2.1.1. Characteristics of Bifacial PV Modules and VPV Systems
Bifacial PV modules use a transparent backsheet or glass on the rear side to capture light reflected from the ground, increasing power generation by >5% compared with conventional monofacial modules. This enhancement is governed by Equation (1).
Here, denotes the total power generation (W); denotes the conversion efficiency of the module (%); denotes the effective area of the module (m2); and denote the rear and front incident radiation (W/m2), respectively; and is the bifaciality factor of the bifacial module.
In a VPV system, bifacial modules can be installed upright, with the front and rear sides facing east and west, respectively, altering the temporal distribution of power output by shifting peak generation to the morning and late afternoon hours. This mitigates midday overgeneration—commonly associated with curtailment in conventional PV systems—by aligning generation more closely with load demand and reducing reverse power flow. As a result, VPV systems contribute to a more balanced power profile, alleviating curtailment without the need for additional energy storage or control infrastructure. Bifacial VPV systems are typically cost-effective in regions above 40° latitude but may also be economically viable in areas below 40° if the ground reflectance (albedo) is higher than usual [
17].
2.1.2. Functions and Characteristics of Smart Inverter-Based ESS
The primary function of an ESS is to balance power supply and demand using three control algorithms. The first stabilizes renewable-energy outputs through power smoothing. The second regulates frequency, ensuring grid stability. The third involves energy time-shifting and peak load reduction, storing energy during off-peak hours and discharging it during peak periods [
18].
In modern distribution grids, voltage–reactive power (Volt-Var) control is essential to address the voltage rise caused by reverse power flow from grid-connected PV systems. In South Korea, regulations require that all new distributed generation (DG) systems be equipped with smart inverters. These inverters provide four-quadrant active/reactive power compensation, frequency and voltage support, parallel operation, unbalanced load compensation, and enhanced grid stability. The present study focuses on Volt-Var control, which is critical for mitigating voltage fluctuations in distribution grids.
In this study, the voltage control capability of the ESS was analyzed without considering the operation of the on-load tap changer, which is typically used to regulate transformer voltage. This exclusion is based on the fundamental difference in control scope: on-load tap changers are installed at the main transformer and operate by adjusting the voltage level of all DLs connected to the main transformer simultaneously. In contrast, the proposed method focuses on localized voltage regulation at the individual DL level.
South Korea’s DG interconnection standards specify a ramp-up control characteristic curve for smart inverter-based Volt-Var control, as shown in
Figure 1. This curve ensures gradual reactive power changes within predefined limits to maintain grid stability. The relationship between reactive power and voltage at the point of common coupling (PCC) is expressed in Equation (2). If the PCC voltage drops below a threshold, reactive power is injected to boost the voltage; if the voltage exceeds the set point, reactive power is absorbed to reduce the voltage rise. Smart inverter-based ESS, through such controls, stabilizes and enhances grid reliability.
This performance curve and equation are illustrated using DG interconnection standards in
Figure 2a. As the voltage increases from 1.02 to 1.08 p.u., the smart inverter absorbs reactive power at a constant slope, whereas between 0.98 and 0.92 p.u., it supplies reactive power.
Additionally, this curve can be adjusted in consultation with the system operator. A simulation was conducted with a more aggressive step-up control strategy, shown in
Figure 2b. In contrast to the constant slope, this strategy features a steeper reactive power response, with charging and discharging occurring more abruptly at the same initiation points of 1.02 and 0.98 p.u., respectively [
19].
However, in the case of the step-up method, if applied to special line conditions where voltage fluctuations are repeated within a specific range, the reactive power output may change rapidly, which may cause problems with system stability. In addition, care must be taken because a large number of distributed power sources may lead to synchronized switching, which may result in large-scale dropouts in the worst case.
2.1.3. Effect of PV-System Interconnection on DL Voltage Rise
PV systems are commonly installed at the ends of DLs to reduce land costs. However, they can introduce reverse currents, causing voltage rise and power quality issues in the distribution grid. The effect of PV generation on the distribution voltage can be quantified as follows [
20]:
where
represents the voltage variation in the DL,
denotes the impedance between the PV system and DL, and
denotes the current generated by the PV system.
Additionally,
and
denote the active and reactive power outputs of the PV system, respectively, while
denotes its bus voltage.
Equation (5) follows from Equations (3) and (4), illustrating how the PV system’s power influences voltage variations in the distribution grid. These variations can be decomposed into d-axis (active) and q-axis (reactive) components, with the total voltage change expressed as
Here,
denotes the overall distribution system voltage. Because the
d-axis voltage is significantly larger than the
q-axis voltage, the latter can be neglected. Thus, Equation (6) simplifies to
in vector form. As shown in
Figure 3, this results in the receiving voltage (
Vr) on the load side exceeding the sending voltage (
Vs) from the substation.
2.1.4. Operational Data for East–West-Oriented VPV Systems
We used operational data collected throughout 2023, originally recorded at 1 min intervals but analyzed using hourly averages. The data for an hour, such as 7:00, represent the average of the values recorded during the preceding hour (i.e., from 6:00 to 7:00).
Figure 4 presents box plots of the maximum hourly generation peaks for a month, focusing on systems with east- and west-facing modules. A statistical analysis of hourly VPV power generation, visualized through box-and-whisker plots, reveals notable diurnal patterns in output variability. During the morning period (up to approximately 11:00 a.m.), power generation steadily increases, accompanied by moderate variability attributed to changing solar irradiance angles and atmospheric conditions.
In contrast, the midday interval (12:00–14:00) demonstrates relatively low and stable power output with minimal variability. This pattern is characteristic of vertically mounted or east–west-oriented PV modules operating under suboptimal solar angles, resulting in limited irradiance during this period.
The late afternoon hours (15:00–17:00) exhibit the highest average generation levels along with increased variability, indicating greater sensitivity to environmental fluctuations and seasonal solar paths.
Overall, standard deviation in PV output—closely associated with variability—remains relatively low between 10:00 and 16:00, while significantly increasing during the early morning and late evening hours, particularly around sunrise and sunset.
Table 1 presents the maximum power generation outputs for each period based on the operational data. These values reflect the generation output pattern from the highest recorded values in the annual dataset for each time zone.
The peak generation of the VPV system was lower than its installed capacity owing to the physical characteristics of vertically mounted solar modules, which limit optimal solar radiation absorption.
To account for potential voltage rise in the distribution grid from high PV-generation output, a conservative approach was adopted by simulating the worst-case generation pattern, defined by the highest peak output in each timeslot. Because this does not represent continuous generation throughout the day, results should be interpreted carefully. The peak power generation of vertically mounted PV modules facing east and west was approximately 88% of the installed capacity. The data were obtained from bifacial PV modules (460 W) on the testbed. The module specifications are presented in
Table 2. The orientation reversal between the front and rear sides of the PV modules resulted in negligible differences in both overall energy yield and peak power generation [
22].