Next Article in Journal
A Feasibility Study of Simulating the Micro-Scale Wind Field for Wind Energy Applications by NWP/CFD Model with Improved Coupling Method and Data Assimilation
Next Article in Special Issue
Experimental and Numerical Investigations on Heat Transfer of Bare Tubes in a Bubbling Fluidized Bed with Respect to Better Heat Integration in Temperature Swing Adsorption Systems
Previous Article in Journal
Addendum: El-Leathy, A. et al. Thermal Performance Evaluation of Two Thermal Energy Storage Tank Design Concepts for Use with a Solid Particle Receiver-Based Solar Power Tower. Energies 2014, 7, 8201–8216
Previous Article in Special Issue
Emissivity Characteristics of Hydrocarbon Flame and Temperature Measurement by Color Image Processing
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Case Report

A Comparative Study of the Oil-Free Centrifugal Water Chillers with the Flooded or Falling Film Evaporator—A Case Study

1
Green Energy & Environment Research Laboratories, Industrial Technology Research Institute, Chutung 310, Taiwan
2
Department of Mechanical Engineering, National Chiao Tung University, Hsinchu 300, Taiwan
*
Author to whom correspondence should be addressed.
Energies 2019, 12(13), 2548; https://doi.org/10.3390/en12132548
Submission received: 12 June 2019 / Revised: 28 June 2019 / Accepted: 1 July 2019 / Published: 2 July 2019
(This article belongs to the Special Issue Experimental Heat Transfer in Energy Systems)

Abstract

:
A comparative study regarding the performance of real-scale oil-free centrifugal chillers having the flooded evaporator or falling film evaporator was conducted in this study. The nominal capacity for the test chillers was around 200~230 USRT (US refrigeration ton) (703~809 kW). The compressors of the two chillers were identical and R-134a was used as the working fluid. Both evaporators employed the same enhanced tubes (GEWA-B) to fulfill phase change. Tests were conducted in full, 75%, 50%, and 25% loading. Test results indicate that both chillers contained a comparable system performance with an integrated part-load value of around 8.62~8.63. The overall heat transfer coefficient for the flooded evaporator was appreciably higher (20~40%) than the falling film evaporator. This is because the falling film flowrate was below the threshold value and the heat transfer was dominated by evaporation mode. Yet, the heat transfer performance for the falling film evaporator was further jeopardized due to starvation of the film flowrate (partial dry-out), especially in the middle or bottom of the tube bundle. This phenomenon became even more pronounced at partial loading (25%), whereas the flooded evaporator did not reveal such a performance dip at partial loading.

1. Introduction

Normally, the designed cooling capacity of a water chiller for air-conditioning applications is based on the peak load demand. For large buildings, a centrifugal chiller is especially popular for large cooling capacity requirements. Yet, in subtropical or tropical zones, centrifugal chillers may work all year round. However, the full-load running period of the chiller is usually shorter than one month during a whole year operation, meaning that most of the time, chillers are in part-load operation [1]. Hence, for more effective characterization of a chiller in association with the part-load operation, implementation of integrated part-load value (IPLV) [2] is adopted as the design concept. The IPLV is defined as follows
IPLV = 0.01A + 0.42B + 0.45C + 0.12D
where A is the coefficient of performance (COP) at 100% load, B is the COP at 75% load, C is the COP at 50% load, and D is the COP at 25% load. From Equation (1), the proportions of 75% and 50% part-loads are much higher than full-load or 25% load.
For effective part-load operation as far as cooling of commercial buildings is concerned, variable speed chillers are increasingly used in central air-conditioning systems, as they can effectively reduce electricity consumption. For conventional variable speed chillers, lubrication of the moving part is essential and oil circuits are used to lubricate the bearings and rotating parts. The problem of lubrication may even become severe at part-load operation due to loss of oil-return. As a consequence, appreciable frictional loss at the rotating shafts occurs and limits the high-speed operation. To tailor this problem, oil-free magnetic bearings that offer a contactless shaft subject to ultrahigh speed rotation are integrated with the compressors [3]. Yu et al. [4] reported an energy saving of 9.6% in the total electricity consumption in a shopping arcade by using oil-free chillers with variable speed control. An optimal control strategy for variable speed centrifugal compressors with magnetic bearings was developed by [5].
Note that the oil-free design not only contains a superior compressor efficiency under variable speed control but also can eliminate the heat transfer deterioration in evaporators [6,7]. For a typical centrifugal water chiller, the evaporator can be either flooded type or falling film type. The major heat transfer mechanism of flooded evaporator is via nucleate boiling, whereas the falling film evaporator makes use of both evaporation and nucleate boiling, and both designs incorporate effective phase-change processes. There were some related studies concerning the heat transfer regrading flooded evaporator or falling film evaporator; performances regarding single tube and tube bundle were reported [8,9,10,11,12,13] and some correlations were developed. Normally, the reported data have shown that the falling film design not only offers a less refrigerant inventory but also contains a higher heat transfer coefficient (HTC) when compared with the flooded evaporator [12,14,15]. However, these studies were based on reduced evaporator size with a much smaller bundle effect. Yet, heat transfer performance is not reported in a large chiller system. The only reported test results for a falling film evaporator in a real-scale large chiller were reported by Yang and Wang [16] and Yang et al. [17]. Yang and Wang [16] conducted heat transfer for falling film evaporators in large compression refrigeration systems via numerical study. They concluded that the mal distribution by the distributor could severely offset the performance of the falling film evaporator. Yang et al. [17] extended the numerical simulations to examine the influence of dry patch on the falling film evaporator and concluded that the heat transfer performance of falling evaporators can be enhanced by increasing the refrigerant flowrate within a certain range due to the decreasing dry patch areas on falling film tubes. Once the dry patches decrease to the minimum value of zero, the evaporators just reach the best thermal performance. Although their studies were applicable for a real-scale system, their main works focused on the numerical studies. Up to now, there were no comparative studies in real scale concerning the performance difference between a falling film evaporator and a flooded evaporator. Hence, the objective of this study is to provide quantitative comparisons from the perspective of system and heat transfer.

2. Experimental Setup and Data Reduction for System Performance

2.1. Introduction to the Experimental Setup

The schematic of the test chiller is shown in Figure 1, which shows the oil-free centrifugal compressor (ITRI model MBC-250, R-134a) with the inverter control (ReymeBus RM6P1-4250E3)—the revolution is detected by a magnetic bearing sensor, which shows a slip deviation to be less than 1% against the inverter controller—a shell-and-tube condenser, an electrical expansion valve (Danfoss ETS-4000), and an evaporator with a shell-and-tube configuration. A level sensor is used to measure the condensate level within the condenser (PAL PVLS-250, range 0-250 mm, sensing resolution 6 mm). The nominal capacities of the centrifugal chillers are 200 USRT (falling-film type, 703 kW), and 230 USRT (flooded type, 809 kW), respectively. Both chillers are incorporated with the same oil-free compressor and R-134a is used as the working fluid. The maximum refrigerant flowrate is 5.46 kg/s. The dimensions of the falling film evaporator and flooded evaporator are shown in Figure 2. Both evaporators adopt a 2-pass arrangement. The shell diameter for the falling-film evaporator is 670 mm, and 680 mm for the flooded evaporator. The test tubes are made from Wieland GEWA B4-enhanced tubes with a nominal outer tube diameter of 19.05 mm (3/4”) and a thickness of 0.63 mm. The tube length of each tube for both evaporators is 3 m. The evaporator is insulated carefully and the heat loss to the ambient is estimated to be less than 0.5% of the nominal capacity.

2.2. Experimental Apparatus and Measurements

To ensure the accurate measurements and fair comparisons, tests are conducted following the and AHRI standard 551/591(SI) [2]. The refrigerant inventory for the falling-film evaporator and the flooded evaporator are 220 kg and 250 kg, respectively. The refrigerant charge is based on the nominal rating at full load. Based on the standard requirement, the following test conditions are carried out:
  • Chilled water flowrate at the evaporator: the flowrate at full-load operation for both chillers is regulated to achieve a fixed temperature difference of chilled water across the evaporator (5 °C, with tolerance being less than 0.3 °C). The required water flowrate is about 10 LPM per USRT (2.84 LPM per kW).
  • Cooling water flowrate at the condenser: the flowrate at full-load operation for both chillers is regulated to achieve a fixed temperature difference of cooling water across the condenser (5 °C, with tolerance being less than 0.3 °C). The required water flowrate is about 12.5 LPM per USRT (3.56 LPM per kW).
  • Outlet temperature of the chilled water: the temperature is required to be maintained at 7 °C with 0.3 °C tolerance.
  • Inlet temperature of the cooling water: tests are conducted in different loading conditions (100%, 75%, 50% and 25%). The corresponding temperatures to arrive at the loading are 30 °C, 24.5 °C, 19.0 °C, and 19.0 °C, respectively, with a tolerance of 0.3 °C.
A magnetic flowmeter (Yokogawa, model SE220MJ with a resolution of 0.5%) of the chilled water is installed at the water return, as shown in Figure 1. The inlet and outlet temperatures of the evaporator and the condenser are measured by calibrated RTD (Resistance Temperature Device, OMEGA Pt100) with a resolution of 0.1 °C. The corresponding evaporation pressure and condensing pressure is measured by pressure transmitter (WIKA R-1) with a calibrated accuracy of 2%. The consumed power of the compressor is measured by Yokogawa WT230 power meter, which has an accuracy of 0.5%.

2.3. Data Reduction of the Experimental Measurements

The capacity of the water chiller is calculated by
Q ˙ = m ˙ e v a , w a t e r c p , w a t e r Δ T e v a , w a t e r
where m ˙ e v a , w a t e r is the chilled water flowrate, c p , w a t e r is the specific heat of chilled water, and Δ T e v a , w a t e r is the temperature difference of chilled water at the evaporator. The corresponding coefficient of performance (COP) is calculated as
C O P = Q ˙ W c o m p
where Wcomp is the power consumption of the compressor. The integrated part load value (IPLV) can be calculated from Equation (1). The effectiveness of the evaporator is calculated as:
ε Q ˙ Q ˙ m a x = Q ˙ C min ( T i n , w a t e r T s a t , e v a )
For the phase change heat exchanger like the present falling film evaporator or flooded evaporator, C min = m ˙ e v a , w a t e r c p , w a t e r , and the effectiveness is only a function of the number of transfer unit (NTU),
N T U U A / C min
As a result,
ε = 1 e N T U
Hence, the NTU can be derived from the measurements to obtain the overall heat transfer conductance (UA) or the overall heat transfer coefficient U. Note that the overall heat transfer coefficient in this study is based on the outer surface of the tube.

3. Results and Discussion

Table 1 shows the test results for the centrifugal water chillers. Note that these two test chillers contain the same compressor. Although the compressor is the same for these two chillers, the nominal capacity for the flooded type is 230 USRT (809 kW), while the falling film evaporator contains a 200 RT (703 kW) chiller capacity. Both chillers reveal an appreciable drop of capacity and compressor power when the compressor revolution is reduced. However, the corresponding COP rises when the loading is reduced and reaches the plateau at 50% part-load with a COP of around 9.9. A further un-loading to 25% leads to a detectable decline of the COP. Basically, the system performance subject to part-load is similar to the test results for the compressor from the calorimeter. Yet the corresponding IPLV for the falling film evaporator is 8.627 while it is 8.634. Basically, the system performance for both systems is about the same both in full-loading and in partial loading conditions. There is barely any difference as far as system performance is concerned.
On the other hand, the corresponding overall heat transfer coefficient (based on outer wall surface area) vs. the heat flux for both the flooded and the falling-film evaporator is shown in Figure 3. Apparently, the overall heat transfer coefficient increases with the rise of loading. Normally, the overall heat transfer coefficient for the flooded type evaporator is about 30~40% higher than the falling film evaporator. Notice that the mean temperature and the chilled water flowrate in the tube side for both evaporators remains the same for both evaporators. Yet the tube pass is the same and the tube number in each pass for the flooded evaporator is about the same as that of the falling evaporator. A quick estimate shows that the dominant thermal resistance is on the shell side (about 60–75%). Hence, the thermal resistance on the tube side for the flooded evaporator is roughly the same as that of the falling film evaporator, indicating that the difference in overall heat transfer performance is due to the difference in the heat transfer coefficient on the shell side rather than on the tube side. Note that some prior studies indicated that the falling evaporation contains a better heat transfer performance than the pure nucleate boiling mode (e.g., [12,13,18]). Hence, it is expected that the falling evaporator should yield a higher overall heat transfer performance, since heat transfer mode for both evaporation and nucleate boiling take place in the tube bundle. Yet, as explained by Christians and Thome [19], the presence of the falling film on the enhanced tubes could result in a low-pressure zone that entrains the bubble more efficiently from the pores, thereby revealing superior heat transfer performance for the falling film evaporator when compared with the flooded evaporator. However, surprisingly, in this study, the flooded evaporator outperforms the falling evaporator as far as overall heat transfer coefficient is concerned, as shown in Figure 3. Yet the difference in overall heat transfer coefficient between the flooded evaporator and the falling film becomes even more pronounced when the loading is increased. In the practical falling film evaporator, the falling film can be made available either by spraying or trickling to distribute liquid refrigerant on the bundles [16]. The falling film evaporators with spraying distribution usually require refrigerant pumps to fulfill the sprayed liquid cycle and the amount of recirculated refrigerant normally exceeds the evaporated mass among the bundles. Hence, most falling film evaporators incorporate trickling design for easier maintenance [16]. Note that the present enhanced surface is the Wieland GEWA B tubing, and the surface reveals a different heat transfer behavior against heat flux for a nucleate boiling condition. For a heat flux below 20 kW/m2, the corresponding heat transfer coefficient increases with the rise of heat flux. Conversely, a detectable decline is seen when the heat flux surpasses the threshold value [20]. In the present tests, the maximum heat flux is around 20 kW/m2 at full-load and ranges around 5~15 kW/m2 at partial load. This suggests a positive influence of heat flux upon HTCs in the present flooded evaporator. Notice that the overall thermal resistance is related to in-tube water side resistance, wall resistance, and shell side resistance in the following:
1 U o = 1 h o + ln ( D o D i ) 2 π k w L + A o h i A i
where Uo is the overall heat transfer coefficient, and hi and ho are the heat transfer coefficient in the tube side and shell side, respectively. kw is the thermal conductivity of the tube material, and Ao and Ai represent the surface area in the shell and tube side, respectively. L is the length of the test tube. The test is conducted at identical water flowrate for all loadings and the variation in chilled water temperature is also small, thereby suggesting a nearly constant HTC at the chilled water side throughout the tests. This is applicable both in full loading and partial loading. Yet the wall resistance remains unchanged during the tests. As a consequence,
1 U o = 1 h o + C 0
where C 0 = ln ( D o D i ) 2 π k w L + A o h i A i . In the meantime, ho~C1qn for the HTC in the shell side is subject to nucleate boiling as long as the heat transfer is below the threshold heat flux [8]. Hence,
1 U o = 1 C 1 q n + C 0 = C 2 X + C 0
A simple linear regression analysis indicates that n~0.45 for the present flooded evaporator while the intercept C0 is equal to 0.028 m2·K/kW. Note that the corresponding R2 value for the regression is 0.972. In this regard, the corresponding HTC of the tube bundle can be obtained by manipulating the reciprocal of Equation (9):
h o = 1 1 U o C 0
Based on the foregoing analysis, the corresponding HTC for the flooded evaporator at full, 75%, 50%, and 25% loading are 14.1, 13.3, 11.2, and 8.9 kW/m2·K, respectively. On the other hand, as depicted in Figure 3, the overall heat transfer coefficient for the falling film evaporator is appreciably lower than that of the flooded evaporator. There are two reasons for the worse performance of the present falling film evaporator when compared with the flooded evaporator. Note that the falling film evaporator contains two heat transfer modes, namely the evaporation at the liquid/vapor interface and the nucleate boiling at the tube wall surface. Commonly, the contribution of nucleate boiling surpasses the evaporation. A typical HTC distribution associated with tube location (from the first tube to the ninth tube) for the enhanced tube bundle vs. the film Reynolds number by Roques and Thome is shown in Figure 4a [8]. Notice that their test is conducted via GEWA-B enhanced tubes, which are the same as the present test tubes. Apparently, the HTC is strongly related to the film Reynolds number. Note that the Reynolds number is defined as:
Re = 4 Γ μ
where Γ is the liquid flowrate on one side of the tube per unit length. When the film Reynolds number is below a certain threshold value (around 200), the HTC increases with the rise of the film Reynolds number, and the HTC remains barely unchanged with the heat flux. This phenomenon prevails for all the tube locations. The results suggest that evaporation is in control. Analogously, Zhao et al. [12] also performed tests on an enhanced tube bundle using R-134a as the working fluid. Their results, shown in Figure 4b, also indicated that the HTC increases with the film flowrate before a threshold film flowrate of around 0.02 kg/m·s, and that the HTC is relatively independent of heat flux. On the other hand, once the film flowrate or Reynolds number exceeds the threshold value, the HTC remains roughly unchanged with the film flowrate. Although the HTC is quite independent of the film flowrate after the threshold value, it is appreciably increased with the rise of heat flux when passing the threshold value. The results indicate that the nucleate boiling plays an essential role when the film flowrate is above the threshold value. Note that in this study, the corresponding average Reynolds number for the falling film evaporator in the first row spans at around 70~285 and the maximum film flowrate ranges from 0.004~0.015 kg/m·s. The results are close to or below the threshold value of the film Reynolds number and the film flowrate, thereby indicating the dominance of evaporation. In the meantime, as depicted in Figure 2a regarding the layout of the falling film evaporator, which contains a 15 tube row, the effective mean film flowrate in the middle or bottom part of the falling film evaporator may show a much lower liquid film flowrate than the upper portion. Thus, the loss of film flowrate in the middle and bottom part of the tube bundle may bring out dry patches on the tube and deteriorate the heat transfer accordingly. Note that the dry-out patch and the very thin liquid film on the enhanced tube may jeopardized the nucleate boiling mode considerably. In essence, the effective decline of the film flowrate from the top tube toward the bottom part of the falling film evaporator renders an appreciably lower overall HTC when compared with the flooded evaporator. The onset of dry-out of the falling evaporator was also investigated in prior studies. For example, Christians and Thome [21] reported the onset of dry-out Reynolds numbers for the falling film evaporator with enhanced tubes (Turbo B5 and GEWA B5) subject to R-134a and R-236fa. Christians and Thome [19] developed an empirical correlation for the onset of dry-out of falling film, i.e.,
Re o n s e t = 20.721 ( q o h l v μ r e f ) 1.04 G t s 0.175
where Gt-s is the tube specific number, which is 0.1777 for the GEWA B tube. hlv is the latent heat of evaporation. Based on the calculations from this formula, the onset of the dry-out Reynolds number ranges from 34 (25% loading) to 137 (full loading). The results imply that the onset of dry-out can easily occur when the row number is in the middle or bottom portion of the tube bundle. Basically, the present data for the falling film evaporator are expected to contain certain dry-out patches according to their onset of dry-out diagram. It is likely that the local HTC in the upper part of the falling evaporator may still be higher than the corresponding flooded evaporator, but the middle and bottom part of the falling film evaporator may suffer a much lower HTC due to dry patches, thereby resulting in a much lower overall HTC, even at full loading operation. To make the operation even worse, the overall HTC for the falling film evaporator shows an appreciable dip at a partial loading (25%), as seen in Figure 3, compared to the flooded evaporator. In fact, the film flowrate in the bottom row may even fall below 0.001 kg/m·s, indicating a considerable starvation of the liquid film flowrate on the enhanced tubes. Note that the flooded evaporator does not reveal such a dramatic decline in the overall HTC since the refrigerant level is always above the top tube. The results are in line with the numerical simulation regarding the influence of dry patch on the falling film evaporator by Yang et al. [17], who concluded that the heat transfer performance of falling evaporators can be enhanced by increasing the refrigerant flowrate within a certain range due to the decreasing dry patch areas on falling film tubes, and the evaporators reach the best thermal performance when no dry patches appear on the tube. Yet, the deterioration can be further accentuated with mal distribution from the distributor, as addressed by Yang et al. [17]. In summary of the foregoing discussion, it is quite likely that the present falling film evaporator may contain superfluous tubes. The overall performance may still be the same by removing some tubes located in the middle and the bottom part of the tube bundle.

4. Conclusions

The present study compares the performance of real-scale oil-free centrifugal chillers with a flooded evaporator and a falling film evaporator. The nominal capacity for the test chillers is around 200~220 RT. The compressors of the two chillers are identical. Both evaporators make use of GEWA-B-enhanced tubes and R-134a is used as the working fluid. Tests were conducted in full, 75%, 50%, and 25% loading. Based on the forgoing discussions, the following conclusions are derived:
  • Both chillers reveal an appreciable drop of capacity and compressor power when the compressor revolution is reduced but the corresponding COP rises when the loading is reduced, and it reaches the plateau at 50% part-load with a COP of around 9.9. A further un-loading to 25% leads to a detectable decline of COP.
  • The system performance in terms of IPLV for the falling film evaporator is 8.627 and it is 8.634 for the flooded evaporator, implying a comparable performance between the falling film evaporator and the flooded evaporator.
  • The overall heat transfer coefficient for the flooded evaporator is appreciably higher than the falling film evaporator by up to 40%. The results do not agree with typical test results on falling film evaporators and flooded evaporators. This is because the falling film flowrate is below the threshold value and the heat transfer is dominated by the evaporation mode. Yet, the heat transfer performance for the falling film evaporator can be further jeopardized due to starvation of the film flowrate (partial dry-out), since the present film flowrate may fall below the threshold critical film flowrate, especially in the middle or bottom of the tube bundle. This phenomenon becomes even more pronounced at partial loading (25%), while the flooded evaporator did not reveal such performance dip at partial loading.

Author Contributions

All the authors have contributed their efforts to complete the paper. K.-S.H. prepared and analyzed the data, J.-C.C. and J.-J.L. conducted the experiments, C.-C.L. supervised the project and C.-C.W. wrote and edited the manuscript.

Funding

This research was funded by Ministry of Economics Affairs, Taiwan and grants from Ministry of Science and Technology, Taiwan under grant numbers 107-2622-E-009-011-CC2 and 108-2622-E-009-004-CC2.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

A, B, C, DA is coefficient of performance (COP) at 100% load, B is the COP at 75% load, C is the COP at 50% load, and D is the COP at 25% load. From Equation (1), the proportions of 75% and 50% part-loads are much higher than full load or 25% load.
Aiinner surface area of the enhanced tube (m2)
Aoouter surface area of the enhanced tube (m2)
C0, C1,C2correlation constant in Equation (9)
C min m ˙ e v a , w a t e r c p , w a t e r (kW/K)
COPcoefficient of performance
c p , w a t e r specific heat of chilled water (kJ/kg·K)
Diinner tube diameter (m)
Doouter tube diameter (m)
Gt-stube specific number
hitube side heat transfer coefficient (W/m2·K)
hoshell side heat transfer coefficient (W/m2·K)
hlvlatent heat of evaporation (kJ/kg)
kthermal conductivity (W/m·K)
Ltube length (m)
m ˙ e v a , w a t e r chilled water mass flowrate at the evaporator (kg/s)
NTUnumber of transfer unit
qheat flux (kW/m2)
Q ˙ heat transfer rate at the evaporator (kW)
Q ˙ max maximum heat transfer rate at the evaporator (kW)
ReReynolds number
T i n , w a t e r inlet water temperature of the chilled water (K)
T s a t , e v a saturation temperature at the evaporator (K)
Uoverall heat transfer coefficient (W/m2·K)
Wcompcompressor power (kW)
Δ T e v a , w a t e r temperature difference of chilled water across evaporator (K)
εeffectiveness of the heat exchanger
Γliquid flow rate on one side of the tube per unit length (kg/m·s)
μviscosity (Pa·s)

References

  1. Hung, K.-S.; Chung, J.-C.; Liu, C.-C.; Huang, J.-M. A study of off-design performance improvement for a centrifugal refrigerant compressor. Adv. Mech. Eng. 2017, 9. [Google Scholar] [CrossRef] [Green Version]
  2. Air-Conditioning, Heating, and Refrigeration Institute (AHRI). Performance Rating of Water-chilling and Heat Pump Water-heating Packages Using the Vapor Compression Cycle. In ANSI/AHRI STANDARD 551/591 (SI)-2018; AHRI: Arlington, VA, USA, 2018. [Google Scholar]
  3. Yu, F.W.; Chan, K.T.; Sit, R.K.Y. Analysis of centrifugal chillers with oil-free magnetic bearings for enhancing building energy performance. Sci. Technol. Built Environ. 2017, 23, 334–344. [Google Scholar] [CrossRef]
  4. Yu, F.W.; Chan, K.T.; Sit, R.K.Y.; Yang, J. Performance Evaluation of Oil-free Chillers for Building Energy Performance Improvement. Procedia Eng. 2015, 121, 975–983. [Google Scholar] [CrossRef] [Green Version]
  5. Lissandrin, M.; Rampazzo, M.; Cecchinato, L.; Beghi, A. Optimal operational efficiency of chillers using oil-free centrifugal compressors. Int. J. Refrig. 2017, 82, 83–96. [Google Scholar] [CrossRef]
  6. Wang, C.-C.; Hafner, A.; Kuo, C.-S.; Hsieh, W.-D. An overview of the effect of lubricant on the heat transfer performance on conventional refrigerants and natural refrigerant R-744. Renew. Sustain. Energy Rev. 2012, 16, 5071–5086. [Google Scholar] [CrossRef]
  7. Wang, C.-C.; Hafner, A.; Kuo, C.-S.; Hsieh, W.-D. Influence of Lubricant on the Nucleate Boiling Heat Transfer Performance of Refrigerant—A Review. Heat Transf. Eng. 2014, 35, 651–663. [Google Scholar] [CrossRef]
  8. Roques, J.F.; Thome, J.R. Falling Films on Arrays of Horizontal Tubes with R-134a, Part I: Boiling Heat Transfer Results for Four Types of Tubes. Heat Transf. Eng. 2007, 28, 398–414. [Google Scholar] [CrossRef]
  9. Roques, J.F.; Thome, J.R. Falling Films on Arrays of Horizontal Tubes with R-134a, Part II: Flow Visualization, Onset of Dryout, and Heat Transfer Predictions. Heat Transf. Eng. 2007, 28, 415–434. [Google Scholar] [CrossRef]
  10. Habert, M.; Thome, J.R. Falling-Film Evaporation on Tube Bundle with Plain and Enhanced Tubes—Part I: Experimental Results. Exp. Heat Transf. 2010, 23, 259–280. [Google Scholar] [CrossRef]
  11. Habert, M.; Thome, J.R. Falling-Film Evaporation on Tube Bundle with Plain and Enhanced Tubes—Part II: New Prediction Methods. Exp. Heat Transf. 2010, 23, 281–297. [Google Scholar] [CrossRef]
  12. Zhao, C.-Y.; Jin, P.-H.; Ji, W.-T.; He, Y.-L.; Tao, W.-Q. Experimental investigations of R134a and R123 falling film evaporation on enhanced horizontal tubes. Int. J. Refrig. 2017, 75, 190–203. [Google Scholar] [CrossRef]
  13. Jin, P.-H.; Zhao, C.-Y.; Ji, W.-T.; Tao, W.-Q. Experimental investigation of R410A and R32 falling film evaporation on horizontal enhanced tubes. Appl. Therm. Eng. 2018, 137, 739–748. [Google Scholar] [CrossRef]
  14. Ji, W.-T.; Zhao, C.-Y.; Zhang, D.-C.; Yoshioka, S.; He, Y.-L.; Tao, W.-Q. Effect of vapor flow on the falling film evaporation of R134a outside a horizontal tube bundle. Int. J. Heat Mass Transf. 2016, 92, 1171–1181. [Google Scholar] [CrossRef]
  15. Van Rooyen, E.; Thome, J.R. Flow boiling data and prediction method for enhanced boiling tubes and tube bundles with R-134a and R-236fa including a comparison with falling film evaporation. Int. J. Refrig. 2014, 41, 60–71. [Google Scholar] [CrossRef]
  16. Yang, L.; Wang, W. The heat transfer performance of horizontal tube bundles in large falling film evaporators. Int. J. Refrig. 2011, 34, 303–316. [Google Scholar] [CrossRef]
  17. Yang, L.; Song, X.; Xie, Y. Effect of the Dryout in Tube Bundles on the Heat Transfer Performance of Falling Film Evaporators. Procedia Eng. 2017, 205, 2176–2183. [Google Scholar] [CrossRef]
  18. Ribatski, G.; Jacobi, A.M. Falling-film evaporation on horizontal tubes—A critical review. Int. J. Refrig. 2005, 28, 635–653. [Google Scholar] [CrossRef]
  19. Christians, M.; Thome, J.R. Falling film evaporation on enhanced tubes, part 2: Prediction methods and visualization. Int. J. Refrig. 2012, 35, 313–324. [Google Scholar] [CrossRef]
  20. Van Rooyen, E.; Thome, J.R. Pool boiling data and prediction method for enhanced boiling tubes with R-134a, R-236fa and R-1234ze(E). Int. J. Refrig. 2013, 36, 447–455. [Google Scholar] [CrossRef]
  21. Christians, M.; Thome, J.R. Falling film evaporation on enhanced tubes, part 1: Experimental results for pool boiling, onset-of-dryout and falling film evaporation. Int. J. Refrig. 2012, 35, 300–312. [Google Scholar] [CrossRef]
Figure 1. Schematic of the test facilty.
Figure 1. Schematic of the test facilty.
Energies 12 02548 g001
Figure 2. Tube bundle for the falling-film evaporator and the flooded evaporator (unit: mm).
Figure 2. Tube bundle for the falling-film evaporator and the flooded evaporator (unit: mm).
Energies 12 02548 g002
Figure 3. The overall heat transfer coefficient U vs. heat flux for the falling film evaporator and the flooded evaporator.
Figure 3. The overall heat transfer coefficient U vs. heat flux for the falling film evaporator and the flooded evaporator.
Energies 12 02548 g003
Figure 4. Trend of HTCs subject to tube position and heat flux for the falling film evaporator with R-134a. Figure 4a Reprinted with permission from [8]. Copyright 2007 Taylor and Francis; Figure 4b Reprinted with permission from [12]. Copyright 2017 Elsevier.
Figure 4. Trend of HTCs subject to tube position and heat flux for the falling film evaporator with R-134a. Figure 4a Reprinted with permission from [8]. Copyright 2007 Taylor and Francis; Figure 4b Reprinted with permission from [12]. Copyright 2017 Elsevier.
Energies 12 02548 g004
Table 1. Test results for the oil-free centrifugal chiller with a falling evaporator and a flooded evaporator associated with full and partial loading.
Table 1. Test results for the oil-free centrifugal chiller with a falling evaporator and a flooded evaporator associated with full and partial loading.
Type of EvaporatorFalling Film EVAFlooded EVA
Loading100%75%50%25%100%75%50%25%
EEV opening (%)5643332093604837
Inverter frequency (Hz)605517428408625535439417
Rpm18,15015,51012,84012,24018,75016,05013,17012,510
Compression ratio2.492.001.631.562.522.041.641.57
Capacity (USRT)198.7149.0101.451.0229.9169.3112.258.6
Capacity (kW)698.7524.0356.5179.3808.5595.1394.5206.1
Suction pressure (bar, gage)2.622.652.692.692.612.632.672.68
Discharge pressure (bar, gage)8.056.35.034.758.126.415.024.77
Chilled water flowrate (LPM)20182018201820182322232223222322
Inlet temperature
Chilled water (°C)
12.311.09.88.512.110.79.68.3
Outlet temperature
Chilled water (°C)
7.37.37.37.27.27.17.17.1
Cooling water flowrate (LPM)25512551255125512796279627962796
Inlet temperature
Cooling water (°C)
29.823.918.918.829.824.519.118.9
Outlet temperature
Cooling water (°C)
34.427.221.119.934.427.921.320.1
COP5.547.519.947.875.587.359.998.3
Power (kW)126.0869.7735.8622.79144.980.9739.1524.85
Evaporation pressure (bar, gage)2.662.672.702.682.722.702.712.71
Evaporation Temperature (°C)6.46.56.76.76.96.76.86.8
Condensing pressure (bar, gage)7.996.194.974.727.816.325.004.77
Condensing Temperature (°C)35.227.521.320.034.528.121.520.2
Discharge Temperature (°C)42.633.425.925.942.734.126.026.3

Share and Cite

MDPI and ACS Style

Hung, K.-S.; Chung, J.-C.; Liu, C.-C.; Lin, J.-J.; Wang, C.-C. A Comparative Study of the Oil-Free Centrifugal Water Chillers with the Flooded or Falling Film Evaporator—A Case Study. Energies 2019, 12, 2548. https://doi.org/10.3390/en12132548

AMA Style

Hung K-S, Chung J-C, Liu C-C, Lin J-J, Wang C-C. A Comparative Study of the Oil-Free Centrifugal Water Chillers with the Flooded or Falling Film Evaporator—A Case Study. Energies. 2019; 12(13):2548. https://doi.org/10.3390/en12132548

Chicago/Turabian Style

Hung, Kuo-Shu, Jenn-Chyi Chung, Chung-Che Liu, Jun-Jie Lin, and Chi-Chuan Wang. 2019. "A Comparative Study of the Oil-Free Centrifugal Water Chillers with the Flooded or Falling Film Evaporator—A Case Study" Energies 12, no. 13: 2548. https://doi.org/10.3390/en12132548

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop