1. Introduction
Electric power transmission and distribution systems have evolved significantly since the late 19th century to meet growing industrial and societal demands. Over the past two decades, these systems have undergone further transformation driven by rapid advancements in quantum technologies, digitalization, and the integration of renewable energy sources. These developments have not only reshaped the structure of modern grids but have also underscored the critical importance of accurate, traceable, and robust measurement systems to ensure the reliability, efficiency, and safety [
1,
2]. Such measurement systems must deliver high precision under challenging conditions. For direct current (DC) measurements, uncertainties better than 0.02% are typically required to ensure that overall system accuracy remains within 0.1% [
3]. For alternating current (AC) and impulse measurements, uncertainties below 1% are generally needed to guarantee accuracy levels within 3% [
4].
To meet these accuracy requirements, regular calibration of high-voltage measuring equipment is essential. This calibration not only minimizes measurement errors but also ensures consistency with national and international references. It supports compliance with standards such as IEC 17025 [
5], enhances confidence in measurement data, and reduces the risk of safety issues or product nonconformity. As the National Metrology Institute (NMI) in France, the LNE (Laboratoire National de Métrologie et d’Essais) is responsible for providing calibrations, tractable to international units (SI), of such quantities. Given that much of the high-voltage equipment is large, fixed, or integrated into the industrial infrastructure, on-site calibration is often the only viable option. A key component in these calibration systems is the high-voltage divider, which scales down voltages to levels compatible with standard measurement instruments such as voltmeters, digitizers, or oscilloscopes. The accuracy of the overall measuring system heavily depends on the performance of the divider, which must be specifically designed to handle the characteristics of voltage, such as DC, AC, or impulse.
However, conducting on-site calibrations using traditional voltage dividers has become increasingly difficult due to environmental regulations and concerns. The existing dividers [
6] rely on insulating substances like sulfur hexafluoride (SF
6) or oil, which, although effective electrically, pose serious environmental risks. SF
6, for instance, is one of the most potent greenhouse gases with a global warming potential thousands of times higher than CO
2. Similarly, oil-based systems involve risks of leakage, contamination, and complex disposal procedures. Regulatory frameworks, particularly in Europe [
7], are moving toward the restriction and eventual elimination of these substances from high-voltage equipment. This shift is driven by a growing need to align industrial practices with global climate and sustainability goals. The regulatory pressure, combined with growing client reluctance to host gas or oil-insulated devices on their sites, underscores the urgent need for more sustainable measurement solutions at very high voltages.
In response to these new environmental needs, we have initiated the development of a new voltage divider, designed specifically to enable high precision on-site measurements while aligning with environmental standards. Similar work has been conducted in the past [
8], but for voltages limited to only 200 kV. By eliminating the use of harmful insulating media, our new approach seeks to balance measurement performance at voltages much higher than 200 kV, operational practicality, and environmental responsibility. Nevertheless, this transition presents challenges as it can lead to a degradation in measurement accuracy compared to SF
6 or oil-based dividers, especially those developed recently by NMIs [
9,
10]. Transitioning to air-insulated dividers is a necessary evolution to meet future emerging environmental standards and to enable calibration operations on-site, especially in sensitive industrial environments.
This paper presents the design methodology, characterization results, and uncertainty analysis of a new voltage divider. The approach developed by LNE aims to meet the growing demand for on-site high-voltage calibration systems that are both technically reliable and environmentally sustainable, particularly in challenging industrial applications [
11,
12,
13], where voltages may reach up to 4 MV for impulse, 2.5 MV for DC, and 1.2 MV for AC. These levels require calibration capabilities, at lower levels, up to 800 kV, 500 kV, and 240 kV, respectively, based on the extrapolation factor of 5 specified in [
2] and validated in the 19ENG02 project [
14]. The developed divider exceeds these requirements, achieving voltage levels of 850 kV for impulse, 500 kV for DC, and 405 kV for AC.
Our prototype divider, built using natural insulation and with cost-effective components, achieves measurement uncertainties suitable for a wide range of calibration needs. We have shown that, with a careful component selection, mechanical design, and modular architectures, it is possible to achieve very good measurement performance.
2. Theoretical Framework and Background
The most basic device in a high-voltage measurement chain is the voltage divider,
Figure 1.
It consists of two impedances
Z1 and
Z2 connected in series. The input voltage
Vin is proportional to the output voltage
Vout based on the impedance ratio according to Equation (1).
This device acts as a voltage-to-voltage converter, reducing the voltage
Vin to a much lower voltage
Vout, typically below 1000 V, so that it can be safely measured using conventional instruments such as voltmeters, acquisition cards, oscilloscopes, or digitizers. Usually, a high-voltage divider is characterized by its scale factor (
SF), or transfer function, which is the ratio between
Vin and
Vout according to Equation (2). The scale factor of a divider indicates how much the input voltage is scaled down.
Several types of voltage dividers are used in high-voltage measurements. The selection and configuration of their impedances (
Z1 and
Z2) must be matched to the type of voltage being measured. Voltage transformers are common in power systems and offer high accuracy at low frequencies (15–400 Hz), better than 0.01% at 50 Hz, and calibration methods down to 0.002% [
15]. Resistive dividers are preferred for precise DC measurements, achieving better than 0.001% accuracy [
16] and capable of capturing fast transients like 1.2/50 µs with 0.5% accuracy when optimized [
17]. Capacitive dividers are mainly used for AC measurements up to several tens of kilohertz, with compressed gas types reaching 0.001% accuracy under strict temperature control [
18], while other types struggle to achieve better than 0.01%. The damped capacitive divider improves impulse measurement performance by adding a resistor to suppress high-frequency oscillations while maintaining standard AC accuracy. Mixed RC dividers combine resistive and capacitive branches in parallel and, with proper compensation, can reach bandwidths of several tens of MHz, making them suitable for both DC and AC applications. Finally, the universal divider includes two branches: a high-ohmic resistive branch for DC in parallel with a damped capacitive branch. Its key strength is the ability to measure all voltage types with good accuracy, including DC, AC, harmonics, supraharmonics, transients, disturbances, and combined waveforms. However, thermal interactions between branches must be carefully managed to ensure high accuracy. This solution was selected for its versatility: with only a single divider, it becomes possible to measure all types of phenomena encountered in high-voltage applications. Very few universal dividers have been developed by NMIs.
Table 1 presents two voltage dividers recently developed by National Metrology Institutes (NMIs). Divider 1 [
9] uses SF
6 insulation and is rated for impulse voltages up to 1400 kV. Divider 2 [
8], by contrast, uses air insulation but is limited to voltages up to 200 kV. The measurement uncertainties reported for both systems are consistent with the levels targeted in our work.
The universal divider is based on the Zaengl principle [
19], as described in
Figure 2.
RHV,
CHV, and
rHV constitute the impedance
Z1,
rd is an additional external damping resistor, and
LHV is its total inductance (inductance of components and connections).
RLV,
CLV, and
rLV compose the impedance
Z2.
LLV is its total inductance. The divider is connected to a digitizer, with its input impedance
Rosc//
Cosc, using a coaxial cable having a characteristic impedance
Za (
rc is its total resistance,
Cc is its total capacitance with neglecting its total inductance). To avoid reflections on the coaxial cable, a damping resistor
ra is added. Its value is approximately equal to the characteristic impedance of the cable.
For distortion-free measurements and to have optimum transfer in the divider, the time constants of the impedance
Z1 and the time constants of the impedance
Z2 must be matched. The value of components needs to be chosen to fulfill approximately the following conditions, Equations (3)–(5):
The non-inductive design prevents oscillations caused by the
RLC resonant circuit. For effective damping, the damping resistor can be calculated [
20] using Equation (6)
where
L is the total inductance of the impedance
Z1, and
C is its total capacitance. In practice, due to the difficulty of determining the total inductance of
Z1 with low uncertainty, the damping is implemented using a combination of internal and external resistors. The internal damping is achieved with the internal resistor
rHV, while the external damping is achieved with an external resistor, which is determined with experimentation (step response technique).
The most critical parameters for achieving high accuracy with a voltage divider are the voltage coefficient (
VC), temperature coefficient (
TC), and the self-heating. The
VC represents the relative deviation of the impedance when measured at 100% (
and 10% (
of the rated voltage using Equation (7).
The
TC represents the relative deviation of the impedance
ZT1 measured from the reference temperature
T1 and the measured resistance Z
T2 at the maximum operating temperature
T2, calculated according to Equation (8). It should be noted that this formula is only valid if the variation between the two temperatures is approximately linear, which is often the case over small temperature intervals.
The self-heating can be characterized by the relative deviation of the impedances
Zt1 and
Zt2 between two time points,
t1 and
t2, respectively, as defined in Equation (9). Unless otherwise specified, time
t1 is generally set to 1 min and
t2 is set to 10 min.
The most critical impedances for ensuring good accuracy are those subjected to high voltage. These include the high-voltage resistors (RHV), the high-voltage capacitance (CHV), and the damping resistor (rHV), which need to be selected with care.
3. Design Methodology
3.1. Selection of the DC Branch (RHV)
To minimize the influence of the leakage current of the resistor RHV, we decided to maintain the DC current at a high level of 0.5 mA. Under these conditions, the use of a shielding technique to eliminate the leakage current is unnecessary. However, the influence of self-heating and the influence of dissipated power must be carefully characterized.
Thick film resistors are commonly used in the field of high-voltage applications as they can handle extreme voltages up to several tens of kilovolts in air insulation. They are also specified to operate over a wide temperature range (e.g., from −55 °C to +225 °C). We have selected and measured the
TC, self-heating, and
VC of several thick-film resistors rated at 50 kV/200 MΩ.
Figure 3 presents the typical results obtained from these measurements. Selected with a
TC of 10 ppm/°C, it appears very suitable, but measurements from 0 °C to 85 °C reveal that its variation is not linear. Most resistor manufacturers calculate the
TC by measuring only the difference between two specific points (typically 25 °C and 85 °C) represented by the red line in
Figure 3a, sometimes leaving out information about the resistor’s behavior between these two points. The red line clearly shows a
TC of 10 ppm/°C between 25 °C and 85 °C, which is consistent with what is declared by the manufacturer, but in reality, the temperature dependence between 25 °C and 85 °C is outside this value.
The results also indicate that these resistors exhibit significant
VC in air insulation, with a resistance variation of approximately 0.1% from 5 kV to 50 kV (
Figure 3b), which is mainly due to the temperature rise within the resistive element of the resistors. The curve shows that their resistance increases steadily before stabilizing. This behavior is due to the internal temperature rise that only reaches a steady state after 10 min. The temperature increase caused by the applied voltage in air insulation makes it challenging to achieve high accuracies. This temperature rise directly affects both the VC and the self-heating behavior.
We decided then to use a set of a great number of low-voltage resistors (e.g., 500 V) assembled in series instead of a small number of high-voltage resistors (e.g., 50 kV). Low-voltage resistors typically exhibit a minimal VC and a linear TC over a wide temperature range. Such characteristics can be found in wire wound resistors, metal film resistors, or ultra-stable foil resistors. Our choice was on metal resistors as they are more readily available in high ohmic values (e.g., >1 MΩ) compared to wire wound resistors, which are only in low ohmic values (e.g., <100 kΩ). They are also relatively 20 to 30 times cheaper than ultra-stable foil resistors.
Resistors of 1 MΩ ± 1% from Vishay, type CMF60, 1 W, 500 V, were selected for their excellent characteristic in withstanding the stress generated by very fast impulses. The VC of these resistors have been measured to be 0.016%. At a rated voltage, the self-heating is only 0.0005%/min, which means that applying the rated voltage for up to 10 min results in a resistance variation of about 0.005%. The T.C is around 25 ppm/°C, which is sufficient to achieve a good accuracy.
Other resistors were also tested: metal electrode leadless face (MELF) resistors from Vishay, 1 MΩ, 300 V, 250 mW, 15 ppm/°C, exhibited better performance with a VC of 0.005% and self-heating of 0.001%. However, we decided not to use these resistors because we have discovered that they are sensitive to electric fields. Indeed, we have developed a 50 kV section by assembling 200 resistors in series on a printed circuit board (PCB). Despite the excellent characteristics of each individual component, it turned out that applying a high voltage generates an intense electric field around the resistors, which influences their VC. We have observed a VC of 0.1% of the 50 kV section instead of 0.005% when considering the VC of each resistor individually.
Resistors from Vishay, type FPT65, 1 MΩ, 1%, 10 ppm/°C, 250 mW have been also tested. They demonstrated a good performance, with a VC identical to the VC of the CMF60 type, but with a better self-heating (<0.0005%). Despite their excellent characteristics, these resistors are approximately five times more expensive than the CMF60 and are only available with very long lead times, which influenced our decision not to consider them.
3.2. Selection of AC and Impulse Branches (CHV and rHV)
The total capacitance of CHV needs to be in the range of 200 pF to 1 nF to minimize the impact of parasitic capacitances to ground and to limit the power dissipation by the voltage source during AC on-site measurements. The capacitor and the damping resistor must be selected carefully. The capacitor must be non-inductive and capable of handling very high currents. Similarly, the damping resistor rHV must also be non-inductive and capable of withstanding very high voltages. Indeed, during very fast transient phenomena (e.g., 1.2/50 µs), the impedance of the capacitor becomes equivalent to a short circuit at high frequencies. In such cases, a very high peak current flows through the capacitor, and a significant portion of the voltage is absorbed by the damping resistor. The capacitor then needs to handle a very high peak current, and the damping resistor needs to handle a very high peak voltage and peak power.
The current level that the capacitor must withstand and the voltage across the damping resistor, during the application of a 1 µs rise time pulse with an amplitude of 900 kV, are simulated and shown in
Figure 4. The pulse divider is modeled as an
RC circuit (neglecting the inductance) with a total capacitance of 200 pF and a total damping resistance of 500 ohms. The current through the capacitor spikes sharply to around 500 A at the initial application of voltage. The current then decreases exponentially as the capacitor charges, approaching zero as the voltage across the capacitor stabilizes. The voltage across the resistor follows the same behavior as the current. It peaks early in the process and then decreases exponentially as the capacitor charging completes. The simulation shows that the capacitor must handle a peak current of approximately 480 A (red curve), and the voltage across the resistor reaches approximately 250 kV (blue curve).
For impulse measurements, the capacitor needs to have a very good frequency and voltage linearity to avoid distorting the impulse wave shape to be measured. A good TC is also needed in order to handle its temperature rise during impulse measurements. Indeed, the application of the impulse will produce a localized temperature rise that can reach several tens of degrees Celsius due to the high current flowing through the capacitor and the damping resistor. For AC measurements, a good VC and a good self-heating effect are needed to achieve high accuracy when measuring the AC voltage.
The number of capacitors that meet these requirements is very limited. Capacitors with excellent performance for AC measurement have very low capabilities for handling high currents, while capacitors capable of absorbing high currents have poor AC characteristics. There are two types of capacitors that can meet our needs: negative/positive-zero (NP0) ceramic capacitors, known for their very low TC (<30 ppm/°C) but also known for being highly fragile to vibrations and transport. Polypropylene capacitors have a higher TC of around (e.g., <300 ppm/°C) but are reputed for their long-term stability, better durability, and their ability to withstand vibrations during transport. Since the divider used in this study will often be transported, we have chosen the second solution.
Polypropylene film capacitors type FKP4 from Wima (Folien Kondensator Polypropylen) have been selected for their small size compared to the FKP1 type. They have been chosen for their high dV/dt rating (high current peak withstanding). Capacitors of 0.1 µF/1000V have been selected; their dV/dt is equal to 9 kV/µs, and the maximum admissible current is then equal to C.dV/dt = 900 A. These capacitors have the ability to withstand 1.5 times of nominal voltage over short durations (e.g., 1.2/50 µs).
Temperature, voltage, and frequency dependencies of the capacitors have been checked to verify the values declared by the manufacturer. The frequency dependence of the capacitors was measured using a calibrated HP 4284A RLC meter. These measurements were performed at a low voltage (a few volts), allowing precise evaluation of the capacitance over a range of frequencies up to 100 kHz. To assess the temperature dependence, the capacitors were placed in a high-precision, temperature-controlled chamber, and measurements were carried out across a temperature range from 10 °C to 30 °C. This ensured a reliable characterization of thermal stability. The voltage dependence was investigated at 50 Hz by applying increasing AC voltages up to 600 V RMS. The applied voltage was measured using a calibrated voltmeter, and the current through the capacitor was recorded to determine the apparent capacitance at each voltage level. These methods allowed for a thorough verification of the values declared by the manufacturer under conditions representative of practical use.
The capacitors demonstrate good capacitance stability and a linear
TC around −200 ppm/°C, measured from 10 °C to 40 °C. The typical influence of frequency is shown in
Figure 5, conducted over frequencies ranging from 50 Hz to 100 kHz. The capacitance remains relatively stable for most of the lower frequency range up to 10 kHz, with only minor fluctuations. Beyond 10 kHz, there is a noticeable increase in capacitance of about 0.3%, with the values rising sharply, potentially caused by changes in dielectric properties. The dissipation factor starts near zero and remains minimal. Beyond 30 kHz, it rises sharply, indicating increased energy dissipation or losses, but still lower than 0.0004. The
VC of some capacitors has been checked up to 600 V rms; typically measured to be in the range of 0.3%, which appears to be a good compromise. These capacitors are capable of withstanding their rated voltage up to at least 2 kHz, then decrease significantly, taking into account the admissible rms current that they can handle. By using these capacitors, the final divider will be capable of measuring relatively high frequencies up to 2 kHz at a maximum voltage, even though calibration requests are absent at such high frequencies.
For the damping resistor rHV, we have chosen to connect a resistor in series with each capacitor. Assuming that each capacitor has an inductance of 100 nH, including the connections, Equation (6) gives a required resistance value of 1 Ω. Resistors of type WNB1R0FET from OMITHE have been selected for their high pulse capability. They are rated at 1 W and can withstand five times the rated power (i.e., 5 W) for 5 s. This means that the maximum energy these resistors can absorb is 5 W × 5 s = 25 J. Since the resistors are subjected to a maximum voltage of 500 V (when the series capacitor-resistor pair is exposed to a 1500 V pulse), the resulting absorbed energy is approximately 0.25 J during approximately 1 µs. For other longer impulses, the voltage at the terminals of the damping resistors decreases.
3.3. Electrical and Mechanical Design
Sections of 7 kV each have been designed in PCB FR4 boards (
Figure 6a). Each section contains 7 capacitors, 7 damping resistors, and 14 DC resistors. The precision components are arranged in a circular pattern, ensuring uniform voltage distribution. The symmetrical arrangement of the components helps maintain electrical stability and thermal balance. The layout follows best practices for high-voltage insulation, with clearance distances to prevent arcing. A 300 V/mm dielectric strength, proprietary to the PCB, taking into account its aging, has been used to fix the minimum distances between components to avoid possible flashover. The distances were doubled to allow each section to operate at 1.5 times its nominal voltage, i.e., 10.5 kV for impulse measurements. The HT_IN and HT_OUT terminals indicate designated input and output points. Three holes are used to insert threaded rods to fix the sections.
To reduce the weight of the divider and for environmental reasons explained in the introduction, we have chosen not to use oil or gas for electrical insulation. Instead, we decided to implement a divider with natural insulation (air). This choice comes with consequences as the use of air introduces an additional level of complexity in managing heat dissipation. Oil, with its thermal inertia and the same equivalent volume, has the advantage of maintaining a certain temperature homogeneity inside the divider. In contrast, the temperature of the air-insulated divider will be influenced by the heat generated by the components during the application of voltage and by the thermal exchange between the components and the external environment.
Three modules have been developed. Each one consists of 27 sections in a vertical configuration. The design has been chosen to prioritize compactness and coaxial alignment to reduce inductance. The sections are mounted in series inside a Plexiglas tube. The distance between the sections is fixed at 35 mm using epoxy spacers. The three modules have been cascaded in series to construct the final divider (
Figure 6b). We used three corona rings to reduce corona effects. For the first and second modules, we used two corona rings with a diameter of 500 mm and a tube size of 125 mm. For the last module, we used one corona ring with a diameter of 740 mm and a tube size of 180 mm. These corona rings, in addition to the coaxial geometric arrangement of the sections, significantly reduce corona effects.
To satisfy Equations (2) and (3), we developed the impedance
Z2 using the same components as the impedance
Z1 (
Figure 6c). This approach helps compensate for the effects of frequency, voltage, and temperature. Each individual element of the impedance
Z2 could be subjected, for better matching, to the same voltage and current constraints as each element of the impedance
Z1. We have then selected the components with the same technologies used in the sections. DC resistance type CMF60, capacitors type FKP4 from Wima, and damping resistors type WNB from Ohmite have been used. Of course, the values will differ from those of the sections, which will result in the compensation system being moderately effective. To satisfy Equation (5), achieving correct compensation for the inductance of the
Z1 is very challenging as it is difficult to estimate accurately. It is not necessary to minimize the inductance entirely, but rather to ensure that the equation is satisfied. For example, if the inductance of
Z1 is estimated at 10 µH, and the divider has a ratio of 1000, the inductance of
Z2 must be equal to 10 nH. The lower the voltage scale factor, the more the condition can be satisfied. This is also favorable because for smaller scale factors, the signal-to-noise ratio is better. Indeed, during a transient phenomenon, transmitted electromagnetic disturbances can be superimposed on the signal transmitted through the coaxial cable, which can influence the accuracy of measurement. The final divider has been adjusted to a scale factor of 1000 by several iterations to satisfy Equations (3)–(6). An external damped resistor of 200 Ω has been used.
A chassis has been developed with appropriate elements to fix the tubes. The impedance Z2 is fixed on the lower side of the chassis, and the modules are fixed on the upper side. Indeed, each module has been equipped with a flange on both sides, and the modules and corona rings could be fixed using these flanges. The flange features multiple holes arranged in a concentric pattern. The outer circle has evenly spaced holes for bolting the modules together. The inner holes are used to fix a threaded rod supporting the sections.
At the output of
Z2, a shielded triaxial cable with a 50 Ω impedance, and a capacitance of 2 nF is used to connect the divider to a digitizer with an input impedance of 30 pF//1 MΩ. This digitizer is exclusively used for impulse measurements. For AC measurements, it is replaced by a voltmeter with an input impedance of approximately 40 pF//1 MΩ. For DC measurements, a precision voltmeter with input impedance of 10 MΩ in parallel with an additional external resistor of 1.111 MΩ is used. In this case, the equivalent resistance in the output of the divider at DC is still 1 MΩ.
Table 2 summarizes the rated voltage that can handle the voltage divider.
The nominal impulse voltage of 850 kV has been derived from the accumulated nominal values of each section of the divider, with each section rated for 10.5 kV under 1.2/50 µs impulse conditions. The final configuration includes 81 sections (3 modules × 27 sections), resulting in a total rated voltage of 81 × 10.5 kV = 850.5 kV. Direct testing at 850 kV was not feasible in our current facility. Therefore, the performance of the divider was first verified at lower voltages (e.g., up to 350 kV) by comparison with our reference system [
16]. No significant deviation in the scale factor was observed within this voltage range. To support the extrapolation to 850 kV, we relied on the characterization of a single 10.5 kV section, whose linearity was measured from 1 kV to 10.5 kV. This extrapolation technique [
1,
2] is commonly used in the high-voltage field when no standard is available at such voltage levels. An extrapolation factor of 5 is allowed.
3.4. Environmental Considerations
The developed voltage divider does not utilize a hermetically sealed enclosure, but instead, it relies on natural air insulation within an open Plexiglas (PMMA) tube structure. It is specifically designed for operation in controlled environments, either on-site or at calibration facilities, where ambient temperatures are maintained between 10 °C and 30 °C and relative humidity remains below 80%. Under these conditions, the influence of environmental factors on electrical performance is minimal.
Several measures were implemented to ensure stability and robustness under these operational conditions. The resistors and capacitors used are industrial-grade, encapsulated components selected for their low sensitivity to environmental factors such as humidity and temperature. These choices contribute to the system reliability in metrology laboratories and semi-industrial settings. To ensure scale factor stability during use, particularly in on-site applications, the calibration procedure includes a verification step before and after each high-voltage measurement, using a reference system at a low voltage (<100 kV), as described in
Appendix A. This approach allows for early detection of any short-term drift caused by environmental or operational effects.
The mechanical structure employs FR4 PCB boards, epoxy spacers, and commercial polypropylene capacitors, materials selected for their proven electrical and mechanical performance in high-voltage systems. Although these materials are not specifically designed for harsh field conditions, they have shown good resilience under repeated high-voltage stress in controlled environments. For example, the polypropylene capacitors used in the high-voltage arm were subjected to over 1000 impulses (1.2/50 µs, 10 kV) during a component-level testing without measurable degradation. Similarly, the FR4-based sections and epoxy spacers showed no visible mechanical or dielectric deterioration.
That said, long-term environmental exposure remains a relevant consideration. FR4 may absorb moisture in high-humidity environments, potentially altering dielectric behavior, while epoxy spacers can degrade under thermal cycling. To mitigate these risks, the divider is operated strictly within its recommended environmental range and is stored and transported using UV-resistant and humidity barrier enclosures.
Our previous experience with smaller air-insulated dividers using similar Plexiglas constructions demonstrated long-term mechanical and thermal stability over several years of use. No significant performance deviations were observed under typical laboratory conditions. These findings support the suitability of this construction approach for higher voltage levels, provided standard environmental controls and handling precautions are observed. Although formal accelerated aging and endurance tests were not conducted as part of this study, the performance of the divider under these conditions could be planned for future work to further assess the durability of the materials and verify long-term reliability.
4. Experimental Characterization
4.1. Frequency and Impulse Response
According to our procedure, the scale factor of the voltage divider is typically determined up to 100 kHz at voltages above 100 V to ensure sufficient resolution while keeping the voltage below 1000 V. This limitation is mainly due to the constraints of the available equipment, such as the Fluke 5720 calibrator (Fluke Corporation, Everett, WA, USA), which cannot generate high frequencies at elevated voltages, and the physical height of the divider, which prevents the use of other instruments such as frequency analyzers. These analyzers are limited both by their maximum input voltage (typically around 10 V) and by environmental influences such as cable length and proximity effects (e.g., stray capacitances). For frequencies above 100 kHz, alternative techniques are more appropriate as explained below. The scale factor is determined by simultaneously measuring the input and output voltages: the input is applied using the calibrated Fluke 5720 (uncertainty <0.01%), and the output is measured using a calibrated voltmeter of a similar accuracy. This scale factor, measured up to 100 kHz, serves two purposes: it verifies the frequency response with respect to harmonics and supraharmonics, and it enables long-term monitoring of stability through annual calibration and drift checks performed before or after each measurement. The detailed on-site calibration procedure is provided in
Appendix A.
The frequency linearity of the scale factor has been measured at 200 V from DC to 100 kHz. The results are presented in
Table 3. A very good frequency linearity has been obtained with a flat frequency response within 0.2% up to 100 kHz. This is mainly due to the use of the same type of components in both impedances
Z1 and
Z2. This excellent linearity provides a reliable estimation of the scale factor if the divider is used to measure high-frequency phenomena (harmonics and supraharmonics up to at least 100 kHz).
For fast impulse measurements, performing a frequency sweep higher than 100 kHz is usually impossible due to the instrument’s limitation. However, we assess this using several methods:
Figure 7a,b illustrate the performance of the high-voltage divider evaluated both in the time and frequency domains. In
Figure 7a, the divider is subjected to a standard 1.2/50 µs lightning impulse with a peak amplitude of 210 kV. The voltage waveform is acquired at the output of the divider (red color), while the input reference signal (blue color) is measured using a standard high-voltage divider [
16] with a known bandwidth of 35 MHz. The response is clean, with no significant overshoot or oscillation, indicating that the divider reproduces the overall time domain shape of the impulse with good fidelity. To investigate the frequency-dependent behavior, the fast Fourier transform (FFT) of both the input and output waveforms was computed and is shown in
Figure 7b. Up to about 1 MHz, both spectra are nearly identical, indicating that the divider has a flat response and negligible amplitude distortion in this range. Beyond this frequency, the FFT magnitude of the divider begins to deviate from that of the reference. The difference becomes significant in the 1–20 MHz range, where the output signal of the divider attenuates more rapidly. The deviation becomes especially pronounced beyond ~10 MHz. It is important to note that this FFT comparison reflects the relative frequency response between the two dividers. Since the reference divider itself has a finite bandwidth (35 MHz), the measured frequency response of the divider may appear artificially better than it is beyond this limit. In other words, the FFT shows not the absolute frequency response of the divider but the difference between its response and that of the standard. Thus, the effective bandwidth of the divider can be estimated to be somewhat lower than 35 MHz, likely in the range of 10–15 MHz, although a more precise characterization would require step response analysis.
We have evaluated the dynamic performance of the divider, and its step response has been measured according to Annex C of IEC 60060-2 [
2]. An external damping resistor of 200 Ω have been used during these tests to suppress oscillations on the front and to better satisfy Equation (5).
Figure 7c shows the unit step response illustrating how the normalized amplitude evolves over time. A small high-frequency oscillatory behavior is observed, indicating minor overshoot and ringing, which suggests that the energy meter is adequately damped. The response stabilizes after approximately 0.5 µs, indicating that the system is capable of accurately measuring impulses with very fast rise times, such as 1.2/50 µs lightning impulses.
To validate the capability, especially for very fast impulses, we have used the convolution technique described in Annex D of IEC 60060-2 [
2] to determine the errors of the divider for fast impulses with front times of 0.84 µs, 1.2 µs, and 1.56 µs, each with a total duration of 50 µs. The results are presented in
Table 4. The peak voltage error is relatively small across all waveforms, ranging from 0.3% to 0.5%. Some variation is observed in the front time error, with the fastest waveform exhibiting the highest error at 2.4%, though this remains within acceptable limits.
4.2. DC and AC Performance
The characterizations at DC and AC/50–60 Hz have been performed for each phase before setting up the final divider. The characterization for each phase is important to ensure that the divider meets high accuracy. The most important parameters are the VC and self-heating. The VC measurements are presented as the relative deviation across voltage levels range from 10% to 100% of the rated voltage. The time behavior was assessed by applying the rated voltage for 10 min.
First, we have evaluated the voltage and time behavior of the individual sections. At DC, the sections exhibited very good voltage linearity with a maximum deviation of 0.006%. The time behavior was even better with a maximum deviation of 0.0005% over 10 min confirming its robustness for long-term voltage applications. For AC, as expected, the VC and self-heating effects were significantly higher, sometimes resulting in voltage deviations exceeding 0.6%, indicating a slightly higher sensitivity to voltage changes compared to DC. The time behavior showed a maximum deviation of 0.08% over 10 min, which is moderate compared with the VC.
The sections have also been tested by applying 1000 impulses 1.2/50 µs of 10 kV, with each impulse spaced 10 s apart. The objective was to test the insulation of the section and to verify the dielectric strength of all components (resistors and capacitors). After this, the DC and AC tests were remeasured once the components had returned to ambient temperature. The DC variations of sections before and after the application of 1000 impulses are extremely small, with a maximum deviation of 0.0002%, indicating excellent stability and excellent pulse capability of the selected resistors. The AC variations are more noticeable, with a variation of 0.07%, indicating slightly higher sensitivity of the sections compared with DC; however, it can be considered negligible, taking into account the large number of applied impulses spaced by only 10 s. Indeed, in routine calibration, the number of impulses is very limited, and the time spacing of the impulses is usually counted in minutes.
The sections have been validated, and their performance is in the same range as the results obtained with the individual elements, which confirms the predictability and calculability of our design. Indeed, by studying the behavior of individual elements, we can predict how the divider will behave. It appears that the influence of the electric field does not affect the performance of the individual elements, which validates our geometry.
Once the sections have been validated, we have then built three modules, each one containing 27 sections. We have evaluated the voltage and time behavior of the three developed modules. For DC, each module has been measured up to 185 kV by comparison with the LNE reference divider, which is capable of calibrating HVDC dividers with an uncertainty of 20 ppm. The modules exhibited very good voltage linearity, with a maximum deviation of 0.010%, and the time behavior showed a deviation of a maximum of 0.015% over 10 min. For AC, each module was measured by comparison with the LNE reference divider, which is capable of calibrating HVAC dividers with an uncertainty of 200 ppm. The VC was approximately 0.4% over the voltage range, and the time dependency was around 0.10% over ten minutes at the rated voltage. These results are consistent with those obtained with the section, which validates that our geometry is moderately sensitive to the electrical field.
Finally, the entire divider was tested at DC, and
Figure 8 represents the
VC of the scale factor of the divider and its variation over time. The parallel calibration method of the three modules was used to highlight the behaviour of the divider when the three sections are connected in series. The principle is that the final divider, at a maximum voltage, will be subjected to the same stresses as the three modules in parallel, but with one-third of the voltage. This method is used when a voltage reference is not available at the nominal voltage. The impedance Z2 was adjusted to achieve a ratio of 1000 with this parallel configuration.
The scale factor is plotted for different voltage levels (90 kV, 150 kV, 210 kV, 300 kV, 390 kV, 450 kV, and 550 kV) over 10 min. The curves show that the scale factor remains relatively stable, with only minor fluctuations over time for each voltage level. The stability of the scale factor over time is crucial for accurate high-voltage measurements, and the observed variations remain within a tight range (0.005%), indicating a well-performing voltage divider with a minimal time-dependent drift. The VC remains smooth, confirming a predictable change with voltage, which allows application of systematic corrections to reach an accuracy of at least 0.01%.
6. Discussion
The development of a high-voltage divider with air insulation instead of environmentally harmful substances like gas or oil is the best alternative to meet the regulatory requirements during transport or during the calibration itself at sensitive sites. Compared to traditional voltage dividers, the developed divider stands out from other precision or commercial dividers due to its simple and practical design; it uses readily available components, ensuring ease of sourcing worldwide with very reduced costs. Most of precision dividers that need high accuracy rely on expensive high-precision components and require long procurement times; our solution remains accessible to a much broader audience. In addition, its compact and lightweight structure allows for quick and easy on-site installation, without requiring heavy equipment like cranes or aerial platforms, thereby reducing the duration of the calibration and avoiding logistical constraints. This makes the divider highly portable without the need for special handling procedures.
A comprehensive characterization was performed at multiple levels: individual components, subsections, modules, and the complete system. The resulting measurement uncertainties are consistent with the precision expected in high-voltage applications. The divider satisfies the requirements for accurate measurement of DC, AC, and impulse waveforms. Due to its large bandwidth, it can also be used to accurately measure harmonics, supraharmonics (up to at least 100 kHz), and complex waveforms combining impulses and steady-state voltages.
The capacitors selected for the high-voltage arm are optimized for handling high peak currents and fast impulses. However, they are not ideal for AC voltage measurements when aiming for uncertainties comparable to those of a pure capacitive divider (e.g., <0.1%). Achieving such performance requires additional compensation for their voltage-dependent behavior on the low-voltage side. The solution to address this is to develop a dedicated low-voltage arm only for AC measurements, using capacitors that either compensate for the undesired voltage dependence or closely match the behavior of the high-voltage arm. This technique can be implemented experimentally by selecting and assembling low-voltage capacitors in a way that allows the low-voltage arm to emulate the characteristics of the high-voltage arm. This symmetry is expected to reduce the overall uncertainty by a factor of two or even three.
Our next objective is to increase the voltage capability of the divider up to 1.5 MV. This could be achieved by stacking three additional modules to reach the target voltage. However, this configuration would reduce the total capacitance to around 60 pF, which is insufficient to maintain high measurement accuracy due to the influence of parasitic capacitances to ground. To overcome this limitation, new developments have been initiated focusing on alternative structures, still using air insulation but increasing the capacitance of each section by a factor of 3 or 4. The aim is for the future 1.5 MV divider to have a total capacitance between 200 pF and 300 pF, ensuring accurate and stable performance for AC and impulses. The findings from this work will be presented in a forthcoming publication.