Statistical Analysis of Design Variables in a Chiller Plant and Their Influence on Energy Consumption and Life Cycle Cost
Abstract
:1. Introduction
2. Materials and Methods
2.1. Research Study: Procedure to Obtain the Optimal Distribution Cooling Capacity of an Air-Condensed Chiller Plant for a Hotel Facility Conceptual Design
- Stage 1: The thermal demand values of the building were analyzed through the transfer method, using the technical description of the real estate project, the meteorological conditions of the region, and the statistical information of occupancy and operation patterns of hotels with similar characteristics;
- Stage 2: The generation of chiller plant alternatives was carried out through a statistical–mathematical procedure using the calculated thermal demand values and black box models of the water chillers. This procedure allowed different plant architectures to be established by modifying the design parameters, i.e., installed cooling capacity, number of units, and distribution of cooling capacity between chillers, regarding constraints according to design standards;
- Stage 3: As an initial state, the chiller plant was a decoupled system comprising n air-cooled chillers arranged in parallel, and only the primary circuit was involved in the analysis. The energy verification of the chiller plants generated was carried out by solving a non-linear, multivariable combinatorial optimization problem of optimal chiller loading (OCL) and optimal chiller sequence (OCS) versus building demand profiles. In order to establish the OCS, a baseline decision was made. A genetic algorithm was used for the optimization procedure. For the LCC analysis, economic and financial parameters and criteria of the region where the case study was analyzed were used.
2.2. Methodology
3. Results and Discussion
- -
- if p-value > α (0.05) Accept H0 = accept that the data were from a normal distribution;
- -
- if p-value < α (0.05) Accept H1 = reject that the data were from a normal distribution.
- -
- Heteroskedasticity Test
- -
- Hypothesis:
- -
- If p-value > α (0.05) Accept H0 = Homoscedastic
- -
- If p-value < α (0.05) Accept H1 = Heteroscedastic
4. Conclusions
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Acknowledgments
Conflicts of Interest
Appendix A
Chiller Plant No. | Chiller Cooling Capacity at STD (kW) | Total Units | Total Cooling Capacity (kW) | Cooling Distribution among Chillers (%) | Energy Consumption (kWh/year) | LCC MMcup | ||
---|---|---|---|---|---|---|---|---|
1 | 2 | 3 | ||||||
1 | 181.3 | 360.0 | - | 2 | 538 | 33/67 | 476.3 | 799.86 |
2 | 199.8 | 360.0 | - | 2 | 557 | 36/ 64 | 487.1 | 816.14 |
3 | 203.1 | 360.0 | - | 2 | 560 | 36/64 | 487.8 | 817.13 |
4 | 229.9 | 312.2 | - | 2 | 540 | 42/58 | 483.2 | 807.17 |
5 | 273.0 | 273.0 | - | 2 | 542 | 50/50 | 545.1 | 891.09 |
6 | 273.0 | 312.2 | - | 2 | 582 | 47/53 | 533.9 | 882.30 |
7 | 98.2 | 98.2 | 360.0 | 3 | 553 | 18/18/65 | 460.8 | 801.82 |
8 | 98.2 | 119.0 | 360.0 | 3 | 574 | 17/21/62 | 432.5 | 766.46 |
9 | 98.2 | 135.1 | 312.2 | 3 | 543 | 18/25/57 | 442.8 | 778.19 |
10 | 98.2 | 151.2 | 312.2 | 3 | 559 | 17/27/56 | 449.3 | 791.61 |
11 | 98.2 | 161.7 | 312.2 | 3 | 569 | 17/28/55 | 446.8 | 790.34 |
12 | 98.2 | 181.3 | 273.0 | 3 | 549 | 18/33/49 | 432.0 | 765.91 |
13 | 98.2 | 199.8 | 273.0 | 3 | 568 | 17/35/48 | 443.7 | 783.34 |
14 | 98.2 | 203.1 | 273.0 | 3 | 571 | 17/35/48 | 444.7 | 785.09 |
15 | 98.2 | 229.9 | 229.9 | 3 | 556 | 18/41/41 | 432.4 | 764.26 |
16 | 119.0 | 119.0 | 312.2 | 3 | 548 | 22/22/57 | 431.8 | 763.54 |
17 | 119.0 | 135.1 | 312.2 | 3 | 564 | 21/24/55 | 435.4 | 772.64 |
18 | 119.0 | 151.2 | 273.0 | 3 | 540 | 22/28/50 | 436.8 | 774.93 |
19 | 119.0 | 151.2 | 312.2 | 3 | 580 | 20/26/54 | 440.3 | 783.24 |
20 | 119.0 | 161.7 | 273.0 | 3 | 551 | 22/29/49 | 427.9 | 763.51 |
21 | 119.0 | 181.3 | 273.0 | 3 | 570 | 21/32/48 | 419.6 | 753.15 |
22 | 119.0 | 199.8 | 229.9 | 3 | 546 | 22/36/42 | 416.0 | 744.67 |
23 | 119.0 | 203.1 | 229.9 | 3 | 550 | 22/37/42 | 417.5 | 747.27 |
24 | 119.0 | 229.9 | 229.9 | 3 | 577 | 20/40/40 | 414.2 | 745.79 |
25 | 135.1 | 135.1 | 273.0 | 3 | 540 | 25/25/50 | 462.1 | 809.18 |
26 | 135.1 | 135.1 | 312.2 | 3 | 579 | 23/23/54 | 460.1 | 808.53 |
27 | 135.1 | 151.2 | 273 | 3 | 556 | 24/27/49 | 447.1 | 750.89 |
28 | 135.1 | 161.7 | 273 | 3 | 566 | 24/28/48 | 436.2 | 742.44 |
29 | 135.1 | 181.3 | 229.9 | 3 | 543 | 25/33/42 | 406.6 | 777.79 |
30 | 135.1 | 181.3 | 273 | 3 | 585 | 23/31/46 | 424.6 | 737.08 |
31 | 135.1 | 199.8 | 229.9 | 3 | 562 | 24/35/41 | 423.1 | 825.32 |
32 | 135.1 | 203.1 | 203.1 | 3 | 538 | 25/38/38 | 471.3 | 753.34 |
33 | 135.1 | 203.1 | 229.9 | 3 | 565 | 24/36/41 | 424.1 | 828.08 |
34 | 151.2 | 151.2 | 273 | 3 | 572 | 26/26/47 | 457.8 | 778.04 |
35 | 151.2 | 161.7 | 229.9 | 3 | 540 | 28/30/42 | 428.5 | 798.99 |
36 | 151.2 | 161.7 | 273 | 3 | 582 | 26/28/47 | 445.3 | 768.39 |
37 | 151.2 | 181.3 | 229.9 | 3 | 559 | 27/32/41 | 424.6 | 806.38 |
38 | 151.2 | 199.8 | 199.8 | 3 | 548 | 27/36/36 | 483.9 | 757.73 |
39 | 151.2 | 199.8 | 203.1 | 3 | 551 | 27/36/37 | 480.5 | 846.01 |
40 | 151.2 | 199.8 | 229.9 | 3 | 578 | 26/34/40 | 437.5 | 844.73 |
41 | 151.2 | 203.1 | 203.1 | 3 | 554 | 27/36/36 | 482 | 775.57 |
42 | 151.2 | 203.1 | 229.9 | 3 | 581 | 26/35/39 | 438.4 | 846.2 |
43 | 161.7 | 161.7 | 229.9 | 3 | 550 | 29/29/42 | 430.7 | 803.73 |
44 | 161.7 | 181.3 | 199.8 | 3 | 539 | 30/33/37 | 458.2 | 811.80 |
45 | 161.7 | 181.3 | 203.1 | 3 | 543 | 30/33/37 | 457.4 | 805.69 |
46 | 161.7 | 181.3 | 229.9 | 3 | 570 | 28/32/40 | 424.3 | 807.89 |
47 | 161.7 | 199.8 | 199.8 | 3 | 558 | 29/36/36 | 483.5 | 758.89 |
48 | 161.7 | 199.8 | 203.1 | 3 | 561 | 29/35/36 | 479.0 | 846.8 |
49 | 161.7 | 203.1 | 203.1 | 3 | 564 | 28/36/36 | 480.1 | 841.14 |
50 | 181.3 | 181.3 | 181.3 | 3 | 540 | 33/33/33 | 475.7 | 838.53 |
51 | 181.3 | 181.3 | 199.8 | 3 | 559 | 32/32/36 | 466.4 | 831.09 |
52 | 181.3 | 181.3 | 203.1 | 3 | 562 | 32/32/36 | 465.4 | 819.71 |
53 | 181.3 | 199.8 | 199.8 | 3 | 578 | 31/34/34 | 491.2 | 820.22 |
54 | 181.3 | 199.8 | 203.1 | 3 | 581 | 31/34/35 | 487.6 | 859.85 |
55 | 181.3 | 203.1 | 203.1 | 3 | 584 | 31/35/35 | 488.4 | 855.43 |
Chiller Plant No. | Chiller Cooling Capacity at STD (kW) | Total Units | Total Cooling Capacity (kW) | Cooling Distribution among Chillers (%) | Energy Consumption (kWh/year) | LCC MMcup | |||
---|---|---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | ||||||
56 | 98.2 | 98.2 | 98.2 | 273.0 | 4 | 564 | 17/17/17/48 | 445.0 | 809.77 |
57 | 98.2 | 98.2 | 119.0 | 229.9 | 4 | 543 | 18/18/22/42 | 412.6 | 763.93 |
58 | 98.2 | 98.2 | 119.0 | 273.0 | 4 | 585 | 17/17/20/46 | 416.5 | 775.88 |
59 | 98.2 | 98.2 | 135.1 | 229.9 | 4 | 559 | 17/17/24/41 | 410.6 | 763.35 |
60 | 98.2 | 98.2 | 151.2 | 199.8 | 4 | 545 | 18/18/28/36 | 434.5 | 797.67 |
61 | 98.2 | 98.2 | 151.2 | 203.1 | 4 | 548 | 18/18/27/37 | 434.2 | 797.41 |
62 | 98.2 | 98.2 | 151.2 | 229.9 | 4 | 575 | 17/17/26/40 | 411.7 | 767.57 |
63 | 98.2 | 98.2 | 161.7 | 181.3 | 4 | 536 | 18/18/30/34 | 418.6 | 773.63 |
64 | 98.2 | 98.2 | 161.7 | 199.8 | 4 | 555 | 18/18/29/36 | 432.1 | 796.08 |
65 | 98.2 | 98.2 | 161.7 | 203.1 | 4 | 558 | 18/18/28/36 | 430.5 | 794.19 |
66 | 98.2 | 98.2 | 161.7 | 229.9 | 4 | 585 | 17/17/27/39 | 407.7 | 764.42 |
67 | 98.2 | 98.2 | 181.3 | 181.3 | 4 | 556 | 18/18/32/32 | 423.9 | 783.34 |
68 | 98.2 | 98.2 | 181.3 | 199.8 | 4 | 574 | 17/17/31/35 | 433.7 | 799.89 |
69 | 98.2 | 98.2 | 181.3 | 203.1 | 4 | 577 | 17/17/31/35 | 432.5 | 798.58 |
70 | 98.2 | 119.0 | 119.0 | 203.1 | 4 | 537 | 18/22/22/38 | 399.4 | 752.36 |
71 | 98.2 | 119.0 | 119.0 | 229.9 | 4 | 564 | 17/21/21/41 | 400.6 | 750.58 |
72 | 98.2 | 119.0 | 135.1 | 199.8 | 4 | 549 | 18/22/24/36 | 411.4 | 768.97 |
73 | 98.2 | 119.0 | 135.1 | 203.1 | 4 | 553 | 18/21/24/37 | 413.1 | 771.65 |
74 | 98.2 | 119.0 | 135.1 | 229.9 | 4 | 580 | 17/20/23/39 | 406.8 | 757.75 |
75 | 98.2 | 119.0 | 151.2 | 181.3 | 4 | 547 | 18/22/28/33 | 399.3 | 750.35 |
76 | 98.2 | 119.0 | 151.2 | 199.8 | 4 | 566 | 17/21/27/35 | 407.8 | 765.13 |
77 | 98.2 | 119.0 | 151.2 | 203.1 | 4 | 569 | 17/21/26/35 | 409.3 | 767.41 |
78 | 98.2 | 119.0 | 161.7 | 161.7 | 4 | 538 | 18/22/30/30 | 402.1 | 756.76 |
79 | 98.2 | 119.0 | 161.7 | 181.3 | 4 | 557 | 18/21/29/32 | 407.1 | 759.09 |
80 | 98.2 | 119.0 | 161.7 | 199.8 | 4 | 576 | 17/21/28/35 | 421.1 | 781.27 |
81 | 98.2 | 119.0 | 161.7 | 203.1 | 4 | 579 | 17/21/28/35 | 423.0 | 784.39 |
82 | 98.2 | 119.0 | 181.3 | 181.3 | 4 | 577 | 17/21/31/31 | 418.9 | 776.52 |
83 | 98.2 | 135.1 | 135.1 | 181.3 | 4 | 546 | 18/25/25/33 | 410.0 | 765.87 |
84 | 98.2 | 135.1 | 135.1 | 199.8 | 4 | 565 | 17/24/24/35 | 418.0 | 767.00 |
85 | 98.2 | 135.1 | 135.1 | 203.1 | 4 | 568 | 17/24/24/36 | 418.8 | 781.43 |
86 | 98.2 | 135.1 | 151.2 | 161.7 | 4 | 543 | 18/25/28/30 | 419.1 | 777.68 |
87 | 98.2 | 135.1 | 151.2 | 181.3 | 4 | 562 | 17/24/27/32 | 418.6 | 773.63 |
88 | 98.2 | 135.1 | 151.2 | 199.8 | 4 | 581 | 17/23/26/34 | 432.1 | 796.08 |
89 | 98.2 | 135.1 | 151.2 | 203.1 | 4 | 584 | 17/23/26/35 | 430.5 | 794.19 |
90 | 98.2 | 135.1 | 161.7 | 161.7 | 4 | 553 | 18/24/29/29 | 407.7 | 764.42 |
91 | 98.2 | 135.1 | 161.7 | 181.3 | 4 | 573 | 17/23/28/31 | 405.7 | 761.68 |
92 | 98.2 | 151.2 | 151.2 | 151.2 | 4 | 549 | 18/27/27/27 | 453.7 | 825.76 |
93 | 98.2 | 151.2 | 151.2 | 161.7 | 4 | 559 | 17/27/27/29 | 442.2 | 812.07 |
94 | 98.2 | 151.2 | 151.2 | 181.3 | 4 | 579 | 17/26/26/31 | 429.3 | 794.90 |
95 | 98.2 | 151.2 | 161.7 | 161.7 | 4 | 569 | 17/26/28/28 | 440.7 | 810.60 |
96 | 98.2 | 161.7 | 161.7 | 161.7 | 4 | 579 | 17/28/28/28 | 442.5 | 814.10 |
97 | 119.0 | 119.0 | 119.0 | 181.3 | 4 | 537 | 22/22/22/34 | 392.2 | 736.27 |
98 | 119.0 | 119.0 | 119.0 | 199.8 | 4 | 555 | 21/21/21/36 | 413.3 | 767.54 |
99 | 119.0 | 119.0 | 119.0 | 203.1 | 4 | 558 | 21/21/21/36 | 414.8 | 769.64 |
100 | 119.0 | 119.0 | 119.0 | 229.9 | 4 | 585 | 20/20/20/39 | 411.8 | 768.95 |
101 | 119.0 | 119.0 | 135.1 | 181.3 | 4 | 552 | 22/22/24/33 | 387.7 | 718.53 |
102 | 119.0 | 119.0 | 135.1 | 199.8 | 4 | 571 | 21/21/24/35 | 405.5 | 760.66 |
103 | 119.0 | 119.0 | 135.1 | 203.1 | 4 | 574 | 21/21/23/35 | 407.9 | 764.44 |
104 | 119.0 | 119.0 | 151.2 | 151.2 | 4 | 539 | 22/22/28/28 | 411.6 | 765.70 |
105 | 119.0 | 119.0 | 151.2 | 161.7 | 4 | 549 | 22/22/27/29 | 402.3 | 754.34 |
106 | 119.0 | 119.0 | 151.2 | 181.3 | 4 | 568 | 21/21/26/32 | 394.8 | 745.03 |
107 | 119.0 | 119.0 | 161.7 | 161.7 | 4 | 559 | 21/21/29/29 | 402.5 | 755.48 |
108 | 119.0 | 119.0 | 161.7 | 181.3 | 4 | 578 | 21/21/28/31 | 392.9 | 743.90 |
109 | 119.0 | 135.1 | 135.1 | 151.2 | 4 | 538 | 22/25/25/28 | 421.5 | 780.67 |
110 | 119.0 | 135.1 | 135.1 | 161.7 | 4 | 548 | 22/24/24/29 | 411.8 | 767.60 |
111 | 119.0 | 135.1 | 135.1 | 181.3 | 4 | 567 | 21/24/24/32 | 401.6 | 755.48 |
112 | 119.0 | 135.1 | 135.1 | 199.8 | 4 | 586 | 20/23/23/34 | 415.2 | 777.81 |
113 | 119.0 | 135.1 | 151.2 | 151.2 | 4 | 554 | 21/24/27/27 | 422.5 | 783.74 |
114 | 119.0 | 135.1 | 151.2 | 161.7 | 4 | 564 | 21/24/27/28 | 411.7 | 770.18 |
115 | 119.0 | 135.1 | 151.2 | 181.3 | 4 | 583 | 20/23/26/31 | 403.4 | 760.75 |
116 | 119.0 | 135.1 | 161.7 | 161.7 | 4 | 574 | 21/23/28/28 | 412.5 | 772.18 |
117 | 119.0 | 151.2 | 151.2 | 151.2 | 4 | 570 | 21/26/26/26 | 444.5 | 816.84 |
118 | 119.0 | 151.2 | 151.2 | 161.7 | 4 | 580 | 20/26/26/28 | 432.1 | 801.51 |
119 | 135.1 | 135.1 | 135.1 | 135.1 | 4 | 537 | 25/25/25/25 | 464.4 | 841.26 |
120 | 135.1 | 135.1 | 135.1 | 151.2 | 4 | 553 | 24/24/24/27 | 447.8 | 819.40 |
121 | 135.1 | 135.1 | 135.1 | 161.7 | 4 | 563 | 24/24/24/29 | 437.1 | 804.99 |
122 | 135.1 | 135.1 | 135.1 | 181.3 | 4 | 583 | 23/23/23/31 | 424.8 | 790.61 |
123 | 135.1 | 135.1 | 151.2 | 151.2 | 4 | 569 | 24/24/26/26 | 447.3 | 820.04 |
124 | 135.1 | 135.1 | 151.2 | 161.7 | 4 | 579 | 23/23/26/28 | 435.6 | 805.29 |
125 | 135.1 | 151.2 | 151.2 | 151.2 | 4 | 585 | 23/26/26/26 | 468.0 | 851.37 |
Chiller Plant No. | Chiller Cooling Capacity at STD (kW) | Total Units | Total Cooling Capacity (kW) | Cooling Distribution among Chillers (%) | Energy Consumption (kWh/year) | LCC MM Cup | ||||
---|---|---|---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | 5 | ||||||
126 | 98.2 | 98.2 | 98.2 | 98.2 | 151.2 | 5 | 541 | 18/18/18/18/28 | 436.8 | 825.18 |
127 | 98.2 | 98.2 | 98.2 | 98.2 | 161.7 | 5 | 551 | 18/18/18/18/29 | 435.7 | 825.45 |
128 | 98.2 | 98.2 | 98.2 | 98.2 | 181.3 | 5 | 571 | 17/17/17/17/32 | 437.5 | 830.07 |
129 | 98.2 | 98.2 | 98.2 | 119.0 | 135.1 | 5 | 546 | 18/18/18/22/25 | 410.2 | 788.54 |
130 | 98.2 | 98.2 | 98.2 | 119.0 | 151.2 | 5 | 562 | 17/17/17/21/27 | 411.3 | 793.40 |
131 | 98.2 | 98.2 | 98.2 | 119.0 | 161.7 | 5 | 573 | 17/17/17/21/28 | 408.6 | 791.19 |
132 | 98.2 | 98.2 | 98.2 | 135.1 | 135.1 | 5 | 561 | 17/17/17/24/24 | 421.6 | 806.30 |
133 | 98.2 | 98.2 | 98.2 | 135.1 | 151.2 | 5 | 578 | 17/17/17/23/26 | 418.9 | 805.36 |
134 | 98.2 | 98.2 | 119.0 | 119.0 | 119.0 | 5 | 552 | 18/18/22/22/22 | 410.5 | 787.51 |
135 | 98.2 | 98.2 | 119.0 | 119.0 | 135.1 | 5 | 567 | 17/17/21/21/24 | 402.6 | 781.18 |
136 | 98.2 | 98.2 | 119.0 | 119.0 | 151.2 | 5 | 583 | 17/17/20/20/26 | 400.6 | 781.26 |
137 | 98.2 | 98.2 | 119.0 | 135.1 | 135.1 | 5 | 583 | 17/17/20/23/23 | 405.8 | 788.54 |
138 | 98.2 | 119.0 | 119.0 | 119.0 | 119.0 | 5 | 573 | 17/21/21/21/21 | 410.5 | 791.43 |
References
- ASHRAE. Fundamentals Handbook; ASHRAE: Atlanta, GA, USA, 2017; Chapter 18; ISBN 10-1939200598. [Google Scholar]
- ASHRAE. Standard 62.2-2016 Ventilation for Acceptable Indoor Air Quality; ASHRAE: Atlanta, GA, USA, 2016; ISSN 1041-2336. [Google Scholar]
- Norma Cubana NC 220-3:2009. Edificaciones-Requisitos de Diseño Para la Eficiencia Energética-Parte 3: Sistemas y Equipamiento de Calefaccion, Ventilación y Aire Acondicionado. Oficina Nacional de Normalización (NC). 2009. Available online: www.nc.cubaindustria.cu (accessed on 10 September 2020).
- Nall, D. Rightsizing HVAC equipment. ASHRAE J. 2015, 57, 1. [Google Scholar]
- Ruya, E.; Augenbroe, G. The impacts of HVAC downsizing on thermal comfort hours and energy consumption. In Proceedings of the ASHRAE and IBPSA-USA SimBuild Conference, Salt Lake City, UT, USA, 10–12 August 2016; Volume 6, p. 1. [Google Scholar]
- Chang, Y.-C. A novel energy conservation method-optimal Chillers loading. Electr. Power Syst. Res. 2004, 69, 221–226. [Google Scholar] [CrossRef]
- Menezes, A.C.; Cripps, A.; Buswell, R.A.; Wright, J.; Bouchlaghem, D. Estimating the energy consumption and power demand of small power equipment in office building. Energy Build. 2014, 75, 199–209. [Google Scholar] [CrossRef]
- Wang, W.; Augenbroe, G.; Wang, S.; Fan, C.; Xiao, F. An uncertainty-based design optimization method for district cooling systems. Energy 2016, 102, 516–527. [Google Scholar]
- Li, M.; Qin, C.; Feng, Y.; Zhou, M.; Mu, H.; Li, N.; Ma, Q. Optimal design and analysis of CCHP system for a hotel application. Energy Procedia 2017, 142, 2329–2334. [Google Scholar] [CrossRef]
- Cheng, Q.; Wang, S.; Yan, C. Sequential Monte Carlo simulation for robust optimal design of cooling water system with quantified uncertainty and reliability. Energy 2017, 118, 489–501. [Google Scholar] [CrossRef]
- Gang, W.; Wang, S.; Augenbroe, G.; Xiao, F. Robust optimal design of district cooling systems and the impacts of uncertainty and reliability. Energy Build. 2016, 122, 11–22. [Google Scholar] [CrossRef]
- Cheng, Q.; Wang, S.; Yan, C.H.; Xiao, F. Probabilistic approach for uncertainty-based optimal design of chiller plants in buildings. Appl. Energy 2017, 185, 1613–1624. [Google Scholar] [CrossRef]
- Kang, Y.; Augenbroe, Q.; Li, W.; Wang, Q. Effects of scenario uncertainty on chiller sizing method. Appl. Therm. Eng. 2017, 123, 187–195. [Google Scholar] [CrossRef]
- Huang, P.; Huang, G.; Augenbroe, G.; Li, S. Optimal configuration of multiple-chiller plants under cooling load uncertainty for different climate effects and building types. Energy Build. 2018, 158, 684–697. [Google Scholar] [CrossRef]
- Chai, J.; Huang, P.; Sun, Y. Life-cycle analysis of nearly zero energy buildings under uncertainty and degradation impacts for performance improvements. Energy Procedia 2019, 158, 2762–2767. [Google Scholar] [CrossRef]
- Liao, Y.; Huang, G.; Ding, Y.; Wu, H.; Feng, Z. Robustness enhancement for chiller sequencing control under uncertainty. Appl. Therm. Eng. 2018, 141, 811–818. [Google Scholar] [CrossRef]
- Yan, C.; Cheng, Q.; Cai, H. Life-Cycle optimization of a chiller plant with quantified analysis of uncertainty and reliability in commercial buildings. Appl. Sci. 2019, 9, 1548. [Google Scholar] [CrossRef]
- Yu, F.W.; Ho, H.T. Assessing operating statuses for chiller system with Cox regression. Int. J. Refrig. 2019, 98, 182–193. [Google Scholar] [CrossRef]
- Chen, Y.; Yang, C.; Pan, X.; Yan, D. Design and operation optimization of multi-chiller plants based on energy performance simulation. Energy Build. 2020, 222, 110100. [Google Scholar] [CrossRef]
- Huang, P.; Huang, G.; Sun, Y. Uncertainty-based life-cycle analysis of near-zero energy buildings for performance improvements. Appl. Energy 2018, 213, 486–498. [Google Scholar] [CrossRef]
- Vasisht, S.; Bhattacharya, A.; Huang, S.; Sharma, H.; Adetola, V.; Vrabie, D. Co-Design of Commercial Building HVAC using Bayesian Optimization. In Proceedings of the 2021 American Control Conference (ACC), New Orleans, LA, USA, 25–28 May 2021; pp. 366–372. [Google Scholar]
- Kapoor, K.; Edgar, T. Chapter 2: Energy efficient chiller configuration. A design Perspective. Comput. Aided Chem. Eng. 2015, 36, 37–52. [Google Scholar]
- Stanford, H.W., III. HVAC Water Chillers and Cooling Towers. Fundamentals, Application, and Operation, 2nd ed.; Marcel Dekker, Inc.: New York, NY, USA, 2016; ISBN 0-8247-0992-6. [Google Scholar]
- Valentina, S.; Nasri, S.M.; Herespatiagni, R. Analysis of the Effect of HVAC System Modification towards Indoor Air Quality (IAQ) and Microbiological Growth at Accommodation and Office Buildings in an Oil and Gas Industry. J. Presipitasi Media Komun. Dan Pengemb. Tek. Lingkung. 2021, 18, 306–316. [Google Scholar] [CrossRef]
- Hong, Y.; Ezeh, C.I.; Deng, W.; Hong, S.-H.; Peng, Z.; Tang, Y. Correlation between building characteristic and associated energy consumption: Prototyping low-rise office building in Shanghai. Energy Build. 2020, 217, 109959. [Google Scholar] [CrossRef]
- Lee, W.L.; Lee, S.H. Developing a simplified model for evaluating chiller-system configurations. Appl. Energy 2007, 84, 290–306. [Google Scholar] [CrossRef]
- Gang, W.; Wang, S.; Xiao, F.; Gao, D. Robust optimal design of building cooling systems considering cooling load uncertainty and equipment reliability. Appl. Energy 2015, 159, 265–275. [Google Scholar] [CrossRef]
- Catrini, P.; Piacentino, A.; Cardona, F.; Ciulla, G. Exergoeconomic analysis as support in decision-making for the design and operation of multiple chiller systems in air conditioning applications. Energy Convers. Manag. 2020, 220, 113051. [Google Scholar] [CrossRef]
- Maasoumy, M.; Zhu, Q.; Li, C.; Meggers, F.; Sangiovanni-Vincentelli, A. Co-design of control algorithm and embedded platform for building hvac systems. In Proceedings of the ACM/IEEE International Conference on Cyber-Physical Systems (ICCPS), Philadelphia, PA, USA, 8–11 April 2013; pp. 61–70. [Google Scholar]
- Bhattacharya, A.; Vasisht, S.; Adetola, V.; Huang, S.; Sharma, H.; Draguna, L. Control co-design of commercial building chiller plant using Bayesian optimization. Energy Build. 2021, 246, 111077. [Google Scholar] [CrossRef]
- Ngyen, A.-T.; Reiter, S.; Rigo, P. A review on simulation based optimization methods applied to building performance analysis. Appl. Energy 2014, 113, 1043–1058. [Google Scholar] [CrossRef]
- Díaz Torres, Y.; Álvarez Guerra, M.; Haeseldonck, D. The air conditioning system. Aspects that regulate their design for building. Part 2. Univ. Soc. 2020, 12, 461–469. [Google Scholar]
- Díaz Torres, Y. Procedimiento Para Determinar la Distribución de la Capacidad Frigorífica Optima de Una Planta de Enfriadoras. Doctoral Thesis, Universidad de Cienfuegos, Cienfuegos, Cuba, 2021. [Google Scholar]
- Díaz Torres, Y.; Reyes, C.R.; Hernandez, H.; Alvarez-Guerra, M.; Gómez, S.J.; Silva, I. Procedure to obtain the optimal distribution cooling capacity of an air-condensed chiller plant for a hotel facility conceptual design. Energy Rep. 2021, 7, 622–637. [Google Scholar] [CrossRef]
- Díaz Torres, Y.R.; Hernandez, H.; Torres, M.; Alvarez-Guerra, M.; Gullo, P.; Silva, I. Statistical-mathematical procedure to determine the cooling distribution of a chiller plant. Energy Rep. 2022, 8, 512–526. [Google Scholar] [CrossRef]
- Rendón, M.E.; Villasís, M.Á.; Miranda, M.G. Estadística descriptiva. Rev. Alerg. Mex. 2016, 63, 397–407. [Google Scholar]
- Shapiro, S.S.; Wilk, M.B. An analysis of variance test for normality (complete samples). Biometrika 1965, 52, 591–611. [Google Scholar] [CrossRef]
- Anderson, T.W.; Darling, D.A. Asymptotic theory of certain “goodness-of-fit” criteria based on stochastic processes. Ann. Math. Stat. 1952, 23, 193–212. [Google Scholar] [CrossRef]
- Anderson, T.W.; Darling, D.A. A Test of Goodness-of-Fit. J. Am. Stat. Assoc. 1954, 49, 765–769. [Google Scholar] [CrossRef]
- Kolmogorov, A. Sulla determinazione empirica di una legge di distribuzione. G. Dell’istituto Ital. Degli Attuari 1933, 4, 83–91. [Google Scholar]
- Smirnov, N. Table for estimating the goodness of fit of empirical distributions. Ann. Math. Stat. 1948, 19, 279–281. [Google Scholar] [CrossRef]
- Pearson, K. Contribution to the mathematical theory of evolution. II. Skew variation in homogenous material. Philos. Trans. R. Soc. Lond. 1895, 91, 343–414. [Google Scholar]
- Cramér, H. On the composition of elementary errors. Scand. Actuar. J. 1928, 1, 13–74. [Google Scholar] [CrossRef]
- Von Mises, R.E. Wahrscheinlichkeit, Statistik und Wahrheit; Julius Springer: Berlin, Germany, 1928. [Google Scholar]
- Lilliefors, H.W. On the Kolmogorov-Smirnov test for normality with mean and variance unknown. J. Am. Stat. Assoc. 1967, 62, 399–400. [Google Scholar] [CrossRef]
- Jarque, C.M.; Bera, A.K. Efficient tests for normality, homoscedasticity and serial independence of regression residuals. Econ. Lett. 1980, 6, 255–259. [Google Scholar] [CrossRef]
- Jarque, C.M.; Bera, A.K. Efficient tests for normality, homoscedasticity and serial independence of regression residuals: Monte Carlo evidence. Econ. Lett. 1981, 7, 313–318. [Google Scholar]
- Jarque, C.M.; Bera, A.K. A test for normality of observations and regression residuals. Int. Stat. Rev. 1987, 55, 163–172. [Google Scholar] [CrossRef]
- D’Agostino, R.B.; Belanger, A.; D’Agostino, R.B., Jr. A suggestion for using powerful and informative tests of normality. Am. Stat. 1990, 44, 316–321. [Google Scholar]
- Hernandez, H. Testing for normality: What is the best method? Fors. Chem. Res. Rep. 2021, 6, 101–138. [Google Scholar]
- Razali, N.M.; Wah, Y.B. Power comparisons of Shapiro–Wilk, Kolmogorov–Smirnov, Lilliefors and Anderson–Darling tests. J. Stat. Modeling Anal. 2011, 2, 21–33. [Google Scholar]
- Demir, S. Comparison of Normality Tests in Terms of Sample Sizes under Different Skewness and Kurtosis Coefficients. Int. J. Assess. Tools Educ. 2022, 9, 397–409. [Google Scholar] [CrossRef]
- Levene, H. Robust testes for equality of variances. In Contributions to Probability and Statistics; Olkin, I., Ed.; Stanford University Press: Palo Alto, CA, USA, 1960; pp. 278–292, MR0120709. [Google Scholar]
- Bartlett, M.S. Properties of Sufficiency and Statistical Tests. Proc. R. Stat. Soc. 1937, 160, 268–282. [Google Scholar]
- Cochran, W.G. Some consequences when the assumptions for the analysis of variance are not satisfied. Biometics 1947, 3, 22–38. [Google Scholar] [CrossRef]
- Brown, M.B.; Forsythe, A.B. Robust tests for equality of variances. J. Am. Stat. Assoc. 1974, 69, 364–367. [Google Scholar] [CrossRef]
- Vorapongsathorn, T.; Taejaroenkul, S.; Viwatwongkasem, C. A comparison of type I error and power of Bartlett’s test, Levene’s test and Cochran’s test under violation of assumptions. Sci. Technol. 2004, 26, 538–547. [Google Scholar]
- Hernandez, J.D.; Espinoza, F.; Rodriguez, J.; Chacon, J.G.; Toloza, C.R.; Arenas, M.K.; Carrillo, S.M.; Pirela, V. On the proper use of the pearson correlation coefficient: Definitions, properties and assumption. Arch. Venez. Farmacol. Ter. 2018, 37, 552–561. [Google Scholar]
- Asuero, A.G.; Sayago, A.; González, A.G. Correlation Coefficient: An Overview. Crit. Rev. Anal. Chem. 2006, 36, 41–59. [Google Scholar] [CrossRef]
- Hair, J.F., Jr.; Money, A.H.; Samouel, P.; Page, M. Research Methods for Business; John Wiley & Sons: Hoboken, NJ, USA, 2007; Available online: https://digitalcommons.kennesaw.edu/facpubs/2952 (accessed on 25 January 2022).
- Park, R.E. Estimation with Heteroscedastic Error Terms. Econometrica 1966, 34, 888. [Google Scholar] [CrossRef]
- Glejser, H. A New Test for Heteroscedasticity. J. Am. Stat. Assoc. 1969, 64, 316–323. [Google Scholar] [CrossRef]
- Goldfield, S.M.; Quandt, R.E. Some Test for Homoscedasticity. J. Am. Stat. Assoc. 1965, 310, 539–547. [Google Scholar] [CrossRef]
- Harrison, M.J.; McCabe, P. A Test for Heteroscedasticity Based on Ordinary Least Square Residuals. J. Am. Stat. Assoc. 1979, 74, 494–499. [Google Scholar]
- Breusch, T.S.; Pagan, A. The Review of Economic Studies. In Econometrics Issue; Oxford University Press: Oxford, UK, 1980; Volume 47, pp. 239–253. [Google Scholar]
- White, H. A heteroskedasticity-consistent covariance matrix estimator and a direct test for heteroskedasticity. Econometrica 1980, 48, 817–838. [Google Scholar] [CrossRef]
- Koenker, R.; Bassett, G. Robust Tests for Heteroscedasticity Based on Regression Quantiles. Econometrica 1982, 50, 43–61. [Google Scholar] [CrossRef]
- Onifade, O.C.; Olanrewaju, S.O. Investigating Performances of Some Statistical Tests for Heteroscedasticity Assumption in Generalized Linear Model: A Monte Carlo Simulations Study. Open J. Stat. 2020, 10, 453–493. [Google Scholar] [CrossRef]
- Rasmussen, J.L.; Dunlap, W.P. Dealing with non-normal data: Parametric analysis of transformed data vs nonparametric analysis. Educ. Psychol. Meas. 1991, 51, 809–820. [Google Scholar] [CrossRef]
- Olvera, O.L.O.; Zumbo, B.D. Heteroskedasticity in multiple Regression analysis: What it is, how to detect it and how to solve it with applications in R and SPSS. Pract. Assess. Res. Eval. 2019, 24, 1. [Google Scholar]
- Huber, P.J. The behavior of maximum likelihood estimates under nonstandard conditions. In Proceedings of the 5th Berkeley Symposium on Mathematical Statistics and Probability, Berkeley, CA, USA, 7 January 1967; Volume 1, pp. 221–223. [Google Scholar]
- Eicker, F. Limit theorems for regressions with unequal and dependent errors. In Proceedings of the 5th Berkeley Symposium on Mathematical Statistics and Probability, Berkeley, CA, USA, 7 January 1967; Volume 1, pp. 59–82. [Google Scholar]
- Davidson, R.; Flachaire, E. The wild bootstrap, tamed at last. J. Econom. 2008, 146, 162–169. [Google Scholar] [CrossRef]
- Flachaire, E. A better way to bootstrap pairs. Econ. Lett. 1999, 64, 257–262. [Google Scholar] [CrossRef]
- Flachaire, E. Bootstrapping heteroskedastic regression models: Wild bootstrap vs. pairs bootstrap. Comput. Stat. Data Anal. 2005, 49, 361–376. [Google Scholar] [CrossRef]
- Godfrey, L.G.; Orme, C.D. Controlling the finite sample significance levels of heteroskedasticity-robust tests of several linear restrictions on regression coefficients. Econ. Lett. 2004, 82, 281–287. [Google Scholar] [CrossRef]
- MacKinnon, J.G. Thirty years of heteroskedasticity-robust inference. In Recent Advances and Future Directions in Causality, Prediction, and Specification Analysis; Chen, X., Swanson, N.R.E., Eds.; Springer: Berlin/Heidelberg, Germany, 2013; pp. 437–462. [Google Scholar]
- Richard, P. Robust heteroskedasticity-robust tests. Econ. Lett. 2017, 159, 28–32. [Google Scholar] [CrossRef]
- Spearman, C. The proof and measurement of association between two things. Am. J. Psychol. 1904, 15, 72–101. [Google Scholar] [CrossRef]
- Kendall, M.G. A new measure of rank correlation. Biometrika 1938, 30, 81–93. [Google Scholar] [CrossRef]
- Statgraphics Centurion 18. Available online: https://www.statgraphics.com/download18 (accessed on 10 May 2022).
- E-View 12 Student Version. Available online: https://www.eviews.com/home.html (accessed on 12 May 2022).
- Scott Long, J.; Ervin Laurie, H. Using Heteroscedasticity Consistent Standard Errors in the Linear Regression Model. Am. Stat. 2000, 54, 217–224. [Google Scholar]
- Johnson, N.L.; Kotz, S.; Balakrishnan, N. Chi-Square Distributions including Chi and Rayleigh. In Continuous Univariate Distributions, 2nd ed.; John Wiley and Sons: Hoboken, NJ, USA, 1994; Volume 1, pp. 415–493. ISBN 978-0-471-58495-7. [Google Scholar]
- IBM SPSS Statistics 20. Available online: https://www.ibm.com/support/pages/downloading-ibm-spss-statistics-20 (accessed on 12 May 2022).
- Huang, P.; Wang, Y.; Huang, G.; Augenbroe, G. Investigation of the ageing effect on chiller plant maximum cooling capacity using Bayesian Markov Chain Monte Carlo method. J. Build. Perform. Simul. 2016, 9, 529–541. [Google Scholar] [CrossRef]
Variable | Symbol | Classification | Characteristic | Total of Values | Unit |
---|---|---|---|---|---|
Total of chiller | Nch | Independent | Numerical | 138 | - |
Total cooling capacity installed | Qch | Independent | Numerical | 138 | kW |
Cooling distribution among chillers | Cdch | Independent | Ordinal | 138 | - |
Annual energy consumption | AEC | Dependent | Numerical | 138 | MWh/year |
Life Cycle Cost | LCC | Dependent | Numerical | 138 | MMCup * |
Total Units | Arrangement Type | Mathematical Expression | Constrains | Equation | Classification | Scale |
---|---|---|---|---|---|---|
2 | Symmetrical | - | (18) | S1 | 48 | |
Similar | CV ≤ 7 | (19) | S2 | 46 | ||
Asymmetrical type1 | CV ≤ 20 | (20) | S3 | 44 | ||
Asymmetrical type2 | CV > 20 | (21) | S4 | 42 | ||
3 | Symmetrical | - | (22) | S1 | 38 | |
Similar | CV ≤ 15 | (23) | S2 | 36 | ||
Asymmetrical type1 | (24) | S3 | 34 | |||
Asymmetrical type2 | (25) | S4 | 32 | |||
Asymmetrical type3 | CV ≥ 18 | (26) | S5 | 30 | ||
4 | Symmetrical (similar) | CV ≤ 11 | (27) | S1 | 26 | |
Asymmetrical type1 | (28) | S2 | 24 | |||
Asymmetrical type2 | c1 > c4 | (29) | S3 | 22 | ||
Asymmetrical type3 | - | (30) | S4 | 20 | ||
Asymmetrical type4 | - | (31) | S5 | 18 | ||
Asymmetrical type5 | CV > 13 | (32) | S6 | 16 | ||
5 | Symmetrical (similar) | CV ≤ 9 | (33) | S1 | 12 | |
Asymmetrical type1 | - | (34) | S2 | 10 | ||
Asymmetrical type2 | - | (35) | S3 | 8 | ||
Asymmetrical type3 | - | (36) | S4 | 6 | ||
Asymmetrical type4 | - | (37) | S5 | 4 | ||
Asymmetrical type5 | - | (38) | S6 | 2 |
Chiller Plant No. | Classification | Scale | Chiller Plant No. | Classification | Scale | Chiller Plant No. | Classification | Scale |
---|---|---|---|---|---|---|---|---|
1 | s4 | 44 | 47 | s4 | 32 | 93 | s5 | 18 |
2 | s4 | 44 | 48 | s2 | 36 | 94 | s5 | 18 |
3 | s4 | 44 | 49 | s4 | 32 | 95 | s5 | 18 |
4 | s4 | 44 | 50 | s1 | 38 | 96 | s3 | 22 |
5 | s1 | 48 | 51 | s2 | 36 | 97 | s2 | 24 |
6 | s2 | 48 | 52 | s2 | 36 | 98 | s2 | 24 |
7 | s3 | 34 | 53 | s2 | 36 | 99 | s2 | 24 |
8 | s5 | 30 | 54 | s2 | 36 | 100 | s2 | 24 |
9 | s5 | 30 | 55 | s2 | 36 | 101 | s5 | 18 |
10 | s5 | 30 | 56 | s2 | 24 | 102 | s5 | 18 |
11 | s5 | 30 | 57 | s5 | 18 | 103 | s5 | 18 |
12 | s5 | 30 | 58 | s5 | 18 | 104 | s4 | 20 |
13 | s5 | 30 | 59 | s5 | 18 | 105 | s5 | 18 |
14 | s5 | 30 | 60 | s5 | 18 | 106 | s5 | 18 |
15 | s4 | 32 | 61 | s5 | 18 | 107 | s4 | 20 |
16 | s3 | 34 | 62 | s5 | 18 | 108 | s5 | 18 |
17 | s5 | 30 | 63 | s5 | 18 | 109 | s1 | 26 |
18 | s5 | 30 | 64 | s5 | 18 | 110 | s5 | 18 |
19 | s5 | 30 | 65 | s5 | 18 | 111 | s5 | 18 |
20 | s5 | 30 | 66 | s5 | 18 | 112 | s5 | 18 |
21 | s5 | 30 | 67 | s4 | 20 | 113 | s1 | 26 |
22 | s5 | 30 | 68 | s5 | 18 | 114 | s6 | 16 |
23 | s5 | 30 | 69 | s5 | 18 | 115 | s6 | 16 |
24 | s4 | 32 | 70 | s5 | 18 | 116 | s5 | 18 |
25 | s3 | 34 | 71 | s5 | 18 | 117 | s1 | 26 |
26 | s3 | 34 | 72 | s6 | 16 | 118 | s1 | 26 |
27 | s5 | 30 | 73 | s6 | 16 | 119 | s1 | 26 |
28 | s5 | 30 | 74 | s6 | 16 | 120 | s1 | 26 |
29 | s5 | 30 | 75 | s6 | 16 | 121 | s1 | 26 |
30 | s5 | 30 | 76 | s6 | 16 | 122 | s2 | 24 |
31 | s5 | 30 | 77 | s5 | 18 | 123 | s1 | 26 |
32 | s4 | 32 | 78 | s5 | 18 | 124 | s1 | 26 |
33 | s5 | 30 | 79 | s6 | 16 | 125 | s1 | 26 |
34 | s3 | 34 | 80 | s6 | 16 | 126 | s2 | 10 |
35 | s5 | 30 | 81 | s6 | 16 | 127 | s2 | 10 |
36 | s5 | 30 | 82 | s5 | 18 | 128 | s2 | 10 |
37 | s5 | 30 | 83 | s5 | 18 | 129 | s4 | 6 |
38 | s4 | 32 | 84 | s5 | 18 | 130 | s4 | 6 |
39 | s2 | 36 | 85 | s5 | 18 | 131 | s4 | 6 |
40 | s5 | 30 | 86 | s6 | 16 | 132 | s4 | 6 |
41 | s4 | 32 | 87 | s6 | 16 | 133 | s4 | 6 |
42 | s5 | 30 | 88 | s6 | 16 | 134 | s3 | 8 |
43 | s3 | 34 | 89 | s6 | 16 | 135 | s5 | 4 |
44 | s2 | 36 | 90 | s5 | 18 | 136 | s5 | 4 |
45 | s2 | 36 | 91 | s6 | 16 | 137 | s5 | 4 |
46 | s5 | 30 | 92 | s3 | 22 | 138 | s1 | 12 |
Statistical Test | AEc (Y) | LCC (Y) | ||
---|---|---|---|---|
Statistic | p-Value | Statistic | p-Value | |
Shapiro–Wilk (SW) | 0.904483 | 1.54798 × 10−12 | 0.957847 | 0.00242575 |
Anderson–Darling (A2) | 3.49206 | 9.01993 × 10−9 | 1.52435 | 0.000603096 |
Equation | Bivariate Relationship (Yi = mXi + n) | Coefficients (m; n) | Standard Error (m; n) | t-Statistic (m; n) | Prob. (m; n) | R-Squared |
---|---|---|---|---|---|---|
(39) | (AEc) vs. (Nch) | (−25.86455; 527.1655) | (2.56915; 9.5579) | (−10.06736; 55.15443) | (0.0000; 0.0000) | 0.427011 |
(40) | (AEc) vs. (Qch) | (−0.171896; 529.7965) | (0.162240; 91.67009) | (−1.059517; 5.779382) | (0.2912; 0.0000) | 0.008187 |
(41) | (AEc) vs. (Cdch) | (2.238676; 379.1052) | (0.168833; 4.343118) | (13.25968; 87.28871) | (0.0000; 0.0000) | 0.563850 |
(42) | (LCC) vs. (Nch) | (−9.305803; 821.8668) | (3.678271; 13.68425) | (−2.529939; 60.05934) | (0.0125; 0.0000) | 0.044948 |
(43) | (LCC) vs. (Qch) | (0.147560; 704.5334) | (0.180214; 101.8261) | (0.818803; 6.918990) | (0.4143; 0.0000) | 0.0.04906 |
(44) | (LCC) vs. (Cdch) | (1.177679; 759.6843) | (0.264905; 6.814493) | (4.445666; 111.4807) | (0.0000; 0.0000) | 0.126884 |
Bivariate Relationship | Equations | p-Value | Heteroscedasticity | Mathematical Model | R-Squared |
---|---|---|---|---|---|
(AEC) vs. (Nch) | (39) | 0.0240 | Yes | 0.036910 | |
(AEC) vs. (Qch) | (40) | 0.4138 | No | 0.004916 | |
(AEC) vs. (Cdch) | (41) | 0.1418 | No | 0.015805 | |
(LCC) vs. (Nch) | (42) | 0.0189 | Yes | 0.039849 | |
(LCC) vs. (Qch) | (43) | 0.6400 | No | 0.001585 | |
(LCC) vs. (Cdch) | (44) | 0.0518 | No | 0.027534 |
Equation | Bivariate Relationship (Yi = mXi + n) | Coefficients (m; n) | Standard Error (m; n) | t-Statistic (m; n) | Prob. (m; n) | R-Squared |
---|---|---|---|---|---|---|
(39) * | (AEc) vs. (Nch) | (−25.86455; 527.1655) | (3.210059; 12.35129) | (−8.057346; 42.68102) | (0.0000; 0.0000) | 0.427011 |
(42) * | (LCC) vs. (Nch) | (−9.305803; 821.8668) | (4.344333; 16.79198) | (−2.142055; 48.94401) | (0.0340; 0.0000) | 0.044948 |
(44) * | (LCC) vs. (Cdch) | (1.177679; 759.6843) | (0.313664; 7.307557) | (3.754583; 103.9587) | (0.0030; 0.0000) | 0.126884 |
Statistic | p-Value | Statistic | p-Value | Statistic | p-Value | |
---|---|---|---|---|---|---|
AEc (Ŷi) Equation (39) * | AEc (Ŷi) Equation (40) | AEc (Ŷi) Equation (41) | ||||
(SW) | 0.831547 | 2.78972 × 10−11 | 0.954328 | 0.000153493 | 0.960179 | 0.000483601 |
(A2) | 11.5387 | <0.01 | 1.49567 | ≥0.10 | 2.44905 | ≥0.10 |
LCC (Ŷi) Equation (42) * | LCC (Ŷi) Equation (43) | LCC (Ŷi) Equation (44) * | ||||
(SW) | 0.831547 | 2.78972 × 10−11 | 0.954328 | 0.0001534 | 0.960179 | 0.000483 |
(A2) | 11.5387 | <0.01 | 1.49567 | ≥0.10 | 2.44905 | <0.10 |
Operational Variables (Dependant) | Design Variables (Independent) | |||
---|---|---|---|---|
Cooling Distribution among Chillers | Total Chillers | Total Installed Cooling Capacity | ||
Energy consumption | rs | - | −0.625 ** | −0.086 |
Sig. (bilateral) | - | 0.000 | 0.314 | |
τ | 0.559 ** | - | - | |
Sig. (bilateral) | 0.000 | - | - | |
LCC | rs | - | −0.135 | 0.063 |
Sig. (bilateral) | - | 0.113 | 0.463 | |
τ | 0.289 ** | - | - | |
Sig. (bilateral) | 0.001 | - | - |
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. |
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Torres, Y.D.; Gullo, P.; Herrera, H.H.; Torres del Toro, M.; Guerra, M.A.Á.; Ortega, J.I.S.; Speerforck, A. Statistical Analysis of Design Variables in a Chiller Plant and Their Influence on Energy Consumption and Life Cycle Cost. Sustainability 2022, 14, 10175. https://doi.org/10.3390/su141610175
Torres YD, Gullo P, Herrera HH, Torres del Toro M, Guerra MAÁ, Ortega JIS, Speerforck A. Statistical Analysis of Design Variables in a Chiller Plant and Their Influence on Energy Consumption and Life Cycle Cost. Sustainability. 2022; 14(16):10175. https://doi.org/10.3390/su141610175
Chicago/Turabian StyleTorres, Yamile Díaz, Paride Gullo, Hernán Hernández Herrera, Migdalia Torres del Toro, Mario A. Álvarez Guerra, Jorge Iván Silva Ortega, and Arne Speerforck. 2022. "Statistical Analysis of Design Variables in a Chiller Plant and Their Influence on Energy Consumption and Life Cycle Cost" Sustainability 14, no. 16: 10175. https://doi.org/10.3390/su141610175