Performance Analysis of Air Cooled Heat Pump Coupled with Horizontal Air Ground Heat Exchanger in the Mediterranean Climate

Department of Engineering for Innovation, University of Salento, 73100 Lecce, Italy
*
Author to whom correspondence should be addressed.
Received: 14 September 2018 / Revised: 2 October 2018 / Accepted: 8 October 2018 / Published: 11 October 2018
Full-Text   |   PDF [5233 KB, uploaded 11 October 2018]   |  

Abstract

A concept of Air-Cooled Heat Pump (ACHP) coupled with a Horizontal Air-Ground Heat Exchanger (HAGHE), also called Horizontal Earth-To-Air Heat Exchanger (EAHX), has been proposed. The Air-Cooled Heat Pump is a system which transfers heat from outside source (air) to inside sink (water) and vice versa in summertime. The innovation is to provide a geothermal treatment of pre-heating/cooling of air before meeting the evaporator in winter or the condenser in summer of the heat pump. Besides, it is known that the variations of the ground temperature, respect to the external air one, are mitigated already in the first layers of the ground throughout the year, due to the high thermal inertia of the ground, letting the heat pump work with more mitigated conditions, improving the performances. The behaviour of HAGHE has been investigated by varying the length and the installation depth of the probes, the air flow rate and the ground thermal properties. All the combinations have been implemented using TRNSYS 17 software (Transient System Simulation Program) to obtain the outlet temperatures from HAGHE, resulting from the 54 configurations. The results are compared in terms of Coefficient of Performance (COP) in wintertime and Energy Efficiency Ratio (EER) in summertime between configurations with and without the coupling with HAGHE. In addition, two seasonal performance SCOP and SEER coefficients have been calculated considering, not only the inlet air temperatures into the Air-Cooled Heat Pump, but also their frequency of occurrence, the off-set external temperature (16 °C), the nominal external temperature and heating and cooling loads. View Full-Text
Keywords: ground; HAGHE; EAHX; SCOP; SEER; COP; EER; Heat Pump; geothermal; TRNSYS ground; HAGHE; EAHX; SCOP; SEER; COP; EER; Heat Pump; geothermal; TRNSYS
Figures

Figure 1

This is an open access article distributed under the Creative Commons Attribution License which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited (CC BY 4.0).
SciFeed

Share & Cite This Article

MDPI and ACS Style

Baglivo, C.; Bonuso, S.; Congedo, P.M. Performance Analysis of Air Cooled Heat Pump Coupled with Horizontal Air Ground Heat Exchanger in the Mediterranean Climate. Energies 2018, 11, 2704.

Show more citation formats Show less citations formats

Note that from the first issue of 2016, MDPI journals use article numbers instead of page numbers. See further details here.

Related Articles

Article Metrics

Article Access Statistics

1

Comments

[Return to top]
Energies EISSN 1996-1073 Published by MDPI AG, Basel, Switzerland RSS E-Mail Table of Contents Alert
Back to Top