI controller under different loading conditions, respectively. As shown in Figure 16, at t = 0.05 s the unbalanced load was energized, and the proposed controller almost eliminated the imbalance in voltage while in case of PI controller, voltage remained unbalanced. Figure 16a,b illustrate the current and voltage waveform under linear and unbalanced loads when MPC is employed. Table 4 presents the comparison between PI and proposed MPC in term of %THD in voltage under different loads.
At t = 0.05 s, the nonlinear load was energized while the unbalanced load was switched off. It was observed in Figure 18b and Figure 19b that the current becomes distorted due to nonlinear load. Figure 18 shows that the PI controller was ineffective to suppress the harmonics in voltage. But, the proposed MPC removed the harmonic distortion in output voltage as demonstrated in Figure 19a.
Table 5 expresses the comparison among the different control techniques. The proposed controller harmonics rejection capability was quite effective, and its performance was far superior as compared to the other controllers.

5.3. Multiple UPS Systems

Two or more inverters were connected in a UPS system to increase the system reliability and decreases the system cost. Therefore, in this subsection, the proposed controller was tested for the parallel-connected UPS operation. Conventional droop control was used for proper load sharing among parallel inverters of the respective UPS systems. At time t = 0.03 s, the load on the system was instantaneously doubled, both the VSIs increased their power generation to fulfill the load demand. Figure 20 illustrates the output voltage and load current of VSI1 and VSI2. It was observed that at t = 0.03 s, increased in demand the load was fulfilled by both inverters and the voltage remained stable. Power sharing between the inverters is shown in Figure 21 where 36 kW active and 16 kvar reactive power were equally shared among the VSI’s.
To verify the proposed system performance during single UPS fault, hot-swap operation was performed, as shown in Figure 22. At t = 0.1 s, VSI2 was disconnected from the system due to an external fault. It can be noticed that VSI1 instantly increased its power generation to fulfill the load demand. Quality of voltage and current remained stable despite the transition period when VSI2 was isolated from the system. Figure 23 represents the active and reactive power provided by the inverter modules in the UPS system.

6. Conclusions

In this paper, an FCS–MPC control scheme is presented for a 2 L three-phase inverter with output LC filter. Furthermore, this paper highlighted the possible implementation of parallel inverters in a UPS system. The proposed controller had no parameters to adjust, requiring a model of the system for calculating predictions of the controlled variables. The gate-drive signals were generated directly by the controller, so a modulator was not needed. The output voltage was directly controlled, without using a cascaded control structure. The performance of the proposed predictive controller was demonstrated by implementing it in the MATLAB/Simulink environment. Simulation results showed that the proposed scheme achieved a good voltage regulation with linear and nonlinear loads. Results were compared with other MPC controllers. The proposed controller showed exemplary results with a considerable reduction in the THD of the system. Droop control was implemented for power sharing among the inverters. It showed accurate power sharing in both steady state and transient conditions. The proposed FCS–MPC showed excellent performance in dynamic steady state, transients conditions, and hot-swap operation of the system.

Author Contributions

H.S.K. studied the literature review and found the research gap, performed the simulation work, and wrote the paper. M.A. helped in controller stability analysis. A.W. and S.U.A. actively contributed to the arrangement and format of the paper. J.I. helped to revise the paper. M.A. supervised this research work.

Funding

This research received no external funding.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Aamir, M.; Kalwar, K.A.; Mekhilef, S. Uninterruptible power supply (UPS) system. Renew. Sustain. Energy Rev. 2016, 58, 1395–1410. [Google Scholar] [CrossRef]
  2. Zhang, C.; Guerrero, J.M.; Vasquez, J.C.; Coelho, E.A.A. Control architecture for parallel-connected inverters in uninterruptible power systems. IEEE Trans. Power Electron. 2016, 31, 5176–5188. [Google Scholar]
  3. Guerrero, J.M.; Hang, L.; Uceda, J. Control of distributed uninterruptible power supply systems. IEEE Trans. Ind. Electron. 2008, 55, 2845–2859. [Google Scholar] [CrossRef]
  4. Cheng, Y.J.; Sng, E.K.K. A novel communication strategy for decentralized control of paralleled multi-inverter systems. IEEE Trans. Power Electron. 2006, 21, 148–156. [Google Scholar] [CrossRef]
  5. Sun, X.; Lee, Y.-S.; Xu, D. Modeling, analysis, and implementation of parallel multi-inverter systems with instantaneous average-current-sharing scheme. IEEE Trans. Power Electron. 2003, 18, 844–856. [Google Scholar]
  6. Tayab, U.B.; Roslan, M.A.B.; Hwai, L.J.; Kashif, M. A review of droop control techniques for microgrid. Renew. Sustain. Energy Rev. 2017, 76, 717–727. [Google Scholar] [CrossRef]
  7. Mattavelli, P. An improved deadbeat control for UPS using disturbance observers. IEEE Trans. Ind. Electron. 2005, 52, 206–212. [Google Scholar] [CrossRef]
  8. Kawabata, T.; Miyashita, T.; Yamamoto, Y. Dead beat control of three phase PWM inverter. IEEE Trans. Power Electron. 1990, 5, 21–28. [Google Scholar] [CrossRef]
  9. Yang, S.; Lei, Q.; Peng, F.Z.; Qian, Z. A robust control scheme for grid-connected voltage-source inverters. IEEE Trans. Ind. Electron. 2011, 58, 202–212. [Google Scholar] [CrossRef]
  10. Willmann, G.; Coutinho, D.F.; Pereira, L.F.A.; Líbano, F.B. Multiple-loop H-infinity control design for uninterruptible power supplies. IEEE Trans. Ind. Electron. 2007, 54, 1591–1602. [Google Scholar] [CrossRef]
  11. Komurcugil, H. Rotating-sliding-line-based sliding-mode control for single-phase UPS inverters. IEEE Trans. Ind. Electron. 2012, 59, 3719–3726. [Google Scholar] [CrossRef]
  12. Marwali, M.N.; Dai, M.; Keyhani, A. Robust stability analysis of voltage and current control for distributed generation systems. IEEE Trans. Energy Convers. 2006, 21, 516–526. [Google Scholar] [CrossRef]
  13. Kim, D.-E.; Lee, D.-C. Feedback linearization control of three-phase UPS inverter systems. IEEE Trans. Ind. Electron. 2010, 57, 963–968. [Google Scholar]
  14. Lu, B.; Jan, L.; Jan, Y.-N. Control of Cell Divisions in the Nervous System: Symmetry and Asymmetry. Annu. Rev. Neurosci. 2000, 23, 531–556. [Google Scholar] [CrossRef] [PubMed]
  15. Precup, R.-E.; Preitl, S.; Korondi, P. Fuzzy controllers with maximum sensitivity for servosystems. IEEE Trans. Ind. Electron. 2007, 54, 1298–1310. [Google Scholar] [CrossRef]
  16. Vrkalovic, S.; Teban, T.-A.; Borlea, I.-D. Stable Takagi-Sugeno fuzzy control designed by optimization. Int. J. Artif. Intell. 2017, 15, 17–29. [Google Scholar]
  17. Kukrer, O.; Komurcugil, H.; Doganalp, A. A three-level hysteresis function approach to the sliding-mode control of single-phase UPS inverters. IEEE Trans. Ind. Electron. 2009, 56, 3477–3486. [Google Scholar] [CrossRef]
  18. Kang, H.-K.; Yoo, C.H.; Chung, I.Y.; Won, D.J.; Moon, S.I. Intelligent coordination method of multiple distributed resources for harmonic current compensation in a microgrid. J. Electr. Eng Technol. 2012, 7, 834–844. [Google Scholar] [CrossRef]
  19. Jiang, S.; Cao, D.; Li, Y.; Liu, J.; Peng, F.Z. Low-THD, fast-transient, and cost-effective synchronous-frame repetitive controller for three-phase UPS inverters. IEEE Trans. Power Electron. 2012, 27, 2994–3005. [Google Scholar] [CrossRef]
  20. Lu, W.; Zhou, K.; Wang, D.; Cheng, M. A general parallel structure repetitive control scheme for multiphase DC–AC PWM converters. IEEE Trans. Power Electron. 2013, 28, 3980–3987. [Google Scholar] [CrossRef]
  21. Cortes, P.; Wilson, A.; Kouro, S.; Rodriguez, J.; Abu-Rub, H. Model predictive control of multilevel cascaded H-bridge inverters. IEEE Trans. Ind. Electron. 2010, 57, 2691–2699. [Google Scholar] [CrossRef]
  22. Yaramasu, V.; Wu, B. Predictive control of a three-level boost converter and an NPC inverter for high-power PMSG-based medium voltage wind energy conversion systems. IEEE Trans. Power Electron. 2014, 29, 5308–5322. [Google Scholar] [CrossRef]
  23. Kwak, S.; Park, J.-C. Model-predictive direct power control with vector preselection technique for highly efficient active rectifiers. IEEE Trans. Ind. Inform. 2015, 11, 44–52. [Google Scholar] [CrossRef]
  24. Cortés, P.; Rodríguez, J.; Quevedo, D.E.; Silva, C. Predictive current control strategy with imposed load current spectrum. IEEE Trans. Power Electron. 2008, 23, 612–618. [Google Scholar] [CrossRef]
  25. Nguyen, T.-T.; Yoo, H.-J.; Kim, H.-M. Application of model predictive control to BESS for microgrid control. Energies 2015, 8, 8798–8813. [Google Scholar] [CrossRef]
  26. Arahal, M.R.; Barrero, F.; Durán, M.J.; Ortega, M.G.; Martín, C. Trade-offs analysis in predictive current control of multi-phase induction machines. Control Eng. Pract. 2018, 81, 105–113. [Google Scholar] [CrossRef]
  27. Lim, C.S.; Levi, E.; Jones, M.; Rahim, N.A.; Hew, W.P. FCS-MPC-based current control of a five-phase induction motor and its comparison with PI-PWM control. IEEE Trans. Ind. Electron. 2014, 61, 149–163. [Google Scholar] [CrossRef]
  28. Arahal, M.R.; Barrero, F.; Ortega, M.G.; Martin, C. Harmonic analysis of direct digital control of voltage inverters. Math. Comput. Simul. 2016, 130, 155–166. [Google Scholar] [CrossRef]
  29. Yaramasu, V.; Rivera, M.; Narimani, M.; Wu, B.; Rodriguez, J. Model predictive approach for a simple and effective load voltage control of four-leg inverter with an output LC filter. IEEE Trans. Ind. Electron. 2014, 61, 5259–5270. [Google Scholar] [CrossRef]
  30. Cortés, P.; Ortiz, G.; Yuz, J.I.; Rodríguez, J.; Vazquez, S.; Franquelo, L.G. Model predictive control of an inverter with output $ LC $ filter for UPS applications. IEEE Trans. Ind. Electron. 2009, 56, 1875–1883. [Google Scholar] [CrossRef]
  31. Nauman, M.; Hasan, A. Efficient implicit model-predictive control of a three-phase inverter with an output LC filter. IEEE Trans. Power Electron. 2016, 31, 6075–6078. [Google Scholar] [CrossRef]
  32. Vazquez, S.; Leon, J.I.; Franquelo, L.G.; Carrasco, J.M.; Dominguez, E.; Cortes, P.; Rodriguez, J. Comparison Between FS-MPC Control Strategy for an UPS inverter application in α-β and abc frames. In Proceedings of the 2010 IEEE International Symposium on Industrial Electronics (ISIE), Bari, Italy, 4–7 July 2010. [Google Scholar]
  33. Hu, J.; Zhu, J.; Dorrell, D.G. Model predictive control of grid-connected inverters for PV systems with flexible power regulation and switching frequency reduction. IEEE Trans. Ind. Appl. 2015, 51, 587–594. [Google Scholar] [CrossRef]
  34. Zhong, Q.-C. Robust droop controller for accurate proportional load sharing among inverters operated in parallel. IEEE Trans. Ind. Electron. 2013, 60, 1281–1290. [Google Scholar] [CrossRef]
  35. Leon, J.I.; Kouro, S.; Franquelo, L.G.; Rodriguez, J.; Wu, B. The essential role and the continuous evolution of modulation techniques for voltage-source inverters in the past, present, and future power electronics. IEEE Trans. Ind. Electron. 2016, 63, 2688–2701. [Google Scholar] [CrossRef]
  36. Loh, P.C.; Newman, M.J.; Zmood, D.N.; Holmes, D.G. A comparative analysis of multiloop voltage regulation strategies for single and three-phase UPS systems. IEEE Trans. Power Electron. 2003, 18, 1176–1185. [Google Scholar]
  37. Hasanzadeh, A.; Onar, O.C.; Mokhtari, H.; Khaligh, A. A proportional-resonant controller-based wireless control strategy with a reduced number of sensors for parallel-operated UPSs. IEEE Trans. Power Deliv. 2010, 25, 468–478. [Google Scholar] [CrossRef]
Figure 1. Block diagram of the online uninterrupted power system (UPS).
Figure 1. Block diagram of the online uninterrupted power system (UPS).
Energies 12 00581 g001
Figure 2. Parallel connected online UPS system.
Figure 2. Parallel connected online UPS system.
Energies 12 00581 g002
Figure 3. Two level three phase VSI.
Figure 3. Two level three phase VSI.
Energies 12 00581 g003
Figure 4. (a) Possible voltage vector of 2L-VSI respective to Table 1. (b) Equivalent filter model in the stationary reference frame.
Figure 4. (a) Possible voltage vector of 2L-VSI respective to Table 1. (b) Equivalent filter model in the stationary reference frame.
Energies 12 00581 g004
Figure 5. Block diagram of finite control set model predictive control (FCS–MPC) technique for UPS system along with droop control.
Figure 5. Block diagram of finite control set model predictive control (FCS–MPC) technique for UPS system along with droop control.
Energies 12 00581 g005
Figure 6. Flowchart of the V-MPC algorithm.
Figure 6. Flowchart of the V-MPC algorithm.
Energies 12 00581 g006
Figure 7. Vector representation of switching frequency. (a) N = 1 (b) N = 2 taking different voltage vectors during each sampling instant. (c) N = 2 taking same voltage vectors during two-sampling instants.
Figure 7. Vector representation of switching frequency. (a) N = 1 (b) N = 2 taking different voltage vectors during each sampling instant. (c) N = 2 taking same voltage vectors during two-sampling instants.
Energies 12 00581 g007
Figure 8. Droop control approach for a parallel UPS system (a) Resistive based impedance (b) Inductive based Impedance.
Figure 8. Droop control approach for a parallel UPS system (a) Resistive based impedance (b) Inductive based Impedance.
Energies 12 00581 g008
Figure 9. Block diagram of droop control.
Figure 9. Block diagram of droop control.
Energies 12 00581 g009
Figure 10. Block diagram of proposed test system.
Figure 10. Block diagram of proposed test system.
Energies 12 00581 g010
Figure 11. Voltage and Load current waveforms under linear RL load conditions.
Figure 11. Voltage and Load current waveforms under linear RL load conditions.
Energies 12 00581 g011
Figure 12. Voltage and current during step change of load.
Figure 12. Voltage and current during step change of load.
Energies 12 00581 g012
Figure 13. RMS voltage at AC bus.
Figure 13. RMS voltage at AC bus.
Energies 12 00581 g013
Figure 14. Output voltage and load current waveforms under nonlinear load.
Figure 14. Output voltage and load current waveforms under nonlinear load.
Energies 12 00581 g014
Figure 15. Output voltage and load current waveforms under load transient conditions.
Figure 15. Output voltage and load current waveforms under load transient conditions.
Energies 12 00581 g015
Figure 16. (a) Current waveform (b) voltage waveform under linear and unbalanced loads when MPC is employed.
Figure 16. (a) Current waveform (b) voltage waveform under linear and unbalanced loads when MPC is employed.
Energies 12 00581 g016
Figure 17. Current and voltage waveform under linear and unbalanced loads when PI is employed.
Figure 17. Current and voltage waveform under linear and unbalanced loads when PI is employed.
Energies 12 00581 g017
Figure 18. Current and voltage waveform under unbalanced and nonlinear loads when PI is employed.
Figure 18. Current and voltage waveform under unbalanced and nonlinear loads when PI is employed.
Energies 12 00581 g018
Figure 19. (a) Voltage waveform; (b) Current waveform under unbalanced and nonlinear loads when MPC is employed.
Figure 19. (a) Voltage waveform; (b) Current waveform under unbalanced and nonlinear loads when MPC is employed.
Energies 12 00581 g019
Figure 20. Waveform output voltage and load current of VSI1 and VSI2.
Figure 20. Waveform output voltage and load current of VSI1 and VSI2.
Energies 12 00581 g020
Figure 21. Active and reactive power sharing amongst the VSI1 and VSI 2 along with RL load.
Figure 21. Active and reactive power sharing amongst the VSI1 and VSI 2 along with RL load.
Energies 12 00581 g021
Figure 22. Simulation results of output voltage and current waveforms during UPS2 when isolated from the test system.
Figure 22. Simulation results of output voltage and current waveforms during UPS2 when isolated from the test system.
Energies 12 00581 g022
Figure 23. Simulation results of active and reactive power waveforms during UPS2 is isolated from the test system.
Figure 23. Simulation results of active and reactive power waveforms during UPS2 is isolated from the test system.
Energies 12 00581 g023
Table 1. Switching arrangement of 2L-VSI.
Table 1. Switching arrangement of 2L-VSI.
Space VectorSwitching VectorOn-State SwitchVector Placing
Zero vector v 0 , 7 [ P P P ] Q 1 , Q 3 , Q 5 v 0 = 0
v 7 = 0
[ O O O ] Q 4 , Q 6 , Q 2
Active vector v 1 [ P O O ] Q 1 , Q 4 , Q 6 v 1 = 2 3 v d c
v 2 [ P P O ] Q 1 , Q 3 , Q 6 v 2 = 1 3 v d c + j 3 3 v d c
v 3 [ O P O ] Q 2 , Q 3 , Q 6 v 3 = 1 3 v d c + j 3 3 v d c
v 4 [ O P P ] Q 2 , Q 3 , Q 5 v 4 = 2 3 v d c
v 5 [ O O P ] Q 2 , Q 4 , Q 5 v 5 = 1 3 v d c j 3 3 v d c
v 6 [ P O P ] Q 1 , Q 4 , Q 5 v 6 = 1 3 v d c j 3 3 v d c
Table 2. Comparison between resistive and inductive impedance-based droop control.
Table 2. Comparison between resistive and inductive impedance-based droop control.
Output Impedance Z = jX   ( Inductive   = 90 ° ) Z = R   ( Resistive   = 90 ° )
Active Power P = E V X s i n E V X P = E V c o s V 2 R V R ( E V )
Reactive Power Q = E V c o s V 2 X V X ( E V ) Q = E V R s i n E V R
Frequency Droop ω = ω k P P ω = ω + k P Q
Amplitude Droop E = E k Q Q E = E k Q P
Droop coefficient k P = Δ ω P N k P = Δ ω 2 Q N
Droop coefficient k Q = Δ E 2 Q N k Q = Δ E P N
Table 3. Parameters of the test system.
Table 3. Parameters of the test system.
ParameterValue
DC link Voltage v d c = 1000   V
Sampling Time T s = 2   μ s
LC-filter C f = 250   μ F ,   L f = 2   mH
Damping Resistance R f = 0.94   Ω
Linear load P = 18   kW ,   Q = 7   kvar
Non-linear load (diode rectifier) P = 10   kW ,   Q = 4   kvar
Nominal Voltage V n o m = 318   V
Average Switching Frequency f s w = 4.4   kHz
Rated Frequency f n o m = 60   Hz
Droop coefficients k q = 0.001 ,   k p = 0.001
Proportional Gain kp = 50
Proportional Integrator k I = 0.15
Table 4. Comparison between Proposed and Conventional Scheme.
Table 4. Comparison between Proposed and Conventional Scheme.
Load TypesProposed MPC Voltage THD (%)PI Voltage THD (%)
Balanced resistive load0.961.22
No Load0.961.22
Non-Linear Load1.234.31
Table 5. Comparison of different control methods.
Table 5. Comparison of different control methods.
ReferenceControl Technique%Voltage THD Linear Load%Voltage THD Non-Linear LoadController Complexity
[36]PI1642Low
[7]Dead Beat2.14.8Medium
[37]PR1.44.6Low
[11]SMC-2.66High
[29]MPC5.16.7High
[30]MPC (observer based)2.823.8Medium
[31]Implicit-MPC2.93Not studiedMedium
ProposedFCS–MPC0.961.23Medium

Share and Cite

MDPI and ACS Style

Khan, H.S.; Aamir, M.; Ali, M.; Waqar, A.; Ali, S.U.; Imtiaz, J. Finite Control Set Model Predictive Control for Parallel Connected Online UPS System under Unbalanced and Nonlinear Loads. Energies 2019, 12, 581. https://doi.org/10.3390/en12040581

AMA Style

Khan HS, Aamir M, Ali M, Waqar A, Ali SU, Imtiaz J. Finite Control Set Model Predictive Control for Parallel Connected Online UPS System under Unbalanced and Nonlinear Loads. Energies. 2019; 12(4):581. https://doi.org/10.3390/en12040581

Chicago/Turabian Style

Khan, Hussain Sarwar, Muhammad Aamir, Muhammad Ali, Asad Waqar, Syed Umaid Ali, and Junaid Imtiaz. 2019. "Finite Control Set Model Predictive Control for Parallel Connected Online UPS System under Unbalanced and Nonlinear Loads" Energies 12, no. 4: 581. https://doi.org/10.3390/en12040581

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop