A Hybrid Machine Learning and NGO Algorithm Approach for Fault Classification and Localization in Electrical Distribution Lines
Abstract
1. Introduction
- A fault localization model based on the cubic spline interpolation method is developed.
- The NGO algorithm is applied as an optimization method for fault resistance estimation.
- A machine learning decision tree is used for classification.
- A comprehensive dataset is generated using MATLAB/Simulink (R2020a) based on the modified IEEE 34-bus distribution network, covering various fault scenarios (fault types, load variations, fault resistance levels, and voltage conditions).
2. Problem Definition
2.1. System Configuration
2.1.1. Transmission Line
2.1.2. Fault Distance
2.1.3. Bus S Voltage
2.1.4. Fault Resistance
2.1.5. Loads
3. Intelligent Fault Location and Classification Method
3.1. Data Collection for Machine Learning
3.1.1. Single-Resistance Faults

- Sweep ranges.
3.1.2. Three-Resistance Faults


- Sweep ranges.
3.1.3. The Data Collection Algorithm in Parallel Computing
| Algorithm 1: Pseudo-code of the data collection in parallel computing. | |
| input | 1: create function of simulation that read the input parameter and run simulation and gives the values of short-circuit for each phase a, b and c. 2: enter the fixed parameters such as the line and station impedance. 3: load the matrix that contains all the parameter values. 4: run parfor loop. 5: read the parameter of each step of the loop. 6: called function of simulation. 7: save the data into matrix 6D for single resistance fault and 8D for three resistance faults. 8: end of parfor loop. |
| output | |
3.2. Intelligent Digital Protection System
3.3. Fault Localization and Classification Algorithm
3.3.1. Fault Distance Estimation
- Input the fault resistance value.
- Estimate the short-circuit current values using 2D or 4D cubic spline interpolation.
- Estimate the fault distance using 1D cubic spline interpolation.
3.3.2. Fault Resistance Estimation
3.3.3. Constraints
- The fault distance of each phase must be a real positive value, as defined in Equations (8) and (9):
- The short-circuit current estimated using cubic spline interpolation must be equal to the value measured by the current transformer, as defined in Equation (10) and (11):
- Fault resistance considered as the decision variable, and it is constrained within predefined lower and upper bounds, as defined in Equation (12):
3.3.4. Multi-Objective Optimization Using NGO Algorithm
| Algorithm 2: Pseudo-code of the multi-objective optimization using NGO. | |
| input | 1: Input the optimization problem variable: fault resistance upper and lower bound and initiate weight of the three-objective function in Equations (7), (13) and (14). 2: Set the number of iterations and population . 3: Set random population using Equation (17) or Equation (18) and their evaluation using Equation (19). 4: Run loop for iterations. 5: Exploration using Equations (20) and (21). 6: Exploitation using Equations (22) and (23). 7: Save the best solution. 8: End loop for. 9: Output best optimal fault resistance solution. |
| searching | |
| output | |
3.3.5. Fault Classification
3.3.6. Fault Zone
4. Computational Experiments and Results
4.1. Case Study
- Five different fault distances from 5% to 95% of the total line length.
- Three different fault resistances: 0, 10, 50 and 100 Ω.
- Three different voltage source substations: 95%, 100%, and 105%.
- Three different voltage phase angles: 0°, 120°, and 240°.
- Three different load consumptions: 80%, 100%, and 120%.
- Ten fault types: A-g, B-g, C-g, AB, BC, AC, AB-g, BC-g, AC-g, and ABC-g.
- A total of 1000 test case chosen randomly for each fault type.

4.2. Results
4.3. Discussion
4.3.1. Fault Distance and Resistance Impact
4.3.2. Voltage Magnitude and Phase Angle Impact
4.3.3. Load Consumption Impact
4.3.4. Fault Type Diversity
4.3.5. Impact of Other Fault Location Methods
4.3.6. Calculation Time and Large Data Capacity Impact
5. Conclusions
Author Contributions
Funding
Data Availability Statement
Acknowledgments
Conflicts of Interest
Abbreviations
| PMUs | Phasor measurement units |
| ML | Machine learning |
| DL | Deep learning |
| ANN | Artificial neural network |
| DNN | Deep neural network |
| WT | Continuous wavelet transform |
| DWT | Discrete wavelet transform |
| VMD | Variational mode decomposition |
| CNN | Convolutional neural network |
| LSTM | Long short-term memory |
| TGATv2 | Graph attention network |
| VAE | Variational autoencoder |
| GCN | Graph convolution network |
| CPU | Central processing unit |
| CT | Current transformer |
| PT | Potential transformer |
| NGO | Northern goshawk optimization |
| , , | Post-fault sending-end voltage of bus S corresponding to phase a, b, and c in kV |
| , , | Post-fault voltage at the fault location corresponding to phase a, b, and c in kV |
| Post-fault sending-end voltage vector of bus S corresponding to phase a, b, and c in kV | |
| Post-fault voltage vector at the fault location corresponding to phase a, b, and c in kV | |
| , , | Post-fault sending-end current corresponding to phase a, b, and c in A |
| , , | Post-fault current at the fault location corresponding to phase a, b, and c in A |
| Post-fault sending-end current vector corresponding to phase a, b, and c in A | |
| Post-fault current vector at the fault location corresponding to phase a, b, and c in A | |
| Post-fault load current vector corresponding to phase a, b, and c in A | |
| Post-fault short-circuit current in A | |
| , | Short-circuit current of the first and the second faulted phase estimate by machine learning using cubic spline interpolation in A |
| , | Short-circuit current of the first and the second faulted phase measured by current transformer in A |
| Load impedance matrix in Ω | |
| Transmission line impedance matrix in Ω | |
| Self-impedance of phases a, b, and c in Ω | |
| Mutual impedance between phases n and m, where n and m are the phases a, b or c in Ω | |
| Fault resistance in Ω | |
| , , | Fault resistance of each phase a, b, and c in Ω |
| Lower bound of the fault resistance in | |
| Upper bound of the fault resistance in Ω | |
| , | Population of northern goshawks in Ω |
| ith proposed solution of fault resistance in Ω | |
| Value of the jth fault resistance specified by the ith proposed solution in Ω | |
| , | New status for the ith proposed solution in Ω |
| , | jth dimension solution in Ω |
| Fault resistance for the ith proposed solution in Ω | |
| , , | Pre-fault power consumed by phase a, b, and c in kW |
| Total active power consumption in the substation in kW | |
| Power base in VA | |
| , , | First, second, and third objective function |
| Multi-objective optimization function | |
| Objective function value vector | |
| Objective function value obtained by ith proposed solution | |
| , | Objective function value based on first phase of NGO |
| Objective function value | |
| Number of population members | |
| Number of problem variables | |
| Random natural number in interval [1, N] | |
| Random number in interval [0, 1] | |
| Random number that can be 1 or 2 | |
| Iteration counter | |
| Maximum number of iterations | |
| Distance between the sending end and the fault location in km | |
| Transmission line length in km | |
| Fault distance in km | |
| Total length of the faulted line in km | |
| Faulted zone in km | |
| Faulted zone coefficient |
References
- Neri Junior, A.L.; Moreira, F.A.; de Souza, B.A. Fault location on radial distribution systems using wavelets and artificial neural networks with a new data processing feature. Adv. Electr. Comput. Eng. 2024, 24, 3–10. [Google Scholar] [CrossRef]
- Akdağ, M.; Mami, M.S.; Akmaz, D. Enhancing fault location accuracy in transmission lines using transient frequency spectrum analysis: An investigation into key factors and improvement strategies. Electricity 2024, 5, 861–876. [Google Scholar] [CrossRef]
- Nsaif, Y.M.; Lipu, M.S.H.; Hussain, A.; Ayob, A.; Yusof, Y.; Zainuri, M.A.M.Z. New voltage based fault detection technique for distribution network connected to photovoltaic sources using variational mode decomposition integrated ensemble bagged trees approach. Energies 2022, 15, 7762. [Google Scholar] [CrossRef]
- Adewole, A.C.; Tzoneva, R.; Behardien, S. Distribution network fault section identification and fault location using wavelet entropy and neural networks. Appl. Soft Comput. 2016, 46, 296–306. [Google Scholar] [CrossRef]
- Bramareswara Rao, S.N.V.; Pavan Kumar, Y.V.; Amir, M.; Muyeen, S.M. Fault detection and classification in hybrid energy-based multi-area grid-connected microgrid clusters using discrete wavelet transform with deep neural networks. Electr. Eng. 2025, 107, 8481–8498. [Google Scholar] [CrossRef]
- Aslan, Y.; Yağan, Y.E. Artificial neural-network-based fault location for power distribution lines using the frequency spectra of fault data. Electr. Eng. 2017, 99, 301–311. [Google Scholar] [CrossRef]
- Pathirage, G.; Razzaghi, R.; Andrew, L. Fault location in power distribution networks using frequency analysis of traveling waves. Electr. Power Syst. Res. 2025, 249, 111971. [Google Scholar] [CrossRef]
- Cheng, L.; Wang, T.; Wang, Y. A novel fault location method for distribution networks with distributed generations based on the time matrix of traveling-waves. Prot. Control Mod. Power Syst. 2022, 7, 46. [Google Scholar] [CrossRef]
- Rezaei, D.; Gholipour, M.; Parvaresh, F. A single-ended traveling-wave-based fault location for a hybrid transmission line using detected arrival times and tw’s polarity. Electr. Power Syst. Res. 2022, 210, 108058. [Google Scholar] [CrossRef]
- Mishra, S.; Gupta, S.; Yadav, A. Novel two-terminal fault location approach utilizing traveling-waves for series compensated line connected to wind farms. Electr. Power Syst. Res. 2021, 198, 107362. [Google Scholar] [CrossRef]
- Jin, W.; Wang, D.; Gao, H.; Peng, F.; Guo, Y.; Gao, M.; Wang, J. Two-terminal traveling wave fault location approach based on frequency dependent electrical parameters of hvac cable transmission lines. Electr. Power Syst. Res. 2024, 235, 110842. [Google Scholar] [CrossRef]
- Wang, Y.; Xie, L.; Liu, Y.; Zeng, X.; Bi, L.; Liu, F.; Tang, X. Fault location method for distribution network considering distortion of traveling wavefronts. Int. J. Electr. Power Energy Syst. 2024, 159, 110065. [Google Scholar] [CrossRef]
- Gabr, M.A.; Ibrahim, D.K.; Ahmed, E.S.; Gilany, M.I. A new impedance-based fault location scheme for overhead unbalanced radial distribution networks. Electr. Power Syst. Res. 2017, 142, 153–162. [Google Scholar] [CrossRef]
- Shu, H.; Nguyen, L.M.T.; Nguyen, X.V.; Doan, Q.H. Fault location on three-terminal transmission lines without utilizing line parameters. Electricity 2025, 6, 42. [Google Scholar] [CrossRef]
- Wang, Y.; Qi, X.; Chen, Y. Enhanced fault localization in multi-terminal transmission lines using novel machine learning. Int. J. Simul. Multidiscip. Des. Optim. 2024, 15, 15. [Google Scholar] [CrossRef]
- Faza, A.; Al-Mousa, A.; Alqudah, R. Optimal PMU placement for fault classification and localization using enhanced feature selection in machine learning algorithms. Int. J. Energy Res. 2024, 2024, 5543160. [Google Scholar] [CrossRef]
- He, G.; Liang, D.; Zhao, Y.; Wang, X. Enhanced fault localization for active distribution networks via robust three-phase state estimation. Energies 2025, 18, 2551. [Google Scholar] [CrossRef]
- Dashtdar, M.; Hussain, A.; Al Garni, H.Z.; Mas’ud, A.A.; Haider, W.; AboRas, K.M.; Kotb, H. Fault location in distribution network by solving the optimization problem based on power system status estimation using the PMU. Machines 2023, 11, 109. [Google Scholar] [CrossRef]
- Ozupak, Y. Machine Learning-Based Fault Detection in Transmission Lines: A comparative study with random search optimization. Bull. Pol. Acad. Sci. Tech. Sci. 2025, 73, e153229. [Google Scholar] [CrossRef]
- Najafzadeh, M.; Pouladi, J.; Daghigh, A.; Beiza, J.; Abedinzade, T. Fault detection, classification and localization along the power grid line using optimized machine learning algorithms. Int. J. Comput. Intell. Syst. 2024, 17, 49. [Google Scholar] [CrossRef]
- Kim, M.-S.; An, J.-G.; Oh, Y.-S.; Lim, S.-I.; Kwak, D.-H.; Song, J.-U. A method for fault section identification of distribution networks based on validation of fault indicators using artificial neural network. Energies 2023, 16, 5397. [Google Scholar] [CrossRef]
- Zhou, C.; Gui, S.; Liu, Y.; Ma, J.; Wang, H. Fault location of distribution network based on back propagation neural network optimization algorithm. Processes 2023, 11, 1947. [Google Scholar] [CrossRef]
- Alhanaf, A.S.; Balik, H.H.; Farsadi, M. Intelligent fault detection and classification schemes for smart grids based on deep neural networks. Energies 2023, 16, 7680. [Google Scholar] [CrossRef]
- Jamali, S.; Bahmanyar, A.; Ranjbar, S. Hybrid classifier for fault location in active distribution networks. Prot. Control Mod. Power Syst. 2020, 5, 17. [Google Scholar] [CrossRef]
- El Ghaly, A. Hybrid ml algorithm for fault classification in transmission lines using multi-target ensemble classifier with limited data. Energies 2025, 6, 4. [Google Scholar] [CrossRef]
- Nguyen, N.B.; Van Dai, L. Fault identification, classification, and location on transmission lines using combined machine learning methods. Int. J. Eng. Technol. Innov. 2022, 12, 91–109. [Google Scholar] [CrossRef]
- Nguyen, Q.M.; Nguyen, T.K.; Vu, H.G. Fault classification and localization in power transmission line based on machine learning and combined CNN-LSTM models. Energy Rep. 2024, 12, 5610–5622. [Google Scholar] [CrossRef]
- Herrada, A.; Orozco-Henao, C.; Pulgarin Rivera, J.D.; Mora-Florez, J.; Marin-Quintero, J. Fault detection system for smart city distribution networks: A long short-term memory-based approach. Energies 2025, 18, 3453. [Google Scholar] [CrossRef]
- Tunio, N.A.; Hashmani, A.A.; Khokhar, S.; Tunio, M.A.; Faheem, M. Fault detection and classification in overhead transmission lines through comprehensive feature extraction using temporal convolution neural network. Eng. Rep. 2024, 6, e12950. [Google Scholar] [CrossRef]
- Hou, S.; Wang, X. Distribution network fault segment localization method based on transfer entropy mtf and improved alexnet. Energies 2025, 18, 4627. [Google Scholar] [CrossRef]
- Ma, X.; Zhen, W.; Ren, H.; Zhang, G.; Zhang, K.; Dong, H. A method for fault localization in distribution networks with high proportions of distributed generation based on graph convolutional networks. Energies 2024, 17, 5758. [Google Scholar] [CrossRef]
- Lu, T.; Hou, S. Fault location algorithm for distribution network with distributed generation based on domain-adaptive TGATv2. IET Gener. Transm. Distrib. 2025, 19, e70033. [Google Scholar] [CrossRef]
- Khan, M.A.; Asad, B.; Vaimann, T.; Kallaste, A.; Pomarnacki, R.; Hyunh, V.K. Improved fault classification and localization in power transmission networks using vae-generated synthetic data and machine learning algorithms. Machines 2023, 11, 963. [Google Scholar] [CrossRef]
- Wu, S.; Yan, X. Power line fault detection combining deep learning and digital twin model. Int. J. Adv. Comput. Sci. Appl. 2025, 16, 705–717. [Google Scholar] [CrossRef]
- Rafique, F.; Fu, L.; Mai, R. End to end machine learning for fault detection and classification in power transmission lines. Electr. Power Syst. Res. 2021, 199, 107430. [Google Scholar] [CrossRef]
- Dai, J.; Zhang, Z.; Li, S.; Li, L. Research on fault section location in an active distribution network based on improved subtraction-average-based optimizer. Symmetry 2025, 17, 107. [Google Scholar] [CrossRef]
- Dashtdar, M.; Bajaj, M.; Hosseinimoghadam, S.M.S.; Mérshêkáér, H. Fault location in distribution network by solving the optimization problem using genetic algorithm based on the calculating voltage changes. Soft Comput. 2022, 26, 8757–8783. [Google Scholar] [CrossRef]
- Wen, J.; Qu, X.; Liu, J.; Lin, S.; Xiao, Q. A novel fault location method for the active distribution network based on dynamic quantum genetic algorithm. Electr. Eng. 2024, 106, 4719–4735. [Google Scholar] [CrossRef]
- Xu, W.; Li, J.; Yang, L.; Yu, Q. Faults locating of power distribution systems based on successive PSO-GA algorithm. Sci. Rep. 2024, 14, 11259. [Google Scholar] [CrossRef]
- Albarakati, A.J.; Azeroual, M.; Boujoudar, Y.; ELIysaouy, L.; Aljarbouh, A.; Tassaddiq, A.; ELMarkhi, H. Multi-agent-based fault location and cyber-attack detection in distribution system. Energies 2023, 16, 224. [Google Scholar] [CrossRef]
- Li, B.; Qian, G.; Tang, L.; Sun, P.; Wu, Z. Fault location and route selection strategy of distribution network based on distributed sensing configuration and fuzzy c-means. Energies 2025, 18, 3271. [Google Scholar] [CrossRef]
- Janjic, A.; Velimirovic, L. Integrated fault location and isolation strategy in distribution networks using markov decision process. Electr. Power Syst. Res. 2020, 180, 106172. [Google Scholar] [CrossRef]
- Chaitanya, B.K.; Yadav, A. Intelligent fault detection and classification scheme for distribution lines integrated with distributed generators. Comput. Electr. Eng. 2018, 69, 28–40. [Google Scholar] [CrossRef]
- Swetapadma, A.; Yadav, A. A hybrid method for fault location estimation in a fixed series compensated lines. Measurement 2018, 123, 8–18. [Google Scholar] [CrossRef]
- Hosen, M.M.; Alam, M.S.; Rashid, S.; Mostafa, S.M.G. Optimized economic dispatch and battery sizing in wind microgrids: A depth of discharge perspective. Electricity 2025, 6, 51. [Google Scholar] [CrossRef]
- Yang, L.; Ningyun, L.; Xiuli, W.; Bin, J. Islanding fault detection based on data-driven approach with active developed reactive power variation. Neurocomputing 2019, 337, 97–109. [Google Scholar] [CrossRef]
- Yuan, C.; Liao, Y.; Kong, L.; Xiao, H. Fault diagnosis method of distribution network based on time sequence hierarchical fuzzy petri nets. Electr. Power Syst. Res. 2021, 191, 106870. [Google Scholar] [CrossRef]
- Mishra, M.; Panigrahi, R.R. Taxonomy of high impedance fault detection algorithm. Measurement 2019, 148, 106955. [Google Scholar] [CrossRef]
- Azeroual, M.; Boujoudar, Y.; Bhagat, K.; ElIysaouy, L.; Aljarbouh, A.; Knyazkov, A.; Fayaz, M.; Qureshi, M.S.; Rabbi, F.; EL Markhi, H. Fault location and detection techniques in power distribution systems with distributed generation: Kenitra city (Morocco) as a case study. Electr. Power Syst. Res. 2022, 209, 108026. [Google Scholar] [CrossRef]
- Guerraiche, K.; Abbou, A.B.; Dekhici, L. Intelligent fault detection and location in electrical high-voltage transmission lines. Rev. Roum. Sci. Tech. Sér. Électrotech. Énergétique 2024, 69, 269–276. [Google Scholar] [CrossRef]
- Wang, J.; Mokhlis, H.; Mansor, N.N.; Illias, H.A.; Ramasamy, A.K.; Wu, X.; Wang, S. Smart fault detection, classification, and localization in distribution networks: Ai-driven approaches and emerging technologies. IEEE Access 2025, 13, 141664–141693. [Google Scholar] [CrossRef]
- Shafiullah, M.; AlShumayri, K.A.; Alam, M.S. Machine learning tools for active distribution grid fault diagnosis. Adv. Eng. Softw. 2022, 173, 103279. [Google Scholar] [CrossRef]
- Cao, Y.; Tang, J.; Shi, S.; Cai, D.; Zhang, L.; Xiong, P. Fault diagnosis techniques for electrical distribution network based on artificial intelligence and signal processing: A Review. Processes 2025, 13, 48. [Google Scholar] [CrossRef]
- Filomena, A.D.; Resener, M.; Salim, R.H.; Bretas, A.S. Distribution systems fault analysis considering fault resistance estimation. Int. J. Electr. Power Energy Syst. 2011, 33, 326–1335. [Google Scholar] [CrossRef]
- Shahnia, F.; Arefi, A.; Ledwich, G. Mathematical Optimization of Unbalanced Networks with Smart Grid Devices. In Electric Distribution Network Planning; Springer: Singapore, 2018; pp. 69–78. [Google Scholar] [CrossRef]
- IEC 60038:2009; International Standard. International Electrotechnical Commission: Geneva, Switzerland, 2009. Available online: https://standards.iteh.ai/catalog/standards/sist/bd26a0a9-bf9f-4094-9ab3-0401e5c3ad69/iec-60038-2009 (accessed on 15 December 2021).
- Paithankar, Y.G.; Bhide, S.R. Introduction. In Fundamentals of Power System Protection; Prentice-Hall of lndia Private Limited: New Delhi, India, 2003; pp. 1–3. ISBN 81-203-2194. [Google Scholar][Green Version]
- Phadke, A.G.; Thorp, J.S. Protection Systems with Phasor Inputs. In Synchronized Phasor Measurements and Their Applications; Pai, M.A., Stankovic, A., Eds.; Springer: New York, NY, USA, 2008; pp. 197–219. [Google Scholar] [CrossRef]
- Mirshekali, H.; Dashti, R.; Keshavarz, A.; Shaker, H.R. Machine Learning-Based Fault Location for Smart Distribution Networks Equipped with Micro-PMU. Sensors 2022, 22, 945. [Google Scholar] [CrossRef]
- Jamil, M.; Sharma, S.K.; Singh, R. Fault detection and classification in electrical power transmission system using artificial neural network. SpringerPlus 2015, 4, 334. [Google Scholar] [CrossRef]
- Richardson, J.; Reiner, P.; Wilamowski, B.M. Cubic spline as an alternative to methods of machine learning, in Industrial Informatics (INDIN). In Proceedings of the 2015 IEEE 13th International Conference on Industrial Informatics (INDIN), Cambridge, UK, 22–24 July 2015; IEEE: New York, NY, USA, 2015. [Google Scholar] [CrossRef]
- Dehghani, M.; Hubálovský, Š.; Trojovský, P. Northern Goshawk Optimization: A New Swarm-Based Algorithm for Solving Optimization Problems. IEEE Access 2021, 9, 162059–162080. [Google Scholar] [CrossRef]
- Deb, K. Classical Methods. In Multi-Objective Optimization Using Evolutionary Algorithms; John Wiley & Sons: Chichester, UK, 2001; pp. 47–75. ISBN 047187339X. [Google Scholar]
- Mitchell, T.M. Decision Tree Learning. In Machine Learning; McGraw-Hill: New York, NY, USA, 1997; pp. 52–78. ISBN 0070428077. [Google Scholar]
- Csanyi, E. What Would be the Worst Type of Three Phase Faults (And Why It Happens). Electrical Engineering Portal. 2020. Available online: https://electrical-engineering-portal.com/worst-type-three-phase-faults (accessed on 4 January 2020).
- Baughman, M.L.; Liu, C.C.; Dugan, R.C.; Liu, E.; Carneiro, S.; Niebur, D.; Mccalley, J.D.; Baldick, R.; Joann, V.; Staron, J.V. IEEE 34 Node Test Feeder; Power System Analysis, Computing and Economics Committee, Distribution System Analysis Subcommittee; IEEE Power Engineering Society: Piscataway, NJ, USA, 2004. [Google Scholar]
- Deng, P.D.; Irungu, G.K.; Munda, J. Implementation of a Deep Learning ANN-based Algorithm utilizing the IEEE 34 Bus Test System to Investigate the Effects of Distributed Generation on Fault Diagnosis in Distribution Networks; Engineering, Technology & Applied Science Research: Gastouni, Greece, 2025; Volume 15, pp. 19506–19521. [Google Scholar] [CrossRef]
- Dashti, R.; Daisy, M. Single phase fault location in electrical distribution feeder using hybrid method. Energy 2016, 100, 356–368. [Google Scholar] [CrossRef]
- Ray, P.; Mishra, D.P. Support vector machine-based fault classification and location of a long transmission line. Eng. Sci. Technol. Int. J. 2016, 19, 1368–1380. [Google Scholar] [CrossRef]
- Grigsby, L.L.; McDonald, J.D.; Harlow, J.H. (Eds.) Power System Analysis and Simulation. In The Electric Power Engineering Handbook, 3rd ed.; CRC Press: Boca Raton, FL, USA, 2012; Volume 5, pp. 1–13. ISBN 978-1-4398-5634-5. [Google Scholar]


















| Algorithm | Convergence Behavior | Sensitivity to Parameters | Applicability to Active Distribution Networks (ADNs) | Remarks |
|---|---|---|---|---|
| PSO (Particle Swarm Optimization) | Moderate; can get trapped in local minima | High; requires careful tuning of inertia weight and acceleration coefficients | Limited in highly nonlinear or multi-modal ADN scenarios | Efficient for simple networks but less reliable under DG penetration |
| GA (Genetic Algorithm) | Slow; may require many generations | Moderate; crossover and mutation rates need tuning | Can handle nonlinear objectives but computationally intensive for large ADNs | Effective for global search but convergence may be slow |
| GWO (Grey Wolf Optimizer) | Good exploration, but may stagnate | Moderate; performance sensitive to leader hierarchy parameters | Suitable for medium-complexity networks; may underperform in dynamic ADNs | Balance between exploration/exploitation, but parameter tuning crucial |
| NGO (Nelder–Goldberg Optimizer) | Fast; robust global and local search | Low; minimal parameter sensitivity | Highly suitable for complex, nonlinear, multi-modal ADNs | Handles multi-modal objective functions efficiently, ensures accurate fault localization and faster convergence |
| Ref. | IEEE Test System/Case Study | Objective Function | Optimization/Learning Method | Category | Main Limitation |
|---|---|---|---|---|---|
| [1] | Distribution feeder | Minimize classification error | Wavelet + ANN | Signal Processing + ML | Sensitive to noise and parameter selection |
| [2] | Transmission line | Fault distance accuracy | Transient frequency spectrum analysis | Signal Processing | Sensitive to noise, high sampling required |
| [3] | PV-integrated network | Voltage variation | VMD + ensemble trees | ML/DL | May not generalize to high-DG penetration |
| [4] | Distribution feeder | Entropy-based error | Wavelet + neural networks | Signal Processing + ML | Sensitive to noise |
| [5] | Microgrid cluster | Detection accuracy | DWT + DNN | Signal Processing + ML | May require high sampling |
| [6] | Distribution feeder | Spectral feature loss | Neural networks on frequency spectra | Signal Processing | Requires spectral accuracy |
| [7] | Distribution network | Frequency deviation | Traveling wave frequency analysis | Signal Processing | Requires precise timing |
| [8] | DG network | Traveling wave timing error | Time matrix method | Signal Processing | Needs accurate measurement |
| [9] | Transmission line | Arrival time error | Single-ended traveling wave | Signal Processing | Sensitive to noise |
| [10] | Wind-compensated line | Traveling wave mismatch | Two-terminal method | Signal Processing | Sensitive to parameter variations |
| [11] | HVAC cable | Frequency-dependent impedance error | Two-terminal analytical method | Signal Processing | Needs precise line parameters |
| [12] | Transmission line | Wavefront distortion error | Traveling-wave-based | Signal Processing | Sensitive to distortion modeling |
| [13] | Unbalanced radial network | Impedance mismatch | Analytical/impedance method | Signal Processing | Limited to radial networks |
| [14] | Three-terminal line | Fault distance error | Parameter-independent method | Signal Processing | Accuracy affected by topology changes |
| [15] | Multi-terminal line | Localization error | ML-based | ML | Scalability to very large networks |
| [16] | IEEE 34-bus system | PMU placement cost and observability | Feature selection optimization | PMU/State Estimation | Installation cost and scalability |
| [17] | Active distribution network | State estimation error | Robust three-phase estimation | PMU/State Estimation | Dependent on PMU deployment |
| [18] | IEEE 34-bus + PMU | State estimation error | Optimization-based | PMU/Optimization | PMU deployment cost |
| [19] | IEEE test system | Classification accuracy | Random search ML optimization | ML | Limited global search capability |
| [20] | Transmission line | Fault diagnosis accuracy | Optimized ML algorithms | ML | Dataset-dependent performance |
| [21] | Distribution feeder | Fault indicator validation error | ANN | ML | Requires training data quality |
| [22] | Distribution system | Fault distance error | Backpropagation neural network | ML | May converge slowly |
| [23] | Smart grid | Detection accuracy | Deep neural network | ML/DL | Large dataset requirement |
| [24] | Active distribution network | Classification accuracy | Hybrid classifier | ML/DL | Needs extensive training |
| [25] | Distribution system | Multi-target classification error | Multi-target ensemble ML | ML/DL | Limited scalability with very large networks |
| [26] | Distribution network | Integrated identification and location loss | Combined ML methods | ML/DL | Complex framework, high computation |
| [27] | Transmission system | Classification and location accuracy | Hybrid CNN–LSTM | ML/DL | High data requirement, computational cost |
| [28] | Smart city network | Classification accuracy | LSTM | ML/DL | High computational cost |
| [29] | Overhead line model | Classification error | Temporal CNN | ML/DL | High data requirement |
| [30] | Distribution network | Fault segment localization loss | Transfer entropy + improved AlexNet | ML/DL | May require feature tuning |
| [31] | High-DG network | Localization loss | Graph convolutional network | ML/DL | Sensitive to topology changes |
| [32] | DG network | Fault location loss | Domain-adaptive TGATv2 | ML/DL | Complexity and data dependency |
| [33] | Transmission line | Classification accuracy | VAE + ML | ML/DL | Synthetic data may not capture all real conditions |
| [34] | Smart grid | Detection error | Deep learning + digital twin | ML/DL | High computational requirement |
| [35] | Transmission line | End-to-end fault loss | Deep learning | ML/DL | Data-intensive |
| [36] | Active distribution network | Minimize fault section mismatch | Subtraction-average-based optimizer | Hybrid and Optimization | May converge to local optima |
| [37] | Distribution line | Voltage change | Genetic algorithm | Metaheuristic | Premature convergence |
| [38] | Active network | Fault localization error | Dynamic quantum genetic algorithm | Metaheuristic | Complexity, sensitive to parameters |
| [39] | DG line | Distance error | Hybrid PSO–GA | Metaheuristic | Premature convergence possible |
| [40] | Distribution system | Fault localization accuracy | Multi-agent system | Hybrid | Communication infrastructure dependent |
| [41] | Distribution system | Clustering error | Fuzzy C-means | Hybrid | Sensitive to initial cluster selection |
| [42] | Distribution system | Location and isolation reward | Markov decision process | Hybrid | Requires accurate reward modeling |
| [43] | DG-integrated lines | Fault localization error | Intelligent scheme | Hybrid | May not handle all fault types |
| [44] | Fixed series-compensated line | Distance error | Hybrid method | Hybrid | Specific to compensated lines |
| [45] | Wind microgrid | Reliability index | Battery sizing optimization | Hybrid | Focused only on battery sizing |
| [46] | DG system | Reactive power variation | Data-driven | ML | May fail under unmodeled dynamics |
| [47] | Distribution network | Sequence-based fault detection | Hierarchical fuzzy petri nets | Hybrid | Complex rule definition |
| [48] | Review | — | Taxonomy of high-impedance fault detection | Review | — |
| [49] | DG network, Kenitra City | Detection accuracy | Data-driven | ML | Case-specific, limited generalization |
| [50] | High-voltage transmission | Detection accuracy | Intelligent method | Hybrid | Large-scale deployment challenging |
| [51] | Review | — | Survey | Review | — |
| [52] | Review | — | Survey | Review | — |
| [53] | Review | — | Survey | Review | — |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance | |||
|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rf (Ω) | (Ω) | |
| 0.001 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 0.001 | 6.53 × 10−8 |
| 25 | 2.858 | 2.858 | 1.04 × 10−4 | 0.001 | 7.89 × 10−8 | |
| 50 | 5.715 | 5.715 | 6.90 × 10−5 | 0.001 | 1.55 × 10−7 | |
| 75 | 8.573 | 8.573 | 1.04 × 10−4 | 0.001 | 1.34 × 10−7 | |
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 0.001 | 1.61 × 10−7 | |
| 10 | 5 | 0.572 | 0.572 | 1.24 × 10−4 | 10.000 | 5.33 × 10−6 |
| 25 | 2.858 | 2.858 | 1.04 × 10−4 | 10.000 | 1.44 × 10−7 | |
| 50 | 5.715 | 5.715 | 1.01 × 10−5 | 10.000 | 6.06 × 10−6 | |
| 75 | 8.573 | 8.572 | 7.49 × 10−5 | 10.000 | 2.79 × 10−5 | |
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 10.000 | 2.67 × 10−7 | |
| 50 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 50.000 | 2.84 × 10−14 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 50.000 | 3.55 × 10−14 | |
| 50 | 5.715 | 5.715 | 1.01 × 10−4 | 50.000 | 3.55 × 10−14 | |
| 75 | 8.573 | 8.573 | 1.04 × 10−4 | 50.000 | 1.42 × 10−14 | |
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 50.000 | 1.42 × 10−14 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance | |||
|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rf (Ω) | (Ω) | |
| 0.001 | 5 | 0.572 | 0.571 | 2.66 × 10−10 | 0.001 | 4.43 × 10−11 |
| 25 | 2.858 | 2.857 | 4.11 × 10−10 | 0.001 | 6.85 × 10−11 | |
| 50 | 5.715 | 5.715 | 1.73 × 10−4 | 0.001 | 1.68 × 10−8 | |
| 75 | 8.573 | 8.572 | 7.02 × 10−10 | 0.001 | 1.22 × 10−10 | |
| 95 | 10.859 | 10.858 | 5.48 × 10−5 | 0.001 | 9.17 × 10−6 | |
| 10 | 5 | 0.572 | 0.572 | 8.38 × 10−5 | 10.000 | 1.25 × 10−5 |
| 25 | 2.858 | 2.858 | 2.88 × 10−10 | 10.000 | 4.12 × 10−11 | |
| 50 | 5.715 | 5.715 | 9.18 × 10−5 | 10.000 | 5.57 × 10−6 | |
| 75 | 8.573 | 8.573 | 2.15 × 10−4 | 10.000 | 2.98 × 10−5 | |
| 95 | 10.859 | 10.859 | 2.18 × 10−5 | 10.000 | 1.46 × 10−6 | |
| 50 | 5 | 0.572 | 0.572 | 1.66 × 10−9 | 50.000 | 3.98 × 10−13 |
| 25 | 2.858 | 2.858 | 2.72 × 10−5 | 50.000 | 6.45 × 10−5 | |
| 50 | 5.715 | 5.715 | 3.07 × 10−6 | 50.000 | 3.13 × 10−13 | |
| 75 | 8.573 | 8.573 | 4.09 × 10−4 | 50.000 | 7.11 × 10−14 | |
| 95 | 10.859 | 10.859 | 7.71 × 10−5 | 50.000 | 2.57 × 10−5 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance | |||
|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rf (Ω) | (Ω) | |
| 0.001 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 0.001 | 2.23 × 10−8 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 0.001 | 2.48 × 10−8 | |
| 50 | 5.715 | 5.715 | 9.68 × 10−5 | 0.001 | 4.21 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.04 × 10−4 | 0.001 | 5.22 × 10−8 | |
| 95 | 10.859 | 10.859 | 7.71 × 10−5 | 0.001 | 4.35 × 10−6 | |
| 10 | 5 | 0.572 | 0.572 | 1.04 × 10−4 | 10.000 | 7.30 × 10−8 |
| 25 | 2.858 | 2.858 | 1.03 × 10−4 | 10.000 | 2.05 × 10−6 | |
| 50 | 5.715 | 5.715 | 1.63 × 10−5 | 10.000 | 5.35 × 10−6 | |
| 75 | 8.573 | 8.573 | 2.18 × 10−4 | 10.000 | 1.66 × 10−5 | |
| 95 | 10.859 | 10.859 | 2.88 × 10−4 | 10.000 | 2.42 × 10−5 | |
| 50 | 5 | 0.572 | 0.572 | 3.68 × 10−4 | 50.000 | 3.97 × 10−5 |
| 25 | 2.858 | 2.858 | 1.04 × 10−4 | 50.000 | 2.13 × 10−14 | |
| 50 | 5.715 | 5.715 | 1.26 × 10−4 | 50.000 | 3.57 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.04 × 10−4 | 50.000 | 4.97 × 10−14 | |
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 50.000 | 1.28 × 10−13 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance | |||
|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rf (Ω) | (Ω) | |
| 0.001 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 0.001 | 3.68 × 10−7 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 0.001 | 2.66 × 10−13 | |
| 50 | 5.715 | 5.715 | 9.21 × 10−5 | 0.001 | 7.40 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.05 × 10−4 | 0.001 | 1.47 × 10−14 | |
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 0.001 | 9.38 × 10−14 | |
| 10 | 5 | 0.572 | 0.572 | 1.06 × 10−4 | 10.000 | 3.60 × 10−8 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 10.000 | 2.77 × 10−8 | |
| 50 | 5.715 | 5.715 | 5.36 × 10−6 | 10.000 | 6.14 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.06 × 10−4 | 10.000 | 3.28 × 10−8 | |
| 95 | 10.859 | 10.859 | 7.66 × 10−5 | 10.000 | 4.99 × 10−6 | |
| 50 | 5 | 0.572 | 0.572 | 1.62 × 10−4 | 50.000 | 1.21 × 10−5 |
| 25 | 2.858 | 2.858 | 1.09 × 10−4 | 50.000 | 3.78 × 10−7 | |
| 50 | 5.715 | 5.715 | 1.73 × 10−4 | 50.000 | 2.66 × 10−5 | |
| 75 | 8.573 | 8.573 | 1.09 × 10−4 | 50.000 | 4.20 × 10−7 | |
| 95 | 10.859 | 10.859 | 2.02 × 10−4 | 50.000 | 1.80 × 10−5 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance | |||
|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rf (Ω) | (Ω) | |
| 0.001 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 0.001 | 4.59 × 10−8 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 0.001 | 4.37 × 10−8 | |
| 50 | 5.715 | 5.715 | 7.17 × 10−5 | 0.001 | 1.02 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.05 × 10−4 | 0.001 | 7.03 × 10−8 | |
| 95 | 10.859 | 10.859 | 9.80 × 10−5 | 0.001 | 1.64 × 10−14 | |
| 10 | 5 | 0.572 | 0.572 | 1.04 × 10−4 | 10.000 | 3.40 × 10−7 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 10.000 | 4.86 × 10−8 | |
| 50 | 5.715 | 5.715 | 1.44 × 10−5 | 10.000 | 9.40 × 10−6 | |
| 75 | 8.573 | 8.573 | 9.18 × 10−5 | 10.000 | 7.15 × 10−6 | |
| 95 | 10.859 | 10.859 | 9.31 × 10−5 | 10.000 | 4.50 × 10−6 | |
| 50 | 5 | 0.572 | 0.572 | 1.07 × 10−4 | 50.000 | 6.40 × 10−8 |
| 25 | 2.858 | 2.858 | 3.45 × 10−4 | 50.000 | 8.27 × 10−5 | |
| 50 | 5.715 | 5.715 | 9.81 × 10−5 | 50.000 | 0.00 × 100 | |
| 75 | 8.573 | 8.573 | 2.90 × 10−4 | 50.000 | 1.42 × 10−14 | |
| 95 | 10.859 | 10.859 | 1.92 × 10−4 | 50.000 | 2.86 × 10−5 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance | |||
|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rf (Ω) | (Ω) | |
| 0.001 | 5 | 0.572 | 0.572 | 9.46 × 10−5 | 0.001 | 2.26 × 10−6 |
| 25 | 2.858 | 2.858 | 8.51 × 10−5 | 0.001 | 3.31 × 10−6 | |
| 50 | 5.715 | 5.715 | 7.08 × 10−5 | 0.001 | 7.36 × 10−7 | |
| 75 | 8.573 | 8.573 | 9.43 × 10−5 | 0.001 | 9.95 × 10−7 | |
| 95 | 10.859 | 10.859 | 1.09 × 10−4 | 0.001 | 1.24 × 10−13 | |
| 10 | 5 | 0.572 | 0.572 | 8.86 × 10−5 | 10.000 | 2.66 × 10−6 |
| 25 | 2.858 | 2.858 | 2.11 × 10−4 | 10.000 | 1.73 × 10−5 | |
| 50 | 5.715 | 5.715 | 3.34 × 10−5 | 10.000 | 1.05 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.04 × 10−4 | 10.000 | 3.85 × 10−8 | |
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 10.000 | 5.54 × 10−8 | |
| 50 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 50.000 | 2.20 × 10−7 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 50.000 | 2.41 × 10−7 | |
| 50 | 5.715 | 5.715 | 9.55 × 10−5 | 50.000 | 2.13 × 10−14 | |
| 75 | 8.573 | 8.573 | 6.31 × 10−4 | 50.000 | 4.98 × 10−5 | |
| 95 | 10.859 | 10.859 | 1.72 × 10−6 | 50.000 | 1.97 × 10−11 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance Rfb | Calculated Fault Resistance Rfc | Calculated Fault Resistance Rfg | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rfa (Ω) | Error (%) | Rfb (Ω) | Error (%) | Rfg (Ω) | Error (%) | |
| 0.001 | 5 | 0.572 | 0.572 | 9.75 × 10−5 | 0.001 | 1.34 × 10−6 | 0.001 | 5.83 × 10−7 | 0.001 | 8.29 × 10−7 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 0.001 | 2.96 × 10−16 | 0.001 | 9.78 × 10−9 | 0.001 | 2.01 × 10−15 | |
| 50 | 5.715 | 5.715 | 6.82 × 10−5 | 0.001 | 8.29 × 10−8 | 0.001 | 3.57 × 10−8 | 0.001 | 2.69 × 10−11 | |
| 75 | 8.573 | 8.573 | 1.05 × 10−4 | 0.001 | 1.06 × 10−14 | 0.001 | 8.79 × 10−9 | 0.001 | 1.93 × 10−8 | |
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 0.001 | 1.34 × 10−15 | 0.001 | 9.38 × 10−9 | 0.001 | 2.61 × 10−8 | |
| 10 | 5 | 0.572 | 0.572 | 1.06 × 10−4 | 10.000 | 3.97 × 10−8 | 10.000 | 2.76 × 10−8 | 10.000 | 7.25 × 10−8 |
| 25 | 2.858 | 2.858 | 1.06 × 10−4 | 10.000 | 4.62 × 10−8 | 10.000 | 2.41 × 10−8 | 10.000 | 7.38 × 10−8 | |
| 50 | 5.715 | 5.715 | 3.44 × 10−5 | 10.000 | 3.66 × 10−6 | 10.000 | 3.53 × 10−6 | 10.000 | 4.59 × 10−6 | |
| 75 | 8.573 | 8.572 | 1.13 × 10−5 | 10.000 | 1.56 × 10−6 | 10.000 | 3.50 × 10−5 | 10.000 | 5.07 × 10−5 | |
| 95 | 10.859 | 10.859 | 1.06 × 10−4 | 10.000 | 8.59 × 10−8 | 10.000 | 2.59 × 10−8 | 10.000 | 1.01 × 10−7 | |
| 50 | 5 | 0.572 | 0.572 | 3.24 × 10−3 | 50.000 | 3.35 × 10−4 | 50.000 | 3.37 × 10−4 | 50.000 | 7.94 × 10−5 |
| 25 | 2.858 | 2.859 | 8.93 × 10−3 | 49.999 | 9.73 × 10−4 | 49.999 | 6.49 × 10−4 | 49.996 | 4.35 × 10−3 | |
| 50 | 5.715 | 5.715 | 2.53 × 10−3 | 50.000 | 2.71 × 10−4 | 50.000 | 2.19 × 10−4 | 49.999 | 7.72 × 10−4 | |
| 75 | 8.573 | 8.573 | 1.53 × 10−4 | 50.000 | 5.07 × 10−6 | 50.000 | 4.10 × 10−6 | 50.000 | 1.75 × 10−5 | |
| 95 | 10.859 | 10.859 | 8.14 × 10−3 | 49.999 | 9.15 × 10−4 | 49.999 | 8.77 × 10−4 | 50.000 | 3.36 × 10−4 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance Rfb | Calculated Fault Resistance Rfc | Calculated Fault Resistance Rfg | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rfb (Ω) | Error (%) | Rfc (Ω) | Error (%) | Rfg (Ω) | Error (%) | |
| 0.001 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 0.001 | 4.85 × 10−9 | 0.001 | 1.33 × 10−11 | 0.001 | 1.07 × 10−11 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 0.001 | 1.19 × 10−9 | 0.001 | 5.14 × 10−9 | 0.001 | 6.85 × 10−9 | |
| 50 | 5.715 | 5.715 | 6.80 × 10−5 | 0.001 | 2.61 × 10−8 | 0.001 | 3.33 × 10−8 | 0.001 | 1.72 × 10−8 | |
| 75 | 8.573 | 8.573 | 1.05 × 10−4 | 0.001 | 1.28 × 10−7 | 0.001 | 4.95 × 10−9 | 0.001 | 3.57 × 10−8 | |
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 0.001 | 5.09 × 10−9 | 0.001 | 1.94 × 10−14 | 0.001 | 3.11 × 10−16 | |
| 10 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 10.000 | 1.54 × 10−8 | 10.000 | 6.75 × 10−8 | 10.000 | 4.06 × 10−8 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 10.000 | 1.72 × 10−8 | 10.000 | 6.93 × 10−8 | 10.000 | 6.01 × 10−8 | |
| 50 | 5.715 | 5.715 | 2.01 × 10−4 | 10.000 | 3.52 × 10−5 | 10.000 | 3.02 × 10−5 | 10.000 | 2.84 × 10−5 | |
| 75 | 8.573 | 8.572 | 1.32 × 10−4 | 10.000 | 3.18 × 10−5 | 10.000 | 3.35 × 10−5 | 10.000 | 8.53 × 10−5 | |
| 95 | 10.859 | 10.859 | 1.06 × 10−4 | 10.000 | 4.82 × 10−9 | 10.000 | 8.79 × 10−8 | 10.000 | 1.50 × 10−7 | |
| 50 | 5 | 0.572 | 0.572 | 3.31 × 10−4 | 50.000 | 2.21 × 10−5 | 50.000 | 2.04 × 10−5 | 50.000 | 9.57 × 10−5 |
| 25 | 2.858 | 2.858 | 1.11 × 10−4 | 50.000 | 0.00 × 100 | 50.000 | 1.30 × 10−6 | 50.000 | 7.45 × 10−7 | |
| 50 | 5.715 | 5.715 | 1.10 × 10−4 | 50.000 | 3.69 × 10−13 | 50.000 | 1.32 × 10−6 | 50.000 | 1.43 × 10−6 | |
| 75 | 8.573 | 8.573 | 6.58 × 10−3 | 49.999 | 7.36 × 10−4 | 49.999 | 6.25 × 10−4 | 49.998 | 1.52 × 10−3 | |
| 95 | 10.859 | 10.859 | 6.74 × 10−3 | 49.999 | 8.71 × 10−4 | 50.000 | 3.35 × 10−4 | 49.997 | 2.62 × 10−3 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance Rfb | Calculated Fault Resistance Rfc | Calculated Fault Resistance Rfg | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rfa (Ω) | Error (%) | Rfc (Ω) | Error (%) | Rfg (Ω) | Error (%) | |
| 0.001 | 5 | 0.572 | 0.572 | 1.03 × 10−4 | 0.001 | 3.33 × 10−7 | 0.001 | 4.11 × 10−7 | 0.001 | 1.30 × 10−7 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 0.001 | 8.46 × 10−9 | 0.001 | 3.73 × 10−8 | 0.001 | 1.67 × 10−16 | |
| 50 | 5.715 | 5.715 | 6.81 × 10−5 | 0.001 | 2.30 × 10−8 | 0.001 | 9.23 × 10−8 | 0.001 | 1.48 × 10−8 | |
| 75 | 8.573 | 8.573 | 1.05 × 10−4 | 0.001 | 5.32 × 10−9 | 0.001 | 5.83 × 10−8 | 0.001 | 6.03 × 10−16 | |
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 0.001 | 9.45 × 10−10 | 0.001 | 5.12 × 10−8 | 0.001 | 4.17 × 10−10 | |
| 10 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 10.000 | 7.12 × 10−8 | 10.000 | 9.77 × 10−9 | 10.000 | 7.48 × 10−8 |
| 25 | 2.858 | 2.858 | 4.19 × 10−4 | 10.000 | 2.55 × 10−5 | 10.000 | 9.30 × 10−6 | 10.000 | 1.05 × 10−4 | |
| 50 | 5.715 | 5.715 | 3.26 × 10−5 | 10.000 | 4.02 × 10−6 | 10.000 | 3.78 × 10−6 | 10.000 | 2.43 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.46 × 10−4 | 10.000 | 1.21 × 10−5 | 10.000 | 1.11 × 10−5 | 10.000 | 1.28 × 10−5 | |
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 10.000 | 9.56 × 10−8 | 10.000 | 1.22 × 10−8 | 10.000 | 1.46 × 10−7 | |
| 50 | 5 | 0.572 | 0.572 | 1.13 × 10−4 | 50.000 | 1.50 × 10−6 | 50.000 | 4.37 × 10−7 | 50.000 | 0.00 × 100 |
| 25 | 2.858 | 2.858 | 1.13 × 10−4 | 50.000 | 1.54 × 10−6 | 50.000 | 4.40 × 10−7 | 50.000 | 1.42 × 10−14 | |
| 50 | 5.715 | 5.715 | 1.09 × 10−4 | 50.000 | 1.25 × 10−6 | 50.000 | 1.05 × 10−7 | 50.000 | 3.31 × 10−7 | |
| 75 | 8.573 | 8.573 | 1.14 × 10−4 | 50.000 | 1.66 × 10−6 | 50.000 | 4.66 × 10−7 | 50.000 | 1.42 × 10−7 | |
| 95 | 10.859 | 10.859 | 6.57 × 10−4 | 50.000 | 8.04 × 10−5 | 50.000 | 2.03 × 10−6 | 50.000 | 1.89 × 10−4 | |
| Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance Rfb | Calculated Fault Resistance Rfc | Calculated Fault Resistance Rfg | |||||
|---|---|---|---|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | (%) | Rfa (Ω) | Error (%) | Rfb (Ω) | Error (%) | Rfc (Ω) | Error (%) | |
| 0.001 | 5 | 0.572 | 0.572 | 1.04 × 10−4 | 0.001 | 1.21 × 10−7 | 0.001 | 8.94 × 10−8 | 0.001 | 2.67 × 10−7 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 0.001 | 3.18 × 10−14 | 0.001 | 4.94 × 10−9 | 0.001 | 1.80 × 10−8 | |
| 50 | 5.715 | 5.715 | 6.82 × 10−5 | 0.001 | 8.56 × 10−8 | 0.001 | 4.41 × 10−8 | 0.001 | 7.29 × 10−8 | |
| 75 | 8.573 | 8.573 | 1.05 × 10−4 | 0.001 | 1.03 × 10−10 | 0.001 | 2.67 × 10−8 | 0.001 | 4.01 × 10−9 | |
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 0.001 | 1.29 × 10−9 | 0.001 | 4.18 × 10−8 | 0.001 | 2.17 × 10−8 | |
| 10 | 5 | 0.572 | 0.572 | 6.17 × 10−4 | 10.000 | 8.39 × 10−5 | 10.000 | 8.68 × 10−5 | 10.000 | 2.42 × 10−4 |
| 25 | 2.858 | 2.858 | 1.05 × 10−4 | 10.000 | 3.80 × 10−8 | 10.000 | 4.46 × 10−9 | 10.000 | 7.09 × 10−8 | |
| 50 | 5.715 | 5.715 | 3.00 × 10−5 | 10.000 | 4.07 × 10−6 | 10.000 | 4.14 × 10−6 | 10.000 | 3.36 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.05 × 10−4 | 10.000 | 6.16 × 10−8 | 10.000 | 6.19 × 10−9 | 10.000 | 3.85 × 10−8 | |
| 95 | 10.859 | 10.858 | 2.05 × 10−4 | 10.000 | 1.54 × 10−5 | 10.000 | 6.77 × 10−5 | 10.000 | 1.69 × 10−4 | |
| 50 | 5 | 0.572 | 0.572 | 3.28 × 10−4 | 50.000 | 2.54 × 10−6 | 50.000 | 3.16 × 10−5 | 50.000 | 3.84 × 10−4 |
| 25 | 2.858 | 2.858 | 1.14 × 10−4 | 50.000 | 5.45 × 10−7 | 50.000 | 9.11 × 10−7 | 50.000 | 7.58 × 10−6 | |
| 50 | 5.715 | 5.715 | 1.06 × 10−4 | 50.000 | 2.46 × 10−7 | 50.000 | 8.38 × 10−8 | 50.000 | 1.51 × 10−6 | |
| 75 | 8.573 | 8.573 | 1.16 × 10−3 | 50.000 | 7.23 × 10−6 | 50.000 | 1.46 × 10−4 | 49.999 | 1.39 × 10−3 | |
| 95 | 10.859 | 10.859 | 2.21 × 10−4 | 50.000 | 6.61 × 10−6 | 50.000 | 1.47 × 10−5 | 50.000 | 8.76 × 10−5 | |
| Voltage (%) | Φ (°) | Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance Rf | |||
|---|---|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | Error (%) | Rf (Ω) | Error (%) | |||
| 95 | 0 | 0.001 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 0.001 | 7.35 × 10−8 |
| 50 | 5.715 | 5.715 | 6.90 × 10−5 | 0.001 | 1.13 × 10−7 | |||
| 95 | 10.859 | 10.859 | 7.96 × 10−5 | 0.001 | 3.72 × 10−6 | |||
| 10 | 5 | 0.572 | 0.572 | 1.10 × 10−4 | 10.000 | 1.13 × 10−6 | ||
| 50 | 5.715 | 5.715 | 9.60 × 10−6 | 10.000 | 6.10 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.53 × 10−4 | 10.000 | 8.84 × 10−6 | |||
| 50 | 5 | 0.572 | 0.572 | 1.04 × 10−4 | 50.000 | 6.39 × 10−14 | ||
| 50 | 5.715 | 5.715 | 1.01 × 10−4 | 50.000 | 3.87 × 10−10 | |||
| 95 | 10.859 | 10.858 | 9.14 × 10−6 | 50.000 | 9.24 × 10−14 | |||
| 120 | 0.001 | 5 | 0.572 | 0.572 | 9.64 × 10−5 | 0.001 | 1.21 × 10−6 | |
| 50 | 5.715 | 5.715 | 6.83 × 10−5 | 0.001 | 1.88 × 10−7 | |||
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 0.001 | 1.89 × 10−7 | |||
| 10 | 5 | 0.572 | 0.572 | 1.04 × 10−4 | 10.000 | 1.21 × 10−7 | ||
| 50 | 5.715 | 5.715 | 1.28 × 10−5 | 10.000 | 9.69 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.43 × 10−4 | 10.000 | 3.34 × 10−6 | |||
| 50 | 5 | 0.572 | 0.572 | 2.73 × 10−4 | 50.000 | 1.47 × 10−5 | ||
| 50 | 5.715 | 5.715 | 8.03 × 10−4 | 50.000 | 0.00 × 100 | |||
| 95 | 10.859 | 10.858 | 4.73 × 10−6 | 50.000 | 2.34 × 10−13 | |||
| 240 | 0.001 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 0.001 | 7.35 × 10−8 | |
| 50 | 5.715 | 5.715 | 6.90 × 10−5 | 0.001 | 1.13 × 10−7 | |||
| 95 | 10.859 | 10.859 | 1.26 × 10−4 | 0.001 | 5.20 × 10−14 | |||
| 10 | 5 | 0.572 | 0.572 | 1.04 × 10−4 | 10.000 | 1.21 × 10−7 | ||
| 50 | 5.715 | 5.715 | 2.83 × 10−5 | 10.000 | 2.07 × 10−6 | |||
| 95 | 10.859 | 10.859 | 2.45 × 10−4 | 10.000 | 2.23 × 10−5 | |||
| 50 | 5 | 0.572 | 0.572 | 2.29 × 10−4 | 50.000 | 6.36 × 10−5 | ||
| 50 | 5.715 | 5.715 | 3.27 × 10−4 | 50.000 | 9.95 × 10−14 | |||
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 50.000 | 2.49 × 10−13 | |||
| Voltage (%) | Φ (°) | Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance Rf | |||
|---|---|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | Error (%) | Rf (Ω) | Error (%) | |||
| 100 | 0 | 0.001 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 0.001 | 6.53 × 10−8 |
| 50 | 5.715 | 5.715 | 6.80 × 10−5 | 0.001 | 8.96 × 10−8 | |||
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 0.001 | 1.61 × 10−7 | |||
| 10 | 5 | 0.572 | 0.572 | 1.04 × 10−4 | 10.000 | 1.08 × 10−7 | ||
| 50 | 5.715 | 5.715 | 1.01 × 10−5 | 10.000 | 6.06 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.25 × 10−4 | 10.000 | 1.06 × 10−7 | |||
| 50 | 5 | 0.572 | 0.572 | 7.25 × 10−5 | 50.000 | 5.23 × 10−6 | ||
| 50 | 5.715 | 5.715 | 2.89 × 10−5 | 50.000 | 1.87 × 10−5 | |||
| 95 | 10.859 | 10.859 | 7.56 × 10−6 | 50.000 | 1.14 × 10−13 | |||
| 120 | 0.001 | 5 | 0.572 | 0.572 | 9.65 × 10−5 | 0.001 | 1.27 × 10−6 | |
| 50 | 5.715 | 5.715 | 6.90 × 10−5 | 0.001 | 1.54 × 10−7 | |||
| 95 | 10.859 | 10.859 | 1.24 × 10−4 | 0.001 | 1.43 × 10−14 | |||
| 10 | 5 | 0.572 | 0.572 | 1.04 × 10−4 | 10.000 | 1.08 × 10−7 | ||
| 50 | 5.715 | 5.715 | 3.21 × 10−5 | 10.000 | 1.44 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 10.000 | 2.67 × 10−7 | |||
| 50 | 5 | 0.572 | 0.572 | 3.25 × 10−4 | 50.000 | 0.00 × 100 | ||
| 50 | 5.715 | 5.715 | 1.01 × 10−4 | 50.000 | 2.20 × 10−13 | |||
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 50.000 | 2.27 × 10−13 | |||
| 240 | 0.001 | 5 | 0.572 | 0.572 | 1.02 × 10−4 | 0.001 | 4.53 × 10−7 | |
| 50 | 5.715 | 5.715 | 4.38 × 10−5 | 0.001 | 5.58 × 10−14 | |||
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 0.001 | 8.09 × 10−16 | |||
| 10 | 5 | 0.572 | 0.572 | 1.02 × 10−4 | 10.000 | 3.81 × 10−6 | ||
| 50 | 5.715 | 5.715 | 1.20 × 10−5 | 10.000 | 5.43 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 10.000 | 2.67 × 10−7 | |||
| 50 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 50.000 | 2.84 × 10−14 | ||
| 50 | 5.715 | 5.715 | 1.64 × 10−4 | 50.000 | 7.82 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 50.000 | 4.26 × 10−14 | |||
| Voltage (%) | Φ (°) | Fault Resistance (Ω) | Actual Distance | Calculated Distance | Calculated Fault Resistance Rf | |||
|---|---|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | Error (%) | Rf (Ω) | Error (%) | |||
| 105 | 0 | 0.001 | 5 | 0.572 | 0.572 | 1.14 × 10−4 | 0.001 | 9.27 × 10−16 |
| 50 | 5.715 | 5.715 | 6.88 × 10−5 | 0.001 | 1.58 × 10−7 | |||
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 0.001 | 1.39 × 10−7 | |||
| 10 | 5 | 0.572 | 0.572 | 1.00 × 10−4 | 10.000 | 6.68 × 10−7 | ||
| 50 | 5.715 | 5.715 | 3.21 × 10−6 | 10.000 | 8.56 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 10.000 | 2.34 × 10−7 | |||
| 50 | 5 | 0.572 | 0.572 | 1.96 × 10−4 | 50.000 | 1.80 × 10−5 | ||
| 50 | 5.715 | 5.715 | 9.13 × 10−5 | 50.000 | 3.48 × 10−13 | |||
| 95 | 10.859 | 10.859 | 6.96 × 10−5 | 50.000 | 6.39 × 10−14 | |||
| 120 | 0.001 | 5 | 0.572 | 0.572 | 9.25 × 10−5 | 0.001 | 3.61 × 10−6 | |
| 50 | 5.715 | 5.715 | 6.35 × 10−5 | 0.001 | 4.70 × 10−8 | |||
| 95 | 10.859 | 10.859 | 1.04 × 10−4 | 0.001 | 5.58 × 10−14 | |||
| 10 | 5 | 0.572 | 0.572 | 6.72 × 10−5 | 10.000 | 3.01 × 10−6 | ||
| 50 | 5.715 | 5.715 | 1.57 × 10−5 | 10.000 | 5.44 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 10.000 | 2.34 × 10−7 | |||
| 50 | 5 | 0.572 | 0.572 | 3.19 × 10−4 | 50.000 | 7.05 × 10−5 | ||
| 50 | 5.715 | 5.715 | 1.02 × 10−4 | 50.000 | 0.00 × 100 | |||
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 50.000 | 1.35 × 10−13 | |||
| 240 | 0.001 | 5 | 0.572 | 0.572 | 1.09 × 10−4 | 0.001 | 1.30 × 10−14 | |
| 50 | 5.715 | 5.715 | 6.88 × 10−5 | 0.001 | 1.58 × 10−7 | |||
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 0.001 | 8.45 × 10−15 | |||
| 10 | 5 | 0.572 | 0.572 | 9.38 × 10−5 | 10.000 | 3.63 × 10−6 | ||
| 50 | 5.715 | 5.715 | 1.05 × 10−5 | 10.000 | 6.02 × 10−6 | |||
| 95 | 10.859 | 10.859 | 1.03 × 10−4 | 10.000 | 2.34 × 10−7 | |||
| 50 | 5 | 0.572 | 0.572 | 1.05 × 10−4 | 50.000 | 6.39 × 10−14 | ||
| 50 | 5.715 | 5.715 | 7.51 × 10−4 | 50.000 | 8.75 × 10−5 | |||
| 95 | 10.859 | 10.859 | 1.05 × 10−4 | 50.000 | 1.42 × 10−14 | |||
| Fault Resistance (Ω) | Line A (%) | Line B (%) | Line C (%) | Actual Distance | Calculated Distance | Calculated Fault Resistance Rf | |||
|---|---|---|---|---|---|---|---|---|---|
| x (%) | d (km) | x (km) | Error (%) | Rf (Ω) | Error (%) | ||||
| 0.001 | 80 | 80 | 80 | 50 | 5.715 | 5.715 | 6.89 × 10−5 | 0.001 | 1.56 × 10−7 |
| 80 | 100 | 120 | 50 | 5.715 | 5.715 | 1.44 × 10−4 | 0.001 | 2.02 × 10−5 | |
| 100 | 120 | 80 | 50 | 5.715 | 5.715 | 6.30 × 10−5 | 0.001 | 2.20 × 10−11 | |
| 120 | 80 | 100 | 50 | 5.715 | 5.715 | 6.95 × 10−5 | 0.001 | 2.73 × 10−7 | |
| 120 | 120 | 120 | 80 | 5.715 | 5.715 | 6.87 × 10−5 | 0.001 | 9.20 × 10−8 | |
| 10 | 80 | 80 | 80 | 50 | 5.715 | 5.715 | 8.59 × 10−5 | 10.000 | 5.50 × 10−7 |
| 80 | 100 | 120 | 50 | 5.715 | 5.715 | 1.07 × 10−5 | 10.000 | 5.94 × 10−6 | |
| 100 | 120 | 80 | 50 | 5.715 | 5.715 | 6.09 × 10−6 | 10.000 | 4.26 × 10−6 | |
| 120 | 80 | 100 | 50 | 5.715 | 5.715 | 9.74 × 10−6 | 10.000 | 6.13 × 10−6 | |
| 120 | 120 | 120 | 50 | 5.715 | 5.715 | 9.57 × 10−6 | 10.000 | 6.15 × 10−6 | |
| 50 | 80 | 80 | 80 | 50 | 5.715 | 5.715 | 4.06 × 10−4 | 50.000 | 5.68 × 10−14 |
| 80 | 100 | 120 | 50 | 5.715 | 5.715 | 1.01 × 10−4 | 50.000 | 1.69 × 10−11 | |
| 100 | 120 | 80 | 50 | 5.715 | 5.715 | 1.01 × 10−4 | 50.000 | 1.56 × 10−13 | |
| 120 | 80 | 100 | 50 | 5.715 | 5.715 | 1.02 × 10−4 | 50.000 | 5.68 × 10−14 | |
| 120 | 120 | 120 | 50 | 5.715 | 5.715 | 5.36 × 10−4 | 50.000 | 3.62 × 10−13 | |
| Fault Type | No. of Test Samples | No. of Test Samples Classified Correctly | No of Test Samples Misclassified | Classification Accuracy (%) |
|---|---|---|---|---|
| A-g | 1000 | 1000 | 0 | 100 |
| B-g | 1000 | 1000 | 0 | 100 |
| C-g | 1000 | 1000 | 0 | 100 |
| AB | 1000 | 1000 | 0 | 100 |
| BC | 1000 | 1000 | 0 | 100 |
| AC | 1000 | 1000 | 0 | 100 |
| AB-g | 1000 | 1000 | 0 | 100 |
| BC-g | 1000 | 1000 | 0 | 100 |
| AC-g | 1000 | 1000 | 0 | 100 |
| ABC-g | 1000 | 1000 | 0 | 100 |
| total | 10,000 | 10,000 | 0 | 100 |
| Fault Type | Fault Resistance (Ω) | Actual Fault Distance | Estimated Fault Distance (km) [67] | Estimated Fault Distance (km) | Accuracy [67] | Accuracy of the Proposed Method |
|---|---|---|---|---|---|---|
| A-g | 0.01 | 2.625 | 2.815 | 2.6354 | 99.8 | 99.99 |
| B-g | 2.714 | 2.6354 | 99.8 | 99.99 | ||
| C-g | 2.687 | 2.6354 | 99.8 | 99.99 | ||
| AB | 2.549 | 2.6334 | 99.9 | 99.99 | ||
| BC | 2.543 | 2.6358 | 99.9 | 99.99 | ||
| AC | 2.684 | 2.6358 | 99.9 | 99.99 | ||
| AB-g | 2.954 | 2.6349 | 99.7 | 99.99 | ||
| BC-g | 2.961 | 2.6461 | 99.7 | 99.98 | ||
| AC-g | 2.941 | 2.6386 | 99.7 | 99.98 | ||
| ABC-g | 2.113 | 2.5973 | 99.5 | 99.97 |
| Fault Type | Fault Resistance (Ω) | Actual Fault Distance | Estimated Fault Distance (km) [68] | Estimated Fault Distance (km) | Accuracy [68] | Accuracy of the Proposed Method |
|---|---|---|---|---|---|---|
| BG | 0 | 11.979148 | 11.978 | 11.97912 | 99.9989 | 99.9994 |
| 20 | 11.9784 | 11.97914 | 99.9994 | 99.9994 | ||
| 50 | 11.9764 | 11.97914 | 99.9973 | 99.9994 | ||
| 100 | 11.9736 | 11.97913 | 99.9944 | 99.9996 | ||
| AG | 0 | 42.3 | 42.387798 | 42.3 | 99.9106 | 99.9999 |
| 20 | 42.417098 | 42.3 | 99.8808 | 99.9998 | ||
| 50 | 42.459398 | 42.2998 | 99.8377 | 99.9988 | ||
| 100 | 42.6822 | 42.3 | 99.8648 | 99.9999 |
| Fault Type | Collection Data Simples | Size | Collection Data Time | Simulation Time |
|---|---|---|---|---|
| A-g | 21,870 | 0.97 MB | 1 h 36 min | 2 min |
| B-g | 0.98 MB | 1 h 33 min | ||
| C-g | 0.98 MB | 1 h 47 min | ||
| AB | 0.97 MB | 1 h 41 min | 2 h 30 min | |
| BC | 0.96 MB | 1 h 45 min | ||
| AC | 0.95 MB | 1 h 29 min | ||
| AB-g | 196,830 | 8.36 MB | 14 h 43 min | |
| BC-g | 8.40 MB | 13 h 38 min | ||
| AC-g | 8.36 MB | 14 h 40 min | ||
| ABC-g | 8.44 MB | 15 h 36 min |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Share and Cite
Guerraiche, K.; Abbou, A.B.; Chatelet, É.; Dekhici, L.; Zeblah, A.; Djari, M.A. A Hybrid Machine Learning and NGO Algorithm Approach for Fault Classification and Localization in Electrical Distribution Lines. Processes 2026, 14, 944. https://doi.org/10.3390/pr14060944
Guerraiche K, Abbou AB, Chatelet É, Dekhici L, Zeblah A, Djari MA. A Hybrid Machine Learning and NGO Algorithm Approach for Fault Classification and Localization in Electrical Distribution Lines. Processes. 2026; 14(6):944. https://doi.org/10.3390/pr14060944
Chicago/Turabian StyleGuerraiche, Khaled, Amine Bouadjmi Abbou, Éric Chatelet, Latifa Dekhici, Abdelkader Zeblah, and Mohammed Adel Djari. 2026. "A Hybrid Machine Learning and NGO Algorithm Approach for Fault Classification and Localization in Electrical Distribution Lines" Processes 14, no. 6: 944. https://doi.org/10.3390/pr14060944
APA StyleGuerraiche, K., Abbou, A. B., Chatelet, É., Dekhici, L., Zeblah, A., & Djari, M. A. (2026). A Hybrid Machine Learning and NGO Algorithm Approach for Fault Classification and Localization in Electrical Distribution Lines. Processes, 14(6), 944. https://doi.org/10.3390/pr14060944

