Next Article in Journal
An Adaptive Deep Learning Framework for Dynamic Image Classification in the Internet of Things Environment
Next Article in Special Issue
Laboratory Calibration of Energy Measurement Systems (EMS) under AC Distorted Waveforms
Previous Article in Journal
Crack Protective Layered Architecture of Lead-Free Piezoelectric Energy Harvester in Bistable Configuration
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Letter

On the Long-Period Accuracy Behavior of Inductive and Low-Power Instrument Transformers

by
Alessandro Mingotti
*,
Lorenzo Bartolomei
,
Lorenzo Peretto
and
Roberto Tinarelli
Department of Electrical, Electronic and Information Engineering, Guglielmo Marconi Alma Mater Studiorum, University of Bologna, Viale del Risorgimento 2, 40136 Bologna, Italy
*
Author to whom correspondence should be addressed.
Sensors 2020, 20(20), 5810; https://doi.org/10.3390/s20205810
Submission received: 8 September 2020 / Revised: 9 October 2020 / Accepted: 12 October 2020 / Published: 14 October 2020
(This article belongs to the Special Issue Advanced Transducers and Systems for Voltage and Current Measurement)

Abstract

:
The accuracy evaluation of instrument transformers is always a key task when proper control and management of the power network is required. In particular, accuracy becomes a critical aspect when the grid or the instrumentation itself is operating at conditions different from the rated ones. However, before focusing on the above non-rated conditions, it is important to fully understand the instrument transformer behavior at rated conditions. To this end, this work analyzed the accuracy behavior of legacy, inductive, and low-power voltage transformers over long periods of time. The aim was to find patterns and correlations that may be of help during the modelling or the output prediction of voltage transformers. From the results, the main differences between low-power and inductive voltage transformers were pointed out and described in detail.

1. Introduction

The ambitious goal of a fully decarbonized European energy supply planned for 2050 [1] requires that all involved actors work synergistically in that direction. A significant part of such a plan involves the massive diffusion and installation of renewable energy sources (RES). However, one of the drawbacks of their diffusion is the increase in grid-injected disturbances, and hence of power quality (PQ) issues [2,3,4,5], that may alter the correct operation of the grid.
A first consequence of the existence of PQ issues in the grid is the fact that proper monitoring, identification, and resolution must be implemented. Therefore, the measurement equipment, in-field deployed, to measure electrical quantities during the normal operation of the network should be also capable of working correctly during anomalous conditions.
As is well known, the devices that are meant to measure electrical quantities in the grid are the instrument transformers (ITs). They can be designed to be installed in all voltage levels (high, medium, and low voltage (HV, MV, and LV)), and they typically scale and send the measured quantities to data concentrators, acquisition systems, and cloud-based solutions.
With the introduction of RES and of a variety of intelligent electronic devices (IEDs), ITs are now required to operate in a harsher environment than in the past. In fact, they should be reliable and correctly measure electrical quantities when they are affected by all kinds of PQ issues. For example, the effects of various disturbances on ITs were assessed in [6,7,8], while authors of [9,10] evaluated how ITs contribute to the overall PQ of the network. Finally, the use of ITs for PQ evaluation was evaluated in [11].
Of course, an IT is not the only grid component that has to work in both normal and anomalous conditions. In fact, all electrical assets, such as energy meters [12,13,14], electric machines [15,16], and accessories [17,18,19], have to be properly designed to avoid (i) encountering any grid malfunctions or (ii) having corrupted and incorrect measurements sent and processed by typical algorithms dedicated to the control and management of the network [20,21,22].
In addition to what was mentioned above, it is clear that PQ, which directly affects the grid, is not the only issue related to electrical assets. In fact, external factors like temperature, humidity, electric fields, and pressure are influential quantities that modify the behavior of the ITs and, in some cases, lead to significant variation in their performance.
The literature is constantly being populated by new material trying to tackle every single aspect related to this topic. In [23,24], for example, the effect of moisture on ITs was studied. The behavior of ITs when subjected to an electric field was addressed in [25,26,27], while temperature as an influential factor was analyzed in [28,29,30].
In light of all of the above, this work aims to contribute in that direction. Its focus is on medium-voltage ITs (in particular, voltage transformers (VTs)), both the legacy and the new-generation ones, and the idea is to understand their accuracy behavior over long time intervals (compared with typical standard tests, which are single tests lasting no more than seconds/minutes). Accuracy is evaluated, according to the standards, in terms of ratio error and phase displacement. To really focus on the long time period behavior, the operating conditions of the ITs under test are the rated ones. The outcomes of this work aim to (i) provide the literature with a set of tests which was not available, (ii) help manufacturers and final users to understand the behavior of different types of VTs, and (iii) support the modelling of VTs, considering that each of them has a specific behavior over time.
The remainder of the work is structured as follows: Section 2 introduces and describes the IT scenario and the related standards. The measurement setup developed within this work is presented in Section 3, and the experimental tests and results performed and obtained by implementing this setup are contained in Section 4. Finally, Section 5 summarizes the main achievements and the conclusion of this research.

2. Instrument Transformers

2.1. Introduction and Standards

Instrument transformers are the key measurement devices for obtaining voltages and currents from the grid. In terms of technological development over the years, ITs can be distinguished into two categories: the legacy inductive ITs and the new generation of low-power ITs (LPITs), also referred to as non-conventional instrument transformers. This latter kind of transformer features smaller dimensions and weight, ease of installation in harsh environments, and larger bandwidth compared with the legacy ones. Furthermore, as the name implies, the LPIT’s output is typically one or two orders of magnitude lower (fewer volts, fewer milliamperes) than the output of an inductive IT. All these characteristics are encouraging the diffusion of LPITs in the distribution network; however, the low economic availability of distribution system operators (DSOs) to invest in meshed networks and a large portion of networks, like the medium- and low-voltage ones, makes the legacy IT a very common and reliable device that is worth being studied and deployed in the field.
All kinds of ITs are standardized by the IEC 61869 series. In particular, IEC 61869-1 [31] and -6 [32] are the general documents for legacy ITs and LPITs, respectively (both current and voltage). The remaining documents of the standard series deal with specific kinds of transformers, providing the necessary information on testing, specifications, accuracy, and definitions for final users and manufacturers. For example, IEC 61869-2 [33] and -3 [34] describe inductive current and voltage transformers (CTs and VTs), respectively, while IEC 61869-10 [35] and -11 [36] are the analogous documents for the low-power current and voltage transformers (LPCTs and LPVTs), respectively.

2.2. Uncertainty Evaluation

First of all, ITs must be compliant with the rated operating conditions of the power network. Two widely adopted standards that define limits and thresholds for the grid quantities are the EN 50160 [37] and the IEEE 519 [38], in which rated and distorted conditions of the grid are considered. Second, each IT is associated with an accuracy class (AC) that defines its performance.
As is well known, accuracy is evaluated by means of two parameters, the ratio error ε and the phase displacement Δφ, which are defined as follows:
ε = k r V 2 V 1 V 1 × 100 %
Δ φ = V ^ 2 V ^ 1
where V 1 and V 2 are the rms values of the 50 Hz component of the primary and secondary voltages, respectively, and k r is the rated transformation ratio of the device under test. Finally, V ^ 1 and V ^ 2 are the 50 Hz phase components of the primary and secondary voltages, respectively.
In what follows, ε and Δφ are the two parameters monitored to understand the accuracy behavior of the ITs in a long time interval. In addition, each ε and Δφ computation is associated with a temperature measurement of the working environment.

2.3. Types of VTs

In Section 2.1, a first distinction among ITs was provided. In this section, more details are given about the VTs used and tested in this work.
The most common VT is the well-known inductive one, which is schematized in Figure 1. It consists of a metallic, magnetic core and of two copper windings referred to as primary and secondary. Each winding has a specific number of turns ( N 1 and N 2 in the picture) that makes it possible to obtain the desired transformer ratio. The inductive VT working principle is based on two famous laws: Faraday’s and Lenz’s. This way, a scaled secondary voltage can be obtained starting from a fixed primary voltage. In particular, it is
N 1 N 2 = V 1 V 2
As for its operation, the inductive VT is affected by some loss sources, which can be due to the Joule effect, leakage flux, eddy currents, and hysteresis (not detailed here because this is out of the scope of the work).
Turning to the new generation of VTs, the LPVTs, they are often designed with a working principle that is not correlated with the induction laws. In fact, two of the most common types of LPVTs are the resistive and the capacitive ones. Both their schematics are depicted in Figure 2 and, as it can be noted, both LPVTs rely on the voltage divider principle.
The simplest one is the resistive LPVT. It consists of two resistors on which V 1 is divided. Therefore, R 1 is a very high resistor compared to R 2 , and the ratio is fixed according to the requirements of the device connected to the secondary terminals of the LPVT. In terms of accuracy, R 1 is typically less accurate due to its high-voltage nature, and hence it is more complicated and expensive to build. The input–output relation of a resistive LPVT is as follows:
V 2 = V 1 R 2 R 1 + R 2
As for capacitive LPVTs, once again the voltage divider principle applies, but it takes into account the behavior of a capacitor, which is substantially opposite to the resistor. In fact, looking at Figure 2, it can be seen that C 2 is the biggest capacitor, subjected to the lowest voltage part of V 1 . In terms of accuracy, C 2 is usually a commercial capacitor, while C 1 can be obtained from the body of the LPVT, hence from the resin or other insulating materials that comprise its case. Consequently, there is not much control over the insulating material accuracy; hence it is the less accurate capacitor of the two. The input–output relation of a capacitive LPVT is as follows:
V 2 = V 1 C 1 C 1 + C 2

3. Experimental Measurement Setup

The measurement setup developed to perform the experimental tests is presented in Figure 3.
It consists of the following:
  • An Agilent 6813B power source to feed the insulating and the step-up transformers. It features a max rms voltage of 300 V and a max power of 1750 VA.
  • An insulating transformer with 1:1 ratio. Its main purpose is to provide galvanic insulation between the low- and the medium-voltage sides.
  • A step-up transformer with 1:142 ratio. It guarantees a stable 20/√3 kV voltage at the terminals of the transformers under test.
  • A reference capacitive-resistive VT used to measure the rated voltage that has to be used in the accuracy computations. It features a 5981:1 ratio and an accuracy of 0.03% on the ratio and 0.3 mrad on the phase, according to its calibration certificate.
  • Three off-the-shelf VTs under test. Two are LPVTs, while the third is a classical inductive VT. Their main characteristics are listed in Table 1. In particular, the type, the primary and the secondary rated voltages ( V 1 R and V 2 R ), and the accuracy class (AC) of the VTs are reported.
  • A pure-resistive voltage divider, previously characterized, has been used to reduce the secondary voltage of B to a level suitable for the acquisition system. The divider ratio is 100:1 and it is composed of high-precision resistors that can be considered insensitive to temperature variations (few ppm/°C).
  • An NI9239 data acquisition board (DAQ) to collect the secondary voltages of the three transformers under test plus the secondary voltage of the reference one. The DAQ features a full scale of ±10 V, a 24-bit architecture, 50 kSa/s per channel of maximum acquisition rate, and gain and offset errors of ±0.03% and ±0.008%, respectively.
  • An NCT75 programmable temperature sensor, the characteristics of which are listed in Table 2. The sensor was used to measure the ambient temperature at which the transformers were operating.
To summarize, the experimental setup was developed to feed the transformers under test with their rated voltage (20/√3 kV) and then to measure and acquire their secondary voltages plus the reference one. In addition, all the measurements are associated with the ambient temperature at which they were collected.

4. Experimental Tests and Results

4.1. Experimental Tests

The main idea of the work was to understand the accuracy behavior of the LPVTs and classical VTs over time when they operate at rated conditions of voltage, frequency, and temperature. The behavior was evaluated in what was called a “long time” interval because, compared to the typical seconds/minutes-long tests described by the standards, what was performed in this work can be considered long. However, even if long tests were performed, they were not considered aging tests because that was not the purpose. Therefore, using the measurement setup described in Section 3, the test consists of feeding the three VTs at 20/√3 kV, 50 Hz, and uncontrolled temperature (but within typical laboratory values, 25 to 27 °C) for 12 days. Within such a time range, every 4 h, 100 measurements of ratio error and phase displacement were performed together with the temperature measurement of the laboratory. Afterwards, the mean value of the 100 measurements and the standard deviation of ε and Δφ were computed and collected to be further processed and assessed.

4.2. Experimental Results

As previously anticipated, the experimental results are given in terms of ε and Δφ for the three VTs under test. Furthermore, such results are associated with their standard deviation of the mean.
Starting from ε, Figure 4 shows the results obtained from measurements on VTs A, B, and C. The graphs contain ε (in %) and the temperature (in °C) on the left and right y-axes, respectively. The two quantities are also differentiated by using blue for ε and orange for temperature. On the x-axes, the time expressed in hours can be found. Considering that the adopted unit for the x-axis is 24 h, in every section of the graphs, one day of measurements can be seen.
Analogously, the results for Δφ (measured in rad) are provided in Figure 5.

4.3. Discussion

The first comment that has to be made is that the three VTs were working properly within their accuracy class limits (Table 1). To better see that, Table 3 contains the measured minimum, maximum, and overall variation of ε and Δφ ( and Δφ, respectively) over the entire duration of the test.
The values in the table are reported with a number of significant digits that takes into account the standard deviation of the mean associated with the measurements from each VT. From a cursory comparison of the three VTs, it can be concluded that VT A (the resistive one) showed less disperse ε and Δ φ values, whereas B (the inductive VT), had the worst performance. In detail, the maximum mean standard deviation observed for ε and Δ φ were in the order of 10−7 and 10−9, 10−4 and 10−7, and 10−6 and 10−8 for A, B, and C, respectively. However, the accuracy level obtained for all the VTs was appropriate for the type of test and study performed on them. To complete the discussion about the uncertainty related to results, it is worth highlighting that the uncertainty introduced by the measurement setup was omitted to avoid any confusion (however, it was in the order of 10−5 and 10−4 for ε and Δφ, respectively, for B). The reason for this is that measurements were performed with the same setup; hence any contribution that it introduced affected all measurements in the same way.
The second comment concerns the general trend of the graphs. In fact, what clearly emerged from both Figure 4 and Figure 5, hence for both ε and Δ φ , is that the inductive VT values were completely stochastic, while the low-power ones (A and C) followed the temperature profile with different laws. To validate the previous statement, the correlation coefficients of the three VTs, which linked both ε and Δ φ with the temperature ( T ), were computed and collected in Table 4. As it emerges from the table, temperature was totally uncorrelated with ε and Δ φ in the case of the inductive B, while an almost complete correlation was found for A and C and for both ε and Δφ. In addition, the obtained coefficients can be considered statistically significantly different from the other parameters computed and listed in Table 4. In fact, it contains the p-value and the 95% confidence interval (CI) limits for each of the provided coefficients.
As an example, Figure 6 shows the correlation between ε and Δ φ and the temperature for VT C.
Focusing now on the patterns of transformers A and C, which follow the temperature profile, the causes have to be explained. For both VTs, the explanation lies in their design and building methodology. In particular, transformer A, the resistive one, consists of a high-voltage resistor (see R 1 in Figure 2) that often features worse performance than the low-voltage resistor due to the high costs associated with the high-voltage technology. Therefore, resistor R 1 is more affected by temperature, causing a variation of the transformer ratio. To be more specific, as it can be seen in the upper graph of Figure 4, ε is negative and keeps decreasing when the temperature increases. In fact, if, as expected, R 1 increases more than R 2 with the temperature, the dominant ratio R 1 / R 2 of Equation (4) increases. Consequently, the actual transformation ratio increases compared to k r , resulting in a further decrease in the computed quantity ε .
Similar reasoning can be used for transformer C, the capacitive one. This time, referring to the left scheme of Figure 2, the biggest and more accurate capacitor is C 2 , and the voltage is measured on its terminals. As for C 1 , what is typically done is that it is obtained from the case-shell of the capacitor, as mentioned before; hence the technical limitations and the need to withstand high voltages result in a less accurate C 1 . Linking this behavior with what was obtained in the bottom graph of Figure 4, it can be noted that a negative ε increases with an increase in temperature. In other words, the temperature affects the dielectric material properties of C 1 increasing its value, hence reducing the ratio C 2 / C 1 and then leading to the measured effect.
Turning to the phase displacement, from all graphs and from Table 3, it is clear that very small variations were measured (fraction of mrad). For VT B, the behavior was the same as ε , hence displaying a stochastic spread of the measured values over time. Furthermore, even for VTs A and C, that which was observed for ε could also be extended for Δφ. In fact, Δφ is inversely proportional to the temperature.
From the above discussion, some relevant conclusions are as follows:
  • In the considered short temperature range, it is possible to conclude that the accuracy of inductive VTs was not affected by temperature. However, it is not automatically true that this conclusion holds for wider ranges of temperature.
  • Over long time intervals, the developed setup allowed even the tiniest variations of ε and Δφ due to very small changes in the ambient temperature to be seen. As a result, such slight temperature variations had a visible effect on the LPVT’s accuracy (even if absolutely moderate). The same could not be stated for the inductive ones.
  • The different ways of spreading ε and Δφ values between LPVTs and legacy ITs raises a significant issue: when modelling them, it is not possible to simulate their behavior in the same way, even at rated conditions.
  • What was observed for LPVT might be a strength or a drawback of this new generation of transformers. However, what is clear is that, considering their diffusion among distribution networks, such information has to be considered when choosing the technology to be installed in a particular operating environment.
  • What was observed at rated conditions and at an ambient temperature that varies not more than a couple of degrees reinforced the studies on the influential quantities affecting the behavior, and hence the accuracy, of all kind of ITs.
  • The different behaviors recorded for classical VTs and LPVTs highlight the need to differentiate the modelling of such transformers. Therefore, general models should be particularized for the specific VT that is going to be used in the considered application.

5. Conclusions

This paper aimed to tackle the accuracy behavior of voltage transformers during long time intervals. To this end, after introducing various voltage transformers and their properties, a measurement setup was introduced. This setup was used to assess the accuracy of three off-the-shelf voltage transformers (capacitive, inductive, and resistive) during a 12-day period. The test was performed at rated conditions but without full temperature control. The results assessment was performed in terms of two widely adopted indices, the ratio error and the phase displacement. The results revealed a huge difference between the behavior of the legacy, inductive, and low-power transformers. These results highlighted how the design of the low-power type influenced its performance, even at rated conditions, while the same did not apply for the inductive type. A strictly related consequence of that is the need to tackle the modelling and the behavior prediction of voltage transformers depending on their design and working principle.

Author Contributions

Conceptualization, A.M. and R.T.; methodology, R.T.; validation, L.P.; formal analysis, L.B. and R.T.; investigation, A.M. and L.B.; resources, L.P.; data curation, A.M. and L.B.; writing—original draft preparation, A.M.; writing—review and editing, R.T. All authors have read and agreed to the published version of the manuscript.

Funding

This research was partially funded by the European project EURAMET 17IND06 “Future Grid II: Metrology for the next-generation digital substation instrumentation”.

Conflicts of Interest

The authors declare no conflict of interest. The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript; or in the decision to publish the results.

References

  1. Our Vision for a Clean Planet for All. Available online: https://ec.europa.eu/clima/sites/clima/files/docs/pages/vision_1_emissions_en.pdf (accessed on 3 September 2020).
  2. Aggarwal, A.; Das, N.; Arora, M.; Tripathi, M.M. A novel hybrid architecture for classification of power quality disturbances. Presented at the 2019 6th International Conference on Control, Decision and Information Technologies (CoDIT 2019), Paris, France, 23–26 April 2019; pp. 1829–1834. [Google Scholar]
  3. Mohammadi, M.; Afrasiabi, M.; Afrasiabi, S.; Parang, B. Detection and classification of multiple power quality disturbances based on temporal deep learning. Presented at the 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe (EEEIC/I and CPS Europe), Genova, Italy, 11–14 June 2019. [Google Scholar]
  4. Xin, K.; Duan, B.; Qu, X. Classification for multiple power quality disturbances based on deep forest. Presented at the IECON Proceedings (Industrial Electronics Conference), Lisbon, Portugal, 14–17 October 2019; pp. 3387–3392. [Google Scholar]
  5. Zhao, L.; Gai, M. Identification of multiple power quality disturbances based on the improved s-transform and wavelet transform energy distribution. J. Inf. Hiding Multimed. Signal Process. 2018, 9, 188–197. [Google Scholar]
  6. Crotti, G.; Giordano, D.; D’Avanzo, G.; Femine, A.D.; Gallo, D.; Landi, C.; Palladini, D. Measurement of dynamic voltage variation effect on instrument transformers for power grid applications. Presented at the I2MTC 2020—International Instrumentation and Measurement Technology Conference, Dubrovnik, Croatia, 25–28 May 2020. [Google Scholar]
  7. Mingotti, A.; Peretto, L.; Tinarelli, R.; Zhang, J. Use of COMTRADE fault current data to test inductive current transformers. Presented at the 2019 IEEE International Workshop on Metrology for Industry 4.0 and IoT, MetroInd 4.0 and IoT, Naples, Italy, 4–6 June 2019; pp. 103–107. [Google Scholar]
  8. Seo, H.C.; Kim, C.H. The analysis of power quality effects from the transformer inrush current: A case study of the jeju power system, Korea. Presented at the IEEE Power and Energy Society 2008 General Meeting: Conversion and Delivery of Electrical Energy in the 21st Century (PES), Pittsburgh, PA, USA, 20–24 July 2008. [Google Scholar]
  9. Draxler, K.; Stybliková, R. Influence of instrument transformers on quality of electrical power and energy measurement. Presented at the IEEE International Symposium on Industrial Electronics, Vigo, Spain, 4–7 June 2007; pp. 1317–1321. [Google Scholar]
  10. Kezunovic, M.; Portillo, L.; Karady, G.; Kucuksari, S. Impact of optical instrument transformer characteristics on the performance of protective relays and power quality meters. Presented at the 2006 IEEE PES Transmission and Distribution Conference and Exposition: Latin America (TDC’06), Caracas, Venezuela, 15–18 August 2006. [Google Scholar]
  11. Kaczmarek, M.; Nowicz, R. Application of instrument transformers in power quality assessment. Presented at the International Symposium: Modern Electric Power Systems (MEPS’10), Wroclaw, Poland, 20–22 September 2010. [Google Scholar]
  12. Bartolomei, L.; Mingotti, A.; Pasini, G.; Peretto, L.; Rinaldi, P.; Tinarelli, R.; Puddu, L. Performance evaluation of an energy meter for low-voltage system monitoring. In Proceedings of the 22nd World Congress of the International Measurement Confederation (IMEKO), Belfast, UK, 3–6 September 2018. [Google Scholar]
  13. Das, H.; Saikia, L.C. Ethernet based smart energy meter for power quality monitoring and enhancement. Presented at the 2017 Recent Developments in Control, Automation and Power Engineering (RDCAPE 2017), Noida, India, 26–27 October 2017; pp. 187–191. [Google Scholar]
  14. Palacios-Garcia, E.J.; Rodriguez-Diaz, E.; Anvari-Moghaddam, A.; Savaghebi, M.; Vasquez, J.C.; Guerrero, J.M.; Moreno-Munoz, A. Using smart meters data for energy management operations and power quality monitoring in a microgrid. Presented at the IEEE International Symposium on Industrial Electronics, Edinburgh, UK, 19–21 June 2017; pp. 1725–1731. [Google Scholar]
  15. Ganev, E. Selecting the best electric machines for electrical power-generation systems: High-performance solutions for aerospace more electric architectures. IEEE Electrif. Mag. 2014, 2, 13–22. [Google Scholar] [CrossRef]
  16. Masoum, M.A.S.; Fuchs, E.F. Power Quality in Power Systems and Electrical Machines, 2nd ed.; Academic Press: Cambridge, MA, USA, 2015; pp. 1–1123. [Google Scholar]
  17. Peretto, L.; Tinarelli, R.; Ghaderi, A.; Mingotti, A.; Mazzanti, G.; Valtorta, G.; Danesi, S. Monitoring cable current and laying environment parameters for assessing the aging rate of MV cable joint insulation. Presented at the Annual Report—Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Cancun, Mexico, 21–24 October 2018; pp. 390–393. [Google Scholar]
  18. Bhattacharyya, S.; Chakraborty, A.; Saha, B.; Chatterjee, S. Electric stress analysis of a medium voltage cable termination subjected to standard and non-standard lightning impulse voltages. Presented at the 2016 International Conference on Intelligent Control, Power and Instrumentation (ICICPI), Kolkata, India, 21–23 October 2016; pp. 169–173. [Google Scholar]
  19. Patel, U.; Jayaram, S.H. Impact of poor power quality on stress grading system of cable termination. Presented at the Annual Report—Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), Montreal, QC, Canada, 14–17 October 2012; pp. 463–466. [Google Scholar]
  20. Mingotti, A.; Peretto, L.; Tinarelli, R. Accuracy evaluation of an equivalent synchronization method for assessing the time reference in power networks. IEEE Trans. Instrum. Meas. 2018, 67, 600–606. [Google Scholar] [CrossRef]
  21. Murray, R.; De Kock, J. Instrument transformers influence on harmonic measurements for grid code compliance. Presented at the 2018 IEEE 4th Global Electromagnetic Compatibility Conference (GEMCCon), Stellenbosch, South Africa, 7–9 November 2018. [Google Scholar]
  22. Mingotti, A.; Peretto, L.; Tinarelli, R. An equivalent synchronization for phasor measurements in power networks. Presented at the AMPS 2017—IEEE International Workshop on Applied Measurements for Power Systems, Liverpool, UK, 20–22 September 2017. [Google Scholar]
  23. Ren, X.; Ding, W.; Zhou, W.; Fan, C.; Wu, J.; Liu, Y.; Zhang, G. The moisture in SF6 insulated CTs considering current and change of ambient temperature. IEEE Trans. Power Deliv. 2014, 29, 1184–1191. [Google Scholar] [CrossRef]
  24. Yan, Z.; Ren, X.; Ren, H.; Ding, W. Study on condensation of the moisture in current transformers with current flow considering sharp temperature decrease. Appl. Mech. Mater. 2013, 241–244, 322–327. [Google Scholar] [CrossRef]
  25. Lesniewska, E.E.; Olak, J. Improvement of the insulation system of unconventional combined instrument transformer using 3-d electric-field analysis. IEEE Trans. Power Deliv. 2018, 33, 2582–2589. [Google Scholar] [CrossRef]
  26. Yan, X.; Sun, Y.; Yu, C.; Xie, D. Electric field analysis and optimal design of main insulation for oil-immersed inverted current transformers. Diangong Jishu Xuebao/Trans. China Electrotech. Soc. 2014, 29, 37–43. [Google Scholar]
  27. Youhua, G.; Dan, G.; Yanbin, L.; Shuqiu, G.; Guogang, W. Improvement of main insulation structure for 110 kV electric power transformer based on electric field analysis. Presented at the 11th International Conference on Electrical Machines and Systems (ICEMS), Wuhan, China, 17–20 October 2008; pp. 4427–4430. [Google Scholar]
  28. Li, Z.; Du, Y.; Abu-Siada, A.; Li, Z.; Zhang, T. A new online temperature compensation technique for electronic instrument transformers. IEEE Access 2019, 7, 97614–97623. [Google Scholar] [CrossRef]
  29. Sivan, V.; Robalino, D.M.; Mahajan, S.M. Measurement of temperature gradients inside a medium voltage current transformer. Presented at the 2007 39th North American Power Symposium (NAPS), Las Cruces, NM, USA, 30 September–2 October 2007; pp. 242–245. [Google Scholar]
  30. Mingotti, A.; Peretto, L.; Tinarelli, R.; Ghaderi, A. Uncertainty sources analysis of a calibration system for the accuracy vs. temperature verification of voltage transformers. In Proceedings of the 22nd World Congress of the International Measurement Confederation (IMEKO), Belfast, UK, 3–6 September 2018. [Google Scholar]
  31. IEC 61869-1: 2010. Instrument Transformers—Part 1: General Requirements; International Standardization Organization: Geneva, Switzerland, 2010. [Google Scholar]
  32. IEC 61869-6:2016. Instrument Transformers—Part 6: Additional General Requirements for Low-Power Instrument Transformers; International Standardization Organization: Geneva, Switzerland, 2016. [Google Scholar]
  33. IEC 61869-2:2012. Instrument Transformers—Part 2: Additional Requirements for Current Transformers; International Standardization Organization: Geneva, Switzerland, 2012. [Google Scholar]
  34. IEC 61869-3:2011. Instrument Transformers—Part 3: Additional Requirements for Inductive Voltage Transformers; International Standardization Organization: Geneva, Switzerland, 2011. [Google Scholar]
  35. IEC 61869-10:2018. Instrument Transformers—Part 10: Additional Requirements for Low-Power Passive Current Transformers; International Standardization Organization: Geneva, Switzerland, 2018. [Google Scholar]
  36. IEC 61869-11:2018. Instrument Transformers—Part 11: Additional Requirements for Low-Power Passive Voltage Transformers; International Standardization Organization: Geneva, Switzerland, 2018. [Google Scholar]
  37. BS EN 50160:2010+A1:2015. Voltage Characteristics of Electricity Supplied by Public Electricity Networks; BSI Standards Publication: London, UK.
  38. IEEE Std. 519-2014. Recommended Practice and Requirements for Harmonic Control in Electric Power Systems; IEEE: New York, NY, USA, 2014. [Google Scholar]
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Figure 1. Basic schematic of an inductive transformer.
Figure 1. Basic schematic of an inductive transformer.
Sensors 20 05810 g001
Figure 2. Working principle of a capacitive (left) and a resistive (right) low-power voltage transformer (LPVT).
Figure 2. Working principle of a capacitive (left) and a resistive (right) low-power voltage transformer (LPVT).
Sensors 20 05810 g002
Figure 3. Schematic representation of the measurement setup.
Figure 3. Schematic representation of the measurement setup.
Sensors 20 05810 g003
Figure 4. Ratio error results for VTs (AC) (from top to bottom).
Figure 4. Ratio error results for VTs (AC) (from top to bottom).
Sensors 20 05810 g004aSensors 20 05810 g004b
Figure 5. Phase displacement for VTs (AC) (from top to bottom).
Figure 5. Phase displacement for VTs (AC) (from top to bottom).
Sensors 20 05810 g005aSensors 20 05810 g005b
Figure 6. Correlation graphs between ε and T (top) and Δφ and T (bottom) for VT C.
Figure 6. Correlation graphs between ε and T (top) and Δφ and T (bottom) for VT C.
Sensors 20 05810 g006
Table 1. Main characteristics of the three voltage transformers (VTs) under test.
Table 1. Main characteristics of the three voltage transformers (VTs) under test.
LPVTType V 1 R   ( V ) V 2 R   ( V ) AC
ALPVT—Resistive 20,000 / 3 3.25 / 3 0.5
BVT—Inductive 20,000 / 3 133 / 3 0.5
CLPVT—Capacitive 20,000 / 3 2.27 / 3 0.5
Table 2. Main characteristics of the NCT75 temperature sensor.
Table 2. Main characteristics of the NCT75 temperature sensor.
Feature–Value
Resolution12 bitsAccuracy±1 °C
Input Voltage3 V to 5.5 VUpdate Rate80 ms
Temperature Range−55 to 125 °C
Table 3. Minimum, maximum, and variation of ε and Δφ during the 12-day test.
Table 3. Minimum, maximum, and variation of ε and Δφ during the 12-day test.
ε [%]Δφ [rad]
minmaxdε minmaxφ
A−0.04713690.03232160.07945850.0066417470.0069250650.000283318
B−0.01190.10510.11700.00188920.00308840.0011992
C−0.261155−0.1566760.1044790.010263140.011084110.00082096
Table 4. Correlation coefficients and statistical parameters for all VTs and both parameters ε and Δφ.
Table 4. Correlation coefficients and statistical parameters for all VTs and both parameters ε and Δφ.
εT
[-]
p-Value95% CI min95% CI maxΔφ–T
[-]
p-Value95% CI min95% CI max
A−0.873<0.0001−0.92−0.803−0.898<0.0001−0.936−0.841
B−0.0110.930−0.245−0.2250.0210.864−0.215−0.255
C0.922<0.00010.8770.951−0.919<0.0001−0.949−0.873

Share and Cite

MDPI and ACS Style

Mingotti, A.; Bartolomei, L.; Peretto, L.; Tinarelli, R. On the Long-Period Accuracy Behavior of Inductive and Low-Power Instrument Transformers. Sensors 2020, 20, 5810. https://doi.org/10.3390/s20205810

AMA Style

Mingotti A, Bartolomei L, Peretto L, Tinarelli R. On the Long-Period Accuracy Behavior of Inductive and Low-Power Instrument Transformers. Sensors. 2020; 20(20):5810. https://doi.org/10.3390/s20205810

Chicago/Turabian Style

Mingotti, Alessandro, Lorenzo Bartolomei, Lorenzo Peretto, and Roberto Tinarelli. 2020. "On the Long-Period Accuracy Behavior of Inductive and Low-Power Instrument Transformers" Sensors 20, no. 20: 5810. https://doi.org/10.3390/s20205810

APA Style

Mingotti, A., Bartolomei, L., Peretto, L., & Tinarelli, R. (2020). On the Long-Period Accuracy Behavior of Inductive and Low-Power Instrument Transformers. Sensors, 20(20), 5810. https://doi.org/10.3390/s20205810

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop