Next Article in Journal
Efficiency at Maximum Power of the Low-Dissipation Hybrid Electrochemical–Otto Cycle
Previous Article in Journal
Preference Structure on the Design of Hydrogen Refueling Stations to Activate Energy Transition
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Experimental Calibration and Validation of a Simulation Model for Fault Detection of HVAC Systems and Application to a Case Study

1
Department of Architecture and Industrial Design, University of Campania Luigi Vanvitelli, 81031 Aversa, Italy
2
C.I.R.A. (Italian Aerospace Research Centre), 81043 Capua, Italy
*
Author to whom correspondence should be addressed.
Energies 2020, 13(15), 3948; https://doi.org/10.3390/en13153948
Submission received: 30 June 2020 / Revised: 27 July 2020 / Accepted: 28 July 2020 / Published: 1 August 2020
(This article belongs to the Section G: Energy and Buildings)

Abstract

:
Automated fault detection and diagnostics (FDD) could provide a cornerstone for predictive maintenance of heating, ventilation and air-conditioning (HVAC) systems based on the development of simulation models able to accurately compare the faulty operation with respect to nominal conditions. In this paper, several experiments have been carried out for assessing the performance of the HVAC unit (nominal cooling/heating capacity of 5.0/5.0 kW) controlling the thermo-hygrometric comfort inside a 4.0 × 4.0 × 3.6 m test room at the Department of Architecture and Industrial Design of the University of Campania Luigi Vanvitelli (Italy); then, a detailed dynamic simulation model has been developed and validated by contrasting the predictions with the measured data. The model has also been used to analyze the dynamic variations of key parameters associated to faulty operation in comparison to normal performance, in order to identify simplified rules for detection of any non-optimal states of HVAC devices. Finally, the simulated performance of the HVAC unit has also been investigated while serving a typical Italian building office with and without the occurrence of typical faults with the main aim of assessing the impact of the faults on thermo-hygrometric comfort conditions as well as electric energy consumption.

1. Introduction

HVAC (heating, ventilation and air-conditioning) systems including air-handling units (AHUs) for space heating, space cooling and ventilation of buildings represent one of the most significant sources of the world’s energy demand [1,2]. In more detail, the residential and tertiary sectors are responsible for nearly 40% of energy use [3] and globally implemented energy efficiency measures in the building sector could deliver CO2 emissions savings as high as 5.8 billion tons by 2050 [3].
Due to lack of proper maintenance, failure of components or incorrect installation, HVAC units are frequently run in faulty conditions where a fault is intended as an unpermitted deviation of at least one characteristic property of the system from the acceptable, usual, standard condition; a study conducted on more than 55,000 HVAC systems, showed that 90% of them runs with one or multiple faults [4]. Faults could result in inefficient usage of energy and/or uncomfortable environment, unless corrective action is taken. Yu et al. [5] highlighted that (i) typical faults of HVAC units are responsible for 25–50% of energy waste in buildings located in the United Kingdom and (ii) this inefficiency could be strongly decreased below 15% thanks to early detection and identification of faulty operation [5]. Yan et al. [6] estimated that the identification and diagnosis of faults in HVAC units can lead to potential savings of about 30%.
Companies follow different maintenance programs in order to guarantee the reliability of systems and reduce the costs; generally, a reactive or a preventive maintenance is adopted. In the case of reactive maintenance, a system is used up to its limits and the repairs are performed only after the system failure; this kind of approach is not convenient with reference to complex systems mainly due to the fact that repairing the damaged parts after failure could (i) be extremely expensive and (ii) cause safety issues. For this reason, it could be useful to prevent the failures by performing regular checks on the equipment by means of preventive maintenance; in this case, the systems are inspected and maintained at fixed time intervals, independent of their actual condition. However, one of the main challenges of this approach is to determine when the maintenance has to be performed; it has to be conservative in order to prevent safety issues as well as reduce the costs of failures, but scheduling the maintenance very early could mean wasting system life that is still usable. The aforementioned critical points associated to both reactive and preventive maintenance programs highlight how “predicting” the failures of components could be extremely important in minimizing the related costs, optimizing the performance as well as avoiding safety issues.
Fault detection and diagnosis (FDD) [5,7,8,9,10] methods can monitor the operation of HVAC components as well as detect and predict the presence of the defects (deviations from normal or expected operation) causing a faulty operation. Ideally, FDD systems could also resolve (diagnose) the type of problem and/or identify its location, giving instructions for undertaking corrective actions. Efficient FDD methods could detect faults before the building occupants notice the effects and they would reduce the repair and maintenance costs of the plants. In addition, these tools could provide manufacturers with information about the design and sales of devices with the aim of identifying where enhancements are required. Moreover, improving the operation of HVAC systems could significantly reduce energy consumption and related emissions. Finally, integrating FDD systems into modern HVAC plants could improve the system efficiency as well as the indoor thermo-hygrometric conditions.
FDD methods are based on the use of accurate instruments measuring key parameters, the variation of which in comparison to a “nominal/healthy” trend is assumed as a symptom of defects; once the test quantity reaches some predetermined levels that reflect the seriousness of the defect requiring corrective actions to take place, the test quantity is set into an alarm state (symptom) and reasoning is started to find the cause of the “alarm-symptom–fault” chain [10,11,12]. In order to apply FDD methods to HVAC units or components, it is necessary to compare real behavior of the systems to the “nominal/healthy” operation without faults that can be modeled by means of a simulation software and/or artificial intelligence techniques. Simulation tools represent a useful approach not only in the design phase, but also in combination with FFD methods thanks to the fact that they could have the required accuracy to predict thermal/cooling loads, energy consumption and quality of indoor environment of buildings, thus allowing for the detection of any non-optimal states of performance by comparing the simulation results with the normal data.
One of the main disadvantages of the FDD approach is that it could require a continuous monitoring with specifically devoted instrumentation and, therefore, the aforementioned benefits alone could fail in justifying the cost of implementing FDD methods [5,12]. As a consequence, in order to obtain a wider utilization of FDD systems, the benefits of this approach throughout the value chain have to be assessed in greater detail. Moreover, the extra investment cost associated with the application of FDD systems should be shared by different parties (electric-grid operators, manufacturers, dealers, installers, service companies, customers) and economic incentives should be put in place to support and speed up their diffusion [5,12]. The prediction of faulty operation is also problematic since some types of faults cannot be easily and practically introduced, and the artificial implementation of faulty conditions may enhance the energy costs or the discomfort of occupants in the built environment; an additional issue is represented by the fact that a strong anomaly detection capability is significantly dependent on the accuracy of measurement sensors. Finally, it should be underlined that a robust data analytics-based FDD tool should be able to automatically prevent the generation of false alarms (for example due to high uncertainty of the instrumentation) that could negatively affect the methods [5,12]. Therefore, additional studies have to be carried out in order to better highlight and evaluate the potential applications and benefits/drawbacks associated with FDD techniques.
FDD techniques have been used for many years in aerospace, nuclear and industrial sectors, and their use in building operation and control applications is becoming more widespread [5,13,14,15,16,17,18]. Several methods and procedures aiming at optimizing the application of FDD tools have been developed in the Annex 25 of the International Energy Agency’s (IEA) Energy Conservation in Buildings and Community System (ECBCS) [13] and then applied to existing buildings in the IEA ECBCS Annex 34 [14]. Furthermore, since 2010 studies on FDD systems steadily increased. Several reviews of FDD studies focusing on AHUs are already available in the literature [5,15,16,17,18]. The literature review demonstrated that a number of recent studies have made significant contributions to the advancement of FDD methods in the building sector, how active the FDD research field is, as well as the high contribution that data analytics methodologies bring. However, the outcomes of these reviews highlight that the application of FDD methods is still in its early stage and there are significant research gaps to be further investigated. In particular, Kim and Katipamula [16] highlighted that:
  • much more research is needed with reference to the identification of threshold values to be used for the detection of faults in the rule-based FDD techniques in order to avoid the generation of false alarms or the mis-identification of faults;
  • the estimation of severity of faults and their energy impact has been poorly assessed; therefore, building operators lack the knowledge to decide whether or not to address and/or repair the faults;
  • additional investigations should be performed with the aim of adapting the FDD methods to the variations in the configuration of HVAC units.
In addition, Katipamula and Brambley [17,18] indicated that the following points require additional attention:
  • a few papers have been published to date on prognostics for HVAC systems; therefore, a significant lack of information based on which decisions can be made regarding the transition from reactive/preventive maintenance as practiced today to future applications of predictive maintenance is recognized;
  • there is a need to more clearly assess the potential drawbacks and benefits associated to FDD applications, identify benchmarks for acceptable costs and provide market information about FDD methods in order to better demonstrate the value of these technologies;
  • additional research is needed in order to further develop the selection and specialization of FDD methods to the constraints of the built environment as well as a more extensive testing of FDD methods to different systems and components adopted in buildings.
An innovative multi-sensorial laboratory, called the SENS-i Lab, has been set-up at the Department of Architecture and Industrial Design of the University of Campania Luigi Vanvitelli (Italy). The laboratory is equipped with an AHU (nominal cooling/heating capacity of 5.0/5.0 kW) aiming to control the thermo-hygrometric comfort inside a 4.0 × 4.0 × 3.6 m test room; the AHU is fully instrumented in order to monitor and control its operation. In this paper, several experiments have been carried out for assessing the performance of the AHU upon varying the boundary conditions; then, a detailed dynamic simulation model has been developed by means of the software TRNSYS [19] and validated by contrasting the predictions with the measured data. Then, the model has been used to analyze and investigate the dynamic variations of key parameters associated to faulty operations in comparison to “normal” performance, in order to identify simplified rules for detection of any non-optimal states of AHU. Finally, the performance of the AHU has also been investigated while serving a typical Italian building office with and without the occurrence of typical faults of AHUs with the main aim of assessing the impact of faults on comfort conditions as well as electric energy consumption. This study aims at covering some of the most important research gaps in the FDD research field and its main objectives can be summarized as follows: (i) suggest threshold values or simplified rules to identify typical HVAC faults in order to avoid the generation of false alarms or the mis-identification of faults; (ii) assess the potential drawbacks and benefits associated to FDD applications in order to better identify the value for these technologies; (iii) estimate the severity of typical faults and their energy impacts in order to help the building operators in understanding whether or not to address and/or repair the faults.

2. Description of the Laboratory and Heating, Ventilation and Air-Conditioning (HVAC) System

The SENS i-Lab is an innovative, multi-sensorial and multi-purpose laboratory, located at the Department of Architecture and Industrial Design of the University of Campania Luigi Vanvitelli (Aversa, Italy, latitude: 40°58′21″ N, longitude: 14°12′26″ E). The laboratory consists of an Integrated Test Room, allowing in vivo or in virtual, subjective tests to be carried out where the human experience of urban/rural or industrial environments, architectures and products, can be measured. The lab is served by an HVAC system including an air-handling unit able to control the indoor air temperature, relative humidity, velocity and quality inside the Integrated Test Room The room is characterized by a floor area of 16.0 m2 with a height of 3.6 m; it is composed of four internal vertical walls, a horizontal ceiling as well as a horizontal floor; two of the vertical walls as well as the floor are integrated with radiant panels for heating/cooling purposes; a door is installed on the south-oriented wall. It is located inside a large open space of the department, so that it is not directly affected by the external climatic conditions. Figure 1 depicts the floor plan of the Integrated Test Room together with an internal view, while Table 1 describes the number and characteristics of layers composing the envelope of the Integrated Test Room.
Figure 2 reports the schematic of the AHU serving the Integrated Test Room.
The AHU is composed of the following main components: supply air fan (SAF), return air fan (RAF), pre-heating coil (PreHC), cooling coil (CC), steam humidifier (HUM), post-heating coil (PostHC), cross flow static heat recovery system (HRS), single-stage vapor-compression air-to-water electric refrigerating unit (supplying the CC), single-stage vapor-compression air-to-water electric heat pump (supplying both the PreHC and PostHC), valves (VPreHC, VPostHC, VCC, VHUM) regulating the heat carrier fluid flow rate entering, respectively, the PreHC, PostHC, CC and HUM, outside air damper (DOA), return air damper (DRA), exhaust air damper (DEA), damper of heat recovery system (DHRS), outside air filter (OAFil), return air filter (RAFil), supply air filter (SAFil). Two 0.08 × 0.18 cm return air intake vents (RAV) are installed on the south-oriented wall and two 0.08x0.18 cm return air intake vents are installed on the north-oriented wall in order to extract air from the indoor space to be returned to the air-handling unit; a 0.60 × 0.60 cm square ceiling swirl diffuser is installed on the ceiling of the room and used as a supply air vent (SAV).
Table 2 describes the main characteristics of the main AHU components. The heat carrier fluid is a mixture of water and ethylene glycol (90/10% by volume). The hot heat carrier fluid supplying both the pre-heating coil as well as the post-heating coil is obtained thanks to the operation of the heat pump, while the refrigerating system is used to provide the cold heat carrier fluid flowing inside the cooling coil. The model ANL 050HQ [20] is used as a vapor compression electric heat pump (HP), while the model ANL 050Q [20] is adopted as a refrigerating system (RS). A 75 L cold thermal energy tank (CT) as well as a 75 L hot thermal energy storage (HT) are coupled with the refrigerating unit and the heat pump, respectively, in order to store the thermal/cooling energy of the heat carrier fluid.
The coefficient of performance (COP, i.e., the ratio between thermal output and power input) of the air-to-water vapor compression heat pumps as well as the energy efficiency ratio (EER, i.e., the ratio between cooling output and power input) of the air-to-water vapor compression refrigerating systems strongly depend on the outside air temperature as well as the supply temperature of the heat carrier fluid. In particular, given the outside temperature, the COP of the heat pumps decreases upon increasing the supply temperature of the heat carrier fluid; on the other hand, given the supply temperature of the heat carrier fluid, the COP of the heat pumps increases at increasing the outside air temperature. The EER of the refrigeration units increases upon increasing the supply temperature of the heat carrier fluid for a given outside air temperature; on the other hand, the EER of the refrigeration units decreases upon increasing the outside air temperature for a given supply temperature of the heat carrier fluid. Figure 3a,b indicate the values of COP and EER (provided by the manufacturer [20]) of the heat pump (model ANL 050HQ [20]) and the refrigeration system (model ANL 050Q [20]), respectively, used in this study as a function of both outside air temperature and supply fluid temperature. In particular, a supply fluid temperature between 30 °C and 50 °C together with an outside air temperature in the range −10–20 °C are considered for the HP; a supply fluid temperature between 20 °C and 45 °C together with an outside air temperature in the range −6–18 °C are considered for the RS. According to the manufacturer’s data [20], the COP of the heat pump varies between 1.91 and 6.11, while the EER of the RS is in the range 2.40–6.52; in greater detail, the COP of the heat pump investigated in this paper ranges between 2.11 and 4.06 for a supply fluid temperature of 45 °C, while the EER of the refrigerating system considered in this study is in the range 2.53–5.73 for a supply fluid temperature of 7 °C.
The AHU is fully equipped in order to monitor, control and record the main operating parameters of the system. The main characteristics of the sensors are reported in Table 3.
The end-users can manually set: the desired targets of both the indoor air temperature (TSP,Room) and relative humidity (RHSP,Room) to be achieved inside the test room, the deadbands DBT and DBRH for both TSP,Room and RHSP,Room, respectively, the velocity of both the return air fan (OLRAF) and the supply air fan (OLSAF), the opening percentages of the return air damper (OPDRA), the outside air damper (OPDOA), the exhaust air damper (OPDEA) and the static heat-recovery system damper (OPDHRS). The air flow rate moved by the supply air fan can be varied between 0 (OLSAF = 0%) and 4800 m3/h (OLSAF = 100%), while the air flow rate of the return air fan is in the range from 0 (OLRAF = 0%) to 2050 m3/h (OLRAF = 100%). The parameters OPDRA, OPDOA and OPDEA can be varied in the range 0–100%, where 100% means that the dampers are fully open. The parameter OPDHRS can be set to 100% (the heat recovery does not occur) or 0% (the heat recovery from return air flow takes place).
A specific control logic has been developed by the manufacturer in order to control the operation of the system and achieve the desired targets. Table 4 describes the conditions controlling the activation and deactivation of the main components of the AHU. Even if the AHU is equipped with a PreHC, this component is never used during normal operation (always de-activated).
The heating coil is devoted to controlling the temperature inside the test room; therefore, its operation is based on the difference between the target temperature inside the test room TSP,Room (set by the end-users) and the current temperature of return air TRA, with a given deadband DBT.
The cooling coil is devoted to satisfying the requirements in terms of both temperature and relative humidity inside the test room; as a consequence, its activation depends on both the difference between target (TSP,Room) and current (TRA) temperatures of return air (with a given deadband DBT) as well as the difference between target (RHSP,Room) and current (RHRA) relative humidity of return air (with a given deadband DBRH).
The humidifier is devoted to enhancing the relative humidity inside the test room; its operation is based on the difference between the target of relative humidity RHSP,Room inside the test room set by the end-users and the current relative humidity of return air RHRA, with a given deadband DBRH.
The operation of the humidifier as well as the flow rate of the heat carrier fluid entering the post-heating coil or the cooling coil can be continuously adjusted between 0% and 100% depending on the differences between the target and current values of parameters to be controlled. In particular, the heat carrier fluid flow rate flowing into the cooling coil or the post-heating coil can ben varied between 0 (OPV_CC/OPV_PostHC = 0%) and 0.860 m3/h (OPV_CC/OPV_PostHC = 100%), while the steam mass flow rate can be modulated from 0 (OPV_HUM = 0%) up to 5 kg/h (OPV_HUM = 100%).
The operation of both the refrigerating unit and the heat pump is controlled in order to maintain the desired temperatures inside the related tanks; in particular, the refrigeration device operates in order to maintain a temperature TCT of 7 °C (with a deadband of 1 °C) inside the cold tank, while the heat pump is activated with the aim of achieving a temperature THT of 45 °C (with a deadband of 1 °C) inside the hot tank.

3. Experimental Tests

Firstly, the air velocity or volumetric flow rate of supply air, return air, outside air and exhaust air) in front of the air vents have been measured upon varying the operating conditions. The results of measurements are reported in Table 5 as a function of OPSAF, OPRAF, OPDRA, OPDOA, OPDEA OPDHRS. The air volumetric flow rate measurements have been performed by using the TSI ProHood Air Capture Hood model PH731 [24], characterized by a measuring range from 42 to 4250 m3/h together with an accuracy ±12 m3/h, whereas the air velocity measurements have been performed by using the hot wire anemometer KIMO AMI 301 [25], characterized by a measuring range from 0 to 30 m/s together with an accuracy of ±3% of readings.
Four experiments have been carried out to investigate the HVAC behavior during steady-state and transient operations. Table 6 describes the operating conditions of the tests in terms of target indoor air temperature TSP,Room, target indoor air relative humidity RHSP,Room, initial indoor air temperature TRoom_initial and indoor relative humidity RHRoom_initial in the test room, OLRAF, OLSAF, DRA, DOA, DEA and duration. The experiments were carried out by measuring the parameters indicated in Table 3 every minute and maintaining constant the following conditions: DBT = 1 °C, DBRH = 5%, and OPDHRS = 100%. During all tests the following parameters have been maintained constant: OLRAF = 50% and OLSAF = 50%; during the tests n. 1, 2, 3 and 4 the following parameters have been maintained constant: OPDRA = 100%, OPDOA = 20% and OPDEA = 20%; during the tests n. 5 and 6 the opening percentages of the return air damper, the outside air damper and the exhaust air damper have been modified with respect to the tests n. 1, 2, 3 and 4.
During the test n.1 the target for indoor air relative humidity is fixed at 50%, while the target for indoor air temperature is gradually increased from 22 °C up to 26 °C; during the test n. 2 the target for indoor air relative humidity is maintained at 50%, while the target for indoor air temperature is gradually reduced from 26 °C up to 22 °C; during the test n. 3 the target for indoor air temperature is fixed at 22 °C, while the target for indoor air relative humidity is gradually increased from 60% up to 70%; during the test n. 4 the target for indoor air temperature is maintained at 28 °C, while the target for indoor air relative humidity is gradually reduced from 55% up to 45%. During the tests 5, 6 and 7 the target of indoor air temperature is set to 22 °C, while 50% is the target in terms of relative humidity inside the test room. Figure 4a–g report the experimental values of TRA, TSA, TOA, TA,out,CC, TBEA, RHRA, RHSA, RHBEA measured during the tests described in Table 6 as a function of the time, together with the values of TSP,Room and RHSP,Room.
The experimental data highlighted that the HVAC system is able to maintain the desired indoor air temperature and relative humidity inside the test room. In fact, the percentages of time during which the indoor air temperature is within the given deadband (1 °C) around the given target with respect to the entire duration of each test have been calculated; they are equal to 70.32%, 78.27%, 81.40%, 100%, 89.66%, 93.33% and 80.65% for the tests 1, 2, 3, 4, 5, 6 and 7, respectively. In addition, the percentages of time during which the indoor air relative humidity is within the given deadband (5%) around the given target with respect to the entire duration of each test have been calculated; they are equal to 91.57%, 92.20%, 65.12%, 79.31%, 94.83%, 78.33% and 70.97% during the tests 1, 2, 3, 4, 5, 6 and 7, respectively. The results of calculation highlight that the aforementioned percentages are quite high, demonstrating a good capability of the HVAC unit to accurately control the thermo-hygrometric indoor conditions. The above-mentioned percentages are lower than 100% due to the periods during which the AHU operates under transient conditions. In particular, the transient operation typically occurs when the AHU is started-up and is approaching the steady-state conditions, or when it is shut down or disturbed from its non-transient regime; these disturbances could be caused by either variation of thermal/cooling loads or by feedback controls; during transient periods some variables can exhibit strong variation in short time and a significant temporally lagged response with respect to the control signals.

4. Simulation Models

Accurate numerical models have been adopted in this study in order to simulate the plant components with the aim of taking into account (i) the thermal behavior of the test room, (ii) the partial load operation of all components, (iii) the coupling between heating/cooling loads and simulation outputs of components, and (iv) the logics controlling the operation of the HVAC.
The software TRaNsient SYStems (TRNSYS) 17 [19] has been adopted in this study. In this program, plant components are simulated by means of mathematical models (called “Types”), which can be linked among themselves, validated based on experimental data. Table 7 lists the main TRNSYS Types used in this paper for modeling the system components; they have been selected from the TRNSYS libraries and calibrated based on data provided by the manufacturers and/or results derived from the updated scientific literature.
Figure 5 reports a screenshot of the model developed in TRNSYS environment, representing the main circuits by means of different colors. In particular, in this figure the circuit of the hot heat carrier fluid produced by the heat pump and supplying both the pre-heating coil and the post-heating coil has been indicated in red; the circuit of the cold heat carrier fluid produced by the refrigeration unit and supplying the cooling coil has been depicted in blue; finally, the circuit of the moist air through the AHU as well as the test room is highlighted in green. The other TRNSYS Types’ connections are characterized by dashed black lines.
The Type 56 has been considered to take into account the thermal behavior of the integrated test room.
The Type 941 has been adopted to model and simulate the performance of both the refrigeration system (model ANL 050Q [20]) and the heat pump (model ANL 050HQ [20]) serving the AHU of the test room; this model is able to calculate and provide as outputs the cooling power (refrigeration unit), the heating power (heat pump), the power absorbed by the compressor as well as the temperature of both heat carrier fluid and air. The calculation is based on user-supplied data files provided as inputs and containing manufacturer data related to both heating/cooling capacity and power as a function of the outside air temperature and supply fluid temperature. In this study, the performance data measured by the manufacturer [20] and reported in Figure 3a,b have been provided as inputs to the Type 941 in order to calculate the desired outputs.
Both the refrigeration unit as well as the heat pump are equipped with a 75 L thermal energy tank for storing the cold and hot heat carrier fluid, respectively. The Type 534 has been used in this study for modeling the storage. It allows to divide the tanks into fully-mixed sub-volumes; in particular, in this study, 10 isothermal temperature layers have been selected for both storages in order to accurately take into consideration the thermal stratification (the layer 1 is located at the top, while the layer 10 is positioned at the bottom). In particular, the temperature at level 2 of the cold tank has been considered for controlling the operation of the refrigeration unit, while the temperature at level 8 of the hot tank has been used for operating the heat pump.
The Types 753e and 508c have been used for modeling the operation of the post-heating coil and the cooling coil, respectively; in these types, the air is heated/cooled passing over a coil where a hotter/colder heat carrier fluid is flowing. These models use the “bypass fraction approach” to estimate the outlet conditions of both air and fluid; this means that a fraction of the air stream that bypasses the coil is specified (the remaining part of the air stream is completely unaltered by the thermal interaction with the coil); then the bypassed air stream is mixed with the conditioned air stream and these conditions are placed on the coil outlet node. According to the information provided by the manufacturers, a by-pass fraction of 15% has been assumed for the cooling coil, while it has been considered equal to 10% for the post-heating coil.
The humidifier has been simulated with the Type 641, where the outlet air state is defined based on an energy balance by neglecting the heat losses. According to the manufacturer data, a constant power consumption of 3.7 kW has been considered while the humidifier is activated.
Type 667b uses a “constant effectiveness–minimum capacitance” approach to model the air-to-air heat recovery device in which two air streams are passed near each other so that energy may be transferred between the streams. According to the manufacturer’s data, a sensible effectiveness of 79.5%, together with a latent effectiveness equal to 47.0%, have been adopted.
The Type 642 has been considered for modeling the fans, allowing motor heat losses and electric consumption to be taken into the related motor efficiency.
The Type 607 models the geometry of air ducts by considering the heat losses to the surroundings; a thermal resistance of 0.25 m2K/W has been considered for all air ducts in this study. The Type 31 allows the geometry of pipes to be modelled, taking into account the thermal behavior of fluid flow; in this paper, a heat loss coefficient equal to 4.0 W/m2K has been assumed for all pipes.
Types 646 and 648 have been used for modeling the dampers that split an inlet air flow into fractional outlet air flows and vice versa. Types 647 and 649 have been adopted for modeling the valves that split an inlet fluid flow into fractional outlet fluid flows and vice versa.
The control logics for operating the plant components are described in Table 4. They have been implemented by means of on/off differential controllers and Proportional–Integral–Derivative (PID) controllers.
The on/off differential controllers have been modeled by means of Type 2, generating a control function (1 or 0) that is defined depending on both (i) the difference between upper and lower deadband values as well as (ii) the input control function associated to the previous timestep. In this paper, Type 2 has been used to activate/deactivate the heat pump (HP) as well as the refrigerating system (RS) according to the difference between the target and the current level of temperatures inside the hot (level 8) and cold (level 2) tanks, respectively. Type 2 has also been used to activate/deactivate the PID controllers.
Type 23 has been considered for simulating the operation of the PID controllers; these components specify the control signal required to maintain the controlled variables at the target conditions, where the control signals are proportional to the tracking error, as well as to the integral and the derivative of that tracking error. In TRNSYS there are two Types that could be used for modelling the PID controllers: Type 23 and Type 22. In this study, Type 23 has been used instead of Type 22 mainly because of the facts that: (i) Type 22 can operate as an iterative controller only, while Type 23 can operate as a non-iterative or an iterative controller; (ii) the performance of Type 22 is sensitive to some simulation settings (order of components as well as convergence tolerances). The PID controllers operate the valves Vcc (supplying the cooling coil), VPostHC (supplying the post-heating coil), and VHUM (supplying the humidifier); the main characteristics of the PID controllers used in this study are described in Table 8.
Type 15, used for modeling the outside climatic conditions, allows to read data at regular time periods from an external weather data file (EnergyPlus) [26] corresponding to the city of Naples (Italy).
Type 33e uses as inputs the dry bulb temperature and relative humidity of moist air and return the other corresponding properties.

5. Model Validation

The model of the HVAC developed in the TRNSYS environment has been validated by contrasting the simulation results with the experimental data described in the previous section. The whole experimental database consists of 1034 points. The simulations have been performed by assuming the following inputs equal to the measured data: desired targets of indoor air temperature (TSP,Room) and indoor air relative humidity (RHSP,Room), velocity of return air fan (OLRAF), supply air fan (OLSAF), opening percentages of return air damper (OPDRA), outside air damper (OPDOA), exhaust air damper (OPDEA), heat recovery system damper (OPDHRS), external air temperature (TOA), deadbands (DBT and DBRH) of targets of both indoor air temperature and relative humidity. The simulations have been carried out with a time-step equal to 1 min (according to the measurement frequency). Figure 6a–g compare the predicted and experimental outputs in terms of return air temperature (corresponding to the temperature inside the test room) and return air relative humidity (corresponding to the relative humidity inside the test room) for the tests 1, 2, 3, 4, 5, 6, 7 (described in Table 6 and Figure 4), respectively.
The experimental results have been compared with the simulation outputs to assess the accuracy of the calibration by using the following metrics quantifying the instantaneous differences: the average error ε ¯ ; the average absolute error | ε ¯ | ; the root mean square error εRMS. These parameters are defined as follows:
ε i = g pred , i g exp , i
ε ¯ = i = 1 N ε i / N
| ε ¯ | = i = 1 N | ε i | / N
ε RMS = i = 1 N ( ε i ε ¯ ) 2 N
where gpred,i and gexp,i are, respectively, the predicted and measured values at time step i and N is the number of points. Table 9 summarizes the values of ε ¯ , | ε ¯ | and ε RMS .
The maximum instantaneous errors ε i are about 1.55 °C and about 11.82%, respectively, for TRA and RHRA; these deviations are mostly related to a few points occurring during transient operation caused by a change of the desired targets. The results reported in Table 9 highlight that, with reference to the whole database, the values of ε ¯ , | ε ¯ | and ε RMS are equal to −0.05 °C, 0.31 °C and 0.39 °C, respectively, for TRA and equal to −1.97%, 3.26% and 3.72%, respectively, for RHRA. The lowest values of ε RMS in terms of TRA and RHRA correspond, respectively, to test 4 and test 5; the largest values of ε RMS in terms of TRA and RHRA are associated, respectively, to tests 3 and 4. The deviations between measured and simulated data are fully coherent with the accuracy of the instruments, demonstrating that predicted outputs agree very well with experimental observations. Therefore, it can be stated that the model gives an accurate representation of the dynamic and steady-state HVAC performance and it can also be usefully adopted in combination with FFD methods for the detection of any non-optimal states of HVAC systems under predictive maintenance programs.

6. Faults Analysis and Results

In this section, the experimental performance (described in the Section 3) has been simulated by intentionally introducing 6 different typical soft faults into the operation of the HVAC; the simulations have been performed by running the calibrated and validated model described in the previous Section 5, while assuming the values of the following inputs equal to the experimental data measured during the tests performed on the AHU operating under normal condition: external air temperature TOA, air temperature TBEA and relative humidity RHBEA around the room, target room temperature TSP,Room and target room relative humidity RHSP,Room, temperature deadband DBT, relative humidity deadband DBRH, velocity of the return air fan OLRAF, velocity of the supply air fan OLSAF, opening percentage of the exhaust air damper OPDEA, opening percentage of the outside air damper OPDOA, opening percentage of the return air damper OPDRA and opening percentage of the heat-recovery system damper OPDHRS. Then, the experimentally measured performances of the AHU operating without faults have been compared with those associated to the operation in the cases of faults occurrence. The comparison has been performed in order to (i) analyze the specific behaviors of key parameters associated to each fault, and (ii) assess the differences in terms of thermo-hygrometric comfort hours as well as electric energy consumption caused by the fault occurrence.
Even though each component of an AHU can be potentially corrupted by a fault, the most common faults can affect sensors (e.g., offset in the measurement), controlled devices (e.g., blockage or leakage of air damper or coil valves), equipment (e.g., coil fouling or reduced capacity, duct leakage, fan complete failure or deviation in the pressure drop or belt slippage) and controllers (e.g., unstable or frozen control signal for dampers, coils or fan) [27]. In particular, in this paper the following 6 typical soft faults, which are independent of each other, have been taken into account:
Fault 1):
positive offset of return air temperature sensor (+2 °C);
Fault 2):
negative offset of return air temperature sensor (−2 °C);
Fault 3):
positive offset of return air relative humidity sensor (+10%);
Fault 4):
negative offset of return air relative humidity sensor (−10%);
Fault 5):
return air damper is stuck (fully closed);
Fault 6):
outside air damper is stuck (fully closed).
Fault 1 means that the measured return air temperature is 2.0 °C higher than the true value; fault 2 means that the measured return air temperature is 2.0 °C lower than the right value; fault 3 means that the measured return air relative humidity is 10.0% higher than the true value; fault 4 means that the measured return air relative humidity is 10.0% lower than the true value; fault 5 means that the return air damper is stuck in the fully closed position; fault 6 means that the outside air damper is stuck in the fully closed position.
Figure 7, Figure 8, Figure 9, Figure 10, Figure 11 and Figure 12 report the differences between normal operation and faulty operation in terms of return air temperature TRA, supply air temperature TSA, return air relative humidity RHRA and supply air relative humidity RHSA as a function of the time. In particular, the following parameters are reported in Figure 7, Figure 8, Figure 9 and Figure 10:
Δ T RA = T RA , pred , w / o _ fault T RA , pred , fault
Δ T SA = T SA , pred , w / o _ fault T SA , pred , fault
Δ RH RA = RH RA , pred , w / o _ fault RH RA , pred , fault
Δ RH SA = RH SA , pred , w / o _ fault RH SA , pred , fault
where TRA,pred,w/o_fault, TSA,pred,w/o_fault, RHRA,pred,w/o_fault, RHSA,pred,w/o_fault, are, respectively, the predicted values under normal operation, while TRA,pred,fault, TSA,pred,fault, RHRA,pred,fault, RHSA,pred,fault represent the predictive values in the case of fault occurrence. In Figure 11 the difference (TOA,pred-TMA,pred) between the predicted outside air temperature TOA,pred and the predicted temperature of the air entering the supply air filter TMA,pred, with and without the occurrence of faults 5, are reported. Figure 12 shows the difference (TRA,pred-TMA,pred) between the predicted return air temperature TRA,pred and the predicted temperature of the air entering the supply air filter TMA,pred, with and without the occurrence of faults 6. Figure 7a, Figure 8a, Figure 9a, Figure 10a, Figure 11a and Figure 12a refer to the operating conditions of the experimental tests 1 and 2 (see Table 6), while Figure 7b, Figure 8b, Figure 9b, Figure 10b, Figure 11b and Figure 12b correspond to the boundary conditions of the experimental tests 3, 4, 5, 6 and 7 (see Table 6). Each figure reports the experimental trends obtained in the case of operation without faults in comparison with the trends of the same key parameters while only one of the aforementioned 6 faults is occurring. The target values of both the indoor air temperature TSP,room and relative humidity RHSP,room are also reported in the same figures.
The trends of key parameters under fault 1 are reported in Figure 7a (tests 1 and 2) and Figure 7b (tests 3, 4, 5, 6 and 7). It can be noticed that, in the case of fault 1, the difference ΔTSA is positive during about 61.5% of the whole simulation time (with TSA,pred,w/o_fault up to about 24 °C larger than TSA,pred,fault1), while the difference ΔRHSA is negative during about 58.1% of the whole tests period (with RHSA,pred,w/o_fault about 62% lower than RHSA,pred,fault1). In the case of fault 1 occurrence, it can be also underlined that the controllers require a 19.1% and 10.8% longer operating time of cooling coil and humidifier, respectively, causing an increase (+8.5%) in terms of electric energy consumption associated to the operation of the refrigerating system as well as the preparation of steam flow. However, this case is also characterized by a 7.1% shorter operating time of post-heating coil (thanks to the fact that the measured TRA is larger than the real one), reducing the electric energy consumed by the heat pump (−14.6%).
The trends associated to key parameters under fault 2 are indicated in Figure 8a (tests 1 and 2) and Figure 8b (tests 3, 4, 5, 6 and 7). The results highlight that, in the case of the fault 2, the difference ΔTSA is negative during about 75.5% of the whole simulation time (with TSA,pred,w/o_fault up to about 24 °C lower than TSA,pred,fault2), while the difference ΔRHSA is positive during about 55.0% of the whole tests duration (with RHSA,pred,w/o_fault about 64% greater than RHSA,pred,fault2). In the case of fault 2 occurrence, it can be also noticed that the controllers require a 14.3% longer operating time of post-heating coil, causing a greater electric energy consumption associated to the heat pump (+26.8%); however, in this case, the operating time of cooling coil and humidifier are reduced by about 18.9% and 32.6% (thanks to the fact that the measured TRA is lower than the real one), lowering the related electricity consumption (−19.7%).
The trends of key parameters under fault 3 are highlighted in Figure 9a (tests 1 and 2) and Figure 9b (tests 3, 4, 5, 6 and 7). The simulations indicate that, in the case of fault 3, the difference ΔRHRA is negative during about 83.0% of the whole simulation time (with RHRA,pred,w/o_fault up to about 21% lower than RHRA,pred,fault3), while the difference ΔRHSA is positive during about 83.1% of the tests duration (with RHSA,pred,w/o_fault up to about 64% greater than RHSA,pred,fault3); in this case, the controllers require a 11.4% shorter operating time of humidifier, reducing the related electric energy consumption (−25%) (thanks to the fact that the measured RHRA is higher than the real one); however, in this case the operating time of the cooling coil is 17.3% longer, causing a larger electricity demand of the refrigerating system (+5.2%).
The trends associated to key parameters under the fault 4 are indicated in Figure 10a (tests 1 and 2) and Figure 10b (tests 3, 4, 5, 6 and 7). The simulation data underline that, in the case of the fault 4, the difference ΔRHRA is positive during about 70.4% of the whole simulation time (with RHRA,pred,w/o_fault up to about 18.1% greater than RHRA,pred,fault4), while the difference ΔRHSA is negative during about 81.0% of the tests duration (with RHSA,pred,w/o_fault up to about 62.6% greater than RHSA,pred,fault4); in this case, the controllers require a small variation of operating time of post-heating coil (about +6.8% of the whole simulation time), whereas there is a significant increase of about 35.2% in the operating time of the humidifier (causing a significant increment of the associated electric energy consumption (+48.3%)), together with a decrease of about 21.3% in the operating time of the cooling coil (causing a slight decrement of the associated electric energy consumption (−2.1%) thanks to the fact that the measured RHRA is higher than the real one).
The trends associated to key parameters under fault 5 are reported in Figure 11a (tests 1 and 2) and Figure 11b (tests 3, 4, 5, 6 and 7). The results provided by the simulation model highlight that, in the case of the fault 5, the difference (TOA,pred-TMA,pred)fault5 is close to zero; in particular, this difference is in the range −0.5–0.5 °C for about 69% of the whole simulation time (while the difference (TOA,pred-TMA,pred)w/o_fault is in the same range for about 17.3% only of the tests duration, reaching a maximum absolute value of about 9.2 °C). This fault causes a slightly longer operating time of cooling coil and humidifier, respectively, together with a slightly shorter operating time of the post-heating coil.
The trends associated to key parameters under fault 6 are indicated in Figure 12a (tests 1 and 2) and Figure 12b (tests 3, 4, 5, 6 and 7). The simulation data underline that, in the case of fault 6, the difference (TRA,pred-TMA,pred)fault6 is always close to zero; in particular, this difference is in the range −0.5–0.5 °C for about 96% of the whole simulation time (while the difference (TRA,pred-TMA,pred)w/o_fault is in the same range for about 19.1% only of the tests duration, with the maximum absolute value equal to about 3.8 °C). This fault causes shorter electric energy consumption with respect to the normal operation; in particular, the controllers require a slightly shorter operating time of post-heating coil and humidifier, respectively, together with a slightly longer operating time of cooling coil.
The data reported in Figure 7, Figure 8, Figure 9, Figure 10, Figure 11 and Figure 12 show that performance differences between the operations with and without faults are often significantly consistent (mainly in the cases of faults 1 and 2); therefore, even if additional analyses and investigations have to be performed over a wider range of boundary conditions, it can be stated that specific rules could be potentially identified in order to detect/predict the presence of non-optimal states of the HVAC operation.

7. Case Study

A typical small-size office building located in the city of Naples (southern Italy, latitude: 40°51′22″ N, longitude: 14°14′47″ E) is assumed as case-study to be served by the air-handling unit described in the Section 2. The building, with a total area of 18 m2 and a volume of 54 m3, is characterized by a flat roof with only one floor; there are two West and East oriented windows with a total area of 1.8 m2 together with a thermal transmittance of 1.40 W/m2K. The characteristics of the building envelope are shown in Table 10, selected according to the threshold values imposed by Italian legislation requirements. The office is empty during the weekends, while in weekdays there is a constant number of 3 people working from 8:00 am to 6:00 pm. The working activity is characterized by an internal sensible and latent gain of 65 W/occupant and 55 W/occupant, respectively; the heat gains due to 3 PCs (420 W), a laser printer (110 W) and artificial lighting systems (3.75 W/m2) are taken into account. The target of indoor air temperature (TSP,Room) is set to 20 °C (±1 °C) during the heating period (1 November–31 March) and 26 °C (±1 °C) during the cooling period (1 April–31 October); the target of relative humidity (RHSP,Room) is always set to 50% (±5%) during the entire year. The AHU system can operate to achieve the targets only when at least one occupant being inside the office.
The performance of the system under normal operation (without faults) is firstly analyzed. In particular, Figure 13a,b show the daily profiles of return air temperature (TRA) and return relative humidity (RHRA), together with the lower (LDB) and upper (UDB) deadbands of return air temperature and relative humidity, for two selected days (1 February and 1 July) of the simulation period during heating and cooling seasons. Table 11 highlights the thermal comfort time (i.e., the percentage of time during which the target of indoor air temperature is achieved), the hygrometric comfort time (i.e., the percentage of time during which the desired target of indoor air relative humidity is achieved), and the overall electric energy consumption due to the operation of the refrigerating system, the heap pump, the humidifier as well as the supply and return air fans.
Figure 14 highlights the thermal comfort hours, the hygrometric comfort hours as well as the overall electric energy consumption, for both the case without faults and the cases when one the six aforementioned faults occurs in order to facilitate the comparison among the different scenarios. In particular, Figure 14a–c refer to the whole year, the heating period only and the cooling period only, respectively. These figures highlight that the thermal comfort hours and hygrometric comfort hours represent 84.5% and 82.5%, respectively, of the entire operation time of the AHU with reference to the scenario without faults. In comparison to the performance under normal operation:
  • the thermal comfort time in the case of occurrence of the fault 1 is decreased by a large amount (from 84.5% down to 9.6% with reference to the entire year), together with a slight reduction of the annual hygrometric comfort time; whatever the period is, fault 1 is characterized by a lower (−26.5%) electricity demand thanks to the reduced operating time of post-heating coil and heat pump (due to the fact that the measured TRA is larger than the real one);
  • whatever the period, the occurrence of fault 2 significantly deteriorates the comfort of occupants taking into account that it greatly reduces the thermal comfort time (from 84.5% down to 4.8% with reference to the entire year) as well as the hygrometric comfort time (from 82.5% down to 67.9% with reference to the entire year); fault 2 causes a larger (+18.1%) electric energy consumption due to a longer operating time of post-heating coil (associated to the fact that the measured TRA is lower than the real one);
  • whatever the period, the occurrence of the faults 3 and 4 substantially decreases the hygrometric comfort time from 82.5% down to 26.6% and 61.0%, respectively, during the entire year (while the thermal comfort time remains almost constant); fault 3 is characterized by a lower (−42.5%) electric energy consumption thanks to a shorter operating time of humidifier (due to the fact that the measured RHRA is larger than the real one); fault 4 causes a larger (+25.4%) electric demand due to a longer operating time of the humidifier (associated to the fact that the measured RHRA is lower than the real one);
  • whatever the period is, the thermal and hygrometric comfort hours remain almost constant in the case of fault 5 occurrence, while the overall electric energy consumption increases (+6.7%);
  • whatever the period, the effect of fault 6 is almost negligible on thermal comfort time; the hygrometric comfort hours decrease, together with a slight reduction (−2.8%) in terms of overall electric energy consumption.
  • The values reported in these figures highlight that, with respect to the normal operation, the occurrence of the aforementioned 6 faults could significantly affect the thermo-hygrometric comfort and/or the overall electric energy consumption; therefore, developing systems and procedures for predictive maintenance programs able to promptly detect and/or predict any non-optimal states of HVAC operation could substantially help in maintaining the desired indoor thermo-hygrometric conditions as well as lowering the inefficient usage of electricity associated with faulty operation.

8. Conclusions

The application of automated fault detection and diagnostics (FDD) under HVAC predictive maintenance programs requires the development of simulation models able to accurately compare the faulty operation with respect to nominal conditions. In this paper, a detailed dynamic simulation model of an existing HVAC system has been developed; the predictions of the model have been contrasted with the measured data, highlighting the capability of the model to represent the dynamic and steady-state HVAC performance (root mean square errors lower than 0.39 °C and 3.72%, respectively, in predicting the measured indoor air temperature and relative humidity) and, therefore, to be usefully applied in combination with FFD methods.
Six different typical soft faults have been intentionally introduced into the validated model and the operation of the HVAC system has been simulated; the analysis of dynamic trends of key parameters associated to faulty conditions in comparison to normal performance allowed confirmation that simplified rules could be identified to promptly detect and/or predict any non-optimal states of HVAC devices. In particular, the simulation results highlighted that:
-
in the case of positive offset of return air temperature sensor (+2 °C), the values of TSA associated to the normal operation are larger than the values corresponding to the faulty operation during about 61.5% of the time;
-
in the case of negative offset of return air temperature sensor (−2 °C), the values of TSA associated to the normal operation are lower than the values corresponding to the faulty conditions during about 75.5% of the time;
-
in the case of positive offset of return air relative humidity sensor (+10%), the values of RHRA associated to the normal operation are greater than the values corresponding to the faulty operation during about 83.0% of the time;
-
in the case of negative offset of return air relative humidity sensor (−10%), the values of RHRA associated to the normal operation are lower than the values corresponding to the faulty conditions during about 70.4% of the time;
-
in the case of the return air damper being stuck (fully closed), the difference (TOA,pred-TMA,pred) is in the range −0.5–0.5 °C for about 69% of the time;
-
in the case of the outside air damper being stuck (fully closed), the difference (TRA,pred-TMA,pred) is in the range −0.5–0.5 °C for about 96% of the time.
Finally, the impacts associated to the occurrence of the aforementioned faults have been assessed with reference to the case study of a typical Italian building office; the results underlined that faulty operation could significantly affect the thermo-hygrometric comfort of occupants as well as the overall electric energy consumption. In particular, the negative offset of the return air temperature sensor (−2 °C), the negative offset of the return air relative humidity sensor (−10%) and the stuck of the return air damper significantly enhance the electric energy consumption (from a minimum of 6.7% up to a maximum of 25.4%), while the positive offset of return air temperature sensor (+2 °C), the positive offset of return air relative humidity sensor (+10%) and the stuck of the outside air damper result in a reduction of electricity demand (from a minimum of −2.8% up to a maximum of −42.5%). The annual thermal comfort time is decreased by a large amount (from 84.5% down to 9.6%) in the case of positive offset of return air temperature sensor (+2 °C); the negative offset of return air temperature sensor (−2 °C) significantly reduces the annual thermal comfort time (from 84.5% down to 4.8%). The occurrence of positive and negative offset of return air relative humidity sensor greatly decreases the hygrometric comfort time from 82.5% down to 26.6% and 61.0%, respectively, during the entire year.
Therefore, developing HVAC predictive maintenance programs could substantially help in maintaining the desired indoor thermo-hygrometric conditions as well as lowering the inefficient usage of electricity associated to faulty operation.

Author Contributions

Conceptualization, A.R., F.G., V.F. and L.M.; methodology, A.R., F.G., V.F. and L.M.; software, A.R. and F.G.; validation, A.R. and F.G.; formal analysis, A.R., F.G., V.F. and L.M.; investigation, A.R. and F.G.; resources, A.R., V.F., S.S. and L.M.; data curation, A.R., F.G., V.F., S.S. and L.M.; writing—original draft preparation, A.R., F.G., V.F., S.S. and L.M.; writing—review and editing, A.R., F.G., V.F., S.S. and L.M.; visualization, A.R., F.G., V.F., S.S. and L.M.; supervision, A.R., V.F., S.S. and L.M.; project administration, A.R., V.F., S.S. and L.M.; funding acquisition, A.R., V.F. and L.M. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Acknowledgments

This work was undertaken as part of the program “PON FSE-FESR Ricerca e Innovazione 2014–2020” of the Italian Ministry of Education, University and Research, Action I.1 “Dottorati Innovativi con caratterizzazione industriale”.

Conflicts of Interest

The authors declare no conflict of interest. The funders had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript; or in the decision to publish the results.

Nomenclature

AHUAir handling unit
CCCooling coil
COPCoefficient of performance
CTThermal energy storage of cold heat carrier fluid
DEAExhaust air damper
DHRSDamper of the heat recovery system
DOAOutside air damper
DRAReturn air damper
DBRHDeadband of RHSP,Room
DBTDeadband of TSP,Room
EAExhaust air
ECBCSEnergy conservation in buildings and community system
ERREnergy efficiency ratio
FDDFault detection and diagnose
HPHeat pump
HRSCross flow static heat recovery system
HTThermal energy storage of hot heat carrier fluid
HUMHumidifier
HVACHeating, ventilation and air-conditioning
IEAInternational energy agency
LDBTLower deadband of air temperature
LDBRHLower deadband of air relative humidity
OAOutside air
OAFilOutside air filter
OLRAFVelocity of the return air fan
OLSAFVelocity of the supply air fan
OPDEAOpening percentage of DEA
OPDHRSOpening percentage of DHRS
OPDOAOpening percentage of DOA
OPDRAOpening percentage of DRA
OPV_CCOpening percentage of VCC
OPV_HUMOpening percentage of VHUM
OPV_PostHCOpening percentage of VostHC
PIDProportional-integral-derivative
PostHCPost-heating coil
PreHCPre-heating coil
RADReturn air duct
RAFReturn air fan
RAFilReturn air filter
RAVReturn air vent
RHBEAAir relative humidity around the room (%)
RHRAReturn air relative humidity (%)
RHRA,pred,faultPredicted return air relative humidity in case of fault occurrence (%)
RHRA,pred,w/o_faultPredicted return air relative humidity under normal operation (%)
RHRoom,initialInitial indoor air relative humidity (%)
RHSASupply air relative humidity (%)
RHSA,pred,faultPredicted supply air relative humidity in case of fault occurrence (%)
RHSA,pred,w/o_faultPredicted supply air relative humidity under normal operation (%)
RHSP,RoomTarget of the indoor air relative humidity (%)
RSRefrigerating system
SADSupply air duct
SAFSupply air fan
SAFilSupply air filter
SAVSupply air vent
TA,out,CCAir temperature at outlet of the cooling coil (°C)
TBEAAir temperature around the room (°C)
TCTTemperature in the cold tank (°C)
THTTemperature in the hot tank (°C)
TMAMixed air temperature (°C)
TMA,predPredicted temperature of air entering the supply air filter (°C)
TOAOutside air temperature (°C)
TOA,predPredicted outside air temperature (°C)
TRAReturn air temperature (°C)
TRA,predPredicted return air temperature (°C)
TRA,pred,faultPredicted return air temperature in case of fault occurrence (°C)
TRA,pred,w/o_faultPredicted return air temperature under normal operation (°C)
TRoom,initialInitial indoor air temperature (°C)
TSASupply air temperature (°C)
TSA,pred,faultPredicted supply air temperature in case of fault occurrence (°C)
TSA,pred,w/o_faultPredicted supply air temperature under normal operation (°C)
TSP,RoomTarget of the indoor air temperature (°C)
UDBTUpper deadband of air temperature
UDBRHUpper deadband of air relative humidity
VCCValve regulating the flow entering the cooling coil
VHUMValve regulating the flow entering the humidifier
VPostHCValve regulating the flow entering the post-heating coil
VPrecHCValve regulating the flow entering the pre-heating coil
ΔRHRARelative humidity difference between RHRA,pred,w/o_fault and RHRA,pred,fault (%)
ΔRHSARelative humidity difference between RHSA,pred,w/o_fault and RHSA,pred,fault (%)
ΔTRATemperature difference between TRA,pred,w/o_fault and TRA,pred,fault (°C)
ΔTSATemperature difference between TSA,pred,w/o_fault and TSA,pred,fault (°C)
ε i Instantaneous error
ε ¯ Average error
| ε ¯ | Average absolute error
ε RMS Root mean square error

References

  1. United Nations Environment Programme. Buildings and Climate Change: Summary for Decision Makers; United Nations Environment Programme: New York, NY, USA, 2009. [Google Scholar]
  2. Layke, J.; Mackres, E.; Liu, S.; Aden, N.; Becqué, R.; Graham, P.; Managan, K.; Nesler, C.; Petrichenko, K.; Mazur-Stommen, S. Accelerating Building Efficiency: Eight Actions for Urban Leaders; World Resources Institut: Washington, DC, USA, 2016. [Google Scholar]
  3. World Resources Institute. Wri Ross Center for Sustainable Cities, Accelerating Building Efficiency: Eight Actions for Urban Leaders. Available online: http://publications.wri.org/buildingefficiency/; https://files.wri.org/s3fs-public/Accelerating_Building_Efficiency_Eight_Actions_for_Urban_Leaders_8_pager.pdf (accessed on 29 July 2020).
  4. Proctor, J. Residential and small commercial central air conditioning, rated efficiency isn’t automatic. In Proceedings of the Present Public Session ASHRAE Winter, Meeting, Anaheim, CA, USA, 24–28 January 2004. [Google Scholar]
  5. Yu, Y.; Woradechjumroen, D.; Yu, D. A review of fault detection and diagnosis methodologies on air-handling units. Energy Build. 2014, 82, 550–562. [Google Scholar] [CrossRef]
  6. Yan, K.; Zhong, C.; Ji, Z.; Huang, J. Semi-supervised learning for early detection and diagnosis of various air handling unit faults. Energy Build. 2018, 181, 75–83. [Google Scholar] [CrossRef]
  7. Rasmussen, J. Diagnostic reasoning in action. IEEE Trans. Syst. Man Cybern. 1993, 23, 981–992. [Google Scholar] [CrossRef] [Green Version]
  8. Struss, P.; Malik, A.; Sachenbacher, M. Qualitative modeling is the key to automated diagnosis. IFAC 1996, 29, 6365–6370. [Google Scholar] [CrossRef]
  9. Himmelblau, D.M. Fault Detection and Diagnosis in Chemical and Petrochemical Processes; American Institute of Chemical Engineers: New York, NY, USA, 1978. [Google Scholar] [CrossRef]
  10. Nakahara, N. Building optimization. Definition and concept. In Building Optimization and Fault Diagnosis System Concept, Laboratory of Heating and Ventilation; Hyvarinen, J., Kohonen, R., Eds.; Technical Research Centre of Finland: Espoo, Finland, 1993; pp. 42–46. [Google Scholar]
  11. Isermann, R. Process Fault Detection Based on Modeling and Estimation Methods. A Survey; Pergamon Press: Oxford, UK, 1984; Volume 20, pp. 387–404. [Google Scholar]
  12. Rogers, A.P.; Guo, F.; Rasmussen, B.P. A review of fault detection and diagnosis methods for residential air conditioning system. Build. Environ. 2019, 161. [Google Scholar] [CrossRef]
  13. Hyvarinen, J.; Karki, S. IEA Annex 25, Real Time Simulation of HVAC System for Building Optimization, Fault Detection and Diagnosis; Technical Research Centre of Finland: Espoo, Finland, 1996. [Google Scholar]
  14. Dexter, A. IEA Annex 34, Demonstrating Automated Fault Detection and Diagnosis Methods in Real Buildings; Technical Research Centre of Finland: Espoo, Finland, 2001. [Google Scholar]
  15. Granderson, J.; Singla, R. Chatacterization and Survey of Automated Fault Detection and Diagnostic Tools; Lawrence Berkeley National Laboratory Energy Technology: Berkeley, CA, USA, 2017.
  16. Kim, W.; Katipamula, S. A review of fault detection and diagnostics methods for building systems. Sci. Technol. Built Environ. 2017, 24, 1–19. [Google Scholar] [CrossRef]
  17. Katipamula, S.; Brambley, M. Review article: Methods for fault detection, diagnostics, and prognostics for building systems—A review, part I. HVACR 2005, 11, 3–25. [Google Scholar] [CrossRef]
  18. Katipamula, S.; Brambley, M. Review article: Methods for fault detection, diagnostics, and prognostics for building systems—A review, part II. HVACR 2005, 11, 169–187. [Google Scholar] [CrossRef]
  19. TRNSYS. Available online: http://www.trnsys.com (accessed on 16 June 2020).
  20. AERMEC. Available online: https://h2r4r4a5.ssl.hwcdn.net/assets/Series/Attachments/8787/aermec-anl-depliant.pdf (accessed on 16 June 2020).
  21. SIEMENS. Available online: https://mall.industry.siemens.com/mall/en/it/Catalog/Product/?mlfb=BPZ%3aQFM2160 (accessed on 16 June 2020).
  22. SIEMENS. Available online: https://mall.industry.siemens.com/mall/en/it/Catalog/Product/?mlfb=BPZ%3aQAM2161.040 (accessed on 29 July 2020).
  23. TSI. Available online: https://www.tsi.com/getmedia/d2a8d1d1-7551-47fe-8a0f-3c14b09b494b/7575_QTrak_A4_UK_5001356-web?ext=.pdf (accessed on 16 June 2020).
  24. TSI. Available online: https://www.tsi.com/getmedia/43e67f65-965c-43ac-89e0-0f99667dad3d/PH730_PH731_A4_5001433_RevE_Web?ext=.pdf (accessed on 27 June 2020).
  25. KIMO. Available online: http://www.kimocanada.com/Anglais/pdf/Manuels-anglais/Portables%20(2002)/8_Classe%20300/NT%20AMI301.pdf (accessed on 27 June 2020).
  26. ENERGYPLUS. Available online: https://energyplus.net/ (accessed on 29 July 2020).
  27. Wen, J.; Li, S. Ashrae 1312-RP Tools for Evaluating Fault Detection and Diagnostic Methods for Air-Handling Unit. Available online: https://bseg.cae.drexel.edu/ashrae-1312-rp-tools-for-evaluating-fault-detection-and-diagnostic-methods-for-air-handling-units/ (accessed on 29 July 2020).
Figure 1. (a) Floor plan, and (b) internal view of the Integrated Test Room.
Figure 1. (a) Floor plan, and (b) internal view of the Integrated Test Room.
Energies 13 03948 g001
Figure 2. Schematic representation of the air-handling unit (AHU) serving the integrated test room.
Figure 2. Schematic representation of the air-handling unit (AHU) serving the integrated test room.
Energies 13 03948 g002
Figure 3. (a) Coefficient of performance (COP) of the heap pump and (b) energy efficiency ratio (EER) of the refrigerating system as a function of both outside air temperature and supply fluid temperature.
Figure 3. (a) Coefficient of performance (COP) of the heap pump and (b) energy efficiency ratio (EER) of the refrigerating system as a function of both outside air temperature and supply fluid temperature.
Energies 13 03948 g003aEnergies 13 03948 g003b
Figure 4. Experimental data measured during the test 1 (a), test 2 (b), test 3 (c), test 4 (d), test 5 (e), test 6 (f) and test 7 (g).
Figure 4. Experimental data measured during the test 1 (a), test 2 (b), test 3 (c), test 4 (d), test 5 (e), test 6 (f) and test 7 (g).
Energies 13 03948 g004aEnergies 13 03948 g004b
Figure 5. Screenshot of the model developed in TRNSYS environment.
Figure 5. Screenshot of the model developed in TRNSYS environment.
Energies 13 03948 g005
Figure 6. Comparison of the experimental results with the predicted data: test 1 (a), test 2 (b), test 3 (c), test 4 (d), test 5 (e), test 6 (f) and test 7 (g).
Figure 6. Comparison of the experimental results with the predicted data: test 1 (a), test 2 (b), test 3 (c), test 4 (d), test 5 (e), test 6 (f) and test 7 (g).
Energies 13 03948 g006aEnergies 13 03948 g006b
Figure 7. Comparison between normal operation and operation with fault 1: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Figure 7. Comparison between normal operation and operation with fault 1: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Energies 13 03948 g007
Figure 8. Comparison between normal operation and operation with fault 2: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Figure 8. Comparison between normal operation and operation with fault 2: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Energies 13 03948 g008
Figure 9. Comparison between normal operation and operation with fault 3: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Figure 9. Comparison between normal operation and operation with fault 3: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Energies 13 03948 g009
Figure 10. Comparison between normal operation and operation with fault 4: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Figure 10. Comparison between normal operation and operation with fault 4: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Energies 13 03948 g010
Figure 11. Comparison between normal operation and operation with fault 5: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Figure 11. Comparison between normal operation and operation with fault 5: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Energies 13 03948 g011
Figure 12. Comparison between normal operation and operation with fault 6: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Figure 12. Comparison between normal operation and operation with fault 6: test 1, 2 (a), test 3, 4, 5, 6, 7 (b).
Energies 13 03948 g012
Figure 13. Daily profiles of return air temperature (TRA) and return relative humidity (RHRA) under normal operation: typical day of the heating period (1 February) (a), typical day of the cooling period day (1 July) (b).
Figure 13. Daily profiles of return air temperature (TRA) and return relative humidity (RHRA) under normal operation: typical day of the heating period (1 February) (a), typical day of the cooling period day (1 July) (b).
Energies 13 03948 g013
Figure 14. Comfort hours and electric consumption with/without faults: whole year (a), heating period (b), cooling period (c).
Figure 14. Comfort hours and electric consumption with/without faults: whole year (a), heating period (b), cooling period (c).
Energies 13 03948 g014
Table 1. Test room envelope characteristics of the Integrated Test Room.
Table 1. Test room envelope characteristics of the Integrated Test Room.
Element of Test Room EnvelopeLayer Material (from Outside to Inside)Thickness (m)Thermal Conductivity (W/mK)Conductive Thermal Resistance (m2K/W)Area (m2)
Horizontal ceilingPlasterboard0.01250.2500.0502.02316.00
Rock wool0.08000.0421.905
Polyurethane panel0.01500.2200.068
Horizontal floorSubfloor0.10001.3500.0743.10716.00
Tiles0.05002.1000.024
Polystyrene panel0.08000.0352.286
Galvanized steel slab0.002052.0000.000
Tiles0.01001.0500.010
Vertical walls with radiant panels (West and East oriented)Plasterboard0.01250.2500.0502.00514.40
Rock wool0.08000.0421.905
Vertical walls without radiant panels (South and North oriented)Plasterboard0.01250.2500.0501.99814.4
Rock wool0.08000.0421.905
Fibre-cement panel0.01500.3500.043
Door (South oriented)Soft wood0.05000.1400.3570.3571.68
Table 2. Characteristics of main AHU components.
Table 2. Characteristics of main AHU components.
Supply (SAF)/Return (RAF) air fanTypeBackward blades
Nominal power of supply/return air fan2.50/0.50
Nominal supply/return air flow rate (m3/h)600/600
Nominal revolutions per minute of supply/return air fan (rpm)2754/2221
Maximum revolutions per minute of supply/return air fan (rpm)3640/3080
Cross flow static heat recovery system (HRS)Efficiency (%)/Recovery capacity (kW)74.7/3.1
Pressure drop on the external/exhaust air side (kPa)0.047/0.048
Return (RAFil) and outside (OAFil) air filterFilter type/Efficiency classFluted/G4
Supply air filter (SAFil)Filter type/Efficiency classRigid pocket/G4
Return (RAD) and supply (SAD) air ductsDiameter (m)0.25
Supply/Return length (m)9.8/16.8
Thermal resistance of the insulating material (m2K/W)0.25
Supply air vent (SAV)Nominal size (m)0.60 × 0.60
Maximum volume flow rate (m3/h)1080
Pre-heating coil (PreHC)Nominal heating capacity (kW)4.1
Nominal heat carrier fluid/air flow rate (m3/h)0.710/600
Nominal heat carrier fluid/air pressure drop (kPa)12.43/0.00321
Cooling coil (CC)Nominal cooling capacity (kW)5.0
Nominal heat carrier fluid/air flow rate (m3/h)0.860/600
Nominal heat carrier fluid/air pressure drop (kPa)13.56/0.0178
Humidifier (HUM)Steam capacity (kg/h)/Nominal power (kW)5.0/3.7
Post-heating coil (PreHC)Nominal heating capacity (kW)5.0
Nominal heat carrier fluid/air flow rate (m3/h)0.860/600
Nominal heat carrier fluid/air pressure drop (kPa)20.35/0.0497
Vapor compression electric Heat Pump (HP)/Refrigerating System (RS) [20]Nominal heating/cooling capacity (kW)14.0/13.4
Nominal input power (kW)4.75/4.48
Nominal fluid flow rate (m3/h)2.41/2.31
Table 3. Characteristics of the sensors used for the AHU monitoring.
Table 3. Characteristics of the sensors used for the AHU monitoring.
ModelMonitored ParameterMeasuring RangeAccuracy
Siemens QFM2160 [21]Return air temperature TRA0–50 °C±0.8 K
Return air relative humidity RHRA0–100%±3%
Siemens QFM2160 [21]Supply air temperature TSA0–50 °C±0.8 K
Supply air relative humidity RHSA0–100%±3%
Siemens QAM2161.040 [22]External air temperature TOA−50–50 °C±0.75 K
Siemens QAM2161.040 [22]Air temperature TA,out,CC at outlet of the CC−50–50 °C±0.75 K
TSI 7575, 982 IAQ [23]Air temperature around the room TBEA−10–60 °C±0.50 K
Air relative humidity around the room RHBEA5–95%±3%
Table 4. Control strategies of the AHU.
Table 4. Control strategies of the AHU.
Component of the AHUONOFF
Humidifier (HUM)RHRA ≤ (RHSP,Room − DBRH)RHRA ≥ (RHSP,Room + DBRH)
Cooling coil (CC)TRA ≥ (TSP,Room + DBT)
OR
RHRA ≥ (RHSP,Room + DBRH)
TRA ≤ (TSP,Room − DBT)
AND
RHRA ≤ (RHSP,Room − DBRH)
Post-heating coil (PostHC)TRA ≤ (TSP,Room − DBT)TRA ≥ (TSP,Room + DBT)
Vapor compression electric Heat Pump (HP)–model ANL 050HQ [20]THT < (45 °C − 1 °C)THT ≥ (45 °C + 1 °C)
Refrigerating System (RS)–model ANL 050Q [20]TCT > (7 °C + 1 °C)TCT ≤ (7 °C − 1 °C)
Table 5. Boundary conditions during the measurements of air velocity or volumetric flow rate.
Table 5. Boundary conditions during the measurements of air velocity or volumetric flow rate.
OPSAF (%)OPRAF (%)OPDRA (%)OPDOA (%)OPDEA (%)OPDHRS (%)Supply Air Flow Rate (m3/h)Return Air Velocity (m/s)Outside Air Velocity (m/s)Exhaust Air Velocity (m/s)
505010020201004304.41.63.3
905010020201009804.83.81.5
705010020201006804.72.13.2
305010020201002064.31.34.6
10501002020100854.01.24.8
509010020201004707.51.87.5
507010020201004505.61.47.2
503010020201004202.51.81.3
501010020201004000.91.21.2
50508020201004364.50.84.0
50506020201004564.50.94.1
50504020201004504.30.95.0
50502020201004183.91.26.6
505010040201004474.20.94.0
505010060201004504.30.93.9
505010080201004554.21.04.0
5050100100201004624.31.23.9
505010020401004574.41.30.6
505010020601004614.31.40.6
505010020801004654.30.90.6
5050100201001004644.30.80.6
5050100202004624.40.93.7
Table 6. Boundary conditions of experimental tests.
Table 6. Boundary conditions of experimental tests.
Test Number1234567
TSP,Room (°C)22 → 24 → 2626 → 24 → 222228222222
TRoom_initial (°C)19.828.122.028.123.123.023.1
RHSP,Room (%)50.050.060 → 7055 → 45505050
RHRoom_initial (%)52.551.151.464.861.250.653.5
OLRAF (%)505050505050100
OLSAF (%)505050505050100
DRA (%)100100100100050100
DOA (%)202020201005020
DEA (%)202020201005020
Duration (h)6.825.970.700.951.231.000.52
Table 7. TRaNsient SYStems (TRNSYS) Types used in the simulation model.
Table 7. TRaNsient SYStems (TRNSYS) Types used in the simulation model.
Simulated ComponentTypeSimulated ComponentType
Integrated Test Room56Cross flow static heat recovery system667b
PostHC753eMoist air properties33e
CC508cAir ducts607
HUM641Fluid pipes31
HP/RS941On/Off differential controllers2
Hot and cold tanks534Proportional–Integral–Derivative (PID) controllers23
Dampers646/648External climatic conditions15
3-way valves647/649Fans642
Table 8. Main parameters of PID controllers.
Table 8. Main parameters of PID controllers.
Controlled Component of the AHUGain ConstantDerivative Time (min)Integral Time (min)
Humidifier (HUM)0.0310.1
Cooling coil (CC)−0.0510.1
Post-heating coil (PostHC)0.110.1
Table 9. Errors between the model predictions and measurements.
Table 9. Errors between the model predictions and measurements.
TestNumber of Experimental PointsParameter ε ¯ | ε ¯ | ε RMS
Test 1409TRA−0.11 °C0.32 °C0.39 °C
RHRA−1.64%3.07%3.68%
Test 2359TRA−0.07 °C0.26 °C0.30 °C
RHRA−3.12%4.06%3.84%
Test 343TRA0.62 °C0.72 °C0.58 °C
RHRA−0.95%1.39%1.39%
Test 458TRA0.32 °C0.33 °C0.23 °C
RHRA1.05%3.11%3.96%
Test 574TRA−0.16 °C0.26 °C0.25 °C
RHRA−0.92%1.27%1.18%
Test 660TRA−0.12 °C0.25 °C0.27 °C
RHRA−1.27%1.41%1.31%
Test 731TRA−0.23 °C0.36 °C0.37 °C
RHRA1.74%1.94%1.79%
Whole database1034TRA−0.05 °C0.31 °C0.39 °C
RHRA−1.97%3.26%3.72%
Table 10. Building envelope characteristics of the office.
Table 10. Building envelope characteristics of the office.
Component of Office Building EnvelopeLayer Material (from Outside to Inside)Thickness (m)Thermal Conductivity (W/mK)Conductive Thermal Resistance (m2K/W)Area (m2)
Horizontal ceilingBitumen0.0080.1700.0473.09518.0
Screed0.0500.0850.588
Reinforced concrete slab0.0500.8500.059
Hollow brick0.2000.2470.810
Expanded polystyrene0.0500.0321.563
Lime plaster0.0200.7000.029
Horizontal floorConcrete slab0.2000.1501.3332.73218.0
Concrete subfloor0.1000.7300.137
Expanded polystyrene0.0400.0321.250
Tiles0.0121.0000.012
Vertical wallsCement plaster0.0200.9000.0222.89613.5–12.0
Hollow brick0.2500.1951.282
Expanded polystyrene0.0500.0321.563
Lime plaster0.0200.7000.029
Table 11. Percentage of thermo-hygrometric comfort time and electric energy consumption during heating, cooling and whole year without faults.
Table 11. Percentage of thermo-hygrometric comfort time and electric energy consumption during heating, cooling and whole year without faults.
Simulation PeriodThermal Comfort Time (%)Hygrometric Comfort Time (%)Electric Energy Consumption (kWh)
Heating period84.780.46291.1
Cooling period84.483.911496.0
Whole year84.582.517787.1

Share and Cite

MDPI and ACS Style

Rosato, A.; Guarino, F.; Filomena, V.; Sibilio, S.; Maffei, L. Experimental Calibration and Validation of a Simulation Model for Fault Detection of HVAC Systems and Application to a Case Study. Energies 2020, 13, 3948. https://doi.org/10.3390/en13153948

AMA Style

Rosato A, Guarino F, Filomena V, Sibilio S, Maffei L. Experimental Calibration and Validation of a Simulation Model for Fault Detection of HVAC Systems and Application to a Case Study. Energies. 2020; 13(15):3948. https://doi.org/10.3390/en13153948

Chicago/Turabian Style

Rosato, Antonio, Francesco Guarino, Vincenzo Filomena, Sergio Sibilio, and Luigi Maffei. 2020. "Experimental Calibration and Validation of a Simulation Model for Fault Detection of HVAC Systems and Application to a Case Study" Energies 13, no. 15: 3948. https://doi.org/10.3390/en13153948

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop