Next Article in Journal
Research on Markov Decision Model Predictive Control of Interior Permanent Magnet Synchronous Motor Based on Lumped Disturbances Compensation
Next Article in Special Issue
Multi-Objective Optimization of Insulation Thickness with Respect to On-Site RES Generation in Residential Buildings
Previous Article in Journal
Harnessing Heterogeneous Interface and Oxygen Vacancy in Cu/Cu2O for Efficient Electrocatalytic Nitrate Reduction to Ammonia
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Development and Application of a Platform for Optimising Heating System Operation Based on the Building User’s Temperature Perception

by
Andre Beblek
1,*,
Florian Felix Sehr
1,
Viktor Grinewitschus
1,
Carolin Baedeker
2 and
Aaron Immanuel Wolber
3
1
EBZ Business School, University of Applied Sciences, 44795 Bochum, Germany
2
Research Unit Innovation Labs, Division Sustainable Production and Consumption, Wuppertal Institute for Climate, Environment, and Energy, 42103 Wuppertal, Germany
3
iBG Inbestergesellschaft GmbH, 50672 Köln, Germany
*
Author to whom correspondence should be addressed.
Energies 2024, 17(17), 4468; https://doi.org/10.3390/en17174468
Submission received: 27 July 2024 / Revised: 28 August 2024 / Accepted: 5 September 2024 / Published: 5 September 2024
(This article belongs to the Special Issue New Insights into Hybrid Renewable Energy Systems in Buildings)

Abstract

:
The energy challenges of overcoming climate change and economic and global political crises require not only the increased integration of renewable energies but also an optimisation of energy generation and use and, as a result, a reduction in energy consumption in various sectors. Thermal energy consumption in buildings in particular accounts for a significant proportion of final energy consumption. With respect to commercial buildings, a central problem in optimising the system settings is the lack of or only limited information about the actual room temperatures as well as the comfort requirements and temperature perception of the users in the rooms on the one hand and the operational management and settings specified by the facility management, for example, the heating curves of the heating circuits, on the other. The aim here is to create a bidirectional flow of data and information so that the compromise between the necessary room temperatures and the comfort of the users and the most energy-efficient operational management possible can be achieved. In this context, the paper presents a developed and tested web platform that makes it possible to optimise the operation of the system technology, particularly the heating system in the building, from an energy point of view and to involve the building user (e.g., office employees) and to pass on information to the facility management, thus pursuing a holistic approach. In the associated Living Lab project (called ComfortLab), it was possible to obtain over 6500 votes on temperature perception and combine this with building operation and the parameters relevant to facility management. This made it possible to bridge the gap between user requirements and room temperatures on the one hand and energy consumption and the inlet temperature of the heating system and supply circuits on the other. The use of the platform makes it possible to optimise the setpoint specification, specifically the inlet temperature of individual heating circuits, considering both regular building operation at times of presence and the setting of weekend and night setback times. The results show a diversified picture regarding temperature perception and possible room temperature reductions of several degrees Celsius and energy savings in the double-digit percentage range.

1. Introduction

The current draft of the Energy Performance of Buildings Directive (EPBD) [1] provides for more buildings to be equipped with building automation systems from 2025 onwards, enabling more comprehensive monitoring of new or extensively renovated buildings, as in many cases buildings do not achieve the specific consumption levels that would be expected based on their building envelope and building technology. This is particularly important because buildings, and especially heating energy consumption, account for a significant proportion of energy consumption. In Germany, for example, this currently amounts to around 28% [2]. Overall, the EU-wide legislation aims to decarbonise the building stock and thus the associated energy supply by 2050. A mix of different measures will be necessary to achieve this ambitious goal. These include the integration of renewable energies, both in the electricity and heating sectors and the flexible and intelligent management of energy generation and consumption. Energy storage also plays a key role in decoupling the timing and can ensure an optimised balance between the supply and consumption of energy flows.
Studies on real buildings show that there is an interaction between user behaviour and the operational management of the building technology and the associated energy consumption [3,4]. Users not only have a direct influence on consumption, e.g., through inappropriate room temperature settings or incorrect ventilation behaviour. In commercially operated buildings, complaints from users about a real or perceived undersupply of heat also lead to adjustments to the system technology by the facility management, which lead to additional consumption and encourage energy wastage through user behaviour. For example, a ventilation heat loss caused by permanent tilt ventilation can be compensated with correspondingly high inlet temperatures at the radiator if sufficient heat is provided. The comfort gain (room temperature and fresh air supply) maintained by the user in this way leads to disproportionately high heat energy consumption.
The plant automation (e.g., control of the heat generator, speed specification of circulation pumps, etc.) and the room automation (e.g., control of the lighting, control of electronic thermostatic valves) are organised as two trades in terms of structure and planning [5]. Although information can be exchanged via interfaces, this is only done in a few cases and mostly in informative form (for example, as the integration of warning messages from room automation in the building management system) and not to optimise operational management (for example, to adapt setpoint specifications for the system technology from the room automation data determined). Energy management is traditionally another system to which information is also transferred via corresponding interfaces and used for evaluation. A central challenge in the operation and optimisation of the operational management of the system technology is therefore the great uncertainty about the real perception of the employees and the situation in the offices on the one hand and the decentralised information situation in the various systems on the other. In traditional building automation systems and platforms, there is no structured way of obtaining and processing feedback apart from unrepresentative individual opinions and problems. This applies not only to settings during working hours, but also to information about the effect and the utilised and still existing potential of setback operations outside working hours. In practice, this often leads to a generalised oversupply of heating energy, especially when individual complaints reach facility management.
This is where the ComfortLab platform presented in this paper comes in. The associated solution is to obtain standardised feedback on the temperature perception of the largest possible number of employees with as little individual effort as possible and to take this into account as a specification for the operational management of the system technology. The platform was developed in a BBSR-funded (Federal Institute for Research on Building, Urban Affairs and Spatial Development) research project by the EBZ Business School and the Wuppertal Institute with the involvement of the design studio ‘inbestergesellschaft’ on the basis of the Living Lab approach [6,7]. The project was carried out in the heating periods 2021/2022 (pre-test) and 2022/2023 (field test) with over 200 participants in the BMUV properties (Federal Ministry for the Environment, Nature Conservation, Nuclear Safety and Consumer Protection) in Berlin and Bonn, which cover a total gross floor area of around 100,000 m2. In the predecessor project (details can be found in the corresponding publication [8]) the main focus was on the user’s individual interaction with the building in terms of heating and ventilation behaviour. To this end, the effect of feedback systems and surveys was analysed and successfully evaluated. In the follow-up project, this approach was continued, but with the focus on reaching a significantly larger number of employees to provide better findings for the operational management of the system technology as a whole and as support for instructions for facility management.
The current status of other research and publication activities was analysed on the basis of a literature search. Several sources were found that take partial aspects of the ComfortLab approach into account. The integral overall approach between querying the temperature perception, analysing the building technology and providing feedback to the facility management, considering an appealing user interface that is understandable for non-technical users, has not yet been tested and represents a novelty with regard to the available publications. The following is a brief description of current research activities and results and how they relate to this publication and the ComfortLab approach.
In [9], a literature search of studies was carried out in which user-centred operational management is described. Various aspects and technologies were considered and summarised here. An existing challenge is seen in the necessary amount of user-related data; the number of studies that take building operators and facility management into account is also summarised as very low and requires further investigation. Di Giuda et al. [10] have developed a system to support adjustments to the system technology, in which data from IoT sensors (e.g., cameras for presence detection) and post-occupancy evaluations were used to support facility management in optimising operations and building use based on defined KPIs. This did not include any kind of direct feedback from employees. The authors in [11] summarise the structure of IoT systems in the context of building management systems and propose an ‘adaptation level’ at the management level that will, for example, incorporate user activities into operational management in the future. In [12], an interface was developed that visualises information on energy consumption for students. Surveys conducted at the same time in the co-design process were met with broad interest; 48 students were surveyed, and the feedback was used to revise the visualisation. Feedback into the operational management or the derivation of recommendations for action for facility management was not investigated. Garg et al. [13] have developed a survey-based interface for households, which is intended to encourage energy savings through feedback. Here too, optimisation or adaptation of the system technology was not investigated.
In [14], the authors examined building automation systems in a review paper with regard to the possibilities of adapting building operation while taking real-time feedback into account. Only a few studies were found that show mathematical relationships between physical factors of the indoor climate and productivity, most of which are still based on static models (e.g., the PMV), and there is potential for an individual approach. Jayathissa et al. [15] have developed an app that can be installed on Fitbit watches. In a four-week test phase, almost 1500 votes were collected from 15 people. Hierarchical K-Means Clustering was used to form four clusters for comfort perception. The use requires configuration and availability of the smart watches and does not offer any direct recommendations for actions for the facility management regarding system technology settings. In [16], a system was developed that provides building users with recommendations for reducing their energy consumption on the basis of operating data; the premise here was a high degree of scalability to other buildings and systems. Feedback from the user or the derivation of system settings was not considered.
In [17], Jin et al. simulatively tested the possibility of reducing the consumption of ventilation systems, plug-in loads and lighting by means of presence detection through WLAN activity; on a daily average, this could lead to energy savings of 10% in the study. There was no transfer to real buildings or a field test. In [18], the acceptance of a building automation system by facility managers was evaluated, with the system providing machine-learning-based information about faults in the system technology. Compliance with the user’s comfort requirements was defined as a goal alongside energy- and cost-efficient operational management but was not specifically taken into account during development. Desogus et al. [19] are actively developing a platform that enables facility management to optimise building operation based on measured comfort indicators. The evaluation of comfort is based on measured parameters and not on feedback. Based on a partial dataset from the ASHRAE Global Thermal Comfort Database II [20], the authors of [21] investigated how the load control of HVAC systems can be realised under the predicted thermal satisfaction based on the dataset. No original data samples were collected, and no tests were carried out on real systems.
The summary of the current research situation shows that individual aspects, such as recommended actions for system settings and feedback from users via end devices (e.g., smart watches), already exist and have been implemented in the research landscape. The ComfortLab platform, on the other hand, offers a device- and user-independent way of intuitively assessing the temperature well-being of the largest possible number of people, combining these data with technical parameters from building automation and making them available to facility management. The platform is both flexible in terms of building technology and cost- and resource-efficient in terms of the necessary data collection for the largest possible group of people. The following research questions were defined as guiding principles and were to be answered:
  • What are the requirements in terms of thermal comfort in the object under investigation and what parameters need to be collected for the envisaged solution?
  • What is the status quo of conventional operational management, considering different operating periods?
  • Is it possible to develop a simple and intuitive, web-based solution that addresses as many participants as possible and obtains their temperature perception over a sufficiently long period of time on one site and considers the requirements of the facility management on the other site?
  • What reduction in the flow temperature in heating circuits as a central control variable is possible, and what effects does this have on heat energy consumption?
The rest of the paper is structured as follows: Section 2 presents the background to the measurements and platform development as well as the functionality and technical parameters. Section 3 presents and interprets the results of the comfort measurements and the use and acceptance of the platform. The resulting energy consumption and room temperatures as well as the results from the final survey, which was carried out with the participants after the test period, are included. Section 4 concludes the article with a summary and critical evaluation of the results, as well as open research questions and planned future developments.

2. Materials and Methods

This section describes the platform and the associated development. The platform was developed and tested in several iteration loops in four heating periods. Initially, measurements were taken to carry out a basic analysis of the comfort, ventilation and presence situation (Section 2.1). These results were used as the basis for the initial assessment of the operational management of the system technology and for evaluating the necessary technical parameters for the development. This is followed by a description of the platform used to collect the participants’ data and provide it together with the system parameters for facility management (Section 2.2).

2.1. Comfort and Room Climate Measurements

To record the current comfort situation and the indoor climate, measurements were carried out in selected rooms using measuring devices to record the relevant parameters for determining the PMV/PPD in accordance with DIN EN ISO 7730 [22]. The measured values include relative humidity, air velocity, air temperature and globe temperature. The clothing index and metabolic rate were assumed to correspond to standard values for office work (metabolic rate: 1.3 MET, clothing insulation: 0.9).
The aim of these measurements was to obtain an assessment of whether there were any fundamental problems in the building, such as draughts, that needed to be considered. Furthermore, as in the previous project, the PIAF ventilation assistant was used in selected offices [23]. This records measurement data on the room climate (carbon dioxide concentration, room air temperature, relative humidity) and uses acoustic and visual signals to alert the user to necessary and sensible ventilation processes. This enabled the occupancy of the offices and the room temperature level to be recorded in selected offices over the entire test period. Technical details on the PIAF ventilation assistant can be found in the corresponding publication [8]. In addition to the data from the system technology, this forms the database that was used in the development of the ComfortLab platform. As part of the comfort monitoring, 36 rooms in Bonn with different types of use (meeting rooms, offices) were measured; details of the measurement technology used can be found in [24]. The values were collected in the period from February to May 2021, so that although only part of the heating period was recorded, there are still sufficient periods with low temperatures below the heating limit. The data storage interval was set to 5 min; measurements were taken for each room for a period of two weeks, after which the measuring devices were installed in the next room. Figure 1 shows an example setup including the data logger and the sensors for measuring indoor air quality, radiant temperature and air velocity.
The devices were positioned in such a way that the effects of sunlight, draughts or other disturbances were avoided.

2.2. Technical Implementation

The ComfortLab platform consists of a decentralised structure with different subsystems as shown in Figure 2. The data interface was set up in such a way that the use of common protocols (e.g., BACnet, OPC, Modbus) of the various building automation systems in individual buildings was possible. The transfer to the ComfortLab platform from the individual properties (left in Figure 2) takes place via IoT and web technologies (e.g., MQTT, REST). Edge devices serve as intermediaries between the property and the platform, recording local information from the building management system and forwarding it (Wi-Fi, LTE). This allows different buildings with different automation solutions to be connected. The second part is the system consisting of a database server, MQTT broker and REST interface (middle part of Figure 2). This is where the data are stored, normalised and made available in various aggregation levels (e.g., daily consumption of individual heating circuits, hourly average inlet temperatures of heating circuits). Different units, intervals, etc., from the individual properties are thus harmonised, and data can be compared. Weather data were obtained from the German Weather Service via a REST interface (upper part of Figure 2). For the Bonn property, data from the weather station “Köln/Bonn (Flugh.)” at a distance of about 17 km were used; for Berlin, data from the station “Berlin-Tempelhof” at a distance of about 1 km were used. The final part is the ComfortLab platform, operated on a separate system in the field test (right part in Figure 2). This combines the information and enables the temperature perception and visual overview to be provided by and for the employees (ComfortStripes) as well as the technical representation for facility management (ComfortHub).
As office staff and facility management have different objectives and a different technical understanding of the indoor climate and system parameters, the presentation of the data collected in the ComfortLab platform was adapted for both groups. The representation for both groups is based on the idea of Ed Hawkins’ “Warming Stripes”, which are used to visualise the long-term rise in global warming temperatures [25]. The “Warming Stripes” show the average annual temperatures of a location or region. On the multi-coloured, sequential colour scale, deep blue stripes represent years with low average temperatures, while deep red stripes show years with high average temperatures. The absolute values differ from location to location, but over the course of many years, there is a general progression from blue to red bars and a corresponding rise in temperature.
This idea was adapted for the ComfortLab platform: Blue colours stand for cold room temperatures and a cold temperature sensation; red colours, for high room temperatures and a warm temperature sensation. An example of the representation of employees and facility management is shown in Figure 3.
In order to reach as many office employees as possible and encourage them to participate, the simplest possible form of interaction was developed—the “ComfortStripes”, which is shown in the left part of Figure 3. The vote on the temperature sensation and the recorded room temperature is visualised over time using a coloured bar. Blue stands for cool, and red for warm temperatures. To collect the data, employees were notified twice a day by e-mail and asked to vote. As wireless temperature sensors could not be installed due to data protection concerns, the room temperature readings from a desktop thermometer had to be entered in addition to the temperature perception data. This step is prone to error and only represents a snapshot, so the aim is to automate this recording in the future. This was successfully tested as a prototype in a selection of rooms. Each participant could view their previous votes and entered room temperatures with access protection using a web browser.
As many office buildings in Germany are heated via radiators and the air is exchanged via manual window openings, targeted humidification and dehumidification or active cooling of the room air, for example, as is possible with air conditioning systems, is not possible or only possible to a very limited extent. This reduces the possibilities for local technology in the office to influence the indoor climate parameters, which are included in the calculation according to the Fanger PMV comfort model, for example. As this limits the possibilities for influencing thermal comfort, a simplified specification of five instead of seven possible levels (warmer, warm, neutral, cold, colder) was chosen for the ComfortLab platform. This should further simplify everyday responses and further increase acceptance and motivation for long-term participation among employees. In addition to stating their temperature perception and the measured temperature, participants were able to enter their days and times of attendance. This information can be used to estimate the occupancy of the building and individual parts of the building and to incorporate the control of the heating circuits. In this way, the data made it possible to optimise operational management during working/operating times as well as during non-attendance times and provide assistance with night and weekend heat supply reduction.
The display for the facility management, shown as an example in the right part of Figure 3, was expanded to include an aggregation level at the heating circuit level as well as the evaluation of inlet and return temperatures and energy consumption depending on the outside temperature. This enabled the facility management team to view the reconciliations for individual heating circuits, together with the entered room temperatures, and to make the necessary adjustments to the system technology on this basis. The aggregation of the individual offices into a heating circuit/line level enables an overall view of the system parameters and recorded temperatures and comfort settings. For example, the temperature level of all offices connected to a heating circuit can be recorded and evaluated. This enables a targeted assessment of whether, for example, the overall temperature level in the corresponding heating circuit is too low or whether there are any individual, local problems in certain rooms. This represents a contrast to the classic approach, in which individual complaints lead to the temperature level of the heat supply being raised at an overall level (heating circuit or entire building) to eliminate individual complaints due to a lack of alternative information.

3. Results

Following the presentation of the infrastructure and the use of the ComfortLab platform, this section presents the key results from the comfort and indoor climate measurements (Section 3.1) and the use of the ComfortLab platform as well as the temperature perception (Section 3.2). Section 3.3 explains and classifies the effects on system operation and the resulting energy consumption. The results are then compared with the findings from the final survey, in which the ComfortLab participants were asked about their experiences following the test period (Section 3.4).

3.1. Results of Comfort and Room Climate Measurements

As the parameters for the ComfortLab platform should be recorded with as little effort as possible in order to enable as many employees as possible to participate, comfort measurements were initially taken in a representative selection of offices, as described in Section 2.1. Should fundamental problems arise, for example with draughts, this would have to be considered in the research design and voting behaviour. Otherwise, the indoor air temperature in the offices should form the basis for the survey as the dominant and relatively easy-to-determine measured value in a large number of offices. As the offices were largely unoccupied in 2021 and partly also in 2022 due to the ongoing COVID-19 pandemic and the resulting predominant home office work of most employees, the measurements represent the indoor climate situation without the effect of the presence of people (settings on thermostats, ventilation processes, etc.) and the necessary temperature control of the offices. In principle, a general lowering of the temperature level would have been possible here, but definitely during non-working hours. The corresponding time periods are defined as follows for all evaluations:
-
Working days’ daytime operation: Monday to Friday from 7 a.m. to 6 p.m.
-
Working days’ night setback: Monday to Friday from 6 p.m. to 7 a.m.
-
Weekend operation: Saturday and Sunday all day.
Figure 4 shows the frequency distribution of the calculated operative temperature as the mean value of the measured room temperature and the mean radiation temperature from the comfort measurements of all rooms as hourly average values for the three time periods. Statistical parameters from the operative temperature distribution are listed in Table 1. Only values from days with average outdoor temperatures below 15 °C corresponding to the heating limit of the building are considered. It can be seen that in daytime operation (left diagram, olive green bars), in night-time operation (middle diagram, slate grey bars) and on weekends (right diagram, dark magenta bars), the average operating temperature on heating days is above 23 °C and also rises to up to 27 °C at times during the night and on weekends.
Accordingly, there should be no problems with the possible heating power provided by the heating system. Even without real presence, the PMV value calculated from the measured values and parameters (metabolic rate: 1.3 MET, clothing insulation: 0.9) allows conclusions to be drawn about the comfort situation for different periods of time. Above all, during the assumed non-working hours and the associated non-occupancy of the building, the temperatures can be lowered considering a minimum building physics temperature. Figure 5 visualises the PMV calculated from the measured values as well as the metabolic rate and the clothing index for the three time periods, analogous to Figure 4. Statistical parameters from the PMV distribution are listed in Table 2.
The red lines (−0.5 to 0.5) represent the range in which the PMV should be when people are present. The comfort index changes only slightly within the different time periods but is also in the rather high range at night and on weekends, sometimes even in the “too warm” range. The few low PMV values are associated with individual cold radiation temperatures but are the exception. Other comfort problems, such as draughts, were not recorded by the measurements and should not have a significant negative impact on comfort. To keep the survey for the ComfortLab test feasible in terms of cost and effort, the room air temperature was therefore chosen as the decisive factor. As the office users were already provided with desktop thermometers to record the room temperature and sensitise them to heating and ventilation behaviour due to the 19-degree strategy specified by the EnSikuMaV [26], these values could also be used pragmatically for the platform.
In addition to the short-term comfort measurements, the PIAF assistance system was installed in almost 30 selected offices in Bonn and Berlin for the entire duration of the test to record the long-term development of room temperatures and indoor air quality, at least on a random basis, and to be able to assess the occupancy of the offices with a high temporal resolution. PIAF records relevant room air parameters and uses acoustic and visual signals to provide users with recommendations on correct ventilation behaviour. The background and details are described in the publication on the previous project [8]. The recorded data on room air temperature and CO2 content were used to gain further insights into the occupancy density and room temperatures, as well as to estimate reduction and savings potential. Figure 6 shows the average hourly indoor air temperature above the hourly maximum value of the carbon dioxide concentration for all offices in Bonn, divided into the pre-test period (heating period 2021/2022: circle) and the ComfortLab field test (heating period 2022/2023: cross). In the status before the ComfortLab platform was used, relatively high room temperatures dominated during the entire heating period, even when the building was not occupied. The evaluation of the comfort measurements, which could only be collected for short periods of time due to the complex and cost-intensive measurement setup, can thus be further validated with the PIAF measurements accompanying the heating period.
The evaluation of the measurements for selected periods and rooms shows that no fundamental comfort problems are to be expected in the rooms. It should be possible to reduce the temperatures to a significant extent, especially a much greater reduction during non-occupancy periods. The possibility of reducing energy consumption by lowering the heating system in residential and non-residential buildings and the practical application have been examined in detail in other studies. In principle, the application in commercial buildings is easier to realise due to the more regular use (often no occupancy on weekends and regular occupancy during the day) compared to residential buildings [27,28].

3.2. ComfortLab Platform Results

The following section summarises the results of the use of the ComfortLab platform in the pre-test in the 2021/2022 heating period and in the field test in the 2022/2023 heating period. The acceptance of the participants and the evaluation of the activity, the individual adjustments to temperature perception and the effects on room temperatures and energy consumption are explained.
The basic idea of the ComfortLab platform and the possible technical realisation was tested in the pre-test in the 2021/2022 heating period with a small number of selected participants (15 in Bonn and 11 in Berlin). An initial version of the platform was presented to them and made available for use. The findings were discussed in a workshop with the participants, and the feedback was used to adapt the platform and design for the field test in winter 2022/2023. This field test took place from 22 November 2022, to 31 March 2023, in the two BMUV buildings in Bonn and Berlin.
A total of 193 participants (111 in Bonn, 82 in Berlin) tested the platform and submitted at least one vote and the corresponding room temperature measurement, with a total of 6509 votes cast (2823 in Berlin, 3686 in Bonn). As the offices in both properties were rather sparsely occupied in both winters, the number of participants as a group of people present can be considered very high. Of the total number of participants, 44 cast at least 50 votes, 70 cast at least 30 votes and 152 cast at least 10 votes during the survey period; a minimum number of votes was considered in the respective evaluations.
To enable a comparison of the two heating periods, the tunings from the pre-test of the first heating period (winter 2021/2022), in which there were no special regulatory requirements for room heating, were compared with the tunings from the field test in the second heating period. Figure 7 shows the change in the tuning in the two test winters. In winter 2021/22, the vote in Berlin (86%) and Bonn (70%) was predominantly neutral, with the room temperatures measured by the participants at around 22 °C (the room temperatures measured using existing sensors in new buildings in Berlin are more in the region of 23 °C). The distribution of votes in the field test tended to shift slightly to the left towards the cold range, although the fine vote still represents the most frequent vote in both properties.
However, it should be noted that in the status quo, the available heating capacity was sufficient to dissipate heat even at cold outside temperatures, for example, by tilting the windows, thus maintaining comfort in terms of temperature and air quality. The average room temperature associated with the respective vote shows an expected correlation between room temperature and perception but is below the temperatures in the pre-test for the individual voting options in the winter field test and is more pronounced in Berlin than in Bonn. The “warmer” votes in the second winter in Berlin came from one participant who felt it was too warm even at just under 19 °C. This effect was not investigated further as an individual opinion.
The evaluation of the feel-good temperature (corresponding to the measured temperature with a vote of “fine”) for all participants in Figure 8 shows that there are large individual differences, with the average measured temperatures ranging between 18 °C and 23 °C. The higher temperatures come from the winter in the pre-test or offices in which, for example, the solar radiation also allowed temperatures above 19 °C in the second winter, corresponding to the limit set by the EnSikuMaV. Only offices in which at least 10 “fine” votes were submitted are listed. While some participants (e.g., office 23, 56, 60) only cast a “fine” vote for one temperature, for other participants (office 15, 86), up to a 3 °C difference in room temperature is acceptable.
The comparison of the votes of the participants who took part in both the pre-test in winter 2021/2022 and the pilot test in 2022/2023 and who cast at least five “fine” votes in Figure 9 shows that low temperatures were acceptable for most participants in the second winter and the associated measured room temperature in the test winter was just under 1 °C lower than in the previous winter. There seems to be a corresponding willingness to adapt to lower room temperatures by wearing warmer clothing, for example.
With reference to the time of day or the day of the week and the temperature perceived as fine, no significant differences can be identified. If the fine temperature is considered for mornings or afternoons or for individual days of the week, there is only a very small difference across locations. Within the heating periods, the difference between mornings and afternoons is a maximum of around 0.2 °C at the two locations, and a comparison of Monday mornings, for example (return to the office after the weekend), with other working days also shows no significant differences. Therefore, the temperature perception in this context does not appear to show any noticeable dependence on the time or day of the week. A slight dependency on the outside temperature can be seen; at outside temperatures above 10 °C, the fine temperature is on average around 21 °C, whereas at outside temperatures below 5 °C, it is closer to 20 °C.

3.3. Effects on System Operation and Energy Consumption

The winter of 2022/2023, during which the ComfortLab platform was field-tested, was overshadowed by the Russian invasion of Ukraine. Due to the resulting tense situation in the energy markets, the German government issued the EnSikuMaV to secure the energy supply. This ordinance limited the heating of public buildings to 19 °C, although higher room temperatures may also have occurred on heating days due to solar radiation, for example. In the properties investigated, the inlet temperature in the heating circuits was noticeably reduced to implement the regulation. The effects and changes in consumption in the field test winter can therefore not be directly transferred to the settings made by the ComfortLab platform. Nevertheless, the recorded data provide a revealing insight into what temperature level is appropriate in the long term and what effects this has on energy consumption. The passive house sector in Berlin is used as a reference for the development of room temperatures, as networked room temperature sensors integrated into the building automation system are installed in around 50 rooms there and high-resolution temperatures from recent years are available.
Figure 10 shows that there were no or only very slight setback times and temperature adjustments in the previous heating periods, regardless of the day of the week, as was already seen from the comfort and PIAF measurements in Bonn. For example, the evaluation of the average temperatures on weekends shows that even in the heating periods (orange-coloured areas) on weekends, hardly any temperature reductions are recognisable, and most room temperatures are above 22 °C, which were achieved by the necessary heating.
In the 2022/2023 heating period with the implementation of the 19-degree strategy, a significant reduction in the temperature level can be seen, as shown in Figure 10. This also applies analogously to night-time operation on weekdays and regular daytime operation.
This also results in a significant reduction in heating energy consumption. If the weather-adjusted consumption is considered (Bonn: exclusive heat supply by district heating, Berlin: supply of the property by district heating and additionally by means of heat pumps for the passive house sector), this has fallen by 15% (Bonn) and 30% (Berlin) compared to the weather-adjusted consumption of recent years. The weather-adjusted consumption in previous years was relatively constant with fluctuations in the low single-digit percentage range, so the reduction can be attributed to the reduction strategy implemented with the EnSikuMaV.
To assess how the settings have affected the inlet temperatures, Figure 11 shows an example of the development of the measured inlet temperatures from the heating curve setting of a heating circuit (old building front house) in Berlin.
If the design temperature is set at −10 °C and the heating limit at 15 °C, the following settings result (Table 3) in the previous heating periods and in winter 2022/2023 (field test).
The values determined result in a gradient in daytime operation of around 1.8 (before) or 1.4 (field test); i.e., the inlet temperature of the heating circuit increases by around 1.8 °C or 1.4 °C for every degree Celsius decrease in the outdoor temperature. At the assumed heating limit of 15 °C average daily outdoor temperature, a reduction in the inlet temperature of around 10 °C can be seen in daytime and setback mode. Overall, therefore, both a reduction in the level and the steepness of the heating curve can be seen. In addition to the reduction in useful energy consumption on the heat transfer side, this also has the advantage of a better coefficient of performance and an associated reduction in electricity demand resulting from lower inlet temperatures in the area supplied by heat pumps. Reducing the inlet temperature in heating systems when using heat pumps is therefore particularly advantageous from an energy point of view [29].
Due to the overlap between the implementation of the 19-degree strategy and the ComfortLab field test, the reductions in consumption due to the two possible effects cannot be directly separated. However, the evaluation of the data shows that a slight increase, which would lead to average room temperatures of just under 20 °C, would already bring about a significant improvement in the perception of temperature. Although this would eliminate a small part of the reductions in consumption achieved, it could, on the other hand, support acceptance of long-term temperature reductions to the necessary minimum and achieve further significant reductions in heat consumption. Studies in which room temperature reductions have been investigated estimate possible reductions in consumption in the range of around 6% per degree reduction in room temperature during the reduction period, although this depends on various parameters such as the building physics, the heating system and the type of building use [30,31,32]. Based on this reference value, a permanent reduction in daytime temperatures in the passive house sector in Berlin from 23 °C to 20 °C would result in potential energy savings of 18% for the period; a further reduction in temperatures on weekends and at night would also be of a similar magnitude in relation to the room temperature values. Due to the parallel 19-degree strategy and the ComfortLab field test, no explicit savings from the use of the platform are shown in this paper. This will be made up for in future applications without the influence of side effects. As the results of the final survey in the following section show, employees are willing to participate in the ComfortLab and adaptation on a permanent basis.

3.4. Results from the Final Survey

Following the test phase of the field trial, participants were invited by email to take part in a 10-min online survey to share their experiences and challenges with using the ComfortLab platform. The survey was active from 5 to 17 May 2023, and 110 people (60% Bonn; 40% Berlin) took part and completed the survey. The retrospective survey was intended to re-evaluate the results of the field test and provide the opportunity to find out about open issues that were not or not sufficiently addressed during the trial period.
Interestingly, in retrospect, almost 72% of respondents stated that the room temperature was (much) too cold overall during the winter; see the left plot in Figure 12. This is a significantly higher proportion than the detailed evaluation of the individual votes; see Figure 7. Reasons for this may include the increased participation of non-satisfied respondents in the survey. In retrospect, the overall situation may also have been perceived more negatively than the everyday situation, also in view of the fact that the room temperatures did not change. Nevertheless, almost 57% of participants felt that the 19-degree strategy was a fundamentally sensible measure to secure the energy supply, at least as a short-term and limited measure; see the right plot in Figure 12. Many participants would have liked a slight adjustment of the room temperature to 20 °C, for example, as can be seen from the evaluations of the votes. This was not possible due to the fixed specification of the 19-degree strategy. Around 45% of respondents were still able to adapt to the lower temperatures by taking measures such as wearing warmer clothing.
An important point when using the platform is the willingness of participants to take part for a sufficiently long period of time. Almost 64% of participants stated that they did not find participation disruptive in any way, and only just under 14% found participation disruptive to their workflow in any form, as shown in the left plot in Figure 13. Over 72% could imagine participating for a long period of time in general, as shown in the right plot in Figure 13. This underlines the participants’ willingness to play an active role in optimising both the temperature settings in their own offices and the associated optimisation of operational management and reduction in energy consumption.
The acceptance of the users is underlined by the fact that almost 80% of those surveyed stated that it is any kind important to them that their feedback on the indoor climate and well-being is considered by the building services and incorporated into the operational management, see the left plot in Figure 14. This goes hand in hand with the assessment of the overwhelming number of participants (57%) that similar temperatures would also be acceptable in the future; see the right plot in Figure 14. Many participants therefore require at least a slight increase in temperatures instead of an inflexible, blanket requirement as specified in the EnSikuMaV.
Overall, it can be concluded from the survey that although the across-the-board reduction has enabled significant savings to be made, this has come at the expense of the satisfaction of a large proportion of the workforce. At the same time, employees are willing to participate, even in the long term. As the 19 °C room temperature had to be implemented as a blanket requirement during the field test winter, acceptance should be even higher if the temperatures are adjusted in a targeted manner. All remaining survey questions and the results are listed in Appendix A.

4. Discussion

In this paper, a platform was presented that combines an integration of the temperature perception of office employees, technical parameters from the building automation system and recommendations for settings on the heating system for the operating personnel. This is intended to close the existing gap between the situation in offices (temperatures and individual perceptions) and technical parameters (inlet and return temperatures of heating circuits, energy consumption). The aim is to capture as broad a picture of the employees’ opinions as possible so that individual opinions are not processed and the technical operating staff can use the information for the iterative optimisation of operational management.
Fundamental comfort problems (e.g., draughts) were not identified in the reference building after exemplary sampling of the indoor air parameters and calculation of the PMV. Based on this, the room temperature was determined as a representative and comprehensive measured value for the ComfortLab platform. This was the first key question that we were able to answer for the property as an example.
With reference to the indoor climate values recorded from various available sources (PIAF measurements, comfort measurements, historical building management system data from the passive house sector in Berlin), it became apparent that the system operation in the status quo was not operated from an energy efficiency perspective, but that maximum comfort with high room temperatures was the requirement. Reduced operation, for example at night or on weekends, could not be detected to any significant extent. The exemplary measurement of indoor air quality as an indicator of building occupancy showed a relatively low attendance rate due to the COVID-19 pandemic, and reduction potential was also identified here. These results cover our second key question.
In an iterative process, the platform was implemented with displays for employees (ComfortStripes) and facility management (ComfortHub). Based on the Warming Stripes, which show the change in global temperature and were adapted to building measurement values, employees were shown a simplified representation of their own room temperatures and temperature perception over time. For facility management purposes, the individual adjustments were aggregated to provide an overall view at the heating circuit level and combined with system data (inlet temperatures, energy consumption, outside temperature). With reference to our third key question, this goal was achieved in that customised solutions were developed and tested for the two groups (office staff and facility management).
The field test in winter 2022/2023 met with great interest among employees and attracted a three-digit number of employees to participate, with over 6000 votes collected. The application shows that the ComfortLab platform can be used to record the individual temperature perception of a large number of participants with little effort. The results, overlaid by the 19-degree strategy specified in the EnSikuMaV, show that although a general reduction in the temperature level can significantly reduce energy consumption, this is accompanied in some cases by a significant deterioration in the thermal well-being of employees. Although considerable weather-adjusted savings of up to 30% were achieved in the example of the Berlin property, these are more of a short-term success. The 19-degree strategy was a temporary measure in the wake of the energy crisis in 2022. It was no longer implemented in the subsequent heating period 2023/2024, which is why it can be assumed that the settings in many properties were raised to the previous level again. This goes beyond the project duration and could therefore not be considered further. These findings only partially answer our fourth key question. Due to the time overlap between the field test and the mandatory implementation of the 19 °C strategy, the effect of temperature reduction and energy savings cannot be completely separated. Further research is required here, and a further field test without restriction to specific system settings is necessary.
The future development of the platform offers scope for some optimisations and adjustments. In the current field test, the test subjects had to read and transmit the room temperature independently. In addition to a certain susceptibility to error, this also only allows a snapshot to be taken at the time of the assessment, without taking into account and evaluating the development of the room temperature over time. Above all, this resolution is not sufficient for evaluation during non-attendance times (evenings, weekends, vacation periods). For this reason, communicative temperature sensors should be used that can automatically transmit their data to the building automation system, for example, and be integrated into the platform. Some of the rooms in the Berlin property in the passive house sector already have these, and a prototype integration into the ComfortLab platform was tested as part of the research project. In view of the requirements of the EPBD, the automated recording of indoor air parameters will be mandatory in the future for new buildings and refurbishments, so information on temperatures and air quality in rooms will be included in the building for standardised data collection. On the other hand, manual input by employees in the workflow can also increase engagement with and awareness of the platform and heating and ventilation behaviour.
An existing challenge is greater interaction with facility management and evaluation of the implementation of the strategies. Due to the 19-degree strategy, the ability of the operating staff to influence and take into account the individual perceptions of the participants when setting system parameters was greatly reduced. Therefore, the field test had to be limited to the evaluation of theoretically possible and sensible reductions. In general, the feedback from facility management on the presentation and information content was positive, and this is to be tested in more detail in the future.
The current approach of the ComfortLab platform provides an overview of the recorded room temperatures and the comfort level, aggregated at the heating circuit level. Although this makes it possible to intuitively adjust settings on the heating curve, the plan is to automate this step in the future and to automate adjustments to the heating characteristic curves for day, night and weekend operation by automatically evaluating the settings and parameter changes. By integrating the various building automation protocols with which the measured values are recorded, it is already possible to transfer setpoint specifications to the building automation system.
Another way of using the data from the ComfortLab platform could be to recommend the re-occupancy of offices based on the required comfort temperatures and the utilisation of certain heating circuits. If, for example, offices connected to a heating circuit are only very underutilised for certain days, it may make sense to lower these heating circuits and motivate employees to move to free office space in other heating circuits. Due to the very high home office rate in some cases, this will also be increasingly the case in the future and open opportunities for lowering heating levels in parts of the building. In [33], a reinforcement-learning-based system was tested that provides employees with recommendations for action to reduce energy consumption. Among other things, a move recommendation was tested in the field test, which recommends that employees move to another office to reduce overall energy consumption. This could also be implemented in the ComfortLab platform to divide heating circuits into different temperature levels.
These four possible further developments of the platform are to be pursued and tested in future projects in the Living Lab approach, thus further strengthening the application of the platform.

Author Contributions

Methodology, A.B.; validation, A.B., F.F.S.; formal analysis, A.B.; resources, A.B., C.B., A.I.W.; data curation, A.B., F.F.S.; writing—original draft, A.B.; supervision, V.G.; project administration, V.G. All authors have read and agreed to the published version of the manuscript.

Funding

This work was funded by the Federal Institute for Research on Building, Urban Affairs and Spatial Development (BBSR) on behalf of the Federal Ministry of Housing, Urban Development and Building (BMWSB) within the research program “Zukunft Bau“ (AZ 10.08.17.7-19.38a, AZ 10.08.17.7-19.38b).

Data Availability Statement

Not available due to data privacy.

Conflicts of Interest

Author Aaron Wolber was employed by the iBG Inbestergesellschaft GmbH. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Appendix A

Figure A1. Do you think that public buildings should act as role models for energy efficiency?
Figure A1. Do you think that public buildings should act as role models for energy efficiency?
Energies 17 04468 g0a1
Figure A2. For what reasons do you think public buildings should act as role models?
Figure A2. For what reasons do you think public buildings should act as role models?
Energies 17 04468 g0a2
Figure A3. How has the 19 °C requirement affected your work performance/productivity?
Figure A3. How has the 19 °C requirement affected your work performance/productivity?
Energies 17 04468 g0a3
Figure A4. How has the 19 °C requirement affected your general mood?
Figure A4. How has the 19 °C requirement affected your general mood?
Energies 17 04468 g0a4
Figure A5. Compared to previous winters—has your ventilation behavior changed?
Figure A5. Compared to previous winters—has your ventilation behavior changed?
Energies 17 04468 g0a5
Figure A6. Where is your office located?
Figure A6. Where is your office located?
Energies 17 04468 g0a6
Figure A7. Which age group do you belong to?
Figure A7. Which age group do you belong to?
Energies 17 04468 g0a7
Figure A8. Which gender do you belong to?
Figure A8. Which gender do you belong to?
Energies 17 04468 g0a8
Figure A9. Did you take part in the ComfortLab project e-mail survey?
Figure A9. Did you take part in the ComfortLab project e-mail survey?
Energies 17 04468 g0a9
Figure A10. How well did you like the daily survey overall?
Figure A10. How well did you like the daily survey overall?
Energies 17 04468 g0a10

References

  1. Energy Performance of Buildings Directive: EPBD; EU: Brussels, Belgium, 2024.
  2. Working Group on Energy Balances. Building-Related Final Energy Consumption for Room Heating, Room Cooling, Hot Water and Lighting. Available online: https://www.umweltbundesamt.de/en/data/environmental-indicators/indicator-energy-consumption-for-buildings#environmental-importance (accessed on 30 June 2024).
  3. Du, Y.; Wang, C.; Li, H.; Song, J.; Li, B. Clustering Heat Users Based on Consumption Data. Energy Procedia 2019, 158, 3196–3201. [Google Scholar] [CrossRef]
  4. Cholewa, T.; Dell’Isola, M.; Canale, L.; Ficco, G.; Michnikowski, P.; Siuta-Olcha, A.; Olszewska, A.; Sadowska, G.; Dudzińska, M.R. On the influence of heat cost allocation on operation of heating system in buildings and possible, additional decrease of supply temperature. Energy Build. 2022, 254, 111599. [Google Scholar] [CrossRef]
  5. VDI. VDI 3814 Part 1:2019-01: Building Automation and Control Systems (BACS)—Fundamentals; Verein Deutscher Ingenieure (VDI): Düsseldorf, Germany, 2019. [Google Scholar]
  6. Liedtke, C.; Baedeker, C.; Hasselkuß, M.; Rohn, H.; Grinewitschus, V. User-integrated innovation in Sustainable LivingLabs: An experimental infrastructure for researching and developing sustainable product service systems. J. Clean. Prod. 2015, 97, 106–116. [Google Scholar] [CrossRef]
  7. Baedeker, C.; Liedtke, C.; Welfens, M.J. Green Economy as a Framework for Product-Service Systems Development: The Role of Sustainable Living Labs. In Living Labs 2016; Keyson, D.V., Guerra-Santin, O., Lockton, D., Eds.; Springer International Publishing AG: Cham, Switzerland, 2016; pp. 35–52. ISBN 978-3-319-33526-1. [Google Scholar]
  8. Baedeker, C.; Piwowar, J.; Themann, P.; Grinewitschus, V.; Krisemendt, B.; Lepper, K.; Zimmer, C.; von Geibler, J. Interactive Design to Encourage Energy Efficiency in Offices: Developing and Testing a User-Centered Building Management System Based on a Living Lab Approach. Sustainability 2020, 12, 6956. [Google Scholar] [CrossRef]
  9. Lorenz, C.L.; André, M.; Abele, O.; Gunay, B.; Hahn, J.; Hensen, P.; Nagy, Z.; Ouf, M.M.; Park, J.Y.; Yaduvanshi, N.S.; et al. A Repository of Occupant-Centric Control Case Studies: Survey Development and Database Overview. Energy Build. 2023, 300, 113649. [Google Scholar] [CrossRef]
  10. Di Giuda, G.; Tagliabue, L.; Pellegrini, L.; Meschini, S.; Seghezzi, E.; Schievano, M.; Marenzi, G. Developing a Decision Support System and a Building Management System for building portfolio management. In Proceedings of the EUBIM 2022-BIM International Conference, Valencia, Spain, 18–21 May 2022. [Google Scholar] [CrossRef]
  11. Bovet, G.; Hennebert, J. Will Web Technologies Impact on Building Automation Systems Architecture? Procedia Comput. Sci. 2014, 32, 985–990. [Google Scholar] [CrossRef]
  12. Ceccarini, C.; Mirri, S.; Prandi, C. Designing Interfaces to Display Sensor Data: A Case Study in the Human-Building Interaction Field Targeting a University Community. Sensors 2022, 22, 3361. [Google Scholar] [CrossRef] [PubMed]
  13. Garg, M.; Garg, V.; Srivastava, P.; Agarwal, R. Interface design for residential energy feedback, in the Indian context. Energy Inf. 2023, 6, 12. [Google Scholar] [CrossRef]
  14. Garzia, F.; Verbeke, S.; Pozza, C.; Audenaert, A. Meeting User Needs through Building Automation and Control Systems: A Review of Impacts and Benefits in Office Environments. Buildings 2023, 13, 2530. [Google Scholar] [CrossRef]
  15. Jayathissa, P.; Quintana, M.; Sood, T.; Nazarian, N.; Miller, C. Is your clock-face cozie? A smartwatch methodology for the in-situ collection of occupant comfort data. J. Phys. Conf. Ser. 2019, 1343, 12145. [Google Scholar] [CrossRef]
  16. Pruvost, H.; Calleja-Rodríguez, G.; Enge-Rosenblatt, O.; Jimenez-Redondo, N.; Peralta-Escalante, J.-J. A recommendation system for energy saving and user engagement in existing buildings. In Proceedings of the 2021 European Conference on Computing in Construction, Online, 26–28 July 2021; University College Dublin: Dublin, Ireland, 2021; pp. 261–268. [Google Scholar]
  17. Jin, X.; Wang, G.; Song, Y.; Sun, C. Smart building energy management based on network occupancy sensing. J. Int. Counc. Electr. Eng. 2018, 8, 30–36. [Google Scholar] [CrossRef]
  18. Degen, H.; Budnik, C.J.; Chitre, K.; Lintereur, A. How to Explain It to Facility Managers? A Qualitative, Industrial User Research Study for Explainability. In HCI International 2021—Late Breaking Papers: Multimodality, eXtended Reality, and Artificial Intelligence; Stephanidis, C., Kurosu, M., Chen, J.Y.C., Fragomeni, G., Streitz, N., Konomi, S., Degen, H., Ntoa, S., Eds.; Springer International Publishing: Cham, Switzerland, 2021; pp. 401–422. ISBN 978-3-030-90962-8. [Google Scholar]
  19. Desogus, G.; Frau, C.; Quaquero, E.; Rubiu, G. From Building Information Model to Digital Twin: A Framework for Building Thermal Comfort Monitoring, Visualizing, and Assessment. Buildings 2023, 13, 1971. [Google Scholar] [CrossRef]
  20. Ličina, V.F.; Cheung, T.; Zhang, H.; de Dear, R.; Parkinson, T.; Arens, E.; Chun, C.; Schiavon, S.; Luo, M.; Brager, G.; et al. Development of the ASHRAE Global Thermal Comfort Database II. Build. Environ. 2018, 142, 502–512. [Google Scholar] [CrossRef]
  21. Lin, G.; Casillas, A.; Sheng, M.; Granderson, J. Performance Evaluation of an Occupancy-Based HVAC Control System in an Office Building. Energies 2023, 16, 7088. [Google Scholar] [CrossRef]
  22. DIN EN ISO 7730; Ergonomics of the Thermal Environment—Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort Criteria. ISO: Geneva, Switzerland, 2005.
  23. Zimmer, C. Twistid GmbH & Co. KG. Available online: https://www.twistid.de (accessed on 30 June 2024).
  24. ELK Elektronische Systeme und Softwaretechnik GmbH. BAPPUevo. Available online: https://www.bappu.de/index.php/en/products/bappu (accessed on 30 June 2024).
  25. Ed Hawkins. Warming Stripes. Available online: https://showyourstripes.info/ (accessed on 30 June 2024).
  26. Measures Laid down in the Ordinance on Securing the Energy Supply through Rapid Impact Measures: EnSikuMaV. 2022. Available online: https://www.bmwk.de/Redaktion/DE/Downloads/E/ensikumav.pdf?__blob=publicationFile&v=4 (accessed on 30 June 2024).
  27. Dolinay, V.; Vasek, L. Benefits of night temperature setback in the control strategy of the district heating system. MATEC Web Conf. 2019, 292, 1052. [Google Scholar] [CrossRef]
  28. Ben, H.; Walker, S.; Brown, C.; Kolo, I.; Falcone, G. Decarbonising heating and cooling using temperature setback and geothermal energy. J. Phys. Conf. Ser. 2023, 2600, 22015. [Google Scholar] [CrossRef]
  29. Jurkschat, S.; Sehr, F.F.; Fransen, K.; Beblek, A.; Grinewitschus, V. Measurement Data-Based Estimation of the Suitability of Existing Properties for the Operation of x to Water Heat Pumps Using a Seed of 100 Multi-Family Houses and Different Power Shifting Approaches. Energies 2023, 16, 7352. [Google Scholar] [CrossRef]
  30. Rohde, C.; Dütschke, E.; Gigli, M.; Bles, M. Behavioural Climate Change Mitigation Options; Domain Report Housing. Available online: https://climate.ec.europa.eu/document/download/49f2248d-e2cd-40b8-b6dd-1b0982ea94dc_en?filename=housing_report_en.pdf (accessed on 30 June 2024).
  31. IEA. Playing My Part: How to Save Money, Reduce Reliance on Russian Energy, Support Ukraine and Help the Planet; IEA: Paris, France, 2022. [Google Scholar]
  32. ul Deen, S.; Farooq, S. European Energy Crises Climate Action and Emerging Market of Carbon-Neutral LNG. J. Eur. Stud. (JES) 2023, 39, 33. [Google Scholar] [CrossRef]
  33. Wei, P.; Xia, S.; Chen, R.; Qian, J.; Li, C.; Jiang, X. A Deep-Reinforcement-Learning-Based Recommender System for Occupant-Driven Energy Optimization in Commercial Buildings. IEEE Internet Things J. 2020, 7, 6402–6413. [Google Scholar] [CrossRef]
Figure 1. Example of the comfort measurement setup.
Figure 1. Example of the comfort measurement setup.
Energies 17 04468 g001
Figure 2. Technical structure of the ComfortLab platform.
Figure 2. Technical structure of the ComfortLab platform.
Energies 17 04468 g002
Figure 3. (a) ComfortStripes view for employees: The bars (blue: cold, orange: warm) show the temperature perception and the measured room temperatures over time; (b) ComfortHub view for facility management: the values are aggregated at heating circuit level.
Figure 3. (a) ComfortStripes view for employees: The bars (blue: cold, orange: warm) show the temperature perception and the measured room temperatures over time; (b) ComfortHub view for facility management: the values are aggregated at heating circuit level.
Energies 17 04468 g003
Figure 4. Probability distributions of the operative temperature (average of the measured air and radiant temperature) during the different time periods.
Figure 4. Probability distributions of the operative temperature (average of the measured air and radiant temperature) during the different time periods.
Energies 17 04468 g004
Figure 5. Probability distributions of the calculated predicted mean vote during the different time periods.
Figure 5. Probability distributions of the calculated predicted mean vote during the different time periods.
Energies 17 04468 g005
Figure 6. Room temperatures and carbon dioxide concentration for different time periods.
Figure 6. Room temperatures and carbon dioxide concentration for different time periods.
Energies 17 04468 g006
Figure 7. Comparison of the frequency of the perceived (bars, left y-axis) and measured (dotted line, right y-axis) temperature for both heating periods (heating period 1: red, heating period 2: blue) for both locations (Bonn: (left plot), Berlin: (right plot)).
Figure 7. Comparison of the frequency of the perceived (bars, left y-axis) and measured (dotted line, right y-axis) temperature for both heating periods (heating period 1: red, heating period 2: blue) for both locations (Bonn: (left plot), Berlin: (right plot)).
Energies 17 04468 g007
Figure 8. Boxplot of the measured room temperatures for times with fine voting of all offices having at least 5 fine votes coloured by different heating circuits.
Figure 8. Boxplot of the measured room temperatures for times with fine voting of all offices having at least 5 fine votes coloured by different heating circuits.
Energies 17 04468 g008
Figure 9. Comparison of the measured room temperatures for participants of both heating periods (heating period 1: red, heating period 2: blue) with a vote for ‘fine’.
Figure 9. Comparison of the measured room temperatures for participants of both heating periods (heating period 1: red, heating period 2: blue) with a vote for ‘fine’.
Energies 17 04468 g009
Figure 10. Average room temperatures in the passive building in Berlin on weekends during different heating periods.
Figure 10. Average room temperatures in the passive building in Berlin on weekends during different heating periods.
Energies 17 04468 g010
Figure 11. Heating curves for different time periods in different heating seasons for one heating circuit in the Berlin building.
Figure 11. Heating curves for different time periods in different heating seasons for one heating circuit in the Berlin building.
Energies 17 04468 g011
Figure 12. Answers to the questions of how the room temperatures were perceived last winter in retrospect (a) and how useful the 19-degree strategy was to ensure the energy supply (b).
Figure 12. Answers to the questions of how the room temperatures were perceived last winter in retrospect (a) and how useful the 19-degree strategy was to ensure the energy supply (b).
Energies 17 04468 g012
Figure 13. Answers to the question of whether the survey was disruptive to the work routine (a) and whether the participants can imagine regular and long-term participation in ComfortLab in the future (b).
Figure 13. Answers to the question of whether the survey was disruptive to the work routine (a) and whether the participants can imagine regular and long-term participation in ComfortLab in the future (b).
Energies 17 04468 g013
Figure 14. (a) Answers to the questions about the extent to which participants feel that their feedback on the indoor climate is taken into account in the management of the company (a) and the acceptance of lower room temperatures in the long term (b).
Figure 14. (a) Answers to the questions about the extent to which participants feel that their feedback on the indoor climate is taken into account in the management of the company (a) and the acceptance of lower room temperatures in the long term (b).
Energies 17 04468 g014
Table 1. Statistical parameters of the operative temperature distribution.
Table 1. Statistical parameters of the operative temperature distribution.
ParameterWeekday DaytimeWeekday NighttimeWeekend
Minimum [°C]17.4415.4518.10
Maximum [°C]32.3528.3733.75
Mean [°C]23.5523.1123.39
Median [°C]23.4423.2023.26
Standard Deviation [°C]1.821.702.00
Skewness0.29−0.550.21
Table 2. Statistical parameters of the PMV distribution.
Table 2. Statistical parameters of the PMV distribution.
ParameterWeekday DaytimeWeekday NighttimeWeekend
Minimum−1.08−1.56−0.88
Maximum1.711.221.89
Mean0.280.180.23
Median0.260.200.23
Standard Deviation0.360.350.40
Skewness0.16−0.610.10
Table 3. Settings of heating curves.
Table 3. Settings of heating curves.
Outside TemperatureOperating PointResulting Inlet Temperature
−10 °CDaytime operation before85 °C
−10 °CDaytime operation field test65 °C
−10 °CSet-back operation before65–75 °C
−10 °CSet-back operation field test55 °C
15 °CDaytime operation before40 °C
15 °CDaytime operation field test30 °C
15 °CSet-back operation before35 °C
15 °CSet-back operation field test25 °C
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Beblek, A.; Sehr, F.F.; Grinewitschus, V.; Baedeker, C.; Wolber, A.I. Development and Application of a Platform for Optimising Heating System Operation Based on the Building User’s Temperature Perception. Energies 2024, 17, 4468. https://doi.org/10.3390/en17174468

AMA Style

Beblek A, Sehr FF, Grinewitschus V, Baedeker C, Wolber AI. Development and Application of a Platform for Optimising Heating System Operation Based on the Building User’s Temperature Perception. Energies. 2024; 17(17):4468. https://doi.org/10.3390/en17174468

Chicago/Turabian Style

Beblek, Andre, Florian Felix Sehr, Viktor Grinewitschus, Carolin Baedeker, and Aaron Immanuel Wolber. 2024. "Development and Application of a Platform for Optimising Heating System Operation Based on the Building User’s Temperature Perception" Energies 17, no. 17: 4468. https://doi.org/10.3390/en17174468

APA Style

Beblek, A., Sehr, F. F., Grinewitschus, V., Baedeker, C., & Wolber, A. I. (2024). Development and Application of a Platform for Optimising Heating System Operation Based on the Building User’s Temperature Perception. Energies, 17(17), 4468. https://doi.org/10.3390/en17174468

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop