Laboratory and In-Situ Measurements for Thermal and Acoustic Performance of Straw Bales

1
Department of Civil Engineering and Architecture, University of Catania, Via Santa Sofia 64, 95123 Catania, Italy
2
Department of Electrical, Electronics and Computer Engineering, University of Catania, Viale Andrea Doria 6, 95125 Catania, Italy
*
Author to whom correspondence should be addressed.
Sustainability 2019, 11(20), 5592; https://doi.org/10.3390/su11205592
Submission received: 23 September 2019 / Revised: 4 October 2019 / Accepted: 5 October 2019 / Published: 11 October 2019

Abstract

:
This paper investigates the performance of timber-framed walls insulated with straw bales, and compares them with similar walls containing expanded polystyrene (EPS) instead of straw bales. First, thermal conductivity, initial water content, and density of the straw bales were experimentally measured in a laboratory set-up, and the dependence of the thermal conductivity of the dry material on temperature was described. Then, the two insulation solutions were compared by looking at their steady and periodic thermal transmittance, decrement factor, phase shift, internal areal heat capacity and surface mass. Finally, the acoustic performance of both wall typologies was analyzed by means of in situ measurements in two-story buildings built in Southern Italy. The weighted apparent sound reduction index for the partition wall between two houses and the weighted standardized level difference for the façades were assessed based on ISO Standard 16283. The results indicate that the dry straw bales have an average thermal conductivity of k = 0.0573 W/(m·K), and their density is around 80 kg/m3. In addition, straw bale walls have good steady thermal performance, but they still lack sufficient thermal inertia, as witnessed by the low phase shift and the high periodic thermal transmittance. Finally, according to the on-site measurements, the results underline that the acoustic performance of the straw bale walls is far better than the walls adopting traditional EPS insulation. Overall, the straw bales investigated are a promising natural and sustainable solution for thermal and sound insulation of buildings.

1. Introduction

Nowadays, synthetic products and mineral wools account for more than 90% of the market of insulating materials in the construction sector, thanks to their excellent performance and their cost effectiveness [1]. However, their production processes consume high amounts of non-renewable resources and have a strong environmental impact, especially in terms of greenhouse gas emissions [2]. Therefore, several researchers have proposed developing new construction materials with low thermal conductivity by using natural materials, such as agricultural residues, including wheat straw [3], barley straw [4], rice straw [5], date palm fibers [6], olive stone [7], and coconut and durian mixtures [8].
In particular, straw is a co-product of agricultural grain, and it is currently produced in excess of its demand; therefore, it is cheap and easily accessible in many regions of the world [9]. Consolidated research shows that in 2016, the global amount of straw produced worldwide equaled 3.6 × 109 tons. The earliest straw bale constructions were built in Nebraska, United States of America (USA), near the end of the 19th century, thanks to the invention of the baling machine. During the 1940s, this construction technique was abandoned, but the energy crisis in the 1970s led to an awareness of the environmental impact of human activities and caused a revival in the use of natural materials in the construction sector. Straw bale buildings can now be found in many locations around the world, including the USA, Europe, Canada, Australasia, Japan, and China.
Over the last ten years, many advantages of this sustainable material have been recognized. First, straw bales act as a carbon sink, and they have significantly lower embodied energy and carbon content than conventional materials [10]. As an example, González [11] estimated that the energy embedded in straw bales needed to cover 1 m2 of wall is about 28 MJ, meaning that they are less impactful than the same area covered by fired bricks (488 MJ/m2) or concrete blocks (169 MJ/m2). Furthermore, one kilogram of straw can sequester about 1.35 kg of CO2 during plant growth. Second, straw bale walls provide high-quality physical properties, including low thermal transmittance, typically between 0.13 and 0.19 W/(m2·K) for a standard thickness of 450–500 mm [12].
However, straw is an organic material, and this introduces some risks in the context of living accommodation, especially regarding long-term durability [13]. Many studies have demonstrated that a moisture content lower than 20% prevents the decomposition of straw, which in turn begins when the moisture content exceeds 30% [14]. Lawrence et al. [15] provided a concise literature review of the methods for measuring the moisture conditions. Unobtrusive methods for moisture monitoring include indirect or direct electrical resistivity measurements, either of embedded wood blocks or the straw itself. Alternatively, moisture contents have been derived indirectly using relative humidity measurements. In order to improve the hygrothermal performance of straw bales and to avoid their degradation, breathability of render materials is critical.
Numerous publications on straw bale construction have appeared in the literature [16]. Wei et al. [17] developed a new thermal insulation material from rice straws with low density (200–350 kg/m3), a thickness of 40 mm, and thermal conductivity around 0.051–0.053 W/(m·K) using high-frequency hot-pressing. Thermal conductivity was found to be correlated with board density and ambient temperature. Experimental investigations indicated that the optimum properties of the new thermal insulation material were obtained with a particle moisture content of 14% and a board density of 250 kg/m3. Zhang et al. [18] studied heat transfer in straw blocks installed in Chinese solar greenhouses by theoretical and experimental analyses. The results showed that the thermal storage coefficient and the total thermal resistance of the wall were 38.5% and 25.4% higher than for a porous clay block wall, respectively. Furthermore, the cost, energy consumption, and CO2 emissions of straw blocks were reduced by 26.3%, 81.7%, and 29.4%, respectively, compared with clay blocks. Gallegos-Ortega et al. [19] attained data of real buildings obtained through on-site monitoring of a straw bale wall in a building in Tecate, Baja California, Mexico, where there is a high availability of straw and extreme climatic conditions. The results of the thermal monitoring for a straw bale unit with 10.5% humidity and 115 kg/m3 density suggested a time lag of 9.12 ± 1.8% h and a temperature reduction of 93.5% ± 1.4%. The results also reported a thermal resistance of 6.92 m2∙K/W ± 1.3%. The use of straw bales in a real building allowed for a nearly constant indoor temperature of around 25.5 °C, while the outdoor temperatures ranged from 14 to 28 °C. Cascone et al. [20] assessed the performance of a technological solution consisting of a vertical closure, combining a platform frame system with a filling of compressed straw as an insulating material. The platform frame system with straw bales reached an approximately 12% lower thermal transmittance and a 22% improvement in periodic thermal transmittance in comparison with the cross-laminated timber (CLT) stratigraphy. Finally, D’Alessandro et al. [21] performed a quantitative analysis to evaluate, both in laboratory and in situ, the strong and weak points of using straw bales in construction. Measurements performed with a guarded hot plate on a straw bale sample with 80 kg/m3 density gave a thermal conductivity of 0.052 W/(m∙K). The thermal transmittance of the wall was 0.119 W/(m2·K).
However, few studies have addressed the acoustic performance of walls made of straw bales. This is a non-negligible issue, since in 2002 the Environmental Noise Directive required member states to pay attention to noise exposure in buildings, which may induce health effects such as sleep disturbance [22]. For this reason, the walls of a building should have very good sound insulation properties, thus limiting the noise coming either from outside or from contiguous units: in Italy, since 1997, national regulations have introduced suitable thresholds for the sound level difference of the façades and the sound reduction index of the partition walls.
Moving toward sustainability, many studies have been looking for noise mitigation also taking into account environmental issues, by using appropriate recycled or recyclable materials [23,24]. In this line, the use of straw bales as a sound insulation material might be very interesting. D’Alessandro et al. [21] carried out in situ façade sound insulation tests, highlighting a weak point of the investigated straw bales walls. Indeed, the weighted apparent sound reduction index R′w, calculated from the measured values of the façade sound insulation index, was only 42 dB. The simulation performed by Trabelsi and Kammoun [25] showed excellent acoustic performance for a straw bale wall, with the absorption of more than 70% of the incident sound energy for medium and high frequencies and a sound reduction index R = 58 dB at high frequencies. Finally, the data collected from Goodhew et al. [26] suggested that it is possible for straw bale walls to achieve a weighted standardized level difference of 48–50 dB.
In this paper, the thermal and acoustic performances of timber-framed walls with straw bale insulation are addressed and compared to that of similar walls containing expanded polystyrene (EPS) instead of the straw bales. These insulation methods were adopted in a series of timber-framed two-story buildings recently built in Sicily (Southern Italy). First, the thermal conductivity of the straw bales was measured through laboratory tests in order to characterize the material at different operating temperatures. Based on the outcomes, the two insulation methods were compared by looking at their steady-state and dynamic thermal parameters. Then, their acoustic performance was evaluated through in situ measurements based on ISO Standard 16283 [27,28]. This allowed to calculate, for both types of wall, the weighted apparent sound reduction index for the partition wall between two houses, as well as the weighted standardized level difference for the façades.
The information provided in this study adds knowledge about the actual thermal and acoustic performance of straw bales used as a building material, and is helpful for designers wishing to make use of this natural material in the design of performing sustainable buildings in the Mediterranean area.

2. Materials and Methods

2.1. Description of the Building Case Studies

The buildings investigated in this study belong to a newly built residential complex located in Pedara, a small town about 13 km north of Catania, Southern Italy (Figure 1). The height above sea level is about 650 m, and the geographical coordinates are latitude 37°37′ N, longitude 15°3′ E. The number of heating degree days is 1568 °C·day, which places the town in climate zone D, according to Italian climatic classification. Minimum temperatures range from 4 °C in January and February to 18 °C in July and August, while maximum temperatures fluctuate between 10 °C in January and February and 27 °C in July and August. The average annual precipitation is 595 mm.
A pair of two-story buildings was built in 2017 with two levels above ground and a floor area between 50 and 100 m2. The ground floor contains the living area, while the sleeping area is located on the first floor.
The load-bearing structure of the houses is made of wood with reinforced concrete foundation beams. The floors and roofs (30% slope) are made with wooden beams (12 × 24 cm every 100 cm) and boards. The windows are made with wooden frame and double glazing. The external walls and internal partitions are realized by means of drywall systems. Figure 2 shows the stratigraphy of the external walls. The stratigraphy and thickness of the internal walls are the same as for the external ones, and the only difference is that layer (1) is also made of plasterboard. In the first instance, the thermo-acoustic insulation of the timber-framed envelope in some buildings was realized with panels of 20 cm thick EPS, with thermal conductivity k = 0.041 W/(m∙K) and density 20 kg/m3. Subsequently, in the second group of buildings, straw bales were used instead of the EPS layer; the straw came from wheat plantations located in the Plain of Catania.
Currently, traditional packing machines are not able to produce wheat straw bales with a small thickness, suitable to be used as thermal insulation in buildings. Common dimensions of straw bales produced with traditional techniques are as follows: width 45 cm, height 35 cm, and length from 95 to 115 cm.
On the contrary, the wheat straw bales considered in this study were specially packaged for this research. Their packaging is based on a new packing machine (patented by Eng. Marco Riccioli). The difference between this new packing machine and other packing machines is the size of the compression chamber and the length of the piston and the adjusting screw (between 15 and 25 cm). The bales produced with this machine can be smaller than common straw bales; in particular, the wheat straw bales used in this study have the following size: width 45 cm, length 50 cm, and thickness 20 cm. During the packaging of the bales, it was not possible to control the orientation of the fibers, which were therefore arranged randomly. In conventional bailing machines, the orientation of the fibers is not controlled, but does result in an orientation.

2.2. Thermal Conductivity: Laboratory Set-Up

One of the objectives of this study was to determine the thermal conductivity of the straw bales. In this study, the thermal conductivity of the straw bales was measured by means of a heat flow meter NETZSCH HFM 436 Lambda. Figure 3 shows the operation scheme and a picture of the laboratory equipment [29].
The heat flow meter was placed in a conditioned laboratory at a temperature of 23 ± 2 °C and relative humidity of 50 ± 5%, according to the test conditions required by standard EN 12667:2001 [30]. The equipment consists of two plates that are heated and cooled by thermoelectric effect. A heat flux sensor is integrated into each plate to monitor the heat flux, due to the temperature difference between the top and bottom plate until a steady-state heat flux is observed. Then, the measured heat flux is used to calculate the thermal conductivity according to FourieR′s Law. The precision of the thermocouple is ± 0.01 °C, while the overall accuracy of the instrument is within 3%, and stable over the course of several days, thus providing excellent repeatability.
As the NETZSCH HFM 436 Lambda is able to hold specimens with a maximum size of 300 × 300 mm and a maximum thickness of 10 cm, three samples of straw bales were produced to comply with this constraint. The samples were coated with a thin high-conductivity aluminum sheet to reduce the surface irregularity and to make them easier to handle. The addition of the thin aluminum sheet does not influence the thermal conductivity, considering its negligible contribution in terms of thermal resistance. Furthermore, the aluminum sheet improved the full contact between the sample and the plates. Figure 4 shows a straw specimen with and without the aluminum cover and its positioning between the two plates in the heat flow meter.
After being prepared, the straw samples were placed in an oven at 65 °C until they were dried to a constant mass (the time to reach the dry conditions varied depending on the initial water content). Before and after each drying cycle, the samples were weighed on a laboratory scale. Thus, the difference between the wet and dry weight, the initial water content and the density of each sample were determined (by measuring the weight and size of the samples).
Then, the samples were introduced into the heat flow meter to measure the thermal conductivity of the dried straw. The tests were conducted by varying the temperatures of the two plates in the heat flow meter while keeping a constant ΔT = 20 °C between them. For each temperature range, the thermal conductivity was obtained. Three series of tests were carried out for each sample over three consecutive days without removing the sample from the heat flow meter in order to maintain the sample in as unchanging conditions as possible.
The next step consisted of calculating, respectively by means of Equations (1) and (2), the mean thermal conductivity for each temperature range (by averaging over the nine values available) and the standard deviation:
λ ¯ ( T ) = i = 1 N λ i ( T ) N
σ ( T ) = i = 1 N [ λ i ( T ) λ ¯ ( T ) ] 2 N
Finally, in agreement with European standard EN ISO 10,456 [31], the dependence of the thermal conductivity on temperature was described through a suitable exponential function, based on the experimental curves.

2.3. Steady and Dynamic Thermal Performance

After evaluating the thermal conductivity of the straw in the laboratory set-up, the thermal performance of the entire wall was assessed through five parameters, describing its response to steady and dynamic thermal forcing conditions. These parameters are the thermal transmittance (U-value), periodic thermal transmittance (YIE), decrement factor (fa), phase shift (φ), internal areal heat capacity (κi), and surface mass (SM). An extensive description of these parameters is reported in ISO Standard 13786 [32].
The thermal transmittance (U-value) measures the attitude of the wall to transfer heat in steady conditions, and it was assessed by means of the following equation:
U = 1 1 h o i + j = 1 n R j + 1 h o e = 1 1 h o i + R g a p + j = 1 n ( d λ ) j + 1 h o e
where n is the number of homogenous layers in the wall, d is their thickness (in m), hoi = 7.7 W/(m2·K) and hoe = 25 W/(m2·K) are respectively the inside and the outside overall surface heat transfer coefficients (ISO 6946 [33]), and Rgap is the thermal resistance for an air gap possibly included in the wall stratigraphy. Being the inverse value of the overall thermal resistance, the U-value of an outside wall should be as low as possible, in order to reduce the conductive heat losses under steady conditions.
On the other hand, a cyclic temperature excitation acting on the outer side of a wall induces the release of cyclic heat flux into the indoor environment. In this case, it is possible to define the periodic thermal transmittance (YIE) as the ratio between the amplitude of the two cyclic functions describing the heat flux and the temperature excitation, respectively. The calculation of the periodic thermal transmittance involves the use of complex numbers and has to be performed according to the algorithms reported in ISO Standard 13786 [32]. A recent national regulation states that external walls in new buildings must have YIE < 0.10 W/(m2·K) [34].
The decrement factor is the ratio between the periodic and the steady thermal transmittance (fa = YIE/U). The lower it is, the higher the attitude of the wall to attenuate the amplitude of the periodic heat wave transferred in dynamic conditions.
The phase shift (φ) is the time lag between the peak outside temperature and the peak heat flux transferred indoors under periodic conditions; accordingly, the phase shift is measured in h. Walls with good dynamic thermal performance have a high phase shift (φ >10 h), whereas φ < 6 h means poor performance.
The internal areal heat capacity (κi) describes the ability of a wall to accumulate heat when a periodic heat wave acts on its inner side. A wall with high internal areal heat capacity has a high potential for accumulation, which helps to attenuate the indoor overheating produced by intense heat gains and to improve the indoor thermal comfort in summer. As an example, according to some studies, κi > 50 kJ/(m2·K) can be regarded as a good performance [35], while a recent Italian regulation [36] states that all new public buildings must have κi > 40 kJ/(m2·K). Finally, the surface mass (SM) is a simplified way to assess the capacity of a wall to accumulate heat:
S M = j = 1 n ( d j ρ j )
where d is the thickness of the layers in the wall and ρ is their density. According to Italian regulations, in new buildings, the surface mass of the opaque walls should be at least as high as 230 kg/m2, with the only exception being walls facing north [34]. The mass of the finishing layers (plaster) should not be included in Equation (4).
In order to calculate the steady and dynamic thermal parameters introduced above, the presence of timber and aluminum studs is neglected, because of their small contribution in terms of thermal resistance and thermal capacity: hence, the corresponding non-ventilated air gap is considered as fully homogenous. In addition, the measured thermal conductivity of straw bales is increased by a suitable factor, in order to take into account the effects of moisture and aging when the material is applied to real buildings [37], as detailed in Section 3.2. Table 1 shows the thermophysical parameters of the external walls, according to Figure 2. The only difference between the two walls under investigation is the insulating material. The properties of the straw are assessed in Section 3.1 and then used to determine the steady and dynamic thermal parameters of a straw bale wall in Section 3.2.

2.4. Sound Insulation: In Situ Measurement Campaign

2.4.1. Partition Apparent Sound Reduction Index

The measurement of the apparent sound reduction index for the partitions between two contiguous apartments was performed for both the EPS and straw bale walls, in compliance with ISO Standard 16283-1 [27]. The sound source was a directional loudspeaker fed with pink noise, while a condenser microphone connected to the sound level meter Solo 01-dB was used to measure the sound pressure levels (Figure 5).
Two positions were selected for the loudspeaker in the source room, close to the corners farthest from the partition under investigation and labeled L1 and L2 in Figure 6. Conversely, five fixed positions were selected for the microphone both in the source room (red color in Figure 6) and in the receiving room (green color in Figure 6). However, in the building with the partition wall insulated with EPS, only three microphone positions were used in the receiving room (Figure 6a). In fact, the room was small and equipped with some furniture; thus, no further positions could be added without breaking the minimum distances from the microphone to other surfaces, as described in ISO Standard 16283-1 [27].
In all cases, the height of the microphone above the ground was 1.5 m; the calibration of the microphone was verified through the calibrator 01-dB Cal 21 at the beginning and at the end of the measurement campaign. The evaluation of the apparent sound reduction index also implied the measurement of the reverberation time in the receiving room. This was done through the interrupted noise method by keeping a fixed position for the loudspeaker while changing the position of the microphone for a total of six measurements, which were eventually averaged.
All the relevant parameters were measured in octave bands from 125 to 2000 Hz. Furthermore, a preliminary check of the background noise level in both rooms showed that this was significantly lower than the sound pressure levels generated by the sound source.
The procedure implies—for each position j of the loudspeaker in the source room—the calculation of the energy average sound pressure level in the source room (Lp1) and in the receiving room (Lp2) by means of the condenser microphone connected to the sound level meter Solo 01-dB. The corresponding value of the apparent sound reduction index R′j was then calculated as:
R j = L p 1 L p 2 + 10 log ( S p A 2 ) = L p 1 L p 2 + 10 log ( T 2 S p 0.161 V 2 )
where Sp is the area of the partition wall, A2 is the sound absorption of the receiving room, T2 is the reverberation time of the receiving room, and V2 is the volume of the receiving room. It must be noted that Equation (5) provides a profile of five values—one for each octave band.
The apparent sound reduction index of the partition wall is the average of the two profiles determined by applying Equation (6) to the two positions of the loudspeaker (j = 1, 2):
R = 10 log ( 1 2 j = 1 2 10 R j 10 )
Finally, starting from the results of Equation (6), it was possible to achieve a single-number rating, called the weighted apparent sound reduction index (R′w), by means of the procedure detailed in ISO Standard 717-1 [36]. This procedure is based on the comparison between the experimental curve for R′ and a reference curve provided by the ISO standard.

2.4.2. Façade Sound Insulation

The measurement of the sound level difference for the blind façades of the two buildings was performed in compliance with the global method described in ISO Standard 16283-3 [28]. Specifically, the sound source was the same directional loudspeaker used to assess the partition apparent sound reduction index (Figure 5).
The loudspeaker should be placed outdoors at a distance of at least 5 m from the façade (Figure 7). The ISO standard also prescribes placing the loudspeaker with an angle of incidence equal to 45°; however, the presence of some hedges did not allow full compliance with this requirement, and the loudspeaker was positioned just in front of the façade.
The sound pressure level generated by the loudspeaker outdoors was measured twice in a single position, placed 2 m from the façade. Furthermore, five fixed positions of the microphone were used to measure the sound pressure level indoors (Figure 7).
In all cases, the height of the microphone above the ground was 1.5 m, and the calibration of the microphone was verified through the calibrator 01-dB Cal 21 at the beginning and at the end of the measurement campaign.
All the relevant parameters were measured in octave bands from 125 to 2000 Hz. Since the volume of the receiving rooms is higher than 25 m3, it was not necessary to extend the measures to the low frequencies (below 100 Hz), as reported by ISO Standard 16283-3 [28]. Furthermore, a preliminary check of the background noise in both rooms showed that this is significantly lower than the sound pressure levels generated by the sound source.
The procedure implies the calculation of the energy average sound pressure level in the outdoor position (L1,2m) and in the receiving room (L2) by means of the condenser microphone connected to the sound level meter Solo 01-dB. Then, the frequency profile of the standardized level difference (D2m,nT) was determined as:
D 2 m , n T = L 1 , 2 m L 2 + 10 log ( T 2 T 0 )
where T2 is the reverberation time of the receiving room and T0 = 0.5 s is a reference value.
Finally, starting from the results of Equation (7), which provided a profile of five values (one for each octave band), it was then possible to achieve a single-number rating, called the weighted standardized level difference (D2m,nt,w), through the procedure detailed in ISO Standard 717-1 [38].

2.4.3. Evaluation Criteria

In order to qualify the acoustic performance of partition walls and façades, based on the previously mentioned parameters (R′w, D2m,nt,w), suitable threshold values must be introduced.
To that end, it is necessary to remember that, in 1997, a national decree stated that all new residential buildings must have R′w ≥ 50 dB and D2m,nt,w ≥ 40 dB [39]. Moreover, the Italian Standard UNI 11367 [40] in 2010 introduced the possibility of performing the acoustic classification of dwellings on a voluntary basis. In order to classify the whole residential unit, it is first necessary to assign a rating to walls and façades, based on R′w and D2m,nt,w: the procedure implies a correction by −1 dB to the measured values, in order to account for uncertainty in the measurements. The threshold values for the rating procedure are reported in Table 2.

3. Results

3.1. Thermal Characterization of the Straw Bales

Table 3 summarizes wet and dry weight, initial water content, and density of the three straw specimens after the drying process and before introducing them into the heat flow meter to evaluate their thermal conductivity.
It is worth noting that the three samples show similar features, both in terms of density (close to 78 kg/m3) and initial water content (slightly more than 8%). These results highlight that the straw used, together with the specific manufacturing process, guarantees homogenous products that may be assumed to be representative for this type of straw bale coming from the Plain of Catania.
The samples were then introduced into the heat flow meter to measure the thermal conductivity of the dried straw. The tests were conducted by varying the temperatures of the two plates in the heat flow meter. The operating conditions and the values of the thermal conductivity for the three straw samples are summarized in Table 4.
The measurements show a good homogeneity for thermal conductivity, especially when looking at samples 1 and 2, whereas sample 3 exceeded the thermal conductivity of the other samples by 10–15%. Since Table 3 shows that the density of the dry material is similar among the samples, the thermal conductivity obtained for sample 3 can be explained by a different arrangement of the straw fibers or by the irregularity in the geometry.
Starting with the results in Table 4, the average thermal conductivity for each temperature range and the standard deviation were determined using Equations (1) and (2), respectively. The results are reported also in Table 4.
According to these results, the thermal conductivity for the dry straw bales is λ = 0.0573 ± 0.0036 W/(m·K). This result is in agreement with the values of thermal conductivity determined by Goodhew and Griffiths [12] and D’Alessandro et al. [21], that is to say, 0.062 W/(m·K) and 0.052 W/(m·K), respectively, for straw bales with a density of about 80 kg/m3.
Figure 8 shows the variation of the thermal conductivity with the temperature, as obtained from this study. The mathematical form chosen to describe this relationship is the exponential function: indeed, this is the form used in EN ISO 10456 to correlate the thermal conductivity of a material to its temperature. Equation (8) shows the exponential function that best approximates the experimental results, according to a best-fit procedure; the very high coefficient of determination (R2 = 0.9774) suggests an excellent fit of the equation to the experimental values.
λ ( T ) = 0.0534 e 0.0026 ( T T 0 )       ( T 0 = 0   ° C )

3.2. Steady and Dynamic Thermal Performance of the Walls

The results refer to both the insulation methods adopted in the buildings under investigation (straw bales and EPS), the thermal properties of which are listed in Table 5. Here, the thermal conductivity of straw bales was increased by 20%, starting from the value determined through the experiments described in Section 2.2, in order to take into account the effects of moisture and aging in real on-site installations. This percentage of increase is suggested by the Standard UNI 10351 [37] for natural materials such as straw. The specific heat of the straw bales is derived from [12] and refers to straw bales with similar features to those considered in this study.
The values of the parameters describing the steady and dynamic thermal performance of the walls, introduced in Section 2.3, are reported in Table 6.
It is possible to observe that both the insulating materials led to good steady thermal performance, as suggested by the low U-value. In fact, the national decree concerning the energy performance of buildings [34] indicates U = 0.29 W/(m2·K) as a reference value for the vertical walls of new buildings in climate zone D; hence, the straw bales only slightly improved on the reference value, whereas EPS reduced the U-value by around 50%.
The straw bale solution demonstrates just slightly better dynamic parameters. Indeed, it shows the same decrement factor (fa) and time shift (φ) as EPS, and slightly higher internal areal heat capacity (κi) and thermal mass. However, even with the straw bales, the dynamic parameters are far from indicating good summer performance for the opaque envelope. For example, as discussed in Section 2.3, φ = 2.5 h can be regarded as “poor”, while κi = 12.5 kJ/(m2·K) is much lower than the reference value reported in the literature, i.e., κi = 50 kJ/(m2·K). Finally, even the surface mass (SM = 58.7 kg/m2) is too low if compared with the threshold value for new buildings (SM >230 kg/m2), and the periodic thermal transmittance YIE = 0.267 W/(m2·K) is more than twice as high as the maximum value for new buildings, i.e., YIE = 0.10 W/(m2·K).
These outcomes suggest that a timber-framed wall including straw bales provides good thermal insulation, but the straw bales are not sufficient to ensure good thermal capacity. Therefore, summer overheating is likely to occur, especially in hot and sunny regions. The frequency and intensity of overheating can only be verified by means of dynamic thermal simulations on a building scale, which is not the topic of this paper.
However, the adoption of straw bales in passive buildings can still be possible by adding a massive layer on the inner side of the wall or by adopting suitable solutions to remove the solar radiation absorbed by the wall, such as green façades or shadings.

3.3. Sound Insulation Performance

3.3.1. Walls with Straw Bales as Insulation Material

Table 7 reports the values of the reverberation time measured in the receiving room for six different microphone positions. The results show a certain spatial variation for the reverberation time at low frequencies (125 Hz and 250 Hz), whereas the values are more uniform at high frequencies.
The average values are quite high considering the relatively low volume of the room, which may suggest a marked reverberating environment.
As far as the single-number ratings are concerned, they can be determined from Figure 9 by reading the value of the shifted reference curve at 500 Hz. The weighted apparent sound reduction index is R′w = 49 dB, whereas the weighted standardized level difference of the façade is D2m,nt,w = 43 dB. Hence, the apparent sound reduction index is just 1 dB below the minimum value imposed by DPCM 05/12/1997, while the standardized level index is 3 dB above the minimum threshold. According to the voluntary certification scheme introduced by UNI Standard 11367 [40], the acoustic performance of the straw bale façades can be rated as “good” after applying the correction (−1 dB); on the contrary, the partition walls showed only “poor” performance.
However, the cause of such a disappointing result was the adoption of finishing layers for the straw bales that were too lightweight. Indeed, an easy and effective strategy for significantly improving the weighted sound reduction index of the partition wall would be the application of two layers of plasterboard on both sides of the straw bales, for a total of 25 mm per side, instead of the single layer applied to the wall investigated in this study. This would allow for the doubling of the effective mass (from 9.5 kg/m2 to 19 kg/m2 per side), thus increasing the sound reduction index by around 6 dB and potentially shifting the rating to Class II (good).

3.3.2. Walls with EPS Insulation

Table 8 reports the reverberation time measured in the receiving room for six different microphone positions. In this case, the reverberation time was spatially uniform both at low and at high frequencies; the average values were quite low, due to the low volume of the room and to the presence of some furniture. The single-number ratings can be determined from Figure 10, by reading the value of the shifted reference curve at 500 Hz.
The weighted standardized level difference of the façade is D2m,nt,w = 42 dB, that is to say 2 dB above the minimum value allowed by DPCM 05/12/1997. This value is only slightly lower than for the straw bale façade, and according to UNI Standard 11367 [40], rates the façade as “good” (Class II). On the other hand, the weighted apparent sound reduction index is R′w = 39 dB: this is 10 dB worse than for straw bales, it is far below the minimum value allowed by DPCM 05/12/1997, and classifies the EPS partition wall as “bad” (no class). Even by applying two layers of plasterboard on both sides of the partition wall, thus increasing the effective mass from 9.5 kg/m2 to 19 kg/m2 per side, the acoustic performance would not improve to better than “poor” (R′w < 50 dB).

4. Discussion

Table 9 summarizes the thermal conductivity and the density of straw bales used as a construction material, as obtained by previous studies available in the literature.
While the thermal properties of industrialized insulating materials are by now reliable [43], Table 9 shows that the data regarding straw bales span a wide range of values. This variability is caused by the type of straw used, water content, bale density, size and quantity of air gaps inside and between the bales, orientation of the fibers, and presence of plaster between the bales. Therefore, designers find it difficult to identify the suitable value to be used in simulation software for thermal analysis: knowing the specific features of the local straw is a key issue to properly assess its thermal properties.
The thermal conductivity for the straw bales described in this paper is λ = 0.0573 ± 0.0036 W/(m·K) in dry conditions, with a density of about 78 kg/m3. D’Alessandro et al. [21] performed measurements on a straw bale sample with a density of 80 kg/m3, which resulted in thermal conductivity of 0.052 W/(m·K). Shea et al. [41] determined a thermal conductivity varying from 0.059 to 0.062 W/(m·K) for straw bales with a density between 63 and 123 kg/m3. Finally, Wei et al. [17] found out that high-density straw bales (250 kg/m3) have a thermal conductivity between 0.051 and 0.053 W/(m·K). This comparison shows that the thermal conductivity measured in this paper is close to the results found in the literature.
However, comparing the thermal conductivity from different studies is not straightforward, because this property depends on many issues. In particular, the thermal conductivity of the straw bales is influenced also by the arrangement of the stems inside the bale: tests carried out by the Danish Technological Institute on a 10 cm thick straw bale have obtained different thermal conductivity when measuring “on flat” (stems parallel to the heat flux), obtaining values of 0.57–0.60 W/(m·K), and “on edge” (stems perpendicular to the heat flux), obtaining values of 0.52–0.56 W/(m·K). Both of these ranges are very close to the thermal conductivity measured in this study. Specific studies should investigate the properties of the local straw in different world regions in order to provide suitable information for both designers and researchers interested in constructing straw bale buildings.
With respect to the weighted apparent sound reduction index of the partition wall made with the straw bales, the value found in this study is R′w = 49 dB. This is just 1 dB below the minimum value imposed by DPCM 05/12/1997 for new residential buildings; however, the application of two layers of plasterboard on both sides of the straw bales, instead of just a single layer, is sufficient to significantly increase R′w, thus complying with the decree. On the other hand, the standardized level difference (D2m,nT,w = 43 dB) already complies with the threshold introduced by DPCM 05/12/1997 for the façades.
Previous studies [26,44] have stated that the sound reduction index of different configurations of straw bale walls can range from 44 to 52 dB: therefore, the value found in this paper is within the range identified in the literature. The present study demonstrates that straw bales provide better acoustic insulation than traditional synthetic materials, such as EPS; however, further research should add more information about the acoustic performance of different straw bales in order to validate their acoustic properties and to eventually introduce them into the new material market as acoustic insulation.

5. Conclusions

According to the outcomes of this paper, the straw bales analyzed here can be effectively used as an insulating material in timber-framed constructions instead of more common materials such as EPS. The main results of the research are as follows:
  • The dry straw bales have an average thermal conductivity λ = 0.0573 W/(m·K), as shown by the laboratory tests, and their density is around 80 kg/m3.
  • The initial water content of the straw bales is above 8%; this suggests that, when addressing the calculation of the thermal properties of a wall insulated with these straw bales, their thermal conductivity should be appropriately increased. In this paper, the authors suggest an increase of 20%, that is to say, up to around 0.07 W/(m·K), based on the national regulations;
  • The timber-framed wall of the selected buildings, in which straw bales were sealed by two finishing layers of dry wall and faux-stone panels, show good steady thermal performance (U = 0.281 W/(m2·K)), which makes this insulation solution appropriate in cold climates but not in extreme or alpine regions, where the thickness should not be lower than 30 cm.
  • The dynamic thermal properties (periodic thermal transmittance, decrement factor, phase shift, internal areal heat capacity, and surface mass) turned out to be less satisfactory. For example, the phase shift is low (φ = 2.5 h), and the periodic thermal transmittance (YIE = 0.267 W/(m2·K)) is above the maximum threshold required by Italian regulations. An improvement in the dynamic thermal performance may be achieved by adding a massive layer on the inner side of the wall or by adopting suitable solutions to remove the solar radiation absorbed by the wall, such as green façades or shadings.
  • According to on-site measurements, the weighted apparent sound reduction index is R′w = 49 dB, whereas the weighted standardized level difference of the façade is D2m,nt,w = 43 dB. These results suggest sufficiently good sound insulation performance of the straw bales. In any case, the sound insulation provided by the straw bales is much higher than for a similar wall containing EPS in place of the straw bales.
All these results refer to straw bales with a relatively small thickness (20 cm) if compared to other straw-based products discussed in other research papers, which makes the results particularly interesting.
Further research should include a life-cycle assessment (LCA) to compare the environmental performance of straw bales and traditional thermal insulating materials (such as EPS) during the production phase, while also considering the operational phase and the need of maintenance. In fact, straw is a natural material that might be re-used after building demolition, for example, in agricultural fields, and this would be a further positive element favoring the use of this material in sustainable buildings.

Author Contributions

Conceptualization, G.E., G.S. and C.B.P.; methodology, S.C., G.E., A.G. and G.S.; investigation, C.B.P.; resources, G.E., A.G. and G.S.; data curation, G.E. and A.G.; writing—original draft preparation, S.C., G.E., A.G. and G.S.; writing—review and editing, S.C., G.E., A.G. and G.S.; visualization, S.C.

Funding

This research was funded by “the Notice 5/2016 for financing the Ph.D. regional grant in Sicily” as part of the Operational Program of European Social Funding 2014–2020 (PO FSE 2014–2020). This work was also financed by the University of Catania within the project “Piano della Ricerca Dipartimentale 2016–2018” of the Department of Civil Engineering and Architecture and the Department of Electric, Electronic and Computer Engineering.

Acknowledgments

The authors would like to thank Eng. Marco Riccioli for providing the straw bales and technical support.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Gellert, R. Inorganic mineral materials for insulation in buildings. Mater. Energy Effic. Therm. Comf. Build. 2010, 193–228. [Google Scholar] [CrossRef]
  2. Ruggieri, G.; Sabbadini, S.; Dotelli, G.; Meli, P. Environmental impacts of natural and conventional building materials: A case study on earth plasters. J. Clean. Prod. 2014, 80, 179–186. [Google Scholar]
  3. Rojas, C.; Cea, M.; Iriarte, A.; Valdés, G.; Navia, R.; Cárdenas-R, J.P. Thermal insulation materials based on agricultural residual wheat straw and corn husk biomass, for application in sustainable buildings. Sustain. Mater. Technol. 2019, 17, 102. [Google Scholar] [CrossRef]
  4. Ashour, T.; Korjenic, A.; Korjenic, S.; Wu, W. Thermal conductivity of unfired earth bricks reinforced by agricultural wastes with cement and gypsum. Energy Build. 2015, 104, 139–146. [Google Scholar] [CrossRef]
  5. Sow, D.; Chafadine, M.A.; Gaye, S.; Adj, M.; Cisse, I.K. Integration of agricultural waste in local building materials for their exploitation: Application with rice straw. Res. J. Appl. Sci. Eng. Technol. 2014, 7, 3030–3035. [Google Scholar] [CrossRef]
  6. Belakroum, R.; Gherfi, A.; Kadja, M.; Maalouf, C.; Lachi, M.; El Wakil, N.; Mai, T.H. Design and properties of a new sustainable construction material based on date palm fibers and lime. Constr. Build. Mater. 2018, 184, 330–343. [Google Scholar] [CrossRef]
  7. Liuzzi, S.; Rubino, C.; Stefanizzi, P.; Petrella, A.; Boghetich, A.; Casavola, C.; Pappalettera, G. Hygrothermal properties of clayey plasters with olive fibers. Constr. Build. Mater. 2018, 158, 24–32. [Google Scholar] [CrossRef]
  8. Khedari, J.; Charoenvai, S.; Hirunlabh, J. New insulating particleboards from durian peel and coconut coir. Build. Environ. 2003, 38, 435–441. [Google Scholar] [CrossRef]
  9. Yin, X.; Lawrence, M.; Maskell, D. Straw bale construction in northern China—Analysis of existing practices and recommendations for future development. J. Build. Eng. 2018, 18, 408–417. [Google Scholar] [CrossRef]
  10. Sodagar, B.; Rai, D.; Jones, B.; Wihan, J.; Fieldson, R. The carbon-reduction potential of straw-bale housing. Build. Res. Inf. 2011, 39, 51–65. [Google Scholar] [CrossRef] [Green Version]
  11. González, A.D. Energy and carbon embodied in straw and clay wall blocks produced locally in the Andean Patagonia. Energy Build. 2014, 70, 15–22. [Google Scholar] [CrossRef]
  12. Goodhew, S.; Griffiths, R. Sustainable earth walls to meet the building regulations. Energy Build. 2005, 37, 451–459. [Google Scholar] [CrossRef]
  13. Thomson, A.; Walker, P. Durability characteristics of straw bales in building envelopes. Constr. Build. Mater. 2014, 68, 135–141. [Google Scholar] [CrossRef] [Green Version]
  14. Yin, X.; Lawrence, M.; Maskell, D.; Ansell, M. Comparative micro-structure and sorption isotherms of rice straw and wheat straw. Energy Build. 2018, 173, 11–18. [Google Scholar] [CrossRef]
  15. Lawrence, M.; Heath, A.; Walker, P. Determining moisture levels in straw bale construction. Constr. Build. Mater. 2009, 23, 2763–2768. [Google Scholar] [CrossRef] [Green Version]
  16. Cascone, S.; Rapisarda, R.; Cascone, D. Physical Properties of Straw Bales as a Construction Material: A Review. Sustainability 2019, 11, 3388. [Google Scholar] [CrossRef]
  17. Wei, K.; Lv, C.; Chen, M.; Zhou, X.; Dai, Z.; Shen, D. Development and performance evaluation of a new thermal insulation material from rice straw using high frequency hot-pressing. Energy Build. 2015, 87, 116–122. [Google Scholar] [CrossRef]
  18. Zhang, J.; Wang, J.; Guo, S.; Wei, B.; He, X.; Sun, J.; Shu, S. Study on heat transfer characteristics of straw block wall in solar greenhouse. Energy Build. 2017, 139, 91–100. [Google Scholar] [CrossRef]
  19. Gallegos-Ortega, R.; Magaña-Guzmán, T.; Reyes-López, J.A.; Romero-Hernández, M.S. Thermal behavior of a straw bale building from data obtained in situ. A case in Northwestern México. Build. Environ. 2017, 124, 336–341. [Google Scholar] [CrossRef]
  20. Cascone, S.; Catania, F.; Gagliano, A.; Sciuto, G. Energy performance and environmental and economic assessment of the platform frame system with compressed straw. Energy Build. 2018, 166, 83–92. [Google Scholar] [CrossRef]
  21. D’Alessandro, F.; Bianchi, F.; Baldinelli, G.; Rotili, A.; Schiavoni, S. Straw bale constructions: Laboratory, in field and numerical assessment of energy and environmental performance. J. Build. Eng. 2017, 11, 56–68. [Google Scholar] [CrossRef]
  22. Douglas, O.; Murphy, E. Source-based subjective responses to sleep disturbance from transportation noise. Environ. Int. 2016, 92, 450–456. [Google Scholar] [CrossRef] [PubMed]
  23. Gori, P.; Guattari, C.; Asdrubali, F.; De Lieto Vollaro, R.; Monti, A.; Ramaccia, D.; Bilotti, F.; Toscano, A. Sustainable Acoustic Metasurfaces for Sound Control. Sustainability 2016, 8, 107. [Google Scholar] [CrossRef]
  24. Danihelová, A.; Nemec, M.; Gergel, T.; Gejdoš, M.; Gordanová, J.; Scensny, P. Usage of Recycled Technical Textiles as Thermal Insulation and an Acoustic Absorber. Sustainability 2019, 11, 2968. [Google Scholar] [CrossRef]
  25. Trabelsi, A.; Kammoun, Z. Experimental evaluation of acoustic characteristics of ball straw walls. Can. Acoust. 2018, 46, 49–57. [Google Scholar]
  26. Deverell, R.; Goodhew, S.; Griffiths, R.; De Wilde, P. The noise insulation properties of non-food-crop walling for schools and colleges: A case study. J. Build. Apprais. 2009, 5, 29–40. [Google Scholar] [CrossRef] [Green Version]
  27. ISO 16283-1. Airborne Sound Insulation; Acoustics—Field Measurement of Sound Insulation in Buildings and of Building Elements—Part 1; ISO: London, UK, 2014. [Google Scholar]
  28. ISO 16283-3. Façade Sound Insulation; Acoustics-Field Measurement of Sound Insulation in Buildings and of Building Elements—Part 3; ISO: London, UK, 2014. [Google Scholar]
  29. Distefano, D.; Gagliano, A.; Naboni, E.; Sapienza, V.; Timpanaro, N. Thermophysical characterization of a cardboard emergency kit-house. Math. Model. Eng. Probl. 2018, 5, 168–174. [Google Scholar] [CrossRef] [Green Version]
  30. EN 12667. Thermal Performance of Building Materials and Products. Determination of Thermal Resistance by Means of Guarded Hot Plate and Heat Flow Meter Methods—Products of High and Medium Thermal Resistance; UNI: Milan, Italy, 2001. [Google Scholar]
  31. EN ISO 10456. Building Materials and Products—Hygrothermal Properties—Tabulated Design Values and Procedure for Determining Declared and Design Thermal Values; ISO: London, UK, 2007. [Google Scholar]
  32. ISO 13786. Thermal Performance of Building Components—Dynamic Thermal Characteristics—Calculation Methods; ISO: London, UK, 2017. [Google Scholar]
  33. ISO 6946. Building Components and Building Elements—Thermal Resistance and Thermal Transmittance—Calculation Methods; ISO: London, UK, 2017. [Google Scholar]
  34. Decreto del Ministero dello Sviluppo Economico 26 Giugno; Italian Ministry of the Economic Development: Rome, Italy, 2015. (In Italian)
  35. Stazi, F.; Ulpiani, G.; Pergolini, M.; Di Perna, C. The role of areal heat capacity and decrement factor in case of hyper insulated buildings: An experimental study. Energy Build. 2018, 176, 310–324. [Google Scholar] [CrossRef]
  36. Criteri Ambientali Minimi per L’affidamento di Servizi di Progettazione e Lavori per la Nuova Costruzione, Ristrutturazione e Manutenzione di Edifici Pubblici; Italian Ministry of the Environment: Rome, Italy, 2017.
  37. UNI 10351. Materiali e Prodotti per Edilizia—Proprietà Termoigrometriche—Procedura per la Scelta dei Valori di Progetto; UNI: Milan, Italy, 2015. [Google Scholar]
  38. ISO 717-1. Airborne Sound Insulation; Acoustics—Rating of sound insulation in buildings and of building elements—Part 1; ISO: London, UK, 2013. [Google Scholar]
  39. D.P.C.M. Determinazione dei Requisiti Acustici Passivi Degli Edifici; Italian First Minister: Rome, Italy, 1997. (In Italian)
  40. UNI 11367. Acustica in Edilizia—Classificazione Acustica Delle Unità Immobiliari—Procedura di Valutazione e Verifica in Opera; UNI: Milan, Italy, 2010. [Google Scholar]
  41. Shea, A.; Wall, K.; Walker, P. Evaluation of the thermal performance of an innovative prefabricated natural plant fibre building system. Build. Serv. Eng. Res. Technol. 2013, 34, 369–380. [Google Scholar] [CrossRef]
  42. Douzane, O.; Promis, G.; Roucoult, J.M.; Tran Le, A.D.; Langlet, T. Hygrothermal performance of a straw bale building: In situ and laboratory investigations. J. Build. Eng. 2016, 8, 91–98. [Google Scholar] [CrossRef]
  43. Schiavoni, S.; Alessandro, F.D.; Bianchi, F.; Asdrubali, F. Insulation materials for the building sector: A review and comparative analysis. Renew. Sustain. Energy Rev. 2016, 62, 988–1011. [Google Scholar] [CrossRef]
  44. Wall, K.; Walker, P.; Gross, C.; White, C.; Mander, T. Development and testing of a prototype straw bale house. Proc. Inst. Civ. Eng. Constr. Mater. 2012, 165, 377–384. [Google Scholar] [CrossRef]
Figure 1. Location of the buildings insulated with expanded polystyrene (EPS; blue) and straw (red) walls in the residential complex.
Figure 1. Location of the buildings insulated with expanded polystyrene (EPS; blue) and straw (red) walls in the residential complex.
Sustainability 11 05592 g001
Figure 2. Internal view and the section of straw bale walls.
Figure 2. Internal view and the section of straw bale walls.
Sustainability 11 05592 g002
Figure 3. Operation scheme and picture of the NETZSCH HFM Lambda heat flow meter.
Figure 3. Operation scheme and picture of the NETZSCH HFM Lambda heat flow meter.
Sustainability 11 05592 g003
Figure 4. Specimen preparation and placement into the heat flow meter.
Figure 4. Specimen preparation and placement into the heat flow meter.
Sustainability 11 05592 g004
Figure 5. Left: Sound level meter Solo 01-dB with its condenser microphone and the calibrator Cal 21. Right: Directional loudspeaker.
Figure 5. Left: Sound level meter Solo 01-dB with its condenser microphone and the calibrator Cal 21. Right: Directional loudspeaker.
Sustainability 11 05592 g005
Figure 6. Plans of the measurement campaign for the apparent sound reduction index. (a) EPS partition wall; (b) straw bale partition wall (x = position of the microphone; L = position of the loudspeaker).
Figure 6. Plans of the measurement campaign for the apparent sound reduction index. (a) EPS partition wall; (b) straw bale partition wall (x = position of the microphone; L = position of the loudspeaker).
Sustainability 11 05592 g006
Figure 7. Plans of the measurement campaign for the façade sound difference. (a) Façade with EPS; (b) Façade with straw bales (x = position of the microphone; L = position of the loudspeaker).
Figure 7. Plans of the measurement campaign for the façade sound difference. (a) Façade with EPS; (b) Façade with straw bales (x = position of the microphone; L = position of the loudspeaker).
Sustainability 11 05592 g007
Figure 8. Relation between thermal conductivity and temperature.
Figure 8. Relation between thermal conductivity and temperature.
Sustainability 11 05592 g008
Figure 9. Determination of the single-number rating from the experimental results for the straw bale walls: (a) apparent sound reduction index; (b) façade sound level difference.
Figure 9. Determination of the single-number rating from the experimental results for the straw bale walls: (a) apparent sound reduction index; (b) façade sound level difference.
Sustainability 11 05592 g009
Figure 10. Determination of the single-number rating from the experimental results for the EPS walls: (a) apparent sound reduction index; (b) façade sound level difference.
Figure 10. Determination of the single-number rating from the experimental results for the EPS walls: (a) apparent sound reduction index; (b) façade sound level difference.
Sustainability 11 05592 g010
Table 1. Composition of the outside walls and corresponding thermal properties.
Table 1. Composition of the outside walls and corresponding thermal properties.
ThicknessThermal ConductivityDensitySpecific Heat
[cm][W/(m·K)][kg/m3][J/(kg·K)]
Plasterboard1.30.217301000
Air gap2.7(Rgap = 0.18 m2·K/W)1.21000
Insulating material20.0VariableVariableVariable
Air gap2.0(Rgap = 0.18 m2·K/W)1.21000
Faux stone panels2.50.441370850
Table 2. Rating for the acoustic performance (UNI Standard 11367:2010 [40]).
Table 2. Rating for the acoustic performance (UNI Standard 11367:2010 [40]).
Class IClass IIClass IIIClass IVNo Class
(Excellent)(Good)(Average)(Poor)(Bad)
R′w≥56 dB≥53 dB≥50 dB≥45 dB<45 dB
D2m,nt,w≥43 dB≥40 dB≥37 dB≥32 dB<32 dB
Table 3. Results of the weighing process for the three dry samples.
Table 3. Results of the weighing process for the three dry samples.
SpecimenSizeWet WeightDry WeightInitial Water ContentDry Density
(cm)(gr)(gr)(gr)(%)(kg/m3)
125.0 × 22.0 × 7.88372340.631.48.4478.57
223.5 × 26.0 × 7.70400367.632.48.1078.17
326.5 × 24.0 × 8.00426392.833.28.4577.20
Table 4. Thermal conductivity measured by the heat flow meter (in W/(m·K)).
Table 4. Thermal conductivity measured by the heat flow meter (in W/(m·K)).
Specimen 1
Cold PlateHot PlateMean TemperatureTest 1.1Test 1.2Test 1.3
10 °C30 °C20 °C0.05560.05550.0553
15 °C35 °C25 °C0.05710.05630.0559
20 °C40 °C30 °C0.05750.05690.0563
25 °C45 °C35 °C0.05840.05730.0567
Specimen 2
Cold PlateHot PlateMean TemperatureTest 2.1Test 2.2Test 2.3
10 °C30 °C20 °C0.05430.05210.0520
15 °C35 °C25 °C0.05450.05230.0536
20 °C40 °C30 °C0.05500.05260.0534
25 °C45 °C35 °C0.05530.05310.0541
Specimen 3
Cold PlateHot PlateMean TemperatureTest 3.1Test 3.2Test 3.3
10 °C30 °C20 °C0.06120.05960.0593
15 °C35 °C25 °C0.06220.06110.0613
20 °C40 °C30 °C0.06350.06160.0620
25 °C45 °C35 °C0.06430.06300.0632
Average for Each Temperature Range
Cold PlateHot PlateMean TemperatureMean Value k(T)Standard Deviation σ (T)
10 °C30 °C20 °C0.05610.0031
15 °C35 °C25 °C0.05710.0034
20 °C40 °C30 °C0.05760.0037
25 °C45 °C35 °C0.05840.0039
Overall average0.05730.0036
Table 5. Properties of the insulating materials used in the study.
Table 5. Properties of the insulating materials used in the study.
ThicknessThermal ConductivityDensitySpecific Heat
[cm][W/(m·K)][kg/m−3][J/(kg·K)]
EPS200.041201400
Straw bale200.06978600
Table 6. Main thermal parameters of the walls: comparison between straw bale and EPS insulation.
Table 6. Main thermal parameters of the walls: comparison between straw bale and EPS insulation.
U-valuefaYIESMφκi
[W/(m2·K)][-][W/(m2·K)][kg/m2][hr][kJ/(m2·K)]
EPS0.1810.950.17246.52.411.8
Straw bale0.2810.950.26758.72.512.5
Reference (*)<0.29-<0.10>230>10>40
(*) See Section 2.3 for further details.
Table 7. Reverberation time(s) for the receiving environment for the straw bales (M = position number for the microphone).
Table 7. Reverberation time(s) for the receiving environment for the straw bales (M = position number for the microphone).
125 Hz250 Hz500 Hz1000 Hz2000 Hz
M10.621.181.701.461.63
M20.420.531.681.881.80
M30.560.861.842.031.78
M40.640.741.571.871.73
M50.410.401.791.931.91
M60.761.132.181.861.76
Average0.570.811.791.841.77
Table 8. Reverberation time(s) for the receiving environment for the EPS insulation (M = position number for the microphone).
Table 8. Reverberation time(s) for the receiving environment for the EPS insulation (M = position number for the microphone).
125 Hz250 Hz500 Hz1000 Hz2000 Hz
M10.410.410.570.630.52
M20.350.520.600.680.63
M30.330.410.660.630.64
M40.320.450.550.650.70
M50.400.430.590.610.54
M60.400.300.520.600.57
Average0.370.420.580.630.60
Table 9. Thermal conductivity (λ) and density (ρ) of straw bales provided by previous studies.
Table 9. Thermal conductivity (λ) and density (ρ) of straw bales provided by previous studies.
AuthorsYearRef.λ [W/(m·K)]ρ [kg/m3]
Goodhew and Griffiths [12]2005 0.07–0.0960–90
Shea et al. [41]2012 0.05963
0.06276.3
0.06287.4
0.064107
0.064114
0.065123
Wei et al. [17]2015 0.051–0.053250
Douzane et al. [42]2016 0.1080
D’Alessandro et al. [21]2017 0.05280
Zhang et al. [18]2017 0.074N/A
Gallegos-Ortega et al. [19]2017 0.094115
Cascone et al. [20]2018 0.06200
0.07250
0.075300
0.08350

Share and Cite

MDPI and ACS Style

Cascone, S.; Evola, G.; Gagliano, A.; Sciuto, G.; Baroetto Parisi, C. Laboratory and In-Situ Measurements for Thermal and Acoustic Performance of Straw Bales. Sustainability 2019, 11, 5592. https://doi.org/10.3390/su11205592

AMA Style

Cascone S, Evola G, Gagliano A, Sciuto G, Baroetto Parisi C. Laboratory and In-Situ Measurements for Thermal and Acoustic Performance of Straw Bales. Sustainability. 2019; 11(20):5592. https://doi.org/10.3390/su11205592

Chicago/Turabian Style

Cascone, Stefano, Gianpiero Evola, Antonio Gagliano, Gaetano Sciuto, and Chiara Baroetto Parisi. 2019. "Laboratory and In-Situ Measurements for Thermal and Acoustic Performance of Straw Bales" Sustainability 11, no. 20: 5592. https://doi.org/10.3390/su11205592

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop