Energy Performance Comparison between Liquid-Desiccant-Assisted Air Conditioning System and Dedicated Outdoor Air System in Different Climatic Regions

1
Department of Architectural Engineering, College of Engineering, Hanyang University, 222 Wangsimni-Ro, Seongdong-Gu, Seoul 04763, Korea
2
School of Architecture, Korea National University of Transportation, Chungju 27469, Korea
*
Author to whom correspondence should be addressed.
Energies 2019, 12(9), 1798; https://doi.org/10.3390/en12091798
Received: 25 April 2019 / Revised: 8 May 2019 / Accepted: 9 May 2019 / Published: 11 May 2019
The main purpose of this research is to analyze and compare the energy performance of two different novel air conditioning systems; one is a dedicated outdoor air system (DOAS) with a parallel system and the other is a heat-pump-integrated liquid-desiccant and evaporative-cooling-assisted 100% outdoor air system (HPLD-IDECOAS). It was assumed that office buildings served by each system were located in six cities representing four different climatic regions in China. The hourly thermal loads of the office buildings meeting the local building design codes of each selected city were predicted by the TRNSYS 18 software package. The hourly thermal load data were imported into the commercial engineering equation solver (EES) program to estimate the operating energy consumption of each system via detailed energy simulations performed using valid system simulation models. The results show that the HPLD-IDECOAS has higher energy-saving potential than the DOAS with a parallel system in climate regions with high humidity, whereas, in dry regions, the difference in energy consumption between the two systems was not significant. View Full-Text
Keywords: liquid desiccant; evaporative cooling; dedicated outdoor air system; heat pump; energy simulation liquid desiccant; evaporative cooling; dedicated outdoor air system; heat pump; energy simulation
Show Figures

Figure 1

MDPI and ACS Style

Liu, S.; No, S.-T.; Jeong, J.-W. Energy Performance Comparison between Liquid-Desiccant-Assisted Air Conditioning System and Dedicated Outdoor Air System in Different Climatic Regions. Energies 2019, 12, 1798. https://doi.org/10.3390/en12091798

AMA Style

Liu S, No S-T, Jeong J-W. Energy Performance Comparison between Liquid-Desiccant-Assisted Air Conditioning System and Dedicated Outdoor Air System in Different Climatic Regions. Energies. 2019; 12(9):1798. https://doi.org/10.3390/en12091798

Chicago/Turabian Style

Liu, Su; No, Sang-Tae; Jeong, Jae-Weon. 2019. "Energy Performance Comparison between Liquid-Desiccant-Assisted Air Conditioning System and Dedicated Outdoor Air System in Different Climatic Regions" Energies 12, no. 9: 1798. https://doi.org/10.3390/en12091798

Find Other Styles
Note that from the first issue of 2016, MDPI journals use article numbers instead of page numbers. See further details here.

Article Access Map by Country/Region

1
Search more from Scilit
 
Search
Back to TopTop