1. Introduction
According to the 2023 NDC Synthesis Report of the United Nations Framework Convention on Climate Change (UNFCCC) [
1], the current decarbonization rate covered by the net-zero emission targets and commitments of countries still falls short of achieving the goals of the Paris Agreement. The International Energy Agency (IEA) reported, in 2023, that buildings’ operations account for 30% of global final energy consumption and 26% of global energy-related emissions [
2]. The Global Status Report on Buildings and Construction released by the United Nations Environment Programme (UNEP) showed that the current rate of building retrofit is far below the speed required to reduce carbon emissions by 50% by 2030. The average retrofit rate of the existing building stock is currently around 1% per year, with these retrofits typically achieving less than a 15% reduction in energy intensity. To align with the goals of the Paris Agreement, by 2030, the retrofit rate needs to be increased to between 2.5% and 5%, and building energy consumption needs to be reduced by about 25%, which requires the gradual replacement of fossil fuels and traditional biomass with new energy sources [
3]. As one of the industries with the highest global energy consumption and emissions, the construction industry’s transition to low carbon is inevitable in the future. The growing demand for clean energy and the urgency of mitigating climate change have driven the rapid development of photovoltaic (PV) technology as a key renewable energy solution [
4]. Solar energy, as an abundant and sustainable resource, plays a crucial role in reducing carbon emissions and enhancing energy security [
5]. In recent years, building-integrated photovoltaic (BIPV) structures have attracted much attention for their dual attributes of being both a building material and a power generation facility [
6], which can optimize land use and enhance urban energy sustainability [
7]. This is a technology that integrates solar photovoltaic power generation modules into buildings [
8]; that is, the photovoltaic power generation system is designed, constructed, and installed simultaneously with the building and forms a perfectly integrated solar power generation system within the building. The building itself uses solar energy to produce electricity to meet its own power needs [
9]. BIPV technology allows photovoltaic modules to be directly integrated into building structures, such as roofs and walls, effectively utilizing spaces that would otherwise not generate energy [
10]. The electricity generated by the BIPV system can be used for self-consumption or fed into the grid for sale, reducing operating costs and bringing economic benefits [
11].
However, existing BIPV research has focused more on public or residential buildings, with insufficient attention to the integration potential of industrial building facilities [
12]. Take the most common substation as an example. As a hub building in the urban energy network, integrating PV systems into substations can also actively explore the deep integration of photovoltaic power generation and the power grid, promoting the design transformation of power infrastructure [
13]. Looking at the building itself, most of them are located in suburban areas away from cities, where solar radiation is not easily blocked, and they have a low window-to-wall ratio and a high proportion of wall area, providing a vast facade area for PV integration, as walls are an underdeveloped carrier. However, the roof area is usually limited and often occupied by ventilation equipment, lightning rods, cable trays, etc. Therefore, when considering PV installation for this type of building, more consideration should be given to attaching the PV module to its facade.
At present, there have been quite a few research results on facade–photovoltaic module integrated structures by predecessors. According to the application of PVs in buildings, different construction methods of PVs combined with the outer envelope structure have been mainly proposed, as well as studies on the passive and active energy-saving effects of PV systems on buildings. ZHANG believes that there are mainly three types of structures for PVs combined with walls. The first is to directly install PV modules on the wall, the second is to form an air cavity between the PV module and the wall, and the third is to use the filling material EPS to seal the air layer between the PV module backplate and the wall [
14]. Zhou summarized the research on the heat transfer of building-integrated photovoltaic walls by predecessors and pointed out that the average daily heat gain of photovoltaic walls in summer is 27% lower than that of traditional walls. Further research on the impact of natural ventilation on photovoltaic walls found that ventilation can reduce the exterior wall temperature by 4.5 °C to 7.3 °C, and the heat gain of naturally ventilated photovoltaic walls is reduced by about 25% to 55%, reducing the cooling load by 33% to 50% compared with traditional walls [
15]. Peng et al. assessed the annual thermal performance of ventilated photovoltaic walls in Hong Kong and the subsequent reduction in air conditioning energy consumption. The results showed that the wall can reduce indoor heat gain by 51% in summer, reduce heat loss by 32% in winter, and reduce air conditioning system energy consumption by 18.6 kWh per square meter per year [
16]. In addition, it has also been proposed that in hot regions, a ventilated cavity should be formed between the photovoltaic module and the wall to reduce heat gain and improve the energy conversion efficiency of the photovoltaic modules [
17]. Yang proposed that naturally ventilated photovoltaic walls perform best in reducing solar heat gain and improving power output, effectively reducing heat gain and improving the energy conversion efficiency of photovoltaic modules, while non-ventilated photovoltaic walls perform best in thermal insulation [
18]. K. Irshad pointed out that air velocity has a significant impact on the performance of photovoltaic walls with cavity ventilation. Within a certain range, the increase in air velocity can significantly increase the heat transfer coefficient of air, which helps to cool the interior of the building and photovoltaic modules [
19]. ElSayed found that the air gap depth has a significant impact on the thermal performance and photovoltaic efficiency of BIPVs. Increasing the air gap depth can reduce heat gain [
20]. Su measured the relationship between air flow and cavity depth [
21]. It was identified that when photovoltaic modules are integrated with buildings as part of the facade envelope structure, they will affect the building’s energy consumption system from two aspects: the positive benefits of power generation for the energy supply and the passive benefits of protecting the surfaces of the building [
22]. First, the most important energy benefit of PV systems is power generation and energy supply. Solar energy is directly converted into electrical energy by photovoltaic panels integrated on the building surface for use by the building itself or for grid connection and sale, which can reduce dependence on external energy, increase energy self-sufficiency, and reduce traditional energy consumption. Second, the application of PV modules to the facade of a building will change the thermal performance of the building envelope, thereby reducing the energy consumption of the air conditioning system, while shading the surface of the building and reducing the total amount of solar radiation projected onto it. The different construction methods also greatly affect their energy saving and power generation efficiency.
However, existing research on building-integrated photovoltaic (BIPV) facades has largely focused on conventional residential and public buildings, with an emphasis on evaluating their energy-saving potential [
23], while overlooking the unique operational loads and internal heat sources characteristic of industrial facilities. Taking substations as an example, these buildings typically house a substantial amount of heat-generating equipment, especially transformers, which emit significant heat during operation and require effective ventilation or cooling systems to maintain safe operating temperatures. While the introduction of PV systems may enhance the thermal insulation of building envelopes, it could also hinder heat dissipation, potentially leading to indoor heat accumulation. This, in turn, may impair equipment efficiency, shorten service life, or even increase the risk of safety incidents, ultimately threatening the stability and reliability of the power supply network. Beyond substations, other types of industrial buildings—such as data centers, manufacturing plants, and smelting workshops—often share similar characteristics, including large wall areas, low window-to-wall ratios, and high internal energy demands. Therefore, the BIPV structural designs and energy analysis methods proposed in this study have good generalizability and may be applied to other types of industrial buildings in the future, providing theoretical support and practical reference for cross-sector BIPV technology transfer and system integration [
24].
Given the current challenges in integrating BIPV systems into industrial buildings, particularly the difficulty in coordinating photovoltaic construction with environmental control and the uncertainty in post-installation energy performance, we aim to address the following key scientific and practical issues by
Investigating the comprehensive impact mechanisms of different photovoltaic facade construction layers (such as direct attachment, air cavity, and EPS filling) on building energy consumption and indoor environments and verifying whether these configurations can not only improve building energy performance but also effectively manage the thermal environment of various functional spaces within the substation, thereby ensuring operational safety and comfort.
Examining the role and constraints of building orientation in optimizing the energy output of BIPV systems, in order to further improve the overall photovoltaic performance.
Assessing the initial investment, maintenance costs, and economic returns of different structural solutions to determine their feasibility for broader application.
2. Materials and Methods
2.1. Research Object
This paper takes a standard 220 kV semi-outdoor substation of the China Southern Power Grid located in the subtropical region as a case for study. Buildings in this region hold a significant strategic position in the global photovoltaic power generation field [
25]. The summer climate is hot, with 30–50% of all their consumed electricity used for cooling and ventilation purposes. Ventilation and air conditioning (HVAC) systems consume a large amount of electricity [
26]. Therefore, formulating strategies to reduce energy consumption has become an essential part of the energy-saving and emission-reduction tasks in these countries. Meanwhile, the region also has the most significant solar advantages, with its high solar radiation intensity and sufficient sunshine duration ensuring a competitive overall power generation capacity [
27]. As countries in the subtropical region, such as Guangdong Province in China and Singapore, complete their urbanization and industrialization phases, they are increasingly facing the challenges of growing energy demands and land resource shortages [
28,
29]. This makes the deployment of traditional photovoltaic systems more challenging. Therefore, selecting buildings in this region for research also has far-reaching significance.
In terms of function, the main functional areas of a substation can be divided into two categories based on the user: one is the equipment room, which is specifically for storing substation equipment, and the other is the living room for employees’ long-term use. These two types of rooms have different requirements for environmental control. The living rooms, such as the guard room, water pump room, and fire control room, usually have staff coming and going, so air conditioning needs to be configured to meet the thermal comfort needs of the personnel. The equipment rooms, such as the main transformer room, need ventilation due to the large amount of heat dissipation from the equipment or the need to remove harmful gases, and this usually includes both natural and mechanical ventilation systems. There are also some spaces that have both heat-generating equipment and human activities, so both air conditioning and ventilation environmental control methods are needed. The specific types of spaces are shown in the
Table 1.
The working conditions inside the transformer room are complex. Therefore, when carrying out the photovoltaic integration design, it is necessary to not only consider the power generation of photovoltaics but also fully take into account the changes that the photovoltaic system brings to the original building envelope’s heat transfer and energy structure. This is especially true for the semi-outdoor main transformer room, where ventilation and heat dissipation are crucial for the safe operation of the transformer. Photovoltaic power generation is often accompanied by the heating of the voltaic module’s backplate. Whether the photovoltaic integration design will affect the transformer’s heat dissipation and the temperature control of other equipment rooms is a key issue that this study needs to verify. Therefore, this paper will classify and discuss the impact of façade–photovoltaic module layout configurations on rooms with different working conditions in the substation. The focus of the analysis is the passive influence of photovoltaics on rooms with different working conditions and the changes in power generation performance after integrating the photovoltaic system.
2.2. Research Methods
This paper will utilize the EnergyPlus V23.2.0 software tool for simulating building conditions and calculating energy consumption. This software is capable of comprehensively simulating systems such as lighting, air conditioning, and ventilation within a building, as well as the various physical processes involved. This makes EnergyPlus widely applicable in multiple fields, including the assessment of buildings’ energy-saving performance, design optimization, and energy management, as well as related policy-making [
30]. The study will be carried out in three phases:
In the first phase, focusing on the research of facade–photovoltaic system construction, the integration of photovoltaic modules with the facade will be divided into three types: (1) the direct installation of photovoltaic modules in contact with the concrete structure; (2) the formation of an air cavity between the photovoltaic modules and the concrete wall; (3) the use of EPS filling between the photovoltaic modules and the concrete wall. By thoroughly analyzing and comparing the impact of these three types of photovoltaic-module-integrated envelope structures on the indoor thermal performance of the substation, the most suitable construction methods for different room conditions in the substation will be precisely determined.
In the second phase, the research findings from the first phase will be fully utilized to set up the envelope structure, and the influence of orientation on photovoltaic power generation and the overall energy consumption of the substation will be explored. By comparing the overall energy consumption and total energy-saving efficiency of buildings with photovoltaic-module-integrated substations under different orientations, comprehensive and precise guidance will be provided for the facade–BIPV module design of substations, and feasible measures and suggestions will be proposed.
In the third phase, a preliminary cost–benefit analysis is conducted for these types of photovoltaic wall systems to evaluate their economic feasibility. Key factors considered include the procurement and installation costs of PV modules and additional construction layer costs; using the estimated annual electricity output, cost savings and discounted cash flows were calculated to determine the payback period and the net present value (NPV), offering a practical economic reference for BIPV applications.
It should be noted that this study is based on a simulation analysis of a typical 220 kV semi-outdoor substation building under subtropical climate conditions. The climate data, room functions, and equipment load parameters used are highly region-specific. Therefore, these contextual constraints limit the generalizability of the results, meaning that the findings are most applicable to substations with similar climatic conditions, building types, and operational characteristics. Applying these results to substations in other climate zones or with significantly different structural configurations may lead to reduced accuracy and applicability. Nevertheless, the study’s method—classifying indoor environments based on control needs and systematically analyzing PV facade types and building orientation—has strong methodological adaptability. The analytical approach and design logic offer valuable references for promoting the use of BIPV structures in substations of other climates and in broader industrial buildings.
2.3. Parameter Setting
2.3.1. Modeling
The modeling of the 220 kV substation was carried out based on the OpenStudio 1.7 platform (
Figure 1). The substation covers an area of 3561 m
2 and houses four transformers. It has three above-ground floors and a partial fourth floor. The main rooms include the transformer rooms, which are located on one side of the long axis, with a total of four rooms. The central part of the building consists of the low-voltage distribution room on the first floor, the 110 kV GIS distribution room on the second floor, and the 220 kV distribution room on the partial fourth floor. On the other side are the living quarters for the transformer room staff and small equipment rooms, such as the capacitor room and reactor room. Each type of room was set as an individual thermal zone in OpenStudio. Based on the actual project configuration, different HVAC parameters, ventilation settings, internal heat gains, and occupant heat disturbances were applied. Detailed settings are shown in
Table 2.
2.3.2. Weather Parameters
The meteorological parameters used in the simulation experiments are sourced from the official website of the China Meteorological Administration (CMA) (
http://data.cma.cn), with Guangzhou City (23.12° N, 113.25° E) selected as a typical representative area for the subtropical region. The Typical Meteorological Year (TMY) data includes several parameters that influence the design of BIPV. Key parameters were extracted from the EPW file, as shown in
Table 3. In Guangdong, the average hourly global horizontal radiation is 129.75 Wh/m
2, peaking at 1252 Wh/m
2. Summer temperatures average above 28 °C, with a maximum outdoor dry bulb temperature of 36.6 °C, while winter averages around 14 °C—indicating a typical hot and humid southern climate. High humidity and low wind speeds limit the cooling effect of natural ventilation on PV modules. The prevailing southerly wind supports the analysis of south-facing facade ventilation designs. All the data are sourced directly from official files without manual modification.
2.3.3. Indoor Environmental Control Parameters
As can be seen from the description in
Section 2.1, there are mainly two working conditions for the indoor environmental control of the substation: one is the transformer room with high-power internal heat sources, where the operating transformers generate a large amount of heat, which needs to be exhausted by thermal pressure ventilation; the other includes the small equipment rooms and living quarters, which have certain heat disturbances inside, need ventilation to remove waste gases, and also need to control the fluctuation of indoor temperature, so both air conditioning and ventilation are needed for environmental control. There is a significant difference between the two working conditions, so they need to be discussed separately.
Working Condition One: Mainly rooms represented by transformers; it is necessary to set the heat dissipation power by the high-power heat sources inside them and the relevant parameters of indoor thermal pressure ventilation. The main transformer room of the semi-outdoor substation adopts a natural air intake mode, introducing fresh air through the louver at the bottom of the main gate. This room does not have a roof and uses the open roof to achieve air exhaustion, thus achieving good ventilation and cooling effects (
Figure 2).
Internal heat source setting: The substation in this investigation has a total of 4 transformers. In engineering, a commonly used method for transformer heat dissipation assumes that the total loss of the transformer equals the heat generated by the equipment. When the transformer is operating normally, the total loss P consists of the no-load loss P
0 and the load loss P
f (P = P
0 + P
f). The no-load loss P
0 is constant, and the load loss P
f is equal to the square of the load ratio multiplied by the load loss Pε at the rated load (P
f = λ
2 × Pε) [
31]. For the 220 kV main transformer room tested this time, according to the manufacturer’s data, the no-load loss of the transformer is P
0 = 95 kW per unit, and the load loss is P
f = 660 kW per unit. In EnergyPlus, no-load and load losses were set as two heat sources. Load variation was applied based on the peak summer day (
Figure 3) to achieve more accurate and clear heat dissipation results.
Natural ventilation setting: The ventilation design of the semi-outdoor substation mainly relies on the principle of thermal pressure ventilation (
Figure 2). When simulating its ventilation effect, the ZoneVentilation:WindandStackOpenArea model of EnergyPlus can be used. By setting the effective opening area of the air inlet, namely the Opening Effectiveness, and the height difference between the air inlet and outlet, the model can more intuitively simulate the ventilation situation. The specific parameters are as follows: the air inlet opening area is 36 m
2, the Opening Effectiveness is 0.6, and the height difference is 25 m.
- 2.
Working Condition Two: Mainly living quarters and other rooms without high-power electrical equipment, including capacitor and reactor rooms, battery rooms, GIS rooms, low-voltage distribution rooms, etc. These rooms need to be equipped with indoor air conditioning and lighting systems. Meanwhile, some rooms also need to be fitted with mechanical ventilation facilities to deal with heat disturbances from personnel and equipment.
Air Conditioning Settings: Most rooms in the substation have clear design requirements for the environmental temperature. For substations in subtropical regions, there is no need to design for winter heating; only summer air conditioning cooling is required. The summer design temperature for capacitor and reactor rooms and GIS rooms should not exceed 40 °C, while that for low-voltage distribution rooms and battery rooms should not exceed 30 °C. For rooms with more frequent human activities, such as relay protection and communication rooms, tool rooms, and document rooms, the summer temperature should be controlled between 26–28 °C. These data provide important references for the HVAC settings in EnergyPlus.
Ventilation Settings: Most rooms in the substation can regulate the environment through natural ventilation. However, some rooms that need to exhaust waste gases in a timely manner have clear mechanical ventilation design requirements. The low-voltage distribution room requires natural air intake and a mechanical exhaust, with an exhaust rate of ≥12 times/h; the relay protection and communication room requires natural air intake and a mechanical exhaust, with an exhaust rate of ≥6 times/h; the GIS room uses mechanical ventilation, and indoor air is not allowed to recirculate, with a normal ventilation rate of no less than 2 times/h. These settings are configured through the ZoneVentilation module in EnergyPlus.
Heat Disturbance Settings: The heat disturbances in these rooms mainly come from human activities and equipment heat generation. Tool rooms, document rooms, and relay protection and communication rooms, which have more frequent personnel movement, are set with a personnel density of 2 to 8 persons in EnergyPlus, according to the substation’s duty situation. In addition, the relay protection and communication rooms also contain a large number of heat-generating equipment cabinets, with the heat disturbance intensity set at 70 W/m2.
Lighting Settings: This part of the heat disturbance is set through the Lights module in EnergyPlus, with the power per unit area set at 4 W/m2 to simulate the energy consumption of the lighting equipment.
2.3.4. Envelope Parameters
To compare the photovoltaic-module-integrated facades suitable for the two working conditions, a computational model for the thermal performance of the building envelope and a thermal balance model for the PV wall were established based on the previously selected typical case. By simulating the performance of ordinary walls and different PV wall constructions, the differences in the thermal insulation effects of the PV walls were compared to determine the optimal wall construction solution.
Typically, building envelopes adopt a uniform multilayer composite system, consisting—from outside to inside—of exterior wall paint, a mortar layer, an EPS insulation layer, and a concrete substrate. The thickness and physical properties of each layer are based on Chinese national standards [
32], ensuring that the thermal balance simulations accurately reflect the building’s actual thermal performance and heat transfer characteristics. The integration of PVs with the envelope is implemented in three configurations, PVs + wall; PVs + air gap + wall; and PVs + EPS + wall, with the material parameters listed in
Table 4. For the PVs + air gap + wall setup, particular attention should be paid to heat dissipation within the air cavity between the PV panel and the concrete wall. The air gap is set to 100 mm, and heat transfer is modeled using the GapConvectionRadiation model, which accounts for both radiative and convective heat exchange.
In EnergyPlus, the power generation performance of PV modules can be simulated using three methods: the simple model, the Equivalent One-Diode model, and the Sandia model [
33]. The simple model allows users to manually define the conversion efficiency, giving them full control over the PV module’s performance. It does not require electrical or optical parameters; instead, it simulates the PV array based solely on the specified efficiency [
34]. Although it is less accurate than other methods, the simple model is commonly used during the early design stage for quick preliminary assessments due to its straightforward setup and rapid computation. In the “PhotovoltaicPerformance: Simple” settings, referring to commonly available photovoltaic module parameters on the market, we set the energy conversion efficiency to 0.18, the power of a single module to 500 W, and the coverage ratio of each surface to 80%.
2.4. Numerical Simulation
The simulation study first focuses on different construction layers of PV walls. Initially, for rooms with high-power heat sources inside and using stack ventilation, a transformer room in the model is selected as the test object. Its front side is equipped with a PV-module-integrated wall, while the other three sides are made of ordinary concrete walls. The coldest day in winter and the hottest day in summer each year are chosen as design days. The indoor temperature changes throughout the day when the front side faces east, west, and south, respectively, are detected, serving as the reference basis for the energy-saving effect of the envelope structure under this condition. Secondly, for rooms with personnel movement that require air conditioning for temperature control, a secondary equipment room in the model is selected as the test object. Its front side is equipped with a PV wall, while the other three sides are made of ordinary concrete walls. In summer, with the air conditioning temperature set at 26 °C, the total annual air conditioning energy consumption when the PV panels are laid on the east, west, and south sides, respectively, is detected, serving as the reference basis for the energy-saving effect of the maintenance structure under this condition (
Figure 4).
Next, analyze the impact of building orientation on the energy-saving performance of substations. By adjusting the building’s long axis to four typical orientations—east, west, south, and north—and installing photovoltaic systems on the three exterior facades excluding the north facade, a coupled model of building energy consumption and PV power generation is established. Based on this, annual dynamic energy consumption simulations and photovoltaic power generation calculations are performed.
The HVAC cooling energy consumption, lighting energy consumption, and ventilation energy consumption of the building are obtained through “Output:Variable”. The sum of these components gives the total building energy consumption E
total. Meanwhile, the direct current electricity generated by the photovoltaic system E
pv is also obtained. In the post-processing stage, the net building energy consumption E
net is calculated as the difference between the total energy consumption and the photovoltaic generation, as shown in Equation (1).
In addition, the energy-saving rate is calculated as a reference for evaluating the energy-saving performance of the PV system. This calculation includes two aspects: the passive energy-saving rate η
passive resulting from the thermal insulation effect of the PV modules, as shown in Equation (2), and the active energy-saving rate η
PVGenerate achieved by replacing conventional electricity with PV generation, as shown in Equation (3). In the equations, E
PVfilled represents the building energy consumption under the PV installation scenario with an air gap or EPS-filled insulation layer; E
Ordinary represents the baseline energy consumption without PV modules; and E
PVGenerate refers to the electricity generated by the photovoltaic system.
The total energy-saving rate of the substation building η is expressed as the sum of the two components, as shown in Equation (4):
Subsequent evaluations of the PV energy-saving performance will be conducted using both net energy consumption Enet and energy-saving rate η as indicators.
2.5. Economic Analysis Method
This study conducts a preliminary cost–benefit analysis of PV wall structures suitable for installation on the surfaces of substations, based on the life cycle cost (LCC) model of the PV system. The economic evaluation mainly includes the calculation of initial costs and operation costs, PV power generation revenue, and payback period.
The installed capacity of the PV system (P) is the primary factor affecting the initial and operation costs. It can be calculated based on the PV area installed on the building facade (S), and the unit power per area of the PV modules (P
1), as shown in Equation (5).
The calculation of the initial cost (C
initial) and the annual operation and maintenance cost (C
annual) can be derived from the unit installed cost (C
1) and the unit operation cost (C
2) of distributed PV systems for industrial and commercial use in China. Both C
1 and C
2 can be obtained from documents published by the China Photovoltaic Industry Association [
35]. The calculations are shown in Equations (6) and (7).
Based on the simulated annual power generation results (E
pv), the annual revenue of the PV system (R
annual) is comprehensively calculated according to the market electricity price (C
e) and the subsidy standards for distributed PV systems set by the Chinese government (R
gov). The revenue includes two parts: electricity cost savings and government subsidies, as shown in Equation (8).
The payback period of the PV system is determined based on the calculation of costs and revenues. It is important to note that PV systems typically have a relatively long payback period. Therefore, when assessing the return on investment, it is essential to take into account the cumulative discounted cash flow CCF(n) and the net present value (NPV), which together provide a more accurate reflection of the project’s actual return after considering both cost and time factors. The calculations are shown in Equations (9) and (10). The year in which the NPV just falls below zero is considered the payback year.
4. Conclusions
This study focuses on the low-carbon transformation needs of semi-outdoor substations under subtropical climatic conditions and systematically explores the optimal configuration of building-integrated photovoltaic (BIPV) systems to balance the synergy between photovoltaic power generation efficiency and the regulation of the indoor environment of industrial buildings. By comparing three types of photovoltaic envelope construction forms—direct installation, the formation of a ventilated cavity, and filling with EPS material—and combining them with different orientations of the building’s long axis (east, south, west, north), the energy-saving potential of two core functional areas, namely the high-heat-load transformer room and the living quarters requiring air-conditioning temperature control, is quantitatively assessed. The core research conclusions are as follows:
4.1. Differential Impact of BIPV Wall Construction on Passive Energy Saving
The comparison of various BIPV wall configurations indicated that the PVs + EPS composite structure demonstrated relatively better energy-saving potential under typical substation conditions. In high thermal load environments, such as transformer rooms, it helps reduce the indoor temperature rise by enhancing the thermal resistance of the building envelope. In air-conditioned living spaces, it also contributes to a noticeable reduction in the cooling energy demand. In contrast, the PVs + air cavity structure relies on convective heat dissipation and shows limited thermal regulation in naturally ventilated spaces, though it can still provide some cooling energy savings in conditioned environments. Notably, the sensitivity analysis showed that the thickness of the filler material in BIPV wall structures affects the building energy use by altering the thermal performance of the envelope. EPS thickness has a more efficient impact on energy savings compared to air cavities. Therefore, the energy-saving performance can be influenced by adjusting its thickness. However, its application should still be evaluated based on actual operating conditions.
4.2. Determinative Role of Building Orientation on PV Power Generation and Net Energy Consumption
Research indicated that the PV system output is the dominant factor influencing a building’s net energy consumption, with a greater impact than the passive thermal performance of the envelope. The simulation results suggested that orienting the transformer room along the east–west axis can notably increase annual PV generation compared to a north–south layout, thereby improving the energy saving rate. This advantage is primarily attributed to higher average annual solar radiation on east and west facades. The sensitivity analysis further showed that even with moderate variations in parameters such as the system efficiency or the coverage ratio, the east–west orientation maintains a relatively strong energy-saving performance, demonstrating a degree of robustness. Under favorable lighting conditions, it is recommended to prioritize an east–west longitudinal layout, combined with an optimized facade–PV module coverage design, to enhance the total energy output efficiency of the system.
4.3. Prospects for Economic Viability
The BIPV system in this study showed some cost recovery potential under current electricity prices and cost levels, but the long payback period limits its economic attractiveness. In the future, improvements in PV systems’ efficiency, better system integration, and lower installation costs are expected to reduce the unit investment costs and enhance the economic performance. Furthermore, where architectural conditions permit, additional photovoltaic systems can be installed in areas with better solar exposure and higher generation efficiency, such as rooftops or ground-level spaces, to enhance the power output and shorten the payback period. Additionally, government subsidies or other incentives could further improve the project’s return on investment, thereby increasing the feasibility of BIPV systems in the industrial building sector.
The photovoltaic structural optimization method and the building energy consumption simulation framework proposed for the 220 kV semi-outdoor substation in this study are also applicable to other types of industrial buildings with high thermal loads and complex environmental control requirements, such as data centers, industrial plants, and smelting workshops. Future research can further extend the model’s applicability by incorporating the operating conditions of different industrial scenarios and deepening the investigation of cross-disciplinary integration strategies for BIPV systems. This will promote the expansion of BIPV technology from power infrastructure to a broader range of industrial building types.