4.1. Optimized Active Power–Voltage Sensitivity Calculation
To calculate the power sensitivity at a certain moment, the voltage of each node at that moment needs to be obtained. MATPOWER was used to calculate the voltage of each node at each moment in this scenario.
Figure 5 shows the node voltage waveforms for the first four scenarios of energy storage configuration, highlighting the impact of PV generation on the voltage distribution. In Scenario 2, which represents the days with the highest PV output, certain bus voltages exceeded the upper limit at midday due to reverse power flow from the distributed PV systems. Conversely, during the evening peak load period, voltages dropped below the lower limit, especially in Scenarios 3 and 4, where PV output was minimal. These voltage violations underscore the need for energy storage systems to mitigate overvoltage and undervoltage issues. The differences in the voltage profiles across the scenarios emphasize the importance of a multi-scenario optimization approach to ensure robust energy storage performance under varying PV and load conditions.
This study calculated the traditional active power–voltage using the standard IEEE 33-bus system. For the first time, the proposed method was applied to compute the upper and lower limit active power sensitivities, as illustrated in
Figure 6. The voltage sensitivity data in
Figure 6 have been normalized for clarity.
As shown in
Figure 6, the voltage sensitivity calculated by the proposed method was significantly higher than the traditional sensitivity near Node 30 for the upper voltage limit. This is because most photovoltaic systems in the improved IEEE 33-node system are connected near Node 30. The rapid increase in photovoltaic output at noon caused current reverse flow on the branch between Nodes 26 and 33, leading to voltage violations.
From the voltage violation analysis in
Figure 5, it is clear that the nodes exceeding the upper voltage limit were all located on the branch between Nodes 26 and 33. According to the IEEE 33-node topology, Nodes 26–33 were influenced by the voltage at Node 6. Assuming the grid as an infinite power source, the voltage at Node 6 was affected by the power flow through Nodes 2–5.
The power changes in Nodes 7–18 and Nodes 26–33 had similar effects on the voltage at Node 6. However, power fluctuations on the branch between Nodes 26 and 33 directly influenced the voltages at these nodes due to their inherent impedance. This unique characteristic was absent in other nodes not on the 26–33 branch.
Therefore, the sensitivity to voltage upper limit violations was naturally higher for Nodes 26–33, as confirmed in
Figure 6. The proposed method fully considers the voltage regulation needs of violation-prone nodes and selects nodes with significant impacts. The same logic applies to the lower voltage limit sensitivity, which traditional methods cannot achieve. After one calculation, Nodes 15, 16, 17, 18, 30, 31, 32, and 33 were identified as candidate nodes for further analysis.
Verification using Equations (10) and (11) showed that the nodes selected for over-limit voltage sensitivity met the requirements, while those for under-limit voltage sensitivity required optimization, prompting a secondary calculation, as illustrated below:
As shown in the
Figure 7, the power changes at Nodes 16, 17, and 18 still significantly affected the lower voltage limit violations across the system after modification. However, their impact was noticeably reduced compared to before the voltage correction. This is because the voltages of the nodes sensitive to their power changes were adjusted. The presence of the remaining voltage violations suggests that these nodes were less affected by the power changes at Nodes 16, 17, and 18. Therefore, it was necessary to continue identifying the nodes with high sensitivity to these violations as potential candidates for energy storage.
On the other hand, the voltage sensitivity near Node 33 increased rapidly after the modification. This indicates that the voltages of some nodes remained low even after correcting the nodes most affected by Node 18. These nodes were more sensitive to the power changes at Nodes 33, 32, and 31. Thus, Nodes 33, 32, and 31 were selected as candidate nodes in this step.
Considering both the upper and lower voltage limit sensitivities, Nodes 15, 16, 17, 18, 30, 31, 32, and 33 were identified as the final candidate nodes for further analysis.
4.2. Analysis of Comparison Results of Energy Storage Optimization Configuration Plans
From the improved over-limit and under-limit voltage sensitivity analyses, the top four nodes with the highest sensitivity values were selected as the candidate nodes for energy storage integration. These nodes were incorporated into a bi-level optimization model for energy storage configuration, yielding the optimal energy storage allocation results, as shown in the
Table 3:
Table 3 compares the energy storage configuration strategies based on the improved voltage sensitivity method and the traditional voltage sensitivity method. The improved method identified Nodes 18, 32, and 33 as the optimal access points, with capacities of 4770 kWh, 2610 kWh, and 2180 kWh, and power ratings of 370 kW, 190 kW, and 220 kW, respectively. In contrast, the traditional method selected Nodes 11, 12, and 17, with capacities of 5580 kWh, 4700 kWh, and 5080 kWh, and power ratings of 600 kW, 470 kW, and 520 kW. The results demonstrate that the improved method, by precisely targeting nodes with high voltage sensitivity, not only ensured effective voltage regulation across diverse operational scenarios but also minimized the scale and complexity of the energy storage system, offering a more efficient and cost-effective solution.
Table 4 and
Table 5 provide a comparative analysis of the performance of energy storage systems using improved active voltage sensitivity and traditional sensitivity across four distinct scenarios. The results demonstrate the economic and operational advantages of the improved active voltage sensitivity method over the traditional sensitivity approach.
In this study, the waveforms in Scenarios 2 and 4 are presented in detail because they determine the maximum power and capacity requirements of the energy storage system, respectively. Scenario 2, with the highest PV output, requires maximum power to mitigate overvoltage conditions, while Scenario 4, with the lowest PV output, requires maximum capacity to address undervoltage conditions. This ensures that the storage system is robust across all scenarios. Although Scenarios 1 and 3 were used in the optimization process, they are not shown in detail as they do not impose extreme system requirements.
The actions and SOC of the energy storage device in Scenario 2 are shown in
Figure 8. Among them, P1, P2, and P3 represent the power of Energy Storage 1, Energy Storage 2, and Energy Storage 3, respectively, while SOC1, SOC2, and SOC3 represent the state of charge (SOC) of Energy Storage 1, Energy Storage 2, and Energy Storage 3, respectively.
Figure 8 and
Table 3 show that all three energy storage systems absorbed power at their maximum rated capacity during the peak photovoltaic generation period at noon. This maintained the system voltage just below the upper limit. A similar pattern was observed during the evening load peak period.
This demonstrates that the configured energy storage power at each node represents the minimum rated power required to prevent voltage limit violations. Thus, the optimal configuration achieves both voltage quality assurance and cost minimization for energy storage power.
The actions and SOC of the energy storage devices in Scenario 4 are shown in
Figure 9.
In Scenario 4, the photovoltaic system maintained a low power output all day. As shown in
Figure 5, the voltage distribution at various times indicates that all node voltages in the distribution network remained below the rated voltage of 12.66 kV.
To address voltage deviation and reduce line losses, the energy storage system should actively output active power. This elevates the distribution network voltage level and minimizes active power transmission from the front end to the terminal, effectively reducing line losses.
Figure 9 illustrates the operational status of the energy storage system, fully validating this conclusion.
This paper set the per-unit value range for voltage fluctuation at 0.95–1.05. Through the optimal configuration of the energy storage system, the simulation results, as shown in
Table 6 and
Figure 10, demonstrate the voltage distribution at each node across four typical scenarios. With the effective regulation of the energy storage system, the voltage of all nodes in the distribution network was precisely controlled within the specified range, completely eliminating voltage violation incidents.
In the traditional active voltage sensitivity approach, Nodes 11–18, with larger values, were selected as candidate nodes for energy storage access and incorporated into the bi-level optimization of energy storage configuration. The resulting energy storage configuration Scheme 2 is shown in
Table 3.
The actions and SOC of the energy storage device in Scenario 2 are shown in
Figure 11.
In
Figure 11, it can be observed that energy storage configuration Scheme 2 operated at maximum power output during the peak load period from 21:00 to 22:00 in Scenario 2, successfully regulating the voltage within the specified range. This behavior is similar to Scheme 1. However, by comparing
Figure 11 with
Figure 8, it is evident that Scheme 2 required the energy storage system to deliver more power to the grid to maintain the node voltages above the minimum allowable level.
While Nodes 11–18 had a significant overall impact on the distribution network voltage, the analysis of
Figure 7 reveals that certain nodes were less influenced by them but more affected by the power variations near Node 33. When the voltages of these nodes dropped below the lower limit, the energy storage devices at Nodes 11–18 had to exert more effort to raise the voltages to the required range.
Through the revised voltage sensitivity calculation proposed in this study, it was accurately identified that Nodes 30–33 had a substantial influence on the voltages at these nodes. By configuring the energy storage at Nodes 30–33, voltage regulation could be achieved with less power. The same principle applies when the voltage at Node 33 and its neighboring nodes exceeds the upper limit. Consequently, Scheme 2 demands energy storage devices with greater power and capacity, resulting in higher construction costs.
The integrated network loss of the system at each moment before and after the configuration of energy storage was calculated by Equation (17), as shown in
Figure 12.
In
Figure 12, it can be observed that the line losses in the distribution network were reduced after implementing energy storage Schemes 1 and 2. Between 0:00 and 10:00, the line losses for both schemes were similar. However, significant differences emerged during the midday and evening periods.
At midday, when the photovoltaic output was at its peak, there was a high demand for voltage regulation to prevent exceeding the upper limit. Traditional Scheme 1, which did not account for this need, required energy storage to draw more power from the grid to maintain voltage stability. This increased the current flowing to the storage devices, resulting in higher line losses compared to Scheme 2.
In the evening, the demand for voltage regulation to prevent dropping below the lower limit was substantial. Scheme 1, constrained by cost considerations, could not excessively increase the storage capacity to minimize line losses. In contrast, Scheme 2, with its larger capacity and power due to strategic placement, effectively reduced line losses during this period. Additionally, its location on the branch of Nodes 1–18, where line losses were the highest, further enhanced its effectiveness. Consequently, Scheme 2 exhibited lower line losses in the evening compared to Scheme 1.