Next Article in Journal
Multi Objective Optimization in Charge Management of Micro Grid Based Multistory Carpark
Previous Article in Journal
Automatic Adaptation of Multi-Loop Wireless Power Transfer to Variable Coupling between Transmit and Receive Coils
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Infeasibility Analysis of Half-Wavelength Transmission Systems

College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China
*
Author to whom correspondence should be addressed.
Energies 2018, 11(7), 1790; https://doi.org/10.3390/en11071790
Submission received: 29 May 2018 / Revised: 18 June 2018 / Accepted: 4 July 2018 / Published: 8 July 2018
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
This paper analyzes the infeasibility of half-wavelength transmission systems in the aspects of power-frequency overvoltage and synchronization stability. The circuit model of the long-distance transmission system is established at first for steady-state and transient analysis. The sending-end system and the receiving-end system are both considered in the model. A test system based on an actual transmission line is given to facilitate the description of system characteristics. Based on the circuit model, the resonant transmission distance of the system is found and calculated. Theoretical analysis and numerical calculations are carried out to determine the feasibility transmission distance. It is demonstrated that the transmission distance should be in a certain range, which is larger than the resonant transmission distance, to satisfy the steady-state overvoltage and the small signal synchronization stability as well as the frequency deviation constraints. For transmission distances in the feasible range, the three-phase short circuit fault at a certain point of the transmission line will cause the most serious transient power-frequency overvoltage, and the system is very likely to lose synchronization stability. Considering the transient power-frequency overvoltage and the transient synchronization stability, the half-wavelength transmission system is technically impossible to operate.

1. Introduction

In countries like Brazil, Russia, and China, renewable energy sources may locate far away from the major load centers [1,2,3]. The half-wavelength transmission is an attractive technique for those situations. This kind of transmission has been studied since the 1940s, however, there is no half-wavelength transmission system operating in the world [4,5]. The feasibility of half-wavelength transmission systems still needs further study.
Existing researches have investigated the basic characteristics of half-wavelength transmission systems. Previous literature declared that the advantages of half-wavelength transmission systems include:
  • The half-wavelength transmission line is free from the usual long-line operating problems, such as Ferranti effect, excessive charging current, and generator self-excitation [6].
  • There is no need of compensating equipment and switching stations for the half-wavelength transmission line [7,8].
  • The half-wavelength transmission lines are considered to be equivalent to short lines. Synchronization stability is not a limiting factor for power transmission [6].
  • The half-wavelength transmission is competitive in terms of economy. Results in previous papers [9,10,11] have shown the economic advantages in comparison with the high-voltage direct current transmission (HVDC).
However, the above declared advantages of half-wavelength transmission systems have not been fully supported in theory. There are some technical problems in the half-wavelength transmission system. Among them, overvoltage and synchronization stability are the most important technical issues that should be considered for the feasibility analysis. Previous researches find that the steady-state voltage is dependent on the transmission power and the power factor [12]. To avoid steady-state overvoltage, the transmission power should not exceed the surge impedance loading (SIL, which is the power under the matched condition) [13]. In terms of small signal synchronization stability, a transmission system whose equivalent electric length is slightly longer than the electrical half wavelength is thought to be suitable [6,12,14]. However, the feasible range of the equivalent electric length has not been figured out clearly. Actually, the feasible range is related to the system resonant transmission distance, which is proposed and clarified in this paper.
Under three-phase short circuit faults and asymmetrical faults, the occurrence of power-frequency overvoltage is inevitable and serious, and the transient synchronization stability of the half-wavelength transmission system varies with the fault type and location [12,15,16]. For three-phase faults, the maximum overvoltage has been given a theoretical explanation in a previous paper [12], but the transient synchronization stability is usually studied by simulations in previous literature, theoretical analysis of the transient synchronization stability is still lacking.
This paper tries to find out the feasible transmission distance of the half-wavelength transmission system in terms of overvoltage and stability. In this process, indicators such as the resonant transmission distance and the synchronization coefficient are proposed to reflect the steady-state characteristics and small signal synchronization stability, and the most serious fault point is defined and derived to study the transient characteristics under three-phase faults.
The main contributions and findings of this paper are:
  • A general circuit model of half-wavelength power transmission system is established, which can be used to analyze the steady-state and transient overvoltage of half-wavelength power transmission system and the problem of small signal synchronization stability and transient synchronization stability.
  • The resonance phenomenon of the half-wavelength power transmission system is found, and the concept of resonant transmission distance is proposed. The resonant transmission distance is less than the half-wavelength transmission distance.
  • When the transmission distance is equal to the resonance transmission distance, there is a specific point on the transmission line whose overvoltage level reaches infinity.
  • The small signal equation of the half-wavelength transmission system is established, the concept of the synchronization coefficient is put forward, and the range of the transmission distance that can keep the small signal synchronization stability is determined.
  • The most serious fault location was found, and the formula for calculating the most serious fault location was derived.
  • It is found that the transient power frequency overvoltage of the transmission system exceeds 10 times the rated voltage when there is a short-circuit fault on the most serious fault location.
  • If the generator adopts “a constant potential behind a reactance” model and neglects the damping effect when the most serious fault occurs, the half-wavelength power transmission system loses its transient stability definitely, regardless of the transmission power.
  • Different from all the previous studies, this paper clearly points out that the half-wavelength transmission system is technically impossible and has no feasibility of engineering, because on the one hand, the transient power frequency overvoltage level is unacceptable, and on the other hand, the transient synchronization stability cannot be guaranteed.
This paper is organized as follows. The circuit model of the half-wavelength transmission system is given in Section 2. The resonant transmission distance is defined in Section 3. The steady-state overvoltage and the small signal synchronization stability of the system are analyzed in Section 4 and Section 5 to determine the feasible transmission distance. After considering the frequency variation, the feasible range of the transmission distance is presented in Section 6. For feasible transmission distances, the transient power frequency overvoltage and the transient synchronization stability characteristics under three-phase short circuit faults are analyzed in Section 7 and Section 8, respectively. At last, conclusions are drawn.

2. Circuit Model

Half-wavelength transmission lines are usually applied in point-to-grid transmission systems or grid-to-grid transmission systems. For both cases, the steady-state characteristics and the synchronization stability of the system can be analyzed by the single-machine-infinite-bus system. When considering the sending-end system and the receiving-end system, a general long-distance transmission system can be represented by Figure 1. The transmission line adopts the positive sequence distributed parameter model; the sending-end generator-transformer unit adopts the classical generator model; the receiving-end system is represented by the Thevenin equivalent circuit.
As shown in Figure 1, Eg and Xg are the equivalent electromotive force and the equivalent impedance of the sending-end generator-transformer unit; Er and Xr are the equivalent source voltage and the equivalent impedance of the receiving-end system. Us and Ur are the voltages at both ends of the transmission line. Is and Ir are the currents of the sending end and receiving end. Ux is the voltage at the point x km away from the sending end. l is the length of the transmission line (or called the transmission distance). Ps and Qs are the active and reactive power of the sending end; Pr and Qr are the active and reactive power of the receiving end.
When taking the line resistance into consideration, the basic characteristic of the transmission line is described by the long line equations:
U r = U s ch γ l I s Z C sh γ l
I r = U s sh γ l / Z C + I s ch γ l
where ZC is the line’s surge impedance; γ is the line’s propagation coefficient. ZC and γ can be calculated by:
Z C = ( R 1 + j ω L 1 ) / ( G 1 + j ω C 1 )
γ = α + j β = ( R 1 + j ω L 1 ) ( G 1 + j ω C 1 )
where R1, L1, G1, and C1 are the positive sequence resistance, inductance, conductance, and capacitance of per unit length, respectively; ω is the angular frequency; α is the attenuation constant and β is the phase constant.
To facilitate the description of system characteristics and to carry out numerical calculations, a test system is analyzed in this paper. The rated frequency of the system is supposed to be 50 Hz. The unit length line parameters are given by [17,18], and the surge impedance and the propagation coefficient are calculated by (3) and (4). Detailed parameters are shown in Table 1.
As shown in Table 1, the attenuation constant (α) is much smaller than the phase constant (β); the phase angle of the surge impedance is negligible. These system parameters are very close to those of lossless lines.
The half wavelength of the test system is:
λ / 2 = π / β = 2938.0   km
The rated voltage of the line (Urated) is supposed to be 1000 kV, and then the surge impedance loading is:
P SIL = U rated 2 / | Z C | = 4062.8   MW
In this paper, the rated voltage and the surge impedance loading of the transmission line are set as the reference voltage (UB) and the reference capacity (SB) for the per-unit system, respectively. The actual values of physical quantities are represented by upper-case letters, and the corresponding per-unit values are represented by lower-case letters in this paper.
In order to analyze the typical application of half wavelength transmission system in transmitting bulk power from energy bases to the load centers, assume the parameters of the two end systems are as shown in Table 2.
First we neglect the losses of the transmission line, according to the long line equations and Figure 1, we have:
[ i s i r ] = [ y ] [ e g e r ]
where the admittance matrix [y] is:
[ y ] = 1 Δ 0 [ j ( x r sin ( β l ) cos ( β l ) ) j j j ( x g sin ( β l ) cos ( β l ) ) ]
Δ 0 = ( 1 x g x r ) sin ( β l ) + ( x g + x r ) cos ( β l )
According to (7), the following per-unit power equations can be derived:
p g = p r = e g e r sin δ g Δ 0
q g = e g ( e r cos ( δ g ) e g x r sin ( β l ) + e g cos ( β l ) ) Δ 0
q r = e r ( e g cos ( δ g ) + e r x g sin ( β l ) e r cos ( β l ) ) Δ 0
where δg is the phase angle difference between eg and er.
Similarly, if the line losses are considered, the power equations become:
p g = C 1 sin δ g + C 2 cos δ g + C 3 Δ loss = K 1 sin ( δ g + φ 1 ) + C 3 Δ loss
q g = C 2 sin δ g C 1 cos δ g + C 4 Δ loss = K 1 sin ( δ g + φ 2 ) + C 4 Δ loss
p r = C 1 sin δ g C 2 cos δ g + C 5 Δ loss = K 1 sin ( δ g + φ 3 ) + C 5 Δ loss
q r = C 2 sin δ g + C 1 cos δ g + C 6 Δ loss = K 1 sin ( δ g + φ 4 ) + C 6 Δ loss
where:
K 1 = C 1 2 + C 2 2
Δ loss = | ( x g x r z c 2 ) sh γ l j z c ( x g + x r ) ch γ l | 2
When the transmission line parameters and xg, xr, eg, er are given, C1–C6 and φ 1 φ 4 are constants. The detail expressions are given in the Appendix A.1.

3. Resonant Transmission Distance

Using (9), we have:
Δ 0 = ( x g + x r ) 2 + ( 1 x g x r ) 2 sin ( β l + φ C )
where:
φ C = arctan x g + x r 1 x g x r ( 0 π 2 )
When l = ( π φ C ) / β , Δ0 = 0. Then according to (8), the denominators of elements in the admittance matrix [y] are zero. Series resonance occurs between the transmission line and the equivalent reactance of both sides of the system. If we define the transmission distance at this condition as the resonant transmission distance and denote it as lresnt, then we have:
l resnt = [ arctan ( x r + x g x r x g 1 ) + π ] / β
As shown in (21), lresnt is dependent on the parameters of the transmission line and the equivalent reactance of both ends, but not related to eg and er.
When the losses of the transmission line are considered, the resonant transmission distance can also be calculated by (21) according to (18). For the test system, lresnt is about 2707 km, βlresnt is about 165.8°.
To analyze the test system’s characteristic, we set a general terminal condition, which is eg = 1.1 p.u. and er = 1.0 p.u. Then qg is calculated under different transmission power and transmission distances, and the results are shown in Figure 2.
As shown in Figure 2, when the transmission distance is close to lresnt (in 2700–2715 km), there is no solution for (13), so the test system cannot operate; when the transmission distance is not in the above range, the test system can operate, but the absolute value of qg is too large. For example, when βl = 167°, if pg = 0 p.u., 0.5 p.u., 1.0 p.u. and 1.5 p.u., then qg is 5.81 p.u., 4.06 p.u., 2.69 p.u., and 1.53 p.u., respectively. It can be seen that the less the pg is, the greater the absolute value of the qg is. With the increase of the deviation between l and lresnt, qg decreases; when l reduces to below 2639 km or l increases to over 2804 km, the absolute value of qg decreases to below 1.0 p.u.
Thereby, the transmission distance should stay away from lresnt to make the system operational and to decrease the reactive power.

4. Steady-State Overvoltage Analysis

In order to further determine the feasible transmission distance, the steady-state overvoltage is analyzed. According to the long line equations, the voltage at the point x km away from the sending end is:
u x = u s ch γ x i s 𝔃 C sh γ x
where:
i s = [ ( p g + j q g ) / e g ] *
u s = e g j i s x g
where * indicates the conjugate complex.
Under the terminal condition eg = 1.1 p.u. and er = 1.0 p.u., taking pg as a parameter, for different transmission distances, the maximum voltage along the whole transmission line, which is defined as ul,max, is calculated as shown in Figure 3. Figure 3a is a large range picture of ul,max in different transmission distances; while Figure 3b is a small range picture of ul,max for clearer presentation.
From Figure 3, it can be drawn that:
(1)
Under different pg, when l gets closer to lresnt, ul,max has an abrupt increase;
(2)
As shown in Figure 3b, for l in the range of 163.3°–164.6° and 167.0°–168.2°, ul,max decreases with the increase of pg;
(3)
As shown in Figure 3a, when pg is 1.5 p.u., there is obvious overvoltage for all the transmission distances and ul,max is close to pg for most transmission distances. Actually, this is true for any transmission power larger than 1.0 p.u.
(4)
As shown in Figure 3a, there is no operation point when pg is 1.5 p.u. and βl is larger than 217.1°; similarly, as shown in Figure 3b, there is no operation point when pg is 0.0 p.u. and βl is in the range of 164.6°–167.0°.
Figure 3 only gives the maximum voltage along the whole line, we still need to know the location where the maximum voltage occurs. The location where the maximum voltage (ul,max) occurs is defined as xumax (in km) or βxumax (in deg.). The maximum voltage (ul,max) and its location (βxumax) for different transmission distances with fixed transmission power are illustrated in Figure 4 and described in Table 3.
As shown in Figure 4 and Table 3, taking pg = 1.0 p.u for example, when the transmission distance is 2448.3 km (150°), 2725.8 km (167°), 2938.0 km (180°), and 3427.7 km (210°), respectively, the maximum voltage along the transmission line (ul,max) is 1.098 p.u., 2.446 p.u., 1.071 p.u., and 1.088 p.u., respectively, and the location where the maximum voltage occurs (xumax or βxumax) is 88.1 km (5.4°), 1682.8 km (103.1°), 2378.1 km (145.7°), and 0.0 km (0°), respectively.
If we choose ul,max < 1.5 p.u. as the permissible range of overvoltage, when pg changes from 0 p.u. to 1.5 p.u., the feasible range of transmission distance for the test system is:
{ 126.0 < β l < 161.5 170.1 < β l < 210.0

5. Small Signal Synchronization Stability Analysis

The rotor motion equation of the system is:
{ d δ g d t = ω 0 ( ω g 1 ) d ω g d t = 1 2 H ( p m p g D ( ω g 1 ) )
where ω0, ωg, H, pm, and D are the rated angular frequency of the system, the angular frequency of the generator, the inertia time constant, the mechanical power and the damping coefficient of the generator, respectively. When pm is supposed to be constant, the linearized equation of the rotor motion equation at the operating point (δg(0), ω0) is:
[ d Δ δ g d t d Δ ω g d t ] = [ 0 ω 0 K 1 cos ( δ g ( 0 ) + φ 1 ) 2 H Δ loss D 2 H ] [ Δ δ g Δ ω g ]
where K1, Δloss and φ 1 have been defined in (13)–(18).
The characteristic equation of the system is:
λ 2 + D 2 H λ + ω 0 2 H K 1 Δ loss cos ( δ g ( 0 ) + φ 1 ) = 0
Because H and D are positive, the small signal synchronization stability condition of the system finally becomes:
K synch = K 1 Δ loss cos ( δ g ( 0 ) + φ 1 ) > 0
We define Ksynch as the synchronization coefficient. The characteristic of the half-wavelength transmission system can be summarized as: if Ksynch is positive, the system is stable under small disturbances; otherwise, the system is unstable. For the test system with the terminal condition of eg = 1.1 p.u. and er = 1.0 p.u., the synchronization coefficient are calculated under different transmission distances with fixed transmission power pg. The results are shown in Figure 5 and described in Table 4.
As shown in Figure 5 and Table 4, taking βl = 150° for example, when pg = 0 p.u., 0.5 p.u., 1.0 p.u., and 1.5 p.u., respectively, Ksynch = −3.88, −3.91, −3.88 and −3.78 respectively. From Figure 5 we can see: in the studied transmission distance range, when l is smaller than lresnt, Ksynch is negative; and when l is greater than lresnt, e.g., βl = 167°, Ksynch becomes positive. So, only when l is larger than lresnt, may the system be stable. Considering the small signal synchronization stability condition of the test system, when pg changes from 0 p.u. to 1.5 p.u., the feasible transmission distance range is:
166.8 < β l < 217.1

6. Feasible Transmission Distance Analysis

Taking the overvoltage constraint (25) and the small signal synchronization stability constraint (30) into consideration, when pg changes from 0 p.u. to 1.5 p.u., the feasible range of the transmission distance for the half-wavelength transmission system is:
170.1 < β l < 210.0
In considering of the frequency variation during transient process, we set an allowable frequency variation range of −3% to +3% of the rated frequency. βl changes with the variation of frequency, as shown in Figure 6.
As shown in Figure 6, when the frequency changes −3%, the feasible transmission distance range for the half-wavelength transmission system is:
2862 . 3   km < l < 3533.7   km
When the frequency changes 3%, the feasible range is:
2695 . 6   km < l < 3327.9   km
In conclusion, after considering the frequency variation, the feasible transmission distance range that satisfies both the overvoltage constraint and the synchronization stability constraint is:
2862 . 3 km < l < 3327.9   km

7. Transient Overvoltage Analysis

This section studies the transient overvoltage characteristic under three-phase short circuit faults. The test system and the transient model mentioned in Section 2 are adopted. The transmission distance is supposed to be in the feasible range given by (34). The system is in the steady state at t = 0−, and the fault occurs at t = 0+. The system model under the three-phase short circuit fault is shown in Figure 7.
In Figure 7, all the per-unit values in lower-case letters are based on SIL and the rated voltage of the transmission line. The meanings of the variables in Figure 7 are the same as in Figure 1. Besides, lf is the distance between the fault point and the sending end; uf is the voltage of the fault point; isf and irf are the currents of the fault point; zsf is the input impedance seen from the sending end.
When the phase angle of Zc is ignored, using uf = 0 and the long line equations, we can deduce:
{ u s = u f ch ( γ l f ) + i s u f sh ( γ l f ) = i s f sh ( γ l f ) i s = u f sh ( γ l f ) + i s f ch ( γ l f ) = i s f ch ( γ l f )
Then, the input impedance zsf can be expressed as:
z sf = u s / i s = th ( γ l f )
During the fault period, the magnitude of eg is constant. According to (36) and the sending end equivalent circuit shown in Figure 7b, us and is can be expressed as:
{ u s = e g z sf / ( z sf + j x g ) i s = e g / ( z sf + j x g )
According to the long line equations and (37), we can calculate ux by:
u x = u s ch γ x i s sh γ x = e g ( th γ l f ch γ x sh γ x ) th γ l f + j x g
Then the magnitude of ux is:
u x = e g | th γ l f + j x g | | th γ l f ch γ x sh γ x |
It can be proved that when the imaginary part of (thγlf + jxg) is zero, ux will get its maximum value ufmax. So we define lfmax as the solution of the equation Im(thγlfmax + jxg) = 0, whose meaning is the fault distance which will cause the largest overvoltage compared to the other fault distance. After lfmax is defined, we next define the location at which the maximum overvoltage occurs, which is defined as xf,umax. The meaning of xf,umax is: when a three phase fault occurs at lfmax, the maximum overvoltage ufmax will occur at xf,umax. According to the definitions of ufmax, lfmax, and xf,umax, we can derive their expressions from (39) as:
l f max = [ π arctan ( x g ) ] / β
x f , umax = l fmax π / ( 2 β )
u f max e g th ( α l fmax ) ( 1 + x g 2 )
It is shown by (40) that lfmax is shorter than the half wavelength, and it is independent of eg and er. For the test system, βlfmax is about 168.7°, which is smaller than any feasible transmission distance given by (34). This means that there is always a fault point on the transmission line that will cause the maximum overvoltage.
According to (41), the maximum overvoltage occurs at the point exactly a quarter wavelength away from the fault point.
Using (42), we can estimate the maximum overvoltage ufmax. Because e g 1 , th ( α l fmax ) < th ( 0.05 ) 0.05 and xg < 1, u f max > 20 / 2 > 10 p.u. So the power-frequency overvoltage is larger than 10 p.u. for the test system. Actually, such a serious overvoltage is unacceptable in the actual power system.
Simulations have been done by PSS/E to illustrate the above conclusion. The structure of the test system is shown in Figure 1. The system parameters given in Section 2 are adopted. The transmission distance is 3200 km. From the sending end of line, a voltage measurement point is set every 160 km, and is numbered from 0 to 20. According to the previous analysis, when the fault point is 2753.4 km away from the sending end (i.e., lfmax = 2753.4 km), the maximum overvoltage (ufmax) will occur at the point 1284.4 km away from the sending end (i.e., xf,umax = 1284.4 km), which is near the 8th measurement point (which is 1280 km away from the sending end).
When the above fault occurs, the voltage profile of the line is shown in Figure 8.
As shown in Figure 8, when pg = 0 p.u., 0.5 p.u., 1.0 p.u., and 1.5 p.u., respectively, the maximum overvoltage is 22.77 p.u., 22.59 p.u., 22.98 p.u., and 23.91 p.u., respectively. This example illustrates that the maximum overvoltage (ufmax) is much larger than 10 p.u., which cannot be accepted in real engineering.

8. Transient Synchronization Stability Analysis

During the fault period, the power of the sending end can be calculated by:
p s + j q s = u s i s * = z sf i s i s * = z sf | i s | 2 = th ( γ l f ) e g 2 | th γ l f + j x g | 2
According to (43), the electromagnetic power of the sending-end generator is not varied with time during the fault period. We denote it by ps(1). When lf = lfmax, ps(1) gets its maximum value psmax(1):
p smax ( 1 ) e g 2 th ( α l fmax ) ( 1 + x g 2 )
Because when lf = lfmax, both ps(1) and ux get their maximum values, we define lfmax as the most serious fault point. Using (44), we can estimate the maximum electromagnetic power. Because e g 1 , th ( α l fmax ) < th ( 0.05 ) 0.05 and xg < 1, so p smax ( 1 ) > 10 p.u.
During the fault period, the rotor motion equation is:
{ d δ g d t = ω 0 ( ω g 1 ) d ω g d t = 1 2 H ( p m p s ( 1 ) D ( ω g 1 ) )
If the effect of the governor is ignored, pm = ps(0), where ps(0) is the electromagnetic power of the steady state. For the convenience of analysis, D is supposed to be zero. If the fault is cleared at time tclear, the states at the fault clearing time can be calculated by:
{ ω g ( 1 ) = 1 2 H ( p s ( 0 ) p s ( 1 ) ) t clear + ω g ( 0 ) δ g ( 1 ) = ( p s ( 0 ) p s ( 1 ) ) ω 0 t clear 2 / ( 4 H ) + δ g ( 0 )
where ωg(0) = 1.0 p.u.; δg(0) is the phase angle difference between eg and er before the fault; ωg(1) and δg(1) are the angular frequency and phase angle difference at the fault clearing time.
Next we analyze the transient synchronization stability under the fault at the most serious fault point lfmax.
For the fault occurs at lfmax, the states at the fault clearing time are:
{ ω g ( 1 ) = 1 2 H ( p s ( 0 ) p smax ( 1 ) ) t clear + ω g ( 0 ) δ g ( 1 ) = ( p s ( 0 ) p smax ( 1 ) ) ω 0 t clear 2 / ( 4 H ) + δ g ( 0 )
After the fault is cleared, the system structure recovers. If the losses of the transmission line are ignored, the expression of the generator electromagnetic power is the same as (10):
p g = p s ( 2 ) e g e r sin δ g Δ 0
where ps(2) is the generator electromagnetic power after the fault is cleared.
According to (48), the electromagnetic power is a sine wave with respect to the power angle of the generator, as shown in Figure 9. During the fault period, the generator gets an initial deceleration area, A1¯. At the fault clearing time, ωg(1) is less than ωg(0) according to (47), so the phase angle (δg) will continue to decrease after the fault is cleared.
For the fault at lfmax, because psmax(1) is much larger than ps(0) and the fault clearance requires a certain amount of time, in general, the acceleration area A1+ cannot compensate A1¯. If the mechanical power of the generator is zero (ps(0) = 0), in any sinusoidal cycle of the phase angle, the acceleration area obtained by the generator is always equal to the deceleration area. The phase angle of the generator will keep decreasing after the fault. This means that the system will lose stability after the fault.
If the mechanical power of the generator is positive (ps(0) > 0), the acceleration area is always larger than the deceleration area in a sinusoidal cycle of the phase angle, as shown in Figure 10. This means the initial deceleration area (A1¯) will be compensated gradually. When the initial deceleration area is totally compensated, ωg will recover to ωg(0). Suppose that when δg reaches δg(2), ωg recovers to ωg(0), and the initial deceleration area is totally compensated, then the last compensating area is gotten at δg(2), this is to say, ps must be smaller than ps(0) when δg is at δg(2).
On the other hand, there is a critical phase angle (δcritical) that makes An+ = An¯, as shown in Figure 10. Before ωg recovers to ωg(0), δg is in the decreasing state. Next we will prove that δg(2) must be less than δcritical, i.e., δg(2) must be on the left of δcritical.
If δg(2) > δcritical, i.e., δg(2) is on the right of δcritical, then An+ cannot compensate An, the sum of the deceleration area and the acceleration area will be negative, and ωg will be still less than ωg(0) when δg reaches (from right to left) δg(2). This contradicts to the definition of δg(2). Thereby, δg(2) must be less than δcritical, i.e., δg(2) must be on the left of δcritical.
After ωg increases to ωg(0), because δg(2) is on the left of δcritical, the acceleration area is always larger than the deceleration area. Then ωg will always be larger than ωg(0), and δg is in the increasing state. In this situation, when δg reaches δgr, ωg is still larger than ωg(0), and δg will keep increasing. The system also loses stability after the fault.
In conclusion, the phase angle δg will keep decreasing, or keep increasing after a certain time of decreasing. In both cases, the system will lose stability under the fault that occurs at the most serious fault point. Actually, the same conclusion will be obtained through similar derivation process when the losses of the transmission line are considered and the power equation is expressed as (13).
The above result shows that if the sending-end generator is modeled by the classical model, the system will lose stability under the fault that occurs at the most serious fault point.
Simulations have been done to illustrate this conclusion. The test system in Section 7 is adopted. The sending end generator is modeled by the classical model with H = 8.692 p.u. and D = 0. The receiving end system is represented by the Thevenin equivalent circuit with xr = 0.05 p.u. In the simulations, the short circuit fault occurs at lfmax at 1 s. The swing curves of the sending-end generator power angle under different fault clearing time (0.03–0.11 s) are shown in Figure 11.
As shown in Figure 11, when pg(0) = 0 p.u., δg keeps decreasing after the fault. When pg(0) = 0.5 p.u., 1.0 p.u. and 1.5 p.u. respectively, δg keeps increasing after a certain time of decreasing. For all the cases, the system is unstable after the fault. This is consistent with the conclusion of the previous analysis.
If a detailed generator model is adopted and the effect of the excitation system is considered (detailed data is given in the Appendix A.2), the results under the same fault are shown in Figure 12.
As shown in Figure 12, when pg(0) = 0 p.u., if the fault clearing time is 0.03 s, the system can keep stable; if the fault clearing time is 0.05 s, 0.07 s, 0.09 s, or 0.11 s, the system will lose stability. When pg(0) = 0.5 p.u., if the fault clearing time is 0.05 s, 0.07 s, or 0.09 s, the system can keep stable; if the fault clearing time is 0.03 s or 0.11 s, the system will lose stability. When pg(0) = 1.0 p.u., if fault clearing time is 0.05 s or 0.09 s, the system can keep stable; if fault clearing time is 0.03 s, 0.07 s, or 0.11 s, the system will lose stability. When pg(0) = 1.5 p.u., if fault clearing time is 0.07 s, the system can keep stable; otherwise, the system will lose stability.
When the system loses stability, if pg(0) = 0 p.u., δg will keep decreasing; if pg(0) is positive, δg will keep increasing after a certain time of decreasing. This is the same as the result of the classical model.
In conclusion, if a detailed generator model is adopted and the effect of the excitation system is considered, the stability of the system is uncertain, it depends on the value of the fault clearing time. However, the fault clearing time that keeps the system stable is segmented, so there is no fault critical clearing time.

9. Conclusions

On the conception of half wavelength power transmission, which was put forward in the 1940s, and is becoming a hot topic again, this paper makes an in-depth analysis with theoretical derivation and numerical calculation. The main conclusions are as follows:
(1)
There exists a resonant transmission distance in the half-wavelength transmission system. The resonant transmission distance is only related to the equivalent reactance of the sending end and the receiving end system, and is independent of the equivalent voltage source of the sending end and the receiving end system, and is less than the half wavelength.
(2)
Under the resonant transmission distance, the maximum voltage along the transmission line will reach infinity. Therefore, the transmission distance of the half-wavelength transmission system must be larger than that of the resonant transmission distance.
(3)
A transmission distance greater than the resonant distance is necessary for the small signal synchronization stability of the half-wavelength transmission system because when the transmission distance is less than the resonant transmission distance, the half-wavelength transmission system loses its small signal synchronization stability.
(4)
There exists a most serious fault location along the transmission line. When a three-phase short circuit fault occurs at this location, the most serious power-frequency overvoltage occurs at the point a quarter of wavelength from this location, and the value of the overvoltage is larger than 10 p.u.
(5)
When a three phase short circuit occurs at the most serious fault location, if the generator is modeled with the classical model and the damping is ignored, the system always loses its transient synchronization stability regardless of the fault clearing time and the initial transmission power.
(6)
When a three-phase short circuit occurs at the most serious fault location, if the generator is modeled with its detailed model and the effect of the field excitation and its control system is considered, the transient synchronization stability of the system is uncertain, i.e., the transient synchronization stability has no definite relationship with the fault clearing time and the initial transmission power.
(7)
Because the transient power frequency overvoltage of the half-wavelength transmission system exceeds 10 p.u. and the transient synchronization stability cannot be guaranteed, the conception of the half wavelength power transmission cannot be established, and the half wavelength transmission system is not feasible.

Author Contributions

Conceptualization, Z.X.; Formal analysis, J.Y. and N.S.; Investigation, J.Y. and N.S.; Methodology, Z.X.; Supervision, Z.X.

Funding

This research received no external funding.

Acknowledgments

This paper is supported by the Headquarters Research Projects of State Grid Corporation of China “Research on flexible transmission network planning evaluation method and key technologies for its application (SGTYHT/15-JS-191)”.

Conflicts of Interest

The authors declare no conflicts of interest.

Appendix A

Appendix A.1. Power Equations of the Lossy Transmission Line

As shown in Figure A1, the transmission line can be equivalent to the π-type equivalent circuit, and then we have:
Z eq = Z C sinh γ l
Y eq = cosh γ l 1 Z C sinh γ l
Figure A1. π-type equivalent circuit of the transmission line.
Figure A1. π-type equivalent circuit of the transmission line.
Energies 11 01790 g0a1
By extracting the real part and the imaginary part, the equivalent impedance and the equivalent admittance are:
z eq = r eq + j x eq
y eq = g eq + j b eq
Based on the node voltage method, the admittance matrix [y] is:
[ y ] = 1 ( x g x r z c 2 ) sinh γ l j z c ( x g + x r ) cosh γ l × [ ( z c ch γ l + j x r sh γ l ) z c z c ( z c ch γ l + j x g sh γ l ) ]
Then, the power equations can be obtained:
p g = C 1 sin δ g + C 2 cos δ g + C 3 Δ loss = K 1 sin ( δ g + φ 1 ) + C 3 Δ loss
q g = C 2 sin δ g C 1 cos δ g + C 4 Δ loss = K 1 sin ( δ g + φ 2 ) + C 4 Δ loss
p r = C 1 sin δ g C 2 cos δ g + C 5 Δ loss = K 1 sin ( δ g + φ 3 ) + C 5 Δ loss
q r = C 2 sin δ g + C 1 cos δ g + C 6 Δ loss = K 1 sin ( δ g + φ 4 ) + C 6 Δ loss
where:
φ 1 = { arctan C 2 C 1 , C 1 > 0 arctan C 2 C 1 + π , C 1 < 0
φ 2 = { arctan C 1 C 2 , C 2 > 0 arctan C 1 C 2 + π , C 2 < 0
φ 3 = { arctan C 2 C 1 , C 1 > 0 arctan C 2 C 1 + π , C 1 < 0
φ 4 = { arctan C 1 C 2 , C 2 > 0 arctan C 1 C 2 + π , C 2 < 0
C 1 = e g e r ( x eq ( b eq 2 x r x g b eq ( x r + x g ) g eq 2 x r x g + 1 ) 2 b eq x r x g ( g eq r eq + 1 ) + ( g eq r eq + 1 ) ( x r + x g ) )
C 2 = e g e r ( r eq ( b eq 2 ( x r ) x g + b eq ( x r + x g ) + g eq 2 x r x g 1 ) + g eq ( x eq ( 2 b eq x r x g + x r + x g ) + 2 x r x g ) )
C 3 = e g 2 ( x r 2 ( ( g eq r eq + 1 ) ( r eq ( b eq 2 + g eq 2 ) + 2 g eq ) + g eq x eq 2 ( b eq 2 + g eq 2 ) 2 b eq g eq x eq ) 2 x r ( b eq ( g eq r eq 2 + g eq x eq 2 + r eq ) g eq x eq ) + g eq r eq 2 + g eq x eq 2 + r eq )
C 4 = e g 2 ( b eq 4 x r 2 x g ( r eq 2 + x eq 2 ) b eq 3 x r ( r eq 2 ( x r + 2 x g ) + x eq ( x eq ( x r + 2 x g ) + 4 x r x g ) ) + b eq 2 ( x g ( 2 x r 2 ( g eq 2 ( r eq 2 + x eq 2 ) + 2 g eq r eq + 2 ) + r eq 2 + x eq 2 + 6 x eq x r ) + x r ( 2 ( r eq 2 + x eq 2 ) + 3 x eq x r ) ) b eq x r 2 ( g eq 2 ( r eq 2 + x eq 2 ) + 2 g eq r eq + 2 ) 2 b eq x g ( x eq ( g eq 2 x r ( x eq + 2 x r ) + 1 ) + x r ( g eq r eq ( g eq r eq + 2 ) + 2 ) ) b eq ( r eq 2 + x eq 2 ) 4 b eq x eq x r + g eq ( g eq x g ( x r 2 ( g eq 2 x eq 2 + ( g eq r eq + 2 ) 2 ) + r eq 2 + x eq 2 + 2 x eq x r ) + g eq x eq x r 2 + 2 r eq x g ) + x eq + x r + x g )
C 5 = e r 2 ( x g 2 ( ( g eq r eq + 1 ) ( r eq ( b eq 2 + g eq 2 ) + 2 g eq ) + g eq x eq 2 ( b eq 2 + g eq 2 ) 2 b eq g eq x eq ) 2 x g ( b eq ( g eq r eq 2 + g eq x eq 2 + r eq ) g eq x eq ) + g eq r eq 2 + g eq x eq 2 + r eq )
C 6 = e r 2 ( b eq 2 x r ( ( r eq 2 + x eq 2 ) ) x g 2 ( b eq 3 ( r eq 2 ) b eq 3 x eq 2 + x r ( b eq 2 + g eq 2 ) ( b eq 2 ( r eq 2 + x eq 2 ) 4 b eq x eq + g eq 2 ( r eq 2 + x eq 2 ) + 4 g eq r eq + 4 ) + 3 b eq 2 x eq b eq g eq 2 r eq 2 b eq g eq 2 x eq 2 2 b eq g eq r eq 2 b eq + g eq 2 x eq ) + x g ( 2 b eq 3 x r ( r eq 2 + x eq 2 ) 2 b eq 2 ( r eq 2 + x eq ( x eq + 3 x r ) ) + 2 b eq x r ( geq 2 ( r eq 2 + x eq 2 ) + 2 g eq r eq + 2 ) + 4 b eq x eq 2 g eq 2 x eq x r 1 ) + b eq ( r eq 2 + x eq ( x eq + 2 x r ) ) x r ( g eq 2 x eq 2 + ( g eq r eq + 1 ) 2 ) x eq )

Appendix A.2. Dynamic Parameters of the Sending-End Generator and Its Excitation System

The sending-end generator is modeled by the round rotor generator model (GENROU). The excitation system is modeled by the 1992 IEEE type ST1A excitation system model (ESST1A). The dynamic parameters of the generator and the excitation system are given in the Table A1 below.
Table A1. Dynamic parameters of the sending-end generator and the excitation system.
Table A1. Dynamic parameters of the sending-end generator and the excitation system.
GeneratorExcitation System
T’d06.4000TR0.0100
T’’d00.0450VI MAX0.2000
T’q00.7000VI MIN−0.2000
T’’q00.0690TC1.0000
H4.3464TB1.0000
D0.0000TC10.1000
Xd2.0870TB10.1000
Xq2.0497KA51.0000
X’d0.2942TA0.0100
X’q0.4449VA MAX4.0000
X’’d = X’’q0.2000VA MIN−4.0000
XI0.0266VR MAX4.0000
S(1.0)0.13VR MIN−4.0000
S(1.2)1.067KC0.0000
KF0.0000
TF1.0000
KLR0.0000
ILR3.0000

References

  1. Tavares, M.C.; Portela, C.M. Half-wave length line energization case test—Proposition of a real test. In Proceedings of the International Conference on High Voltage Engineering and Application (ICHVE), Chongqing, China, 9–12 November 2008; pp. 261–264. [Google Scholar]
  2. Xiang, X.; Qi, L.; Cui, X. Electromagnetic transient characteristic of 1000 kV half-wavelength AC transmission lines. In Proceedings of the 5th International Conference on Critical Infrastructure (CRIS), Beijing, China, 20–22 September 2010; pp. 1–4. [Google Scholar]
  3. Gomes, L.C.F.; Silva, L.C.P.D.; Tavares, M.C. Half-wavelength transmission lines for connecting power plants in Amazon region to the Brazilian system. In Proceedings of the 2013 IEEE Grenoble PowerTech (POWERTECH), Grenoble, France, 16–20 June 2013; pp. 1–6. [Google Scholar]
  4. Wolf, A.A.; Shcherbachev, O.V. On normal working conditions of compensated lines with half-wave characteristics. Elektrichestvo 1940, 1, 147–158. (In Russian) [Google Scholar]
  5. Gatta, F.M.; Iliceto, F. Analysis of some operational problems of half-wave length power transmission lines. In Proceedings of the 3rd Africon Conference (AFRICON ′92), Ezulwini Valley, Swaziland, 22–24 September 1992; pp. 59–64. [Google Scholar]
  6. Hubert, F.J.; Gent, M.R. Half-wavelength power transmission lines. IEEE Trans. Power Appar. Syst. 1965, 84, 965–974. [Google Scholar] [CrossRef]
  7. Wang, G.; Li, Q.; Zhang, L. Research status and prospects of the half-wavelength transmission lines. In Proceedings of the 2010 Asia-Pacific Power and Energy Engineering Conference (APPEEC), Chengdu, China, 28–31 March 2010; pp. 1–5. [Google Scholar]
  8. Santos, M.L.D.; Jardini, J.A.; Casolari, R.P.; Vasquez-Arnez, R.L.; Saiki, G.Y.; Sousa, T.; Nicola, C.G.L. Power transmission over long distances: Economic comparison between HVDC and half-wavelength line. IEEE Trans. Power Deliv. 2014, 29, 502–509. [Google Scholar] [CrossRef]
  9. Samorodov, G.; Kandakov, S.; Zilberman, S.; Krasilnikova, T.; Tavares, M.C.; Machado, C.; Li, Q. Technical and economic comparison between direct current and half-wavelength transmission systems for very long distances. IET Gener. Transm. Distrib. 2017, 11, 2871–2878. [Google Scholar] [CrossRef]
  10. Song, Y.; Fan, B.; Bai, Y.; Qin, Z.; Zhang, Z. Reliability and economic analysis of UHV Half-Wave-length AC Transmission. In Proceedings of the 2012 IEEE International Conference on Power System Technology (POWERCON), Auckland, New Zealand, 30 October–2 November 2012; pp. 1–6. [Google Scholar]
  11. Sun, K. Economic analysis on UHV half-wavelength AC power transmission. Power Syst. Technol. 2011, 35, 51–54. (In Chinese) [Google Scholar]
  12. Wang, L.; Cui, X. A method for suppressing steady-state operating overvoltages of the half wave-length UHV AC power transmission line. In Proceedings of the 7th Asia-Pacific International Conference on Lightning, Chengdu, China, 1–4 November 2011; pp. 551–554. [Google Scholar]
  13. Prabhakara, F.S.; Parthasarathy, K.; Ramachandra Rao, H.N. Analysis of natural half-wave-length power transmission lines. IEEE Trans. Power Appar. Syst. 1969, 88, 1787–1794. [Google Scholar] [CrossRef]
  14. Dias, R.; Lima, A.; Portela, C.; Aredes, M. Extra long-distance bulk power transmission. IEEE Trans. Power Deliv. 2011, 26, 1440–1448. [Google Scholar] [CrossRef]
  15. Santos, M.L.; Jardini, J.A.; Masuda, M.; Nicola, G.L.C. Electrical requirements for half-wavelength power transmission line design. In Proceedings of the 2010 IEEE/PES Transmission and Distribution Conference and Exposition: Latin America, Sao Paulo, Brazil, 8–10 November 2010; pp. 486–490. [Google Scholar]
  16. Santos, M.L.; Jardini, J.A.; Masuda, M.; Nicola, G.L.C. A study and design of half-wavelength lines as an option for long distance power transmission. In Proceedings of the 2011 IEEE Trondheim PowerTech (POWERTECH), Trondheim, Norway, 19–23 June 2011; pp. 1–6. [Google Scholar]
  17. Qin, X.; Zhang, Z.; Xu, Z.; Zhang, D.; Zheng, J. Study on the steady state characteristic and transient synchronization stability of UHV AC half-wave-length transmission system based on quasi-steady model. Proc. CSEE 2011, 31, 66–76. (In Chinese) [Google Scholar]
  18. Wang, A.; Ren, D.; Tang, Y.; Yi, J.; Zhang, J. Power transmission capability and transient synchronization stability influence factors of UHV half-wavelength transmission line. Power Syst. Technol. 2017, 41, 3168–3173. (In Chinese) [Google Scholar]
Figure 1. Equivalent circuit of the long distance transmission system.
Figure 1. Equivalent circuit of the long distance transmission system.
Energies 11 01790 g001
Figure 2. qg of different transmission power and transmission distances.
Figure 2. qg of different transmission power and transmission distances.
Energies 11 01790 g002
Figure 3. The maximum voltage along the whole line for different transmission distances. (a) βl in the range of 120°–240°; (b) βl in the range of 160°–170°.
Figure 3. The maximum voltage along the whole line for different transmission distances. (a) βl in the range of 120°–240°; (b) βl in the range of 160°–170°.
Energies 11 01790 g003
Figure 4. The maximum voltage and its location for different transmission distances. (a) ul,max and βxumax when pg = 0.0 p.u.; (b) ul,max and βxumax when pg = 0.5 p.u.; (c) ul,max and βxumax when pg = 1.0 p.u.; (d) ul,max and βxumax when pg = 1.5 p.u.
Figure 4. The maximum voltage and its location for different transmission distances. (a) ul,max and βxumax when pg = 0.0 p.u.; (b) ul,max and βxumax when pg = 0.5 p.u.; (c) ul,max and βxumax when pg = 1.0 p.u.; (d) ul,max and βxumax when pg = 1.5 p.u.
Energies 11 01790 g004
Figure 5. Ksynch of different transmission power and transmission distances.
Figure 5. Ksynch of different transmission power and transmission distances.
Energies 11 01790 g005
Figure 6. l of different frequency.
Figure 6. l of different frequency.
Energies 11 01790 g006
Figure 7. System model under the three-phase short circuit fault. (a) Schematic diagram of the fault location and related variables; (b) Sending end equivalent circuit under the fault.
Figure 7. System model under the three-phase short circuit fault. (a) Schematic diagram of the fault location and related variables; (b) Sending end equivalent circuit under the fault.
Energies 11 01790 g007
Figure 8. Voltage profile under the three-phase short circuit fault at lfmax.
Figure 8. Voltage profile under the three-phase short circuit fault at lfmax.
Energies 11 01790 g008
Figure 9. Schematic diagram of the generator electromagnetic power.
Figure 9. Schematic diagram of the generator electromagnetic power.
Energies 11 01790 g009
Figure 10. Schematic diagram of the critical phase angle.
Figure 10. Schematic diagram of the critical phase angle.
Energies 11 01790 g010
Figure 11. The swing curves of the sending-end generator power angle (classical model). (a) pg(0) = 0 p.u.; (b) pg(0) = 0.5 p.u.; (c) pg(0) = 1.0 p.u.; (d) pg(0) = 1.5 p.u.
Figure 11. The swing curves of the sending-end generator power angle (classical model). (a) pg(0) = 0 p.u.; (b) pg(0) = 0.5 p.u.; (c) pg(0) = 1.0 p.u.; (d) pg(0) = 1.5 p.u.
Energies 11 01790 g011aEnergies 11 01790 g011b
Figure 12. The swing curves of the sending-end generator power angle (detailed model). (a) pg(0) = 0 p.u.; (b) pg(0) = 0.5 p.u.; (c) pg(0) = 1.0 p.u.; (d) pg(0) = 1.5 p.u.
Figure 12. The swing curves of the sending-end generator power angle (detailed model). (a) pg(0) = 0 p.u.; (b) pg(0) = 0.5 p.u.; (c) pg(0) = 1.0 p.u.; (d) pg(0) = 1.5 p.u.
Energies 11 01790 g012
Table 1. Transmission Line Parameters.
Table 1. Transmission Line Parameters.
ItemsValues
Unit length line parametersResistance0.00801 Ω/km
Reactance0.83747 mH/km
Conductance0 S/km
Capacitance0.01383 μF/km
Propagation coefficientAttenuation constant (α)1.6273 × 10−5 km−1
Phase constant (β)1.06929 × 10−3 km−1
Surge impedance (ZC)246.135 ∠ −0.87° Ω
Table 2. Parameters of the sending-end and the receiving-end systems.
Table 2. Parameters of the sending-end and the receiving-end systems.
ItemsValues
Sending end systemRated capacity of the generator2 × SIL
Subtransient reactance of the generator0.1 p.u.
Rated capacity of the transformer2 × SIL
Leakage inductances of the transformer0.1 p.u.
Equivalent impedance of the sending-end system (xg)0.2 p.u.
Receiving-end systemShort circuit capacity of the receiving-end system20 × SIL
Equivalent impedance of the receiving -end system (xr)0.05 p.u.
Table 3. Description of specified points in Figure 4.
Table 3. Description of specified points in Figure 4.
Transmission Power pg/p.u.Transmission DistanceThe Maximum Voltage
ul,max/p.u.
The Maximum Voltage Location
βll/kmβxumaxxumax/km
01502448.31.08600
1672725.85.35790.31473.9
1802938.01.099158.12580.5
2103427.71.126185.23022.9
0.51502448.31.08100
1672725.83.59596.01566.9
1802938.01.072159.52603.4
2103427.71.1215.589.8
1.01502448.31.0985.488.1
1672725.82.446103.11682.8
1802938.01.071145.72378.1
2103427.71.08800
1.51502448.31.39964.31049.5
1672725.81.787104.11699.1
1802938.01.38589.91467.4
2103427.71.501101.01648.5
Table 4. Description of specified points in Figure 4.
Table 4. Description of specified points in Figure 4.
Transmission DistanceTransmission Power pg/p.u.Synchronization Coefficient Ksynch
βll/km
1502448.30−3.88
0.5−3.91
1.0−3.88
1.5−3.78
1672725.804.65
0.56.69
1.08.21
1.59.46
1802938.004.24
0.54.31
1.04.33
1.54.29
2103427.701.53
0.51.50
1.01.28
1.50.74

Share and Cite

MDPI and ACS Style

Xu, Z.; Yang, J.; Sheng, N. Infeasibility Analysis of Half-Wavelength Transmission Systems. Energies 2018, 11, 1790. https://doi.org/10.3390/en11071790

AMA Style

Xu Z, Yang J, Sheng N. Infeasibility Analysis of Half-Wavelength Transmission Systems. Energies. 2018; 11(7):1790. https://doi.org/10.3390/en11071790

Chicago/Turabian Style

Xu, Zheng, Jian Yang, and Nengjin Sheng. 2018. "Infeasibility Analysis of Half-Wavelength Transmission Systems" Energies 11, no. 7: 1790. https://doi.org/10.3390/en11071790

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop