Next Article in Journal
Dynamic Modeling of a Three-Phase BLDC Motor Using Bond Graph Methodology
Previous Article in Journal
Data-Driven Controller Design Based on Response Estimation for Multi-Performance Optimization
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Reliability Study of Low-Voltage Electrical Appliances in Transport Vehicles Under Variable-Load Conditions

1
School of Mechanical and Automotive Engineering, Shanghai University of Engineering Science, Shanghai 201620, China
2
School of Traffic and Transport Engineering, Central South University, Changsha 410075, China
*
Author to whom correspondence should be addressed.
Actuators 2025, 14(11), 522; https://doi.org/10.3390/act14110522
Submission received: 2 September 2025 / Revised: 14 October 2025 / Accepted: 24 October 2025 / Published: 27 October 2025
(This article belongs to the Section Actuators for Surface Vehicles)

Abstract

Low-voltage electrical appliances, represented by circuit breakers, contactors, and proximity switches, are widely used in various electrical control systems in transportation vehicles. During vehicle operation, engine vibrations, poor workplace balance, constantly changing operating directions, unbalanced transmission systems, emergency braking, and other factors can all cause variable loads. These variable loads may decrease the effectiveness of low-voltage electrical contacts; the failure rate of the low-voltage electrical appliances used in transportation vehicles is three times that of normal indoor low-voltage electrical appliances. This study analyzes the failure mechanism of low-voltage electrical appliances used in transportation vehicles and establishes a model for their reliability evaluation and prediction based on a variable-load data-driven approach. This variable-load data comes from the constructed simulated vehicle operation test platform. Nonlinear variable-load test data generated by simulation is collected through the test platform and is then processed. An evaluation feature dataset is constructed and input into the reliability evaluation and prediction model to obtain the remaining life of low-voltage electrical appliances. The analysis and verification of the predicted evaluation values and the real values detected through platform equipment showed that the accuracy of this model for these appliances based on the variable-load data-driven approach reached 94%, meeting the requirements of practical applications. This method used in this study to derive the model can provide a theoretical basis for online evaluation and prediction of low-voltage electrical appliance reliability for transportation vehicles. This can not only prevent vehicle failures and avoid sudden accidents, but also fully utilize the remaining life of low-voltage electrical appliances and reduce the cost of replacing them.

1. Introduction

The term transport vehicles refers to vehicles, rail trains, airplanes, ships, etc. Low-voltage electrical appliances are widely used in the electrical control systems of these vehicles, playing a role in controlling, switching on–off, protecting, and regulating circuits. The working environment of these appliances is much harsher than that of general indoor environments, and includes vibrations, high temperatures, and electromagnetic radiation [1]. Variable loads may also be generated. A sudden change in load intensifies the impact of the arc on the low-voltage electrical contact system, potentially for a long time, resulting in failure or malfunction [2,3]. Passive components in low-voltage electrical appliances typically exhibit good reliability data, but they still cause most electronic device failures [4]. However, research on the reliability of these appliances for transportation vehicles has encountered difficulties such as complex load changes, temperature effects, vibration and shock, and limitations in evaluation and prediction models and testing. Therefore, with the advancement of transport technology and the increasing demand for reliability, research in this field is urgently needed.
At present, traditional reliability theory is still used to evaluate the reliability of low-voltage electrical appliances, generally using the truncated method of fixed number tests, taking the final failure time of the samples obtained from the test as the statistical data object, and then using the optimal distribution type to evaluate the reliability of the product. The methods commonly used for determining failure distribution types are generally graphical estimation, optimal linear unbiased estimation, and maximum likelihood estimation. This study analyzes in-depth the failure mechanism of low-voltage electrical appliances used in transport vehicles under variable-load conditions, establishing a model for reliability evaluation and prediction based on data-driven variable load. By building a simulation test platform for the operation of transport vehicles, variable-load test data was collected. After processing this data, a complete evaluation dataset was constructed, which was then input into the evaluation prediction model to predict the remaining life of these appliances used in transport vehicles. The accuracy of this model was verified by comparing the remaining life value of these appliances obtained based on the prediction model with the actual measured value on the test platform. This research provides a theoretical basis for assessing the reliability of low-voltage electrical appliances used in transport vehicles. By predicting the remaining life of these appliances in advance, safety accidents caused by failure of these appliances can be effectively avoided, especially in the field of transport vehicles that require extremely high safety requirements.

2. Analysis of Failure Mechanisms of Low-Voltage Electrical Appliances Used in Transport Vehicles

There are three failure modes for low-voltage electrical appliances used in transport vehicles: mechanical system failure, electromagnetic system failure, and contact system failure. Figure 1 shows the tested low-voltage electrical appliances, where the contact system has the highest probability of failure. Therefore, the focus of this study is on the reliability of the contact system under variable-load conditions.
During the operation of transport vehicles, if the internal low-voltage electrical appliances are subjected to continuous vibration impact or the impact frequency matches the natural frequency, it will have adverse effects on the structural and functional integrity of the appliances. Vibration shock is often accompanied by vibration variable load, temperature rise variable load, and electromagnetic variable load. Variable load can lead to arcs, and failure of the contact system is mainly due to the impact of electrical arcing on the damage mechanisms of the contacts and the resulting microstructural characteristics of the ablated surfaces [5].

2.1. Failure Mechanism of Contact Systems with a Rise in Temperature

When the transport vehicle is in operation, there is minimal mutual friction between the surface layers of the moving and static contact bimetallic sheets of low-voltage electrical appliances in the electronic control system. This friction will cause tiny protrusions on the contact surface to squeeze and rub against each other, resulting in energy loss and temperature rise during this squeezing and rubbing process. This increase in temperature leads to material expansion, and thermal expansion of the contacts may change the contact pressure and contact resistance, resulting in variable loads. This change in load can also cause a rise in temperature, during which the contact system may experience fatigue due to mechanical vibration or arc effects, where the accumulation of fatigue can lead to the failure of low-voltage electrical contact systems. Here, the failure mechanism of the contact system is analyzed by introducing the fatigue damage theory model. This model incorporates a fatigue life degradation function to characterize the cumulative damage effect of load cycles [6]. The motion state of the transport vehicle can be simulated through a vibration test bench, and the functional relationship between the vibration stress and fatigue life cycles of the test bench is described by the S-N curve [7], which is the number of stress cycles to failure. Its expression is provided and can directly be used in fatigue analysis without needing to run a nonlinear optimization [8]. This curve shown in Figure 2 describes the average value of a series of tests. In Formula (1), S is the amplitude of vibration stress and N is the number of vibration stress actions that cause contact failure. The effective range in the S-N curve approximates a straight line in double logarithmic coordinates.
As shown in Figure 1, once the slope is determined, the approximate algebraic relationship of S-N is
NS b = H c
where b represents the correlation with the properties of metal materials, and Hc is a constant value. The model of the relationship between the electrical life of low-voltage electrical appliances used in transport vehicles and their exposure to vibration stress based on the principle of cumulative loss is derived as follows:
L s = H c S b
where LS represents electrical lifespan. Vibration stress causes an increase in temperature of low-voltage electrical contacts, which then causes cumulative damage to the contact. The damage model is represented as follows:
V S n
where V represents the damage rate, S n represents the vibration stress, and n is a constant. This indicates that the remaining life of the permanent low-voltage electrical equipment of the carrier is closely related to the vibration stress it is subjected to. The temperature rise in the contact part of low-voltage electrical appliances may lead to variable-load generation, and arcs may occur under these variable-load conditions. The surface condition of the bimetallic contact layer of low-voltage electrical appliance contacts under the action of arcs is shown in Figure 3.
The main reasons for the rise in temperature of bimetallic contacts in low-voltage electrical appliances are the heat generated by current and the frictional heat generated by vibration. During the operation of these appliances used in transport vehicles, there will be energy loss when the current passes through the contact resistor of the appliances. Almost all these losses are converted into thermal energy, which can cause an increase in the temperature of low-voltage electrical contacts used in transportation vehicles. The consequences of temperature rise are as follows:
  • This may lead to an increase in contact resistance, thereby generating more heat, forming a vicious cycle, further accelerating the aging and damage of contacts;
  • Under high-temperature conditions, the material of low-voltage electrical contacts may melt or burn, leading to contact failure;
  • High-temperature environments may accelerate the oxidation process of the contact surface, form an oxide film, and affect conductivity;
  • The reaction rate of certain chemicals increases at high temperatures, which may corrode the contact material.
Due to the influence of the above factors, the reliability of the contacts in high-temperature environments is reduced, increasing the risk of faults occurring. To quantitatively analyze the impact of temperature rises on the reliability of low-voltage electrical contacts used in transport vehicles, a thermal equilibrium equation is established based on the surface condition of the contact layer of the bimetallic strip in Figure 2.
d 2 τ d x 2 - C T g λ A τ = I 2 ρ λ A
where the contact point area is A, the thermal conductivity is λ, the contact point resistivity is ρ, the contact point surface circumference is g, the heat dissipation coefficient is CT, the contact point resistance temperature rise is τ, and x is related to the shape of the contact point area. By solving the second-order differential of the thermal equilibrium equation,
τ w = I 2 ρ C T g A
when x→∞, the rise in low-voltage electrical temperature is τw. The heat generation of the narrow part of the contact point is ρA1l, where ρ is the thermal conductivity, A1 is the area of the heating conductor, l is the length of the heating conductor, and the heat dissipation of low-voltage electrical appliances is CTgl τmax. When x→0, the maximum temperature rise τmax can be obtained:
τ max = ρ A 1 l + 2 α λ A τ w 2 α λ A + C T g l
where α = C T g λ A . Therefore,
τ = I 2 ρ C T g A + ( ρ A 1 l + 2 α λ A τ w 2 a λ A + C T g l I 2 ρ C T g A ) e a x
Due to the uneven surface of the contact point, the interface of the contact layer is actually a series of concave–convex contacts, resulting in a rough contact surface. Due to the presence of vibration stress and contact pressure, sliding friction will occur during the closing process of the contacts, especially in the contact layer of low-voltage electrical appliances inside high-speed trains, which will generate relative motion friction during the vibration process. Friction will generate heat, and under the continuous friction between friction points, the temperature will rise, represented by τf.
τ f = 2 ξ c μ L ( v 1 v 2 ) ( k 1 v 1 + k 2 v 2 ) h
where ξ c is a constant, L is the normal length of the load, μ is the friction coefficient, v1 and v2 are the velocities of the two surfaces, k1 and k2 are the material constants of the two surfaces, and h is the width of the contact zone. During the closing process, the contact will generate heat through friction. Let tc be the time when the contact undergoes displacement and an instantaneous temperature rise. The temperature rise generated during the friction process is calculated and integrated in Formula (8):
τ f = ξ c μ l c 0 N f ( δ ) A z d t
where N is the number of experiments, the height of the surface contact point is represented by Az, and the material constant is represented by c. f(δ) is the relevant friction correction factor and is approximately equal to the height value Az in the calculation. The temperature rise generated by dynamic friction and that generated by the thermal equilibrium of contact resistance are fused together to obtain the temperature rise Tf:
T f = I 2 ρ C T g A + ( ρ A 1 l + 2 α λ A τ w 2 α λ A + C T g l I 2 ρ C T g A ) e α x + ξ c μ L c 0 N t c f ( δ ) A z d t
Under the action of temperature rise and vibration load stress, the corrosion and oxidation of contact bimetallic strips are the main reasons for the failure of low-voltage electrical contacts used in transport vehicles, while under vibration load, the reason for failure is micro-motion wear on concave and convex areas. Under the combined action of vibration, friction, and temperature changes, the heat generated by friction intensifies the corrosion and oxidation of the contact bimetallic strip. At the same time, the relative motion of friction leads to the rupture of the oxide film, exposing the metal contact material and continuing the oxidation reaction, shortening the contact life. The process of contact point failure caused by temperature and vibration is shown in Figure 4.
There is a complex mutual coupling effect between vibration stress and temperature stress, and it is difficult to quantitatively analyze the impact of these two stresses on contact failure. Under the combined effects of temperature changes and vibration friction stress, the failure mechanism of low-voltage electrical appliances used in transport vehicles is the same. Statistical analysis of their electrical life shows that they comply with the principle of mutual independence and follow a two-parameter Weibull distribution. Combined with the temperature rise effects caused by vibration and temperature, the functional relationship model between the electrical life of low-voltage electrical appliances used in transport vehicles and the temperature and vibration stress caused by variable loads satisfies Formula (11):
L = α β exp E η ( T + T f ) N δ γ
where L represents the electrical life of the contact, α represents the temperature rise sensitivity coefficient, β represents the vibration sensitivity coefficient, η represents the Boltzmann constant, Tf represents the temperature rise, E represents the thermal sensitivity of the bimetallic strip, N represents the vibration stress, δ represents the cumulative damage constant, and γ represents the correlation with the properties of the metal material.

2.2. Failure Mechanism of Contact System Under Arc Conditions

When the static and moving contacts of the contact system are disconnected, if the conditions for generating an arc are reached between the contacts, these arcs occur naturally even at low voltage when the roughness is in the micron range [9]. An arc is a gas with strong light and extremely high temperature. This arc, accompanied by high temperature, melts the surface material of the contact metal sheet, with the resulting molten liquid being sprayed and dispersed under the action of airflow and a magnetic field, which leads to electrical wear of the contacts during the disconnection process. The mechanism of electrical wear involves the loss of quality of the contact metal sheet caused by the energy and time of arc ignition. This arc ignition causes cumulative damage to the contact system, ultimately leading to the failure of low-voltage electrical appliances. This damage mainly occurs in three stages: connection, the closed state, and disconnection.
When the contact passes through higher voltage and current in the process of making, closing, and breaking, the facial mask on the contact metal sheet may be broken down by the circuit voltage or burned by the circuit current. Due to heat dissipation caused by the current passing through the contact resistor, there is an increase in the temperature of the conductive spots on the metal sheet that the contact connects with, leading to local melting and even fusion welding on the surface of the metal sheet. When the contact resistance current is high, it is likely that the arc breaks through the surface facial mask at the contact metal sheet when the contact opens. When the contact closes, this contact resistance may generate a lot of joule heat, removing the organic matter at the contact and decreasing the size of the film resistance on the metal sheet. At this point, the main reason for the failure of the contact system is no longer the resistance of the contact film but is arc generation and the subsequent welding problems. When the contact is close to closing, a line voltage is generated and may break down, forming an arc. The current becomes connected when the contact is closed, and the arc is extinguished. When the contacts collide, kinetic energy is generated, and the electric repulsion may cause the contacts to bounce, resulting in the formation of an arc when the contacts break, melting and vaporizing the metal surface of the contacts. When the contact bounces to the maximum distance, the contact connects and closes again, the arc is extinguished, the metal material on the surface of the metal sheet melts, and after dispersing, it cools down to produce welding. When the contact is disconnected or repelled by electric force, the formation of an instantaneous arc will melt and vaporize the metal surface of the contact. When the contact is closed again, the molten liquid on the surface of the metal sheet will quickly cool down, causing the metal to solidify and form a fusion weld. From the above analysis, it can be concluded that the failure modes vary depending on the process of contact connection, closure, and disconnection.
Systems usually suffer from failures due to internal degradation (e.g., corrosion, fatigue, or wear) and external shocks [10]. Because arcing can cause changes in the contact gap of low-voltage electrical contacts, the damage model is an effective way to resolve contradictions in lifetime prediction [11] and the degradation rate model of contact bimetallic strips [12]:
d y d N = K W ( N ) y m
where the erosion coefficient K reflects the relationship between the arc energy and the change in contact gap and is influenced by the contact area, contact material, arc motion, and other environmental factors such as humidity, temperature, and air pressure, which collectively affect the change in the contact metal gap. m is the degradation index, reflecting the degradation rate and randomness of the contact gap. When m < 0, the change function W (N) of the arc energy reflects the factors that affect this energy, such as the breaking rate and load type. N is the operating life of the low-voltage electrical contact. The degradation model of the contact gap is obtained by integrating the model of Formula (12):
y = ( 1 m ) ( K W ( N ) d N ) 1 1 m = K ( 1 m ) φ ( N ) 1 1 m
when m < 0, the accumulated energy of the arc is φ ( N ) . In practical situations, due to the influence of the initial value of the contact surface gap, it is necessary to modify the parameters of the degradation model in Formula (13):
y = K ( 1 m ) φ ( N ) 1 1 m + y 0
where m < 0. The initial value of the contact surface gap between the contacts is y 0 . The arc energy generated during a single disconnection process E is
E = a b u n i n Δ t = n = a b u n i n f s
where the sampling parameters are voltage value un, current value in, frequency n, time interval Δ t , and frequency f s .
Taking a circuit breaker as an example, the mechanism of arc energy generation in the contact system under arc conditions is analyzed. The arc initiation phase angle of AC power is divided into three zones: [0, π/3), [π/3, 2π/3), and [2π/3, π). When the initial arc phase angle is in the [0, π/3) zone, the expression of arc current is
i A = 2 I sin ( ω t ) + 2 I u h 3 λ U ( e λ ω 1 λ 2 ( φ ω t ) 1 ) i B = 2 I sin ( ω t 2 π 3 ) 4 I u h 3 λ U ( e λ ω 1 λ 2 ( φ ω t ) 1 ) i C = 2 I sin ( ω t + 2 π 3 ) + 2 I u h 3 λ U ( e λ ω 1 λ 2 ( φ ω t ) 1 )  
where φ ω < t < t f . When the C-phase current is disconnected, the A-phase and B-phase currents form a loop, and their arc currents are represented as follows:
i A B = i B A = 6 2 I sin ( ω t + π 6 ) + n I u h λ U ( e λ ω 1 λ 2 ( φ ω t ) 1 n )       t f < t < t x
where tf is the moment the arc extinguishes when the current begins to disconnect, and tx is the moment the arc extinguishes when the current ends. The initial value i A B can be calculated according to Formula (17), and the constant n value can be obtained. When φ in the range of [π/3, 2π/3), the A-phase arc current can be expressed as
i A = 2 I sin ( ω t ) + 4 I u h 3 λ U ( e λ ω 1 λ 2 ( φ ω t ) 1 )       φ ω < t < t f
At the moment the arc extinguishes when the B-phase current is disconnected, the A-phase and C-phase currents form a loop, and the current iAC is calculated as follows:
i A C = i C A = 6 2 I sin ( ω t π 6 ) + n I u h λ U ( e λ ω 1 λ 2 ( φ ω t ) 1 n )       t f < t < t x
when φ is in the [2π/3, π) interval, the arc of the A phase-disconnected current begins to extinguish. In this case, the current iA is calculated as follows:
i A = 2 I sin ( ω t ) + 2 I u h 3 λ U ( e λ ω 1 λ 2 ( φ ω t ) 1 )     φ ω < t < t f
In summary, the Joule integral of the A-phase contact is calculated as follows:
W A J = φ j φ f i A 2 ( φ ) d φ + φ f φ x i A B 2 ( φ ) d φ ( 0 φ < π 3 ) φ j φ f i A 2 ( φ ) d φ + φ f φ x i A C 2 ( φ ) d φ ( π 3 φ < 2 π 3 ) φ j φ f i A 2 ( φ ) d φ ( 2 π 3 φ < π )
where φf is the initial extinguishing phase angle when the current is turned on, and φx is the final arc extinguishing phase angle when the current is disconnected.

3. Reliability Assessment Modeling Based on Variable-Load Data-Driven Approach

Due to the greatly improved reliability and lifespan of low-voltage electrical appliances used in transport vehicles, it is generally difficult to obtain data on their failure time [13]. Therefore, residual life prediction methods based on failure time are in a dilemma. Data-driven and machine learning methods provide efficient and accurate approaches for solving impact problems [14], so this study adopts a data-driven approach to evaluate the reliability and predict the electrical life of these appliances. The key to data-driven methods is to use performance degradation data to establish degradation models without the need for failure time, which is very suitable for reliability assessment and prediction of the appliances. If traditional reliability life assessment methods are used, a large number of vehicles would need to use low-voltage electrical test samples for fatigue testing, which is impossible; instead, Bayesian models [15] are used to solve the problem. The Bayesian evaluation method can comprehensively utilize historical information and overcome the limitations caused by small sample sizes [16]. Data-driven policies can be used in a more intelligent way to achieve anomaly detection and effectively avoid the introduction of expert experience, thus having a broader scope of application [17].
Take n (n ≤ 2) pieces from low-voltage electrical products used in transport vehicles as samples for timed truncation tests [18], and conduct a total of k tests on this group of samples, with each test lasting ti (0 < t1 < t2 < t3 < tk) and the number of samples that have not failed at time ti being ni. The number of samples without failure after testing is t i ,   n i  i =1, 2, 3, … k. If S i = n i + n i + 1 + n i + 2 + + n k , then the sample has no failures: t i ,   s i  i = 1, 2, 3, … k. The cumulative failure probabilities obtained from conducting k tests on the samples are p 1 ,       p 2   ,   p 3   , ,   p k   . The cumulative failure probability is pi at time ti. There are two types of test results, invalid or not invalid, which follow a binomial distribution. Therefore, the probability of ri failure in the total number of samples si is
P r i p i = C s i r i p i r i 1 p i s i r i
where C s i r i represents the combination of failure probabilities, and the sample has a normal probability of no failure:
P 0 p i = 1 p i s i
In Bayes statistical inference, selecting an appropriate prior distribution is crucial for parameter estimation. It is very reasonable to use the Beta distribution as a prior distribution for cumulative failure probability, especially when dealing with small sample situations [19]. Therefore, the prior distribution Beta is changed to an incomplete Beta distribution, and its probability density function is
f x = x θ 1 α 1 θ 2 x β 1 B α ,   β θ 2 θ 1 α + β 1     θ 1 < x < θ 2
where B α ,   β = 0 1 x α 1 1 x β 1 d x is the Beta function, α > 0, β > 0, and θ 1 < θ 2 . From the above analysis, it can be seen that under the aforementioned conditions, the prior function of p1 is
f p 1 c = 1 c p 1 0.5 1 p 1 B 0.5 ,   β β 1 1 c 1 d β
According to Bayes’ theorem, the posterior distribution of cumulative failure probability p1 is
f p 1 s 1 = f p 1 c L 0 p 1 0 1 f p 1 c L 0 p 1 d p 1
The point estimate of cumulative failure probability p1 is the mean of the posterior distribution, which is
p ^ 1 = E f p 1 s 1 = 0 1 f p 1 s 1 d p 1
where E f p 1 s 1 is the cumulative failure probability of posterior mean p ^ 1 .
Due to p1p2 ≤⋯≤ pk, take the prior distribution of p2 as Beta ( p ^ 1 , 1, 0.5, β). The hyperparameter β follows a uniform distribution of (1, c), and the prior distribution of cumulative failure probability p2 is
f p 2 c , p ^ 1 = p 2 p ^ 1 0.5 1 p 2 β 1 B 0.5 ,   β 1 p ^ 1 β 0.5 1 c 1 d β
According to Bayes’ theorem, the posterior distribution of the cumulative failure probability p2 is
f p 2 s 2 = f p 2 c , p ^ 1 L 0 p 2 p ^ 1 1 f p 2 c ,   p ^ 1 L 0 p 2 d p 2
The Bayes point estimate of cumulative failure probability p2 is
p ^ 2 = E f p 2 s 2 = p ^ 1 1 f p 2 s 2 d p 2
According to mathematical induction, the prior distribution [20] of cumulative failure probability pi is known as
f p i s i = p i , p ^ i 1 0.5 1 p i β 1 p ^ i 1 1 B 0.5 ,   β 1 p ^ 1 β 0.5 1 c 1 d β
Similarly, the posterior distribution of cumulative failure probability pi is
f p i s i = f p i c , p ^ i 1 L 0 p i p ^ i 1 1 f p i c , p ^ i 1 L 0 p i d p i
Therefore, based on the Bayes model, the general form of cumulative failure probability p ^ i is obtained:
p ^ i = E f p i s i = p ^ i 1 f p i s i d p i
After obtaining pi through the above method, it can be concluded from the above formula that the scale parameter η and shape parameter β in the Weibull model [21] can be obtained through the weighted least squares method. The two-parameter classical Weibull distribution is commonly implemented to cater for the product’s reliability, model the failure rates, and analyze lifetime phenomena [22]. η is a scale parameter that is related to the lowest contact failure rate, and β is a shape parameter that is related to the trend of contact failure rate.
By combining Bayes’ method with the weighted least squares method [23], one of the most commonly used methods in producing the Weibull distribution is the ordinary least squares technique, which is useful in reliability and lifetime modeling [24]. Prior information and data features can be effectively utilized in parameter estimation, thereby improving the accuracy and reliability of the estimation. First, take the weight as wi, and then calculate p ^ i using Bayes’ method and substitute it into Formula (37):
w i = n i t i i = 1 k n i t i i = 1,2 , , k
Consider the following:
Q β , η = i = 1 k w i p i 1 + e x p t i η 2
𝜕 Q 𝜕 β = 𝜕 i 1 k w i p i 1 + e x p t i η β 2 𝜕 β 𝜕 Q 𝜕 η = 𝜕 i 1 k w i p i 1 + e x p t i η β 2 𝜕 η
β = i = 1 k w i ln ( ln 1 1 p ^ i ) 2 i = 1 k w i ln ( ln 1 1 p ^ i ) 2 i = 1 k w i ln t i ln ( ln 1 1 p ^ i ) i = 1 k w i ln ln ( ln 1 1 p ^ i ) i = 1 k w i ln t i η = exp ( B C A D / ( B A 2 )
is obtained, where
A = i = 1 k w i ln ln 1 1 p ^ i B = i = 1 k w i l n ln 1 1 p ^ i 2 C = i = 1 k w i ln t i D = i = 1 k w i ln t i ln ln 1 1 p ^ i
In an actual operation process, the failure rate of low-voltage electrical appliances used in transport vehicles is often affected by various factors, resulting in their time-varying and non-uniform failure characteristics. To effectively simulate this complex performance degradation process, a stochastic process with nonlinear drift can be used for modeling the stochastic nonlinear degradation process, which can more flexibly and accurately describe the nonlinearity of the degradation process [25]. If the initial value of the random process is 0, the model of the random process with nonlinear drift is as follows:
X ( t ) = μ 0 t u ( τ , b ) d τ + σ W ( t )
where X(t) represents the actual performance degradation degree of low-voltage electrical appliances used in the transport vehicle at time t in the random process. The cumulative effect of the performance degradation failure process is represented by 0 t u ( τ , b ) d τ . The drift coefficient and diffusion coefficient represent the impact of uncertain factors on the performance of low-voltage electrical equipment. W(t) is a standard stochastic process.
To reflect the individual differences in the evaluation prediction model, the parameters are treated as random variables. If they follow the same distribution, they are denoted as σ 2 = D. Since D > 0, and thus 1 D > 0, assuming they follow the Gamma function distribution, then D follows the inverse Gamma model [26] function distribution.
g D ( x ; a 0 , β 0 ) = α 0 β 0 Γ ( β 0 ) x ( β 0 + 1 ) e α 0 x
where a 0 determines the shape of the distribution, β 0 determines the degree of expansion of the distribution, x > 0, a 0 > 0, and β 0 > 0, further assuming that under given conditions of σ 2 , μ follows a normal distributions:
μ | σ 2 ~ N ( μ 0 , η 0 σ 2 )
After determining the prior distribution, D follows the inverse Gamma function distribution Ga(v(τ − t),u) as shown in Formula (40). When D is given and μ follows a normal distribution, the estimated value of parameters μ , σ is calculated according to
μ = i = 1 N X i m i = 1 N t i m σ 2 = 1 i = 1 N M i i = 1 N j = 1 M i ( Δ X i j ) 2 Δ t i j ( i = 1 N X i m ) i = 1 N t i m  
where N is the total number of samples and Mi is the total number of i-th detections. At time ti1, the i-th degradation quantity of tim is Xi1, Xim, and Δ X i j = X i j X i , j 1 are the i-th degradation increments at time t i , j 1 ~ t i j . Δ t i j = t i j t i , j 1 is the time interval, j is the number of detections, and μ and σ are calculated according to the above formula.
When X(t) reaches the failure threshold L for the first time, the low-voltage electrical equipment used in the transport vehicle fails, and the probability density function of the remaining life is as follows:
f ( t , u , σ , N ) = N 2 π σ 2 0 t u ( τ , b ) d τ exp ( L s u 0 t u ( τ , b ) d τ ) 2 2 σ 2 0 t u ( τ , b ) d τ
In general, the expected value of the probability density function of the remaining life distribution can be used as the predicted value. This expected value can be obtained from the above equation:
E ( N ) = L L 0 μ
In formulas (42) and (43), N represents the remaining number of operations, L represents the number of failures, and L0 is the cumulative number of operations.
Based on the aforementioned Bayesian non-parametric uncertainty inference model, assuming that the reliability of low-voltage electrical equipment used in transport vehicles follows a two-parameter Weibull distribution [27], the reliability calculation function is
R ( t ) = 1 F ( t ) = exp t η β
where F(t) is the cumulative distribution function CDF of the fault distribution of low-voltage electrical appliances used in transport vehicles, and T is the fault-free operating time of these appliances. The estimated CDF has a lower spread, higher reliability, and sharper probabilistic forecasts with better accuracy [28].

4. Validation of Reliability Evaluation Model Based on Variable-Load Data-Driven Approach

4.1. Construction of a Reliability Testing Platform

The research and design of a reliability testing platform for low-voltage electrical appliances used in transport vehicles mainly aim to evaluate and verify the performance and reliability of these appliances. The reliability testing platform is integrated with a management software system and a variable-load testing device. The overall plan of the testing platform is shown in Figure 5. The platform management software system includes a series of functions such as test parameter setting, test process control, test data collection, storage, query, printing, remote monitoring, fault alarm, and reliability evaluation. The variable-load test device includes a vibration variable-load test device, an electromagnetic variable-load test device, a temperature rise variable-load test device, etc., where vibration variable load is the main influencing factor on the reliability of low-voltage electrical appliances used in transport vehicles.
The vibration variable-load test device was used to simulate transport vehicles and generate variable excitation vibrations with different vibration intensity characteristics. The dynamic response signals of the tested low-voltage electrical contact system are captured by sensors, and the upper computer software system processes, analyzes, evaluates, and visualizes the collected signals.
Taking circuit breaker detection as an example, its contact current and voltage data contain rich electrical performance characteristic information, which can be used to evaluate and predict the remaining life of the circuit breaker. The electrical life of circuit breakers is generally long, so their failure tests take a long time. In order to quickly collect failure test data, the accelerated life method is adopted to shorten the failure test schedule. Detection parameters are set according to the national standard GB/T14048.1-2023 [29] “Low voltage switchgear and control equipment”, and the parameter settings for the accelerated test are shown in Table 1. The circuit breaker is installed on the vibration table as shown in Figure 6a. During the test, the management software system collects variable-load current and voltage data as shown in Figure 6b. The data collected during the experiment includes action time, bounce frequency, bounce time, contact pressure, arc time, coil voltage, coil current, arc time, breaking current, contact resistance, arc energy, pull-in time, cumulative arc energy, trigger time, release voltage, contact voltage drop, release time, rebound time, over travel time, and the power factor, a total of 20 characteristic parameter data categories.
The reliability of low-voltage electrical appliances used in transport vehicles is affected by various environmental factors, and some parameters have significant interference, with no discernible trend in their changes. In addition, some parameters have a high correlation with each other, resulting in consistent trends in their changes, due to the large number of feature parameters that consume computer resources and affect the evaluation effect. Using the Spearman index to define the Spearman matrix, which is a mathematical object expressing the pattern of dependence among the components of a multivariate functional dataset [30], the Spearman rank correlation coefficient method was used to analyze and study the top seven feature parameters in terms of weight ranking, which are cumulative arc energy, contact voltage drop, contact resistance, release voltage, arc time, suction time, and arc energy. These seven feature parameters constitute the evaluation feature dataset.

4.2. Construction of Reliability Assessment Feature Parameter Set

(1) Reliability characteristic parameter calculation
The calculation method for evaluating feature parameters is as follows:
① Adhesion time tx: The interval time from the initial state to the suction state, excluding bounce time.
tx = t2t1
where t1 is the starting time of the coil current and t2 is the first closing time of the contact.
② Arcing time tr: The entire process from the formation of the arc to its final extinction, which refers to the time when the current passes through the contact point and the arc discharge phenomenon occurs.
tr = t4t3
where t3 is the moment of starting the arc and t4 is the moment of extinguishing the arc.
③ Arc energy: The energy released by arc combustion during the arc time.
e = t 3 t 4 u ( t ) i ( t ) d x
where u (t) is the arc voltage and i (t) is the arc current.
④ Accumulated arc energy: As the data collected in the experiment is discrete, the values of voltage and current sampling points are, respectively, recorded as un and in. Calculation of arc energy:
E = n = a b u n i Δ t = n = a b u n i n f s
where is the interval time between adjacent two samples, and fs is the sampling frequency.
⑤ Contact resistance refers to the resistance between two conductors at the contact point, which may cause an increase in temperature at the contact point. The formula for calculating the relationship between contact resistance R and temperature is
R = R 0 ( 1 + 2 3 σ T θ )
When the temperature is 0, the contact resistance is, the temperature coefficient of resistivity is, and the calculation formula in the above equation is
T θ = U 2 8 ρ ¯ λ ¯
where the resistivity ρ, thermal conductivity λ, and the integrated median calculated from ρ ¯ λ ¯ T θ = 0 T ρ λ d δ are ρ ¯ λ ¯ .
⑥ Contact voltage drop refers to the voltage decrease caused by contact resistance when current passes through a contact point. Calculation formula for contact pressure drop:
U d = I × R c
where Ud is the contact pressure drop (unit: V); I is the current passing through the contact point (unit: A); and Rc represents contact resistance (unit: Ω).
⑦ Release voltage refers to the voltage drop at both ends of the contact during 40% of the breaking process, which can be collected by sensors.
⑧ Kernel principal component analysis can handle the nonlinearity and the dynamic features simultaneously [31]. Due to the nonlinear nature of the variable loads generated by low-voltage electrical appliances used in transport vehicles, the analysis and evaluation of nonlinear high-dimensional data require efficient algorithms and models that can capture nonlinear features in high-dimensional space. The process of processing raw data to obtain kernel principal components is as follows:
Standardize the collected feature parameter data to form a feature parameter set xi (i = 1, …, n, xiR), and map xi to a high-dimensional space using a nonlinear function ξ. If xi meets the centralization condition, then the covariance matrix [32] of the samples in high-dimensional space is
C m = 1 n i = 1 n ξ ( x i ) ξ ( x i ) T
The eigenvalues and eigenvectors of matrix Cm can be obtained according to the above formula. In λ v = C m v , λ is the eigenvalue of matrix Cm, and v is the eigenvector corresponding to λ. There are
λ ξ ( x k ) v = ξ ( x k ) C m v
where h = 1, …, n. Given that λ = 0 and wi = (1, …, n) exists, let
v = i = 1 n w i ξ ( x h )
According to formulas (53) and (54),
λ i = 1 n w i ( ξ ( x h ) , ξ ( x i ) ) = 1 n i = 1 n w i ( ξ ( x h ) , j = 1 M ξ ( x i ) ) ( ξ ( x j ) , ξ ( x i ) )
Define an n × n matrix h such that
h i j = h ( x i , x j ) = ( ξ ( x i ) , ξ ( x i ) )
According to Equation (56), we have
n λ h w = h 2 w
where w = (w1, …, wn), and the eigenvalues and eigenvectors are obtained by solving the characteristic equation nλw = hw. The h-th (h = 1, 2,..., n) principal component th in the feature space can be obtained from the feature vector vh.
t h = ( V h , ξ ( x ) ) = i = 1 n w i h ( ξ ( x i ) , ξ ( x ) ) = i = 1 n w i h h ( x , x i )
h = 1 q λ h > E k = 1 n λ h
The selection of th is based on Formula (59), where E is a predetermined constant. When xi does not meet the centralization criteria, use fij instead of hij:
f i j = h i j 1 n n = 1 n l i w h w j 1 n o = 1 n h i o l o j + 1 n 2 w , o = 1 n l i w h w o l o j
where lij = 1, hij is the kernel principal component function.
(2) Evaluate the process of constructing feature parameter sets
Constructing the initial feature parameter vector X0 includes contact voltage drop, contact resistance, release voltage, arc time, pull-in time, arc energy, and cumulative arc energy. Due to the differences in magnitude and dimension between the feature parameters in the feature parameter vector X0, normalization of X0 is required [33] to alleviate the adverse impact of handling effects in the setting of differential expression analysis [34], and the large weight may mask the decimal changes in the weight. Therefore, the deviation normalization method is adopted:
x = x min ( x ) max ( x ) min ( x )
where x is the original data, min (x) is the minimum value in the data, max (x) is the maximum value in the data, and x is the normalized data. Using kernel principal component analysis to reduce the dimensionality of feature parameter X0, kernel principal component X2 is obtained. The feature quantity X1 = x and the kernel principal component X2 are merged to construct the full feature quantity X, that is, X = [ X 1 , X 2 ] . The construction process of parameter set X for reliability evaluation of low-voltage electrical appliances based on variable-load operation tools is shown in Figure 7:

4.3. Verification of Reliability Assessment Model Evaluation

(1) Construction of Variable-Load Feature Dataset
Taking the variable-load test of circuit breaker model NDM3-15 as an example, seven samples from the same manufacturer and batch are selected for the variable-load test, and any one sample is chosen as the validation sample. The evaluation data obtained through experiments are shown in Table 2.
(2) Screening of strongly correlated feature data
Due to the nonlinear nature of the characteristic data collected during variable-load testing, the correlation between reliability evaluation characteristic parameters is evaluated and screened using the Spearman correlation coefficient method. The Spearman correlation coefficient method [35] ranks two variables X and Y, with a ranking difference of d i :
d i = R ( X i ) R ( Y i )
Among them, R (Xi) and R (Yi) are the rankings of variables X and Y, respectively.
r s = 1 6 d i 2 n ( n 2 1 )
where r s is the correlation coefficient, n is the number of feature parameters, and d i 2 is the sum of the squares of all ranking differences.
The range of correlation coefficient values is r s < 1 . The closer r s approaches 0, the weaker the correlation. When r s approaches 1 or −1, the stronger the correlation. When r s = 1 , the degradation feature quantity is completely negatively correlated with contact failure. When r s = 1 , the degradation feature quantity is completely positively correlated with contact failure. Judging the strength of correlation based on the range of r s , 0.0 ~ 0.2 indicates extremely weak correlation or no correlation, 0.2 ~ 0.4 indicates weak correlation, 0.4 ~ 0.6 indicates moderate correlation, 0.6 ~ 0.8 indicates strong correlation, and 0.8 ~ 1.0 indicates strong correlation.
According to the variable-load test data in Table 2, the correlation between the failure characteristic parameters shown in Table 3 and the electrical life is calculated. From Table 3, it can be intuitively seen that the cumulative arc energy has a strong correlation with the electrical life, and the other related strengths are ranked in order of nuclear principal component, contact resistance, and contact voltage drop.
(3) Evaluation and validation of predictive applications based on variable-load data-driven models
Methods based on data-driven models are widely used in the field of dynamic evaluation and prediction [36,37]. Through these methods, prior information is obtained through simulation experiments and prior and posterior failure information is integrated. Based on this prior and posterior information, a data-driven model is used to construct a probability distribution of the remaining lifespan and then determine the reliability of the tested sample from the probability distribution of the remaining lifespan. Table 4 shows the correspondence between the number of circuit breaker test operations and accumulated arc energy obtained through simulation experiments. The table shows that the number of operations (electrical lifetime) for samples 1, 2, and 3 is 35,700, 35,870, and 36,100, respectively. The average accumulated arc energy of three samples is taken as the failure threshold [38], which is ω = 1,076,392.
The analysis of experimental data shows that the optimal evaluation parameters are the cumulative arc energy, nuclear principal components, contact resistance, and contact voltage drop, with a cumulative arc energy failure threshold of ω = 1,076,392. The evaluation and prediction process based on the variable-load data-driven model is shown in Figure 8. Experiments are conducted on any selected validation sample; accumulated arc energy, nuclear principal components, contact resistance, and contact voltage drop test data are collected and processed using a reliability testing platform; and the constructed evaluation dataset is input into the reliability evaluation model. The evaluation prediction results are shown in Table 5.
According to Table 5, the relative error RE of the predicted values is mostly less than 6%, indicating that the evaluation of the prediction effect based on the variable-load data-driven model can meet the engineering needs.
Based on the data in Table 5, the predicted values of the model evaluation are compared with the actual test values as shown in Figure 9. The black and red curves in Figure 9 represent the actual test value and the model evaluation prediction value, respectively. The black and red curves are close, indicating that the model evaluation prediction value is consistent with the actual test value, which verifies the high reliability of the evaluation results based on variable-load data-driven models.
The reliability assessment model is applied to the reliability testing platform management software system, 32 samples of circuit breakers are randomly selected for transport vehicles, and their remaining operation times are predicted through experiments. The prediction results are shown in Table 6, and the reliability is calculated according to Formula (44). According to the table, there are 1000 remaining operations for the predicted sample, and the reliability is close to 0, indicating that the sample has failed. The remaining number of operations for the predicted sample is around 14,000, with a reliability of approximately 60%. If this remaining number of operations is around 30,000, and the reliability of the sample is close to 100%, the product reliability can fully meet user needs.
The remaining operation times and reliability curves are drawn based on the predicted remaining number of operations (lifespan) and reliability in Table 6, as shown in Figure 10. Figure 10 indicates that the higher the remaining lifespan of the predicted sample, the higher the reliability of the sample.
In summary, based on the variable-load data-driven reliability evaluation model, the input feature parameters such as cumulative arc energy, nuclear principal components, contact resistance, contact voltage drop, and threshold parameter values have high accuracy and good performance in outputting evaluation prediction values. Therefore, data-driven models based on variable loads meet the evaluation and prediction needs of low-voltage electrical appliances for transport vehicles.

5. Conclusions

To study the reasons for failure of low-voltage electrical appliances used in operating tools under variable-load conditions, a data-driven reliability evaluation model based on variable load was established and applied to the management software system of the low-voltage electrical reliability testing platform for transportation vehicles. The main research results of the study are as follows:
(1)
Analysis of the Failure Mechanism of Low-Voltage Electrical Appliances for Downloading and Operating Tools under Variable-Load Conditions: We studied the mechanism of variable-load generation in low-voltage electrical appliances used in transportation vehicles, the composition of the vibration sources, and the failure of low-voltage electrical appliances in vibration environments. Research has shown that temperature and vibration environmental stresses are considered the main reasons for the degradation of contact performance in low-voltage electrical appliances used in transportation vehicles. The reliability of these appliances is directly related to the safe operation of transportation vehicles. Reasonably optimizing the replacement cycle of these appliances inside transportation vehicles not only ensures their safe operation but also reduces maintenance and replacement costs. The analysis of the failure mechanism of low-voltage electrical appliances used in operation under variable-load conditions is the theoretical basis for establishing a reliability assessment and prediction model.
(2)
Adopting data-driven models to evaluate the reliability of low-voltage electrical appliances used in transportation vehicles: During the movement of transportation vehicles, the internal low-voltage electrical components may experience periodic or non-periodic changes in load over time under vibration and impact conditions. Taking the circuit breaker for transportation vehicles as an example, characteristic parameters were collected under dynamic environmental conditions. Then, the feature parameters were preprocessed, a set of variable-load feature parameters was constructed, and the correlation between their feature parameters was analyzed. Finally, feature parameters with a significant performance degradation weight and strong correlation were selected to input into the reliability evaluation prediction model. The reliability evaluation prediction results were output, and they were compared with the actual data detected by the detection platform to verify the accuracy of the reliability evaluation model and the reliability of the prediction results.
In order to verify the effectiveness of the model, we analyzed the evaluation results based on the indicators of model application performance and found that the relative error, RE, of the predicted values was mostly less than 6%. The verification analysis shows that our data-driven reliability evaluation model based on variable load meets the requirements of practical engineering applications.

Author Contributions

Conceptualization, L.L. and M.Y.; methodology, L.L.; software, L.L.; validation, L.L., S.C. and W.Z.; formal analysis, L.L.; investigation, L.L.; resources, L.L.; data curation, M.Y.; writing—original draft preparation, L.L.; writing—review and editing, L.L.; supervision, S.C.; project administration, L.L. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The data presented in this study are available upon request from the corresponding author.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Hwang, M.; Mo, Y.-K.; Woo, P.-S.; Kim, Y.-N.; Kim, Y.-S.; Shong, K.-M. A Study on the Prevention of Low-voltage Equipment Failure by Analyzing Switching Surges on Low-voltage. Trans. Korean Inst. Electr. Eng. 2023, 72, 1753–1759. [Google Scholar] [CrossRef]
  2. Park, J.; Kim, J.; Lee, S. Evaluation of Electrical Damage to Electric-vehicle Bearings under Actual Operating Conditions. Tribol. Lubr. 2024, 40, 111–117. [Google Scholar]
  3. Dong, B.; Zhang, Z.; Xiang, N.; Zhang, Z.; Ding, L.; Chen, W. Study on Triggering Characteristics and Induced Breakdown Rules of SF6 Gap Switch Plasma Jets a Extremely Low Working Voltage. IEEE Trans. Plasma Sci. 2022, 50, 873–882. [Google Scholar] [CrossRef]
  4. Wiss, E.; Metasch, R.; Barth, D.; Serea, V.; Roellig, M.; Wiese, S. Electrical diagnostics of passive components failure during reliability testing. In Proceedings of the 23rd International Conference on Thermal, Mechanical and Multi-Physics Simulation and Experiments in Microelectronics and Microsystems (EuroSimE), St Julian, Malta, 25–27 April 2022. [Google Scholar]
  5. Liu, S.; Liu, M.; Lu, P.; Zhang, F.; Hong, J.; Wang, L. Study on the electrical properties of Cu-based ECMs prepared by TiBN powder instead of W. Int. J. Refract. Met. Hard Mater. 2023, 117, 106402. [Google Scholar] [CrossRef]
  6. Cui, D.; Xie, R.; Li, M.; Cheng, W. Time-dependent reliability analysis for structures under multilevel loads based on fatigue damage theory. Eng. Fail. Anal. 2024, 162, 108396. [Google Scholar] [CrossRef]
  7. Wang, M.; Liu, X.; Wang, X.; Wang, Y. Probabilistic modeling of unified S-N curves for mechanical parts. Int. J. Damage Mech. 2018, 27, 979–999. [Google Scholar] [CrossRef]
  8. Marques, J.M.E.; Mzourek, M.; Papuga, J.; Ruzicka, M.; Mara, V.; Trojan, K.; Benasciutti, D. Evaluating size effects on fatigue life of 42CrMo4+QT steel using a statistical S-N model with highly-stressed volume and surface. In Proceedings of the 23rd International European Conference on Fracture (ECF), Funchal, Portugal, 27 June–1 July 2022; pp. 1414–1421. [Google Scholar]
  9. Jonckheere, B.; Bouzerar, R.; Mohamed, S.A.; Bausseron, T. Electrical arc transfer in a multi-contact interface. Sens. Actuators A-Phys. 2022, 335, 113215. [Google Scholar] [CrossRef]
  10. Gan, S.; Song, Z. Reliability Evaluation by a Dependent Competing Failure Model Including a Time-Varying Rate for Sudden Degradation Increments. Arab. J. Sci. Eng. 2021, 46, 10137–10152. [Google Scholar] [CrossRef]
  11. Song, H.; Xie, H.; Zhang, Z.; Zhang, Q.; Kang, Y. Prediction Model of Capacity Degradation in Lithium-Ion Batteries Based on Fatigue Damage Theory and Electrochemical Impedance Spectroscopy. Acta Mech. Solida Sin. 2025, 38, 517–525. [Google Scholar] [CrossRef]
  12. Kaaya, I.; Chowdhury, G.; Morlier, A. A physics based approach for PV lifetime and degradation signatures prediction. In Proceedings of the IEEE 50th Photovoltaic Specialists Conference (PVSC), San Juan, PR, USA, 11–16 June 2023. [Google Scholar]
  13. Yu, M.; Zheng, X.; Zhao, C. Research on the Prediction Method of Clock Tester Calibration Data Based on Radial Basis Function Neural Network. Electronics 2023, 12, 4677. [Google Scholar] [CrossRef]
  14. Li, X.; Li, Z.; Chen, Y.; Zhang, C. A data-driven approach for predicting the ballistic resistance of elastoplastic materials. Eng. Fract. Mech. 2023, 293, 109706. [Google Scholar] [CrossRef]
  15. Gao, T.; Li, Y.; Huang, X.; Wang, C. Data-Driven Method for Predicting Remaining Useful Life of Bearing Based on Bayesian Theory. Sensors 2021, 21, 182. [Google Scholar] [CrossRef] [PubMed]
  16. Zou, T.; Wu, W.; Liu, K.; Wang, K.; Lv, C. Bayesian Averaging Evaluation Method of Accelerated Degradation Testing Considering Model Uncertainty Based on Relative Entropy. Sensors 2024, 24, 1426. [Google Scholar] [CrossRef]
  17. Zhou, H.; Lei, Z.; Zio, E.; Wen, G.; Liu, Z.; Su, Y.; Chen, X. Conditional feature disentanglement learning for anomaly detection in machines operating under time-varying conditions. Mech. Syst. Signal Process. 2023, 191, 110139. [Google Scholar] [CrossRef]
  18. Gong, Y.; Feng, S. Research on calculating aerospace single machine products mean time between failures using timing truncation method. In Proceedings of the International Conference on Mechanical Design and Simulation (MDS), Wuhan, China, 18–20 March 2022. [Google Scholar]
  19. Zou, T.; Liu, K.; Wu, W.; Wang, K.; Lv, C. Uncertainly Analysis of Prior Distribution in Accelerated Degradation Testing Bayesian Evaluation Method Based on Deviance Information Criterion. Symmetry 2024, 16, 160. [Google Scholar] [CrossRef]
  20. Hansen, T.M.; Finlay, C.C. Use of Machine Learning to Estimate Statistics of the Posterior Distribution in Probabilistic Inverse Problems-An Application to Airborne EM Data. J. Geophys. Res.-Solid Earth 2022, 127, e2022JB024703. [Google Scholar] [CrossRef]
  21. Jia, X. Reliability analysis for q-Weibull distribution with multiply Type-I censored data. Qual. Reliab. Eng. Int. 2021, 37, 2790–2817. [Google Scholar] [CrossRef]
  22. Wu, X.; Ahmad, Z.; Hussam, E.; Alhelali, M.H.; Aldallal, R.; Almuqrin, M.A.; Riad, F.H. A new Cosine-Weibull model: Distributional properties with applications to basketball and medical sectors. Alex. Eng. J. 2023, 66, 751–767. [Google Scholar] [CrossRef]
  23. Zuo, Y.; Zuo, H. Weighted Least Squares Regression with the Best Robustness and High Computability. Axioms 2024, 13, 295. [Google Scholar] [CrossRef]
  24. Aydi, W.; Alduais, F.S. Estimating Weibull Parameters Using Least Squares and Multilayer Perceptron vs. Bayes Estimation. Cmc-Comput. Mater. Contin. 2022, 71, 4033–4050. [Google Scholar] [CrossRef]
  25. Zhang, Y.; Yang, Y.; Li, H.; Xiu, X.; Liu, W. A Data-Driven Modeling Method for Stochastic Nonlinear Degradation Process with Application to RUL Estimation. IEEE Trans. Syst. Man Cybern.-Syst. 2022, 52, 3847–3858. [Google Scholar] [CrossRef]
  26. Zhang, Z.; Gao, D.; Guan, T.; Liang, Y.; Zhao, J.; Wang, L.; Tang, J. A Reliability Evaluation Method for Gamma Processes with Multiple Random Effects. Machines 2023, 11, 905. [Google Scholar] [CrossRef]
  27. Yan, T.; Fang, K.-T.; Yin, H. A novel approach for parameter estimation of mixture of two Weibull distributions in failure data modeling. Stat. Comput. 2024, 34, 221. [Google Scholar] [CrossRef]
  28. Ahmad, T.; Zhou, N.; Zhang, Z.; Tang, W. Enhancing Probabilistic Solar PV Forecasting: Integrating the NB-DST Method with Deterministic Models. Energies 2024, 17, 2392. [Google Scholar] [CrossRef]
  29. GB/T14048.1-2023; Low-voltage switchgear and controlgear—Part 1: General rules. National Low Voltage Electrical Equipment Standardization Committee: Shanghai, China, 2023.
  30. Ieva, F.; Ronzulli, M.; Romo, J.; Paganoni, A.M. A Spearman dependence matrix for multivariate functional data. J. Nonparametric Stat. 2025, 37, 82–104. [Google Scholar] [CrossRef]
  31. Fang, H.; Tao, W.; Lu, S.; Lou, Z.; Wang, Y.; Xue, Y. Nonlinear Dynamic Process Monitoring Based on Two-Step Dynamic Local Kernel Principal Component Analysis. Processes 2022, 10, 925. [Google Scholar] [CrossRef]
  32. Yang, J.; Lian, H.; Zhang, W. A Class of Structured High-Dimensional Dynamic Covariance Matrices. Commun. Math. Stat. 2023, 13, 371–401. [Google Scholar] [CrossRef] [PubMed]
  33. He, C.; Cao, Y.; Yang, Y.; Liu, Y.; Liu, X.; Cao, Z. Fault Diagnosis of Rotating Machinery Based on the Improved Multidimensional Normalization ResNet. IEEE Trans. Instrum. Meas. 2023, 72, 3293554. [Google Scholar] [CrossRef]
  34. Ni, A.; Qin, L.-X. Performance evaluation of transcriptomics data normalization for survival risk prediction. Brief. Bioinform. 2021, 22, bbab257. [Google Scholar] [CrossRef] [PubMed]
  35. Zhang, Q. On relationships between Chatterjee’s and Spearman’s correlation coefficients. Commun. Stat.-Theory Methods 2025, 54, 259–279. [Google Scholar] [CrossRef]
  36. Lee, J.; Mitici, M.; Blom, H.A.P.; Bieber, P.; Freeman, F. Analyzing Emerging Challenges for Data-Driven Predictive Aircraft Maintenance Using Agent-Based Modeling and Hazard Identification. Aerospace 2023, 10, 186. [Google Scholar] [CrossRef]
  37. Cui, P.-H.; Wang, J.-Q.; Li, Y. Data-driven modelling, analysis and improvement of multistage production systems with predictive maintenance and product quality. Int. J. Prod. Res. 2022, 60, 6848–6865. [Google Scholar] [CrossRef]
  38. Wang, F.; Tang, S.; Li, L.; Sun, X.; Yu, C.; Si, X. Remaining useful life prediction of aero-engines based on random-coefficient regression model considering random failure threshold. J. Syst. Eng. Electron. 2023, 34, 530–542. [Google Scholar] [CrossRef]
Figure 1. Tested low-voltage electrical appliances.
Figure 1. Tested low-voltage electrical appliances.
Actuators 14 00522 g001
Figure 2. S-N curve diagram.
Figure 2. S-N curve diagram.
Actuators 14 00522 g002
Figure 3. Schematic diagram of contact layer of bimetallic strip under arc action.
Figure 3. Schematic diagram of contact layer of bimetallic strip under arc action.
Actuators 14 00522 g003
Figure 4. Flowchart of complex factors affecting contact resistance.
Figure 4. Flowchart of complex factors affecting contact resistance.
Actuators 14 00522 g004
Figure 5. Overall plan of the test platform.
Figure 5. Overall plan of the test platform.
Actuators 14 00522 g005
Figure 6. Variable-load testing system. (a) Circuit breaker installation diagram; (b) the management software system.
Figure 6. Variable-load testing system. (a) Circuit breaker installation diagram; (b) the management software system.
Actuators 14 00522 g006
Figure 7. Flowchart for constructing parameter set for variable-load reliability evaluation.
Figure 7. Flowchart for constructing parameter set for variable-load reliability evaluation.
Actuators 14 00522 g007
Figure 8. Flowchart of evaluation and prediction based on variable-load data-driven model.
Figure 8. Flowchart of evaluation and prediction based on variable-load data-driven model.
Actuators 14 00522 g008
Figure 9. Comparison between predicted evaluation values and actual test values.
Figure 9. Comparison between predicted evaluation values and actual test values.
Actuators 14 00522 g009
Figure 10. Model prediction of remaining lifespan and reliability curve graph.
Figure 10. Model prediction of remaining lifespan and reliability curve graph.
Actuators 14 00522 g010
Table 1. Parameter settings for variable-load test.
Table 1. Parameter settings for variable-load test.
ConditionParameterConditionParameter
Detecting current15 ACoil Voltage220 V
Detection voltage380 VLOAD70 A
Detection frequency620 times/hsampling frequency1.2 KHz
Vibration lawsine wavePower factor0.65
max temperature50 °CMax impact force180 KN
Vibration frequency30 Hzvibration acceleration1.2 g
Table 2. Characteristic parameter set data for variable-load evaluation.
Table 2. Characteristic parameter set data for variable-load evaluation.
Sample NumberAccumulated Arc Energy (J)Contact Voltage
(V)
Contact Resistance
(Ω)
Release Voltage
(V)
Arcing Time
(ms)
Pickup Time
(ms)
Arc Energy
(J)
Kpca
195,1072.92910.0447235.714.776215.872815.2290−0.1887
2113,0102.90520.0430235.245.431516.751318.4150−0.0852
3131,8302.88890.0395235.195.476216.636918.9170−0.0460
4150,3002.98310.0432236.175.381815.974418.2830−0.0372
5169,6502.65020.0380232.465.740416.827719.7024−0.0415
6189,3202.89760.0428231.915.854216.861019.6413−0.0343
Table 3. Correlation between failure characteristic parameters and electric life.
Table 3. Correlation between failure characteristic parameters and electric life.
Failure IndicatorSample OneSample
Two
Sample
Three
Sample
Four
Sample
Five
Sample
Six
Accumulated energy−0.9983−0.9679−0.9879−0.9974−0.9989−0.9865
Arc energy−0.26960.87650.3958−0.44350.4106−0.0121
Contact voltage −0.6083−0.9103−0.7070−0.6133−0.5291−0.8130
Contact resistance−0.5603−0.8784−0.6734−0.6122−0.0341−0.4102
Release voltage−0.4119−0.4742−0.3414−0.47910.22360.0418
Arcing time−0.31410.84350.3478−0.44260.0301−0.0565
Pickup time−0.2938−0.5411−0.4643−0.11740.4106−0.0888
KPCA−0.26960.87650.3958−0.44350.4106−0.0121
Table 4. Correspondence between the number of operations and accumulated arc energy.
Table 4. Correspondence between the number of operations and accumulated arc energy.
Number of Testing IterationsSample 1 Accumulated Arc EnergySample 2 Accumulated Arc EnergySample 3 Accumulated Arc Energy
10013,68112,13212,996
30027,25225,33226,790
50050,38258,62050,580
70074,65370,96074,250
90098,74594,98098,365
35,7001,079,7001,058,6601,058,620
35,8701,059,4001,086,447
36,1001,090,076
36,850
Table 5. Evaluation values and relative errors of electrical life of low-voltage electrical appliances for transport vehicles.
Table 5. Evaluation values and relative errors of electrical life of low-voltage electrical appliances for transport vehicles.
StageOperation Time RangeNumber of Operations PredictedActual Number of OperationsRelative Error (%)
11~300031,06131,8922.6
23001~600028,40229,9065.0
36001~12,00027,84227,1012.7
412,001~15,00022,59621,8933.2
515,001~18,00018,68118,0950.3
618,001~21,00016,26215,8982.3
720,001~24,00012,28611,9872.5
824,001~27,000816678044.6
927,001~30,000415843704.9
1030,001~33,0008037950.1
Table 6. Model-predicted remaining operations and reliability.
Table 6. Model-predicted remaining operations and reliability.
Serial NumberNumber of Operations PredictedReliabilitySerial NumberNumber of Operations PredictedReliability
1001722,88092.77%
214300.92%1824,31094.81%
328603.53%1925,74096.39%
442908.17%2027,17097.62%
5572013.76%2128,60098.35%
6715020.91%2230,03098.87%
7858028.96%2331,46099.27%
810,01037.53%2432,89099.51%
911,44047.12%2534,32099.27%
1012,87054.70%2635,75099.84%
1114,30062.66%2737,18099.91%
1215,73070.08%2838,61099.98%
1317,16076.26%2924,31080.81%
1418,59082.93%3027,17085.62%
1520,02088.21%3142,90099.77%
1621,45089.83%3244,330100%
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Long, L.; Cheng, S.; Zhang, W.; Yue, M. Reliability Study of Low-Voltage Electrical Appliances in Transport Vehicles Under Variable-Load Conditions. Actuators 2025, 14, 522. https://doi.org/10.3390/act14110522

AMA Style

Long L, Cheng S, Zhang W, Yue M. Reliability Study of Low-Voltage Electrical Appliances in Transport Vehicles Under Variable-Load Conditions. Actuators. 2025; 14(11):522. https://doi.org/10.3390/act14110522

Chicago/Turabian Style

Long, Lin, Shu Cheng, Wei Zhang, and Min Yue. 2025. "Reliability Study of Low-Voltage Electrical Appliances in Transport Vehicles Under Variable-Load Conditions" Actuators 14, no. 11: 522. https://doi.org/10.3390/act14110522

APA Style

Long, L., Cheng, S., Zhang, W., & Yue, M. (2025). Reliability Study of Low-Voltage Electrical Appliances in Transport Vehicles Under Variable-Load Conditions. Actuators, 14(11), 522. https://doi.org/10.3390/act14110522

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop