Next Article in Journal
Comparative Analysis of Performance and Emission Characteristics of Biodiesels from Animal Fats and Vegetable Oils as Fuel for Common Rail Engines
Next Article in Special Issue
Influence of the Skin and Proximity Effects on the Thermal Field in Flat and Trefoil Three-Phase Systems with Round Conductors
Previous Article in Journal
A Detection Method for Slight Inter-Turn Short-Circuit Fault in Dry-Type Air-Core Shunt Reactors
Previous Article in Special Issue
Data-Driven Techniques for Short-Term Electricity Price Forecasting through Novel Deep Learning Approaches with Attention Mechanisms
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Mathematical Model of a Nonlinear Power Transformer for Needs of Relay Protection

by
Evgeniy Kolesnikov
1,*,
Aleksandr Novozhilov
1,
Dilara Rakhimberdinova
1,
Aleksandr Kislov
1 and
Timofey Novozhilov
2
1
Electrical Engineering and Automation Department, Toraighyrov University, Lomov Str., 64, Pavlodar 140008, Kazakhstan
2
Department of Power Supply of Industrial Enterprises, Omsk State Technical University, Mira av., 11, Omsk 644050, Russia
*
Author to whom correspondence should be addressed.
Energies 2024, 17(7), 1710; https://doi.org/10.3390/en17071710
Submission received: 7 February 2024 / Revised: 23 March 2024 / Accepted: 25 March 2024 / Published: 3 April 2024
(This article belongs to the Special Issue Energy, Electrical and Power Engineering 2024)

Abstract

:
In this work, a mathematical model of a three-phase nonlinear transformer is suggested. The model enables simulating the transformer operation with allowance for its nonlinearity and covers needs of the relay protection. Our model has been developed on the basis of a mathematical model with phase coordinates, where differential equations are composed by the Kirchhoff’s phase-voltage law. Based on this model, we first compose a mathematical model for simulating steady-state operation modes of a transformer, taking into account the asymmetry and nonlinearity of its ferromagnetic core. In this model, the initial values of inductances and mutual inductances of loops are determined from the main phase inductance calculated by the experimentally found no-load current, and their current values are determined from the currents in windings and the magnetic fluxes in legs of the transformer core. The magnetic fluxes are calculated by the nodal-pair method. This improved mathematical model is verified through a comparison between the calculated harmonic components of the phase currents and the experimental results. The harmonic components are calculated with the use of Fourier expansion of the calculated phase currents. Their experimental values are determined with a spectrum analyzer. The calculated and experimental harmonic components of the currents of phase A during no-load and rated-load operation of the transformer are tabulated. The comparison of these results shows that the mathematical model of a three-phase transformer we suggest makes it possible to simulate currents in transformer windings under steady-state operation modes with accuracy acceptable for relay protection.

1. Introduction

A great number of power transformers are used in electric power systems to convert one voltage class to another. For example, about 461,864 substations are equipped with them in Russia [1]. Three-phase two-winding asymmetrical transformers are most often used for these purposes due to their high performance.
World practice in operating three-phase transformers has shown turn-to-turn faults to be among the most common short circuits in them. According to [1,2], they are up to 70–80% of all transformer failures depending on the power and operating conditions.
One of the main ways of decreasing the statistics of failures and extending the service life of transformers is the use of relay protection devices based on current transformers [3,4,5] and nonconventional high-sensitive protection devices based on inductive measuring transducers [2,6]. Such devices can be improved, in particular, their sensitivity to turn-to-turn faults can be increased, by means of receiving information about characteristic features of currents in the transformer windings in the form of the spectrum of harmonic components of the currents during transformer operation. This is especially important for choosing the response threshold of relay protection devices, the operation of which is based on the differential principle, which consists of comparing two electrical quantities with different spectra. Both currents in the transformer windings [3,4,5] and their magnetic leakage fluxes [2,6] can be used as compared parameters.
The experimental way of acquiring this information is the easiest. For this, necessary measurements are made during the operation of a three-phase power transformer. However, the comprehensive study of a transformer during its operation is not always possible. For example, currents in the secondary windings attain 150 kA in ore furnace transformers; therefore, current transformers are not installed on them, and currents in the load circuit cannot be measured. Hence, a mathematical simulation is more convenient.
Many mathematical models of transformers have been developed by now for different purposes. Most of these models are reviewed in [7,8]. Some of them are intended for the description of the current transformer operation [9]. The model in [10] is used for simulating transient processes in a single-phase transformer. The authors of work [11] suggested using the finite different method for simulating transient processes in network transformers, thus increasing computational costs and requiring an external circuit interface. Reference [12] suggests an equivalent scheme for determining multiwinding transformer-leakage inductances. The mathematical model proposed by [13] enables the simulation of three-phase saturating transformers. An equivalent scheme for the real-time simulation of nonlinear power transformers was developed in detail in [14]. However, the models of [12,13,14] require a significant amount of initial data, thus making these models unsuitable for practical purposes, in particular, when these data should be received from working transformers. Moreover, output of certain models cannot be used to implement relay protection. Thus, to estimate capabilities of known mathematical models in terms of their suitability for use in relay protection, for example, for choosing the differential protection response threshold, one should analyze the purpose of a model, the required transformer modeling mode, the ease of acquiring the initial data for modeling, and results of protection device modeling. Considering all of these points, the quite well-known mathematical model of a three-phase transformer suggested by P. Bastard et al. [8] for analyzing the processes occurring in the transformer is apparently the most suitable.
This model is based on ElectroMagnetic Transient Program (EMTP-RV4.1) software with BCTRAN package. The BCTRAN package describes a transformer based on data received in different tests. For a three-phase two-winding transformer, BCTRAN computes two sixth-order matrices. One of them is the matrix of resistances of the transformer windings, and another is the matrix of the self-inductances of these windings. However, the use of EMTP hampers comprehension of the model and limits access to internal variables (magnetic couplings) for their analysis—the more so since these couplings are complex.
Reference [15] shows that the operation of a three-phase transformer can be described without EMTP, but with any other computing software, for example, MATLAB v6.5.
According to [16], the process of energy conversion in three-phase power transformers is most fully described by a quite simple and easily understandable mathematical model with phase coordinates. In this model, the operation of a three-phase two-winding transformer is described by only four differential equations [17]. These differential equations are compiled by the loop current method [18,19] for phase-to-phase voltages. This mathematical model can be implemented not only in a MATLAB environment, but also in Turbo Basic [20].
However, this mathematical model does not take into account the nonlinearity of parameters of the magnetic core of a transformer. Self-inductances and mutual inductances are calculated in the differential equations of the mathematical model in a simplified form, neglecting transformer core design features. All of these shortcomings reduce the simulation accuracy and do not enable one to sufficiently and accurately determine the response threshold of, e.g., high-sensitive turn-to-turn fault protections based on built-in inductive measuring transducers [2,6].
To get rid of these shortcomings, the mathematical model presented in [17] as a set of differential equations is transformed into a mathematical model described by a set of linear equations. When simulating steady-state load operation modes of a transformer in this model, the duration of a mode under study is divided into time intervals within which the transformer parameters are considered constant. The initial values of inductances and mutual inductances in the mathematical model are determined using the main inductance of a transformer phase and the ratios of magnetic fluxes in the core legs during the no-load operation of the transformer. The current values of these parameters are calculated from the currents in the windings and magnetic fluxes in the legs of the core of this transformer.

2. Mathematical Model of a Transformer

The mathematical model of a transformer [17], represented as a set of differential equations, is transformed into a mathematical model described by a set of linear equations, taking into account the diagram of the core (Figure 1) and the electric circuit of the transformer (Figure 2).
In Figure 1, uA, uB, and uC (ua, ub, and uc) are the instantaneous values of phase voltages in the primary (secondary) windings of phases A, B, and C (a, b, and c); iA, iB, and iC (ia, ib, and ic) are the instantaneous values of currents in the primary (secondary) windings of phases A, B, and C (a, b, and c); wA, wB, and wC (wa, wb, and wc) are the numbers of turns in the primary (secondary) windings of phases A, B, and C (a, b, and c), w A = w B = w C = w 1 and w a = w b = w c = w 2 ; ϕA, ϕB, and ϕc are the magnetic fluxes in the legs of phases A, B, and C of the core; ϕN is the magnetic leakage flux.
For the experimental estimation of the simulation error, an experimental 6.0 kVA TT-6-type transformer is used; its parameters are given in Table 1.
In Figure 2, i 1 i 4 are the instantaneous values of currents in the 1st–4th loops; R A , R B , R C , and R a , R b , R c are the active resistances of the primary and secondary windings of the transformer equal to R1 and R2, respectively; Rla, Rlb, and Rlc are the active resistances of the transformer phase loads.
If the voltages are considered sinusoidal in the mathematical model [17], then the operator of differentiation, d / dt , in its equations can be changed to the expression j ω with allowance given [15]. In this case, the set of equations of this mathematical model is transformed into the set
u AB = i 1 ( R A + R B ) i 2 R B + u x 1 ; u BC = ( i 2 i 1 ) R B + i 2 R C + u x 2 ; 0 = i 3 ( R a + R b + R la + R lb ) i 4 ( R b + R lb ) + u x 3 ; 0 = ( i 4 i 3 ) ( R b + R lb ) + i 4 ( R c + R l c ) + u x 4 ,
where u A B and u B C are the instantaneous values of the linear voltages of phases A, B, and C; and u x 1 u x 4 are the voltage drops across the inductive resistances and the mutual inductive resistances of the 1st–4th loops:
u x 1 = j i 1 X 11 + j i 2 X 12 + j i 3 X 13 + j i 4 X 14 ;
u x 2 = j i 1 X 21 + j i 2 X 22 + j i 3 X 23 + j i 4 X 24 ;
u x 3 = j i 1 X 31 + j i 2 X 32 + j i 3 ( X la + X lb + X 33 ) + j i 4 ( X lb + X 34 ) ;
u x 4 = j i 1 X 41 + j i 2 X 42 + j i 3 ( X lb + X 43 ) + j i 4 ( X lb + X lc + X 44 )
where Xla, Xlb, and Xlc are the inductive resistances of the transformer load; X vw = ω L vw ; v and w take on values from 1 to 4; and L vw represents the self-inductances and mutual inductances of the flux linkages of the loops.
The self-inductances in the flux linkages of the loops are defined as
L 11 = L A L AB L BA + L B ; L 22 = L B L BC L CB + L C ;
L 33 = L a + L la L ab L ba + L b + L lb ; L 44 = L b + L lb L bc L cb + L c + L lc ,
And the mutual inductances are
L 12 = L A B L A C L B + L B C ; L 23 = L B a L B b L C a + L C b ;
L 21 = L B A L C A L B + L C B ; L 32 = L a B L b B L a C + L b C ;
L 13 = L A a L A b L B a + L B b ; L 24 = L B b L B c L C b + L C c ;
L 31 = L a A L b A L a B + L b B ; L 42 = L b B L c B L b C + L c C ;
L 14 = L A b L A c L B b + L B c ; L 34 = L a b L a c L b + L b c ;
L 41 = L b A L c A L b B + L c B ; L 43 = L b a L c a L b + L c b ,
where L A , L B , L C and L a , L b , L c are the inductances of the phases of the primary and secondary windings; LAB and LBA, LBC and LCB, and LCA and LAC are the mutual inductances between the phases of the primary winding; and Lab and Lba, Lbc and Lcb, and Lca and Lac are the mutual inductances between the phases of the secondary winding. Moreover, L A a , L a A ; L A b , L b A ; L A c , L c A ; L B a , L a B ; L B b , L b B ; L B c , L c B ; L C a , L a C ; L C b , L b C ; and LCc and LcC are the mutual inductances between the phases of the primary and secondary windings.

3. Inductances, Mutual Inductances, and Active Resistances in the Mathematical Model of a Transformer

The calculation of the inductive resistances of the windings of a three-phase transformer in the general form is difficult [2,21]. However, if the transformer core is considered non-saturated and the magnetic leakage flux of the windings is neglected, then the main inductive resistance, X 0 , and inductance, L 0 , of a phase can be calculated as follows [21]:
Z m = U 1 / I xx ;   X m = Z m 2 R 1 2 ;   X 0 = X m / 1 . 5 ;   L 0 = X 0 / 2 π f
The accuracy must be acceptable for relay protection. Here, Z m is the impedance of the phase of the primary winding of the transformer, and f is the network frequency. The phase voltage U 1 , the no-load current I x x , and the active resistance R 1 of the primary winding can be easily found in an experimental way.
If the phase voltage U2 and load current Il are known, then the active and inductive resistances of a symmetrical load can be quite accurately found from the following mathematical equations:
Z l = U 2 / I l ;   X l = Z l 2 R l 2 ;   L l = X l / 2 π f ;
R l a = R l b = R l c = R l ,   L l a = L lb = L lc = L l ,
where R l and X l are the active and inductive load resistances; and Z l and Ll are the load impedance and resistance. The active resistance R l can also be easily experimentally determined.
Following [18], the inductances of the primary and secondary windings of a transformer are determined by the values of the magnetic fluxes ϕA, ϕB, and ϕc in the core legs. The inductance of a winding is proportional to the squared number of turns of the winding.
Mutual inductances, for example, between the winding of phase A and other primary windings of the transformer, are determined by the distribution of the magnetic flux of phase A over legs B and C of the transformer. Figure 3 shows that the magnetic flux of phase A ϕA splits into magnetic fluxes ϕAB and ϕAC at point and then flow through the legs of phases B and C. Just these fluxes determine the magnetic couplings between the winding of phase A and the windings of phases B and C. These magnetic couplings can be represented by the coefficients
K A B = ϕ A B / ϕ A   and   K A C = ϕ A C / ϕ A .
The magnitudes of ϕAB and ϕAC depend on the design features of the core and materials that it is made of. The accurate calculation of these fluxes is a difficult task. However, if we suggest equal cross-sections of the legs and yokes of the transformer core and the permeability of the steel that they are made of, then, taking into account [18,19], the ratio of magnetic fluxes, i.e., the coefficients K A B and K A C , can be approximately determined as follows.
According to Figure 3, the lengths of the ϕAB and ϕAC closing lines in the core are
l A B = 2 ( l 1 + l 2 )   and   l A C = 2 ( l 1 + 2 l 2 ) .
Since the magnitudes of ϕAB and ϕAC fluxes are inversely proportional to their path lengths in the core, the coefficients for the experimental TT-6 transformer are
K A B = l A C / ( l A B + l A C ) = 0.577   and   K A C = l A B / ( l A B + l A C ) = 0.423 .
Figure 3 shows that the transformer core is symmetrical about the leg of phase B. Hence, the ϕAB and ϕAC magnetic fluxes are equal. Therefore, the coefficients are calculated as follows:
K B A = K BC = 0.5 .
The distribution of the magnetic flux of the leg of phase C over the legs of phases B and A is a mirror image of the distribution of the magnetic flux of the leg of phase A over the legs of phases B and C. Therefore, the coefficients KCA and KCB should be taken to be equal to the coefficients KAC and KAB.
We should add that the K A , K B , and K C coefficients should be taken to be equal to unity when calculating the inductances of the primary and secondary windings and closed turns. The inductances of the primary and secondary windings are calculated as follows:
L A = K A L 0 , L B = K B L 0 , L C = K C L 0 ,
L a = w a w A 2 K A L 0 .   L b = w b w B 2 K B L 0 .   L c = w c w C 2 K C L 0 .
The mutual inductances between the high-voltage winding of phase A and other windings of the transformer can be determined as follows:
L A B = K A B L 0 ,   L A C = K A C L 0 ,
L A a = w a w A K A L 0 ,   L A b = w b w A K A B L 0 ,   L A c = w c w A K A C L 0 .
The mutual inductances between the high-voltage winding of phase B and other windings of the transformer can be determined as follows:
L B A = K B A L 0 ,   L B C = K B C L 0 ,
L B a = w a w B K B A L 0 ,   L B b = w b w B K B L 0 ,   L B c = w c w B K B C L 0 .
The mutual inductances between the high-voltage winding of phase C and other windings of the transformer can be determined as follows:
L C A = K C A L 0 ,   L C B = K C B L 0 ,
L C a = w a w C K C A L 0 ,   L C b = w b w C K A B L 0 ,   L C c = w c w C K C L 0 .
The mutual inductances between the low-voltage winding of phase A and other windings of the transformer can be determined as follows:
L a A = w a w A K A L 0 ,   L a B = w a w B K A B L 0 ,   L a C = w a w C K A C L 0 .
The mutual inductances between the low-voltage winding of phase B and other windings of the transformer can be determined as follows:
L b A = w b w B K B A L 0 ,   L b B = w b w B K B L 0 ,   L b C = w b w B K B C L 0 ,
L b a = w b w B w a w A K B A L 0 ,   L b c = w b w B w c w C K B C L 0 .
The mutual inductances between the low-voltage winding of phase C and other windings of the transformer can be determined as follows:
L c A = w c w C K C A L 0 ,   L c B = w c w C K C B L 0 ,   L c C = w c w C K C L 0
L c a = w c w C w a w A K C A L 0 ,   L c b = w c w C w b w B K C B L 0 .
The inductances and mutual inductances of the loops in this mathematical model do not depend on the saturation of the core. Therefore, the model enables the simulation of currents in the windings of only a linear three-phase power transformer under arbitrary symmetrical and asymmetrical steady-state operation modes. However, this mathematical model can be used to simulate the operation of a nonlinear transformer in the following way.

4. Modeling a Nonlinear Transformer

Real three-phase power transformers are nonlinear. To simulate currents in their windings, mathematical model (1) of a linear transformer can be used, and the self-inductances and mutual inductances in this mathematical model should depend on the magnitude of magnetic fluxes in components of the transformer core and the magnetization curve of steel the core made of. However, a simulation of the currents in the transformer windings is quite a difficult task in this case. It can be simplified by using the method of successive intervals.
For this, the duration of a transformer operation mode is divided into time intervals, Δt, within which the magnetic fluxes in the core legs, currents i1–i4, and inductances and mutual inductances in loops 1–4 are constant. During simulation, these parameters at the beginning of the (q + 1)th time interval are taken equal to their values at the end of the previous qth interval. The magnetic fluxes in the core legs, currents i1–i4, and inductances and mutual inductances of the loops are calculated within each time interval as follows.
As can be seen from Figure 1, the magnetic circuit of the TT-6 transformer is branched. Therefore, according to [18,19,21], the magnetic fluxes ϕ A , ϕ B , and ϕ C in the branches of this circuit can be determined by the nodal-pair method (the nodes are marked by a and b in Figure 1). It should be taken into account that, in addition to these magnetic fluxes in the transformer core legs, there is a magnetic flux ϕ N , which is closed between points a and b through air and the steel tank of the transformer. With the known numbers of turns in the transformer windings and the currents in them at an arbitrary time point, t, the magnetic fluxes ϕ A , ϕ B , and ϕ C in the phase legs of the core and the magnetic flux ϕ N are determined in the following order.
First, following [18,19], the positive direction of all of these magnetic fluxes is chosen. In Figure 1, they are directed from node a to node b. After that, the dependences ϕ A = f ( u m A ) , ϕ B = f ( u m B ) , ϕ C = f ( u m C ) , and ϕ N = f ( u m C ) are plotted, where u m A , u m B , u m C , and u m N are the magnetic voltages in the branches of phases A, B, and C and the branch N where ϕ N is closed. To plot, for example, the dependence ϕ A = f ( u m A ) , a series of numerical values of the magnetic flux ϕ A are specified. Then, the magnetic field induction in the branch of phase A is found for each ϕ A value as follows:
b A = ϕ A / S
where S is the cross-section area of the transformer core leg, S = 5.77 × 10−3 m2 for the TT-6 transformer. When calculating the magnetic field induction in the branches, the cross-section areas of the legs and the yokes of the transformer core can be considered equal since they differ by no more than 10%, and this assumption does not result in significant errors.
Again, the magnetic field strength, h A , in the leg is determined from the magnetization curve shown in Figure 4 by the calculated b A value. This magnetization curve was experimentally derived for the TT-6 transformer.
If the path length of the magnetic flux ϕ A in the branch of phase A is considered equal to l A , then, taking into account the data in Figure 1, the magnetic voltage in this branch is
u m A = h A l A .
The magnetic voltage, u m A , is calculated for each ϕ A value from the magnetic flux series in the same way, and the dependence, u m A = f ( ϕ A ) , is plotted based on the calculation results (curve 1 in Figure 5). The curves u m B = f ( ϕ B ) and u m C = f ( ϕ C ) are plotted in the same way (curves 2 and 3). The curves u m B = f ( ϕ B ) and u m C = f ( ϕ C ) coincide in Figure 5 because of the same path lengths of the magnetic fluxes ϕ A and ϕ C .
The calculation of the dependence u m C = f ( ϕ N ) in general form is complicated since the sizes and configuration of the air gaps and components of the ferromagnetic tank of the transformer should be taken into account. The calculation can be simplified if ϕ N is assumed to be closed through an additional ferromagnetic branch with the cross-section area S and the length being l N = ( 3 10 ) l A . In this case, the length, lN, should increase with the transformer power.
The dependence u m C = f ( ϕ N ) for the length of l N = 3 l A is plotted in Figure 5 (curve 4). This procedure does not lead to significant errors. The errors are estimated below.
The magnetic fluxes ϕ A , ϕ B , ϕ C , and ϕ N can take on negative values; therefore, the dependences u m A = f ( ϕ A ) , u m B = f ( ϕ B ) , u m C = f ( ϕ C ) , and U m C = f ( ϕ N ) are shown in Figure 5 by curves 5–8, which are resulted from rotation of curves 1–4 by 180° around the origin of coordinates.
According to the nodal-pair method [18,19], the magnetic voltages u m A , a b , u m B , a b , u m C , a b , and u m N , a b for the branches of phases A, B, and C and branch N are found from the following equations:
u m A , a b = u m A + i A w 1 + i a w 2 ;
u m B , a b = u m B + i B w 1 + i b w 2 ;
u m C , a b = u m C + i C w 1 + i c w 2 ;
u m N , a b = u m N .
The way of graphical estimation of magnetic fluxes in the legs of a three-phase transformer is shown in Figure 6, where the curves u m A = f ( ϕ A ) , u m B = f ( ϕ B ) , u m C = f ( ϕ C ) , and u m N = f ( ϕ N ) are mirror-reflected about the u m axis according to Equation (20), and the curves u m A = f ( ϕ A ) , u m B = f ( ϕ B ) , and u m C = f ( ϕ C ) are shifted along this axis by the values ( i A w 1 + i a w 2 ) , ( i B w 1 + i b w 2 ) , and ( i C w 1 + i c w 2 ) , respectively. The resulted curves, u m A , a b = f ( ϕ A ) , u m B , a b = f ( ϕ B ) , u m C , a b = f ( ϕ C ) , and u m N , a b = f ( ϕ N ) , are marked by numbers 1–4 in Figure 6.
To estimate the fluxes from Figure 6, line 5 is drawn parallel to the φ axis. It is moved along the magnetic voltage axis until the condition
ϕ A + ϕ B + ϕ C + ϕ N = 0
is satisfied. In this case, the magnetic fluxes in the legs of phases A, B, and C are equal to ϕ A , ϕ B , and ϕ C .
According to [18,19], the flux linkage and the inductance in an arbitrary winding are defined as ψ = w ϕ and L = ψ / i , respectively. Hence, the current values of the self-inductances and mutual inductances of the primary and secondary windings of the transformer in Equations (3) and (4), required for estimation of the flux linkage in the loops by Equation (2), are calculated as
L A = w 1 ϕ A / i A ,   L B = w 1 ϕ B / i B ,   L C = w 1 ϕ C / i C ;
L a = w 2 ϕ A / i a ,   L b = w 2 ϕ B / i b ,   L c = w 2 ϕ C / i c .
The mutual inductances between the winding phases are
L A B = L A K A B ,   L A C = L A K A C ,
L A a = L A w a w A 2 K A ,   L A b = L A w b w A 2 K A B ,   L A c = L A w c w A 2 K A C ,
L B A = L B K B A ,   L B C = L B K B C ,
L B a = L B w a w B 2 K B A ,   L B b = L B w b w B 2 K B ,   L B c = L B w c w B 2 K B C ,
L C A = L B K B A ,   L C B = L B K B C ,
L C a = L C w a w C 2 K C A ,   L C b = L C w b w C 2 K C B ,   L C c = L B w c w C 2 K C ,
L a A = L A w a w A K A ,   L a B = L A w a w B K A B ,   L a C = L A w a w C K A C
L a b = L A w a w A w b w B K A B ,   L a c = L A w a w A w c w C K A C ,
L b A = L B w b w A K B A ,   L b B = L B w b w B K B ,   L b C = L B w b w C K B C
L b a = L B w b w B w a w A K B A ,   L b c = L B w b w B w c w C K B C ,
L c A = L C w c w A K C A ,   L c B = L C w c w B K C B ,   L c C = L C w c w C K B C
L c a = L B w c w C w a w A K C A ,   L c b = L C w c w C w b w B K C B .
The loop currents are changed to phase currents in Figure 2, following the equations.
i A = i 1 , i B = i 2 i 1 , i C = i 2 , i a = i 3 , i b = i 4 i 3 , i c = i 4
Figure 5 shows that the magnetic flux is low at the length l N = 3 l A as compared to the magnetic fluxes in the transformer core legs, and it decreases as l N increases. Thus, the choice of the length l N within the limits ( 3 10 ) l A does not lead to significant errors in the inductances of the transformer.

5. Results and Discussion

The mathematical model developed makes it possible to simulate almost all stationary processes in a healthy three-phase transformer accounting for its nonlinearity. Special software has been created for the model implementation in the TurboBasic V1.1 environment [20].
The mathematical model was verified by simulating the rated load and no-load modes. The load resistance of the experimental transformer was taken to be equal to 2.5 Ohm in the load mode and infinity in the no-load mode.
It is difficult to visually estimate the adequacy of this mathematical model, for example, through a comparison between the calculated and experimental dependences i A = f ( t ) of a three-phase transformer. This estimation is much easier to make from a comparison between the harmonic components of these dependencies. To distinguish them, we used the graphical–analytical Fourier-transform method [18,19].
To measure the parameters of the experimental TT-6 transformer and the spectrum of harmonic components in the network voltage and the current in the primary winding of the transformer, we used an experimental setup, the electrical circuit of which is shown in Figure 7.
As can be seen from Figure 6, the experimental setup is connected to a three-phase 380 V AC line through circuit breaker SF. The current in the phases of the high- and low-voltage windings of the transformer is measured by ammeters PA1 and PA2. PA1 is a class 0.5 E59 ammeter; it is connected in series with the phases of the primary windings through a class 0.2 I54/1-type current transformer TA with the use of sockets X S 1 X S 3 and plugs with jumpers. This connection of ammeter PA1 makes it possible to use the same device to measure currents in the three phases in turn. This significantly reduces the measurement error.
The spectrum of the harmonic components of currents in the primary winding is recorded with two-beam oscilloscope DSO1. It is based on a personal computer with ELENA-2014 software. The entrance of this oscilloscope is connected to the terminals of ammeter PA1. This provides galvanic isolation of the oscilloscope entrance and the supply line. The voltage at the entrance of DSO1 is controlled with high-ohm resistor R4. The voltage and the harmonic spectrum are controlled with UNI-T UT101 voltmeter PV1 and RIGOL DS1054Z oscilloscope DSO2.
Ammeter PA2 is a class 0.2 D566 device. It is connected in series with the phases of the secondary windings with the use of sockets X S 4 X S 6 and plugs with jumpers. Voltmeter PV2 of YX-360TRD type is connected to the neutral of load, which is resistors R1–R3, and one of the terminals of ammeter PA2. This enables the simultaneous control of current and voltage. The transformer load is commutated with the use of plugs with jumpers and sockets X S 7 X S 9 . The experimental setup is shown in Figure 8.
The results of the spectral analysis of phase A current during the transformer operation in the no-load and load modes are given in Table 2 and Table 3. The comparison between the calculation and experimental results shows the simulation error to be no more than 14% in these operation modes.
One of the reasons for this error is the presence of higher harmonics in the voltage of the supply line during the experiment. Another reason can be the use of numerical methods for estimating the magnetic fluxes in legs.
Nevertheless, the suggested mathematical model of a three-phase transformer enables simulating currents in the transformer windings under steady-state operation modes with accuracy acceptable for the relay protection. Since the requirements for the design of transformers do not depend on their power, there is every reason to believe that the errors will be similar in simulation of the operation of industrial transformers of arbitrary power.
This mathematical model was developed for asymmetrical three-phase transformers with two star-star connected windings without zero grounding. However, it can be used to simulate processes in nonlinear two-winding three-phase transformers with any connection of its windings. In each specific case, the equations of the mathematical model are transformed several times, except for the equations which consider the nonlinearity of the transformer; they remain unchanged.

6. Conclusions

One of the main causes of failures and shortening the service life of two-winding asymmetrical core transformers is the turn-to-turn faults in their windings, which are up to 70–80% of all transformer failures depending on the power and operating conditions.
One of the main ways of decreasing the statistics of these failures and increasing the service life of transformers is the improvement of differential current protections, which is reduced to an increase in their sensitivity to turn-to-turn faults. The operation of these protections is based on the comparison between two electrical quantities with different spectra of currents in phases. Therefore, their sensitivity can be increased by acquiring and taking into account information in the form of the spectrum of these harmonics when choosing the response threshold for differential current protections.
For these purposes, the model with phase coordinates, which is easy for understanding and implementing, can be used. Its differential equations are compiled by the loop current method for phase-to-phase voltages. It uses fourth-order matrices to describe the operation of a three-phase two-winding transformer. Both MATLAB and Turbo Basic environments can be used to implement this mathematical model. However, despite all of its advantages, this model cannot take into account the asymmetry and nonlinearity of a transformer.
In contrast to this model, the mathematical model we suggest makes it possible to consider the asymmetry and nonlinearity of the core of a three-phase transformer by replacing a set of differential equations with a set of linear equations. In the resulted mathematical model, the initial values of its inductances and mutual inductances are determined based on the use of no-load current taking into account the transformer core size, and current values of these parameters are calculated from the currents in the windings and the magnetic fluxes in transformer core legs. The latter are calculated by the nodal-pair method.
The simulation results are presented in the form of harmonics derived from the Fourier transform of the currents, because a visual estimation of the simulation error is quite difficult.
The comparison between the calculation and experimental results showed the error in the harmonic currents in transformer windings to be no higher than 14%. This enables us to estimate the influence of the transformer nonlinearity on the simulation results with acceptable accuracy. We believe that this error is due to the presence of high-order harmonics in the supply voltage during the experiment and the use of numerical method for calculation of these currents.

Author Contributions

Conceptualization, E.K. and A.N.; data curation, D.R. and A.K.; methodology, E.K., A.N. and D.R.; software, T.N., A.N. and E.K.; project administration, E.K. and A.N.; resources, A.N., A.K. and D.R.; supervision, E.K.; validation, A.N. and D.R.; visualization, T.N. and A.N.; formal analysis, A.K., T.N. and D.R.; writing original, E.K. and A.N.; writing, E.K. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by Committee of Science of the Ministry of Science and Higher Education of the Republic of Kazakhstan (grant no. AP14972779).

Data Availability Statement

The original contributions presented in the study are included in the article, further inquiries can be directed to the corresponding author.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

EMTPElectroMagnetic Transient Program

References

  1. Kazakul, A.A.; Kushnareva, Y.A. Analysis of the number of working transformers at substations of branches of JSC “DRSK”. Gl. Energetik 2022, 10, 1–10. [Google Scholar]
  2. Patel, D.; Chothani, N. Digital Protective Schemes for Power Transformer. In Power System; Springer: Singapore, 2020. [Google Scholar]
  3. Elmore, W.A. Protective Relaying Theory and Applications; Marcel Dekker Inc.: New York, NY, USA; Basel, Switzerland, 2004. [Google Scholar]
  4. Blackburn, J.L.; Domin, T.J. Protective Relaying: Principles and Applications, 4th ed.; CRC Press: Boca Raton, FL, USA, 2014. [Google Scholar]
  5. Paithankar, Y.G. Transmission Network Protection. Theory and Practice; CRC Press: Boca Raton, FL, USA, 1997. [Google Scholar]
  6. Rakhimberdinova, D.; Novozhilov, A.; Kolesnikov, E.; Andreeva, O.; Talipov, O.; Kislov, A. Arc Fault Protection of the High-Current Busbar Assembly of an Ore Furnace. Energies 2023, 16, 7834. [Google Scholar] [CrossRef]
  7. Islam, M.; Musil, M.; Shohan, J.A.; Faruque, O.; Lauss, G.; Dehkordi, A.; Forsyth, P.; Kotsampopoulos, P.; Strunz, K.; Li, Z.; et al. A review of modelling techniques of power transformers for digital real-time simulation. J. Eng. 2023, 2023, e12221. [Google Scholar] [CrossRef]
  8. Bastard, P.; Bertrand, P.; Meunier, M. A transformer model for winding fault studies. IEEE Trans. Power Deliv. 1994, 9, 690–699. [Google Scholar] [CrossRef]
  9. Marti, J.; Linares, L.; Dommel, H. Current transformers and coupling-capacitor voltage transformers in real-time simulations. IEEE Trans. Power Deliv. 1997, 12, 164–168. [Google Scholar] [CrossRef]
  10. Garcia, S.; Medina, A.; Perez, C. A state space single-phase transformer model incorporating nonlinear phenomena of magnetic saturation and hysteresis for transient and periodic steady-state analysis. In Proceedings of the 2000 Power Engineering Society Summer Meeting (Cat. No.00CH37134), Seattle, WA, USA, 16–20 July 2000; Volume 4, pp. 2417–2421. [Google Scholar] [CrossRef]
  11. Liu, P.; Dinavahi, V. Real-time finite-element simulation of electromag- netic transients of transformer on ffPGA. IEEE Trans. Power Deliv. 2018, 33, 1991–2001. [Google Scholar] [CrossRef]
  12. Alvarez-Marino, C.; Leon, F.; Lopez-Fernandez, X. Equivalent circuit for the leakage inductance of multiwinding transformers: Unification of terminal and duality models. IEEE Trans. Power Deliv. 2012, 27, 353–361. [Google Scholar] [CrossRef]
  13. Ke, X.; Ionutiu, R. Modeling three-phase saturable transformers for real-time simulation. In Proceedings of the IECON-40th Annual Conference of the IEEE Industrial Electronics Society, Piscataway, NJ, USA, 29 October–1 November 2014; pp. 3783–3789. [Google Scholar]
  14. Liu, J.; Dinavahi, V. Detailed magnetic equivalent circuit based real-time nonlinear power transformer model on FPGA for electromagnetic transient studies. IEEE Trans. Ind. Electron. 2016, 63, 1191–1202. [Google Scholar] [CrossRef]
  15. Díaz, G.; Gómez-Aleixandre, J.; Arboleya, P. Electromagnetic model of turn-to-turn short circuits in transformers. Int. J. Comput. Math. Electr. Electron. Eng. 2004, 23, 562–575. [Google Scholar]
  16. Kopylov, I.P. Mathematical Modeling of Electrical Machines; Vysshaya Shkola: Moscow, Russia, 1994. (In Russian) [Google Scholar]
  17. Volgina, E.; Novozhilov, A.; Kolesnikov, E.; Rahimberdinova, D.; Novozhilov, T.; Andreeva, O. Simulation of three-phase transformer operational conditions. In News of the National Academy of Sciences of the Republic of Kazakhstan; Series of Geology and Technology Sciences; Institute of Geological Sciences named after K.I.Satpayev: Almaty, Kazakhstan, 2019; Volume 5, pp. 26–33. [Google Scholar]
  18. Bobrow, L.S. Foundations of Electrical Engineering; Oxford University Press: Oxford, UK, 2013. [Google Scholar]
  19. Simonyi, K. Foundations of Electrical Engineering: Fields–Networks–Waves; The Maximillan Company: New York, NY, USA, 1963. [Google Scholar]
  20. Structured, E.W. Programming Using Turbo Basic; Ellis, W., Jr., Lodi, E., Eds.; Academic Press Inc. (London) Ltd.: London, UK, 1988; p. 337. [Google Scholar]
  21. Sahdev, S.K. Electrical Machines; Cambridge University Press: Cambridge, UK, 2018. [Google Scholar]
Figure 1. Diagram of the core of a three-phase power transformer.
Figure 1. Diagram of the core of a three-phase power transformer.
Energies 17 01710 g001
Figure 2. Electrical circuit of a three-phase power transformer.
Figure 2. Electrical circuit of a three-phase power transformer.
Energies 17 01710 g002
Figure 3. Distribution of magnetic fluxes of phase A.
Figure 3. Distribution of magnetic fluxes of phase A.
Energies 17 01710 g003
Figure 4. Experimental magnetization curve for the TT-6 transformer.
Figure 4. Experimental magnetization curve for the TT-6 transformer.
Energies 17 01710 g004
Figure 5. Dependence u m = f ( ϕ ) for the branches of phases A, B, and C.
Figure 5. Dependence u m = f ( ϕ ) for the branches of phases A, B, and C.
Energies 17 01710 g005
Figure 6. Graphical estimation of magnetic fluxes in phase legs.
Figure 6. Graphical estimation of magnetic fluxes in phase legs.
Energies 17 01710 g006
Figure 7. Circuit of the experimental setup.
Figure 7. Circuit of the experimental setup.
Energies 17 01710 g007
Figure 8. Experimental setup: experimental TT-6 transformer (TV); 2.5–10-ohm variable load resistors (R1, R2, and R3); AP50 circuit breaker (SF); UNI-T UT101 and YX-360TRD voltmeter (PV1 and PV2); I54/1 measuring current transformer (TA); E59 and D566 ammeter (PA1 and PA2); laptop-based digital oscilloscope with ELENA-2014 software (DSO1); high-ohm resistor (R4); RIGOL DS1054Z digital oscilloscope (DSO2); Schneider Electric socket-outlet (XS1–S9).
Figure 8. Experimental setup: experimental TT-6 transformer (TV); 2.5–10-ohm variable load resistors (R1, R2, and R3); AP50 circuit breaker (SF); UNI-T UT101 and YX-360TRD voltmeter (PV1 and PV2); I54/1 measuring current transformer (TA); E59 and D566 ammeter (PA1 and PA2); laptop-based digital oscilloscope with ELENA-2014 software (DSO1); high-ohm resistor (R4); RIGOL DS1054Z digital oscilloscope (DSO2); Schneider Electric socket-outlet (XS1–S9).
Energies 17 01710 g008
Table 1. Parameters of the experimental TT-6 transformer.
Table 1. Parameters of the experimental TT-6 transformer.
ParameterDesignationValue
Phase voltage, V U 1 222
No-load current, A I x x 0.127
Number of turns in the primary/secondary winding w 1 / w 2 252/31
Primary/secondary winding resistance, ohm R 1 / R 2 0.9/0.06
Table 2. Calculated and experimental harmonic components of current in the primary winding of the transformer operating in the no-load mode.
Table 2. Calculated and experimental harmonic components of current in the primary winding of the transformer operating in the no-load mode.
Harmonic No.No-Load Mode
Calculation Result, Rel. UnitsExperimental Result, Rel. UnitsRelative Error, %
11.00001.00000
20.03000.03034.64
30.01510.01586.14
40.01630.01532.95
50.16930.16432.95
60.00240.00291
70.04330.04334.64
Table 3. Calculated and experimental harmonic components of current in the primary winding of the transformer operating in the load mode.
Table 3. Calculated and experimental harmonic components of current in the primary winding of the transformer operating in the load mode.
Harmonic No.Load Mode
Calculation Result, Rel. UnitsExperimental Result, Rel. UnitsRelative Error, %
11.00001.00000
20.01090.012211.93
30.00820.009313.42
40.00790.00737.60
50.07020.07192.42
60.00280.003110.71
70.01990.02105.53
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Kolesnikov, E.; Novozhilov, A.; Rakhimberdinova, D.; Kislov, A.; Novozhilov, T. Mathematical Model of a Nonlinear Power Transformer for Needs of Relay Protection. Energies 2024, 17, 1710. https://doi.org/10.3390/en17071710

AMA Style

Kolesnikov E, Novozhilov A, Rakhimberdinova D, Kislov A, Novozhilov T. Mathematical Model of a Nonlinear Power Transformer for Needs of Relay Protection. Energies. 2024; 17(7):1710. https://doi.org/10.3390/en17071710

Chicago/Turabian Style

Kolesnikov, Evgeniy, Aleksandr Novozhilov, Dilara Rakhimberdinova, Aleksandr Kislov, and Timofey Novozhilov. 2024. "Mathematical Model of a Nonlinear Power Transformer for Needs of Relay Protection" Energies 17, no. 7: 1710. https://doi.org/10.3390/en17071710

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop