Next Article in Journal
Scheduling Model for Renewable Energy Sources Integration in an Insular Power System
Previous Article in Journal
Evaluation of the Theoretical Geothermal Potential of Inferred Geothermal Reservoirs within the Vicano–Cimino and the Sabatini Volcanic Districts (Central Italy) by the Application of the Volume Method
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

PMU Measurement-Based Intelligent Strategy for Power System Controlled Islanding

1
School of Electrical Engineering, Southeast University, Nanjing 210096, China
2
College of Automation, Nanjing University of Posts and Telecommunications, Nanjing 210023, China
*
Author to whom correspondence should be addressed.
Energies 2018, 11(1), 143; https://doi.org/10.3390/en11010143
Submission received: 28 November 2017 / Revised: 2 January 2018 / Accepted: 3 January 2018 / Published: 7 January 2018
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
Controlled islanding is an effective remedy to prevent large-area blackouts in a power system under a critically unstable condition. When and where to separate the power system are the essential issues facing controlled islanding. In this paper, both tasks are studied to ensure higher time efficiency and a better post-splitting restoration effect. A transient stability assessment model based on extreme learning machine (ELM) and trajectory fitting (TF) is constructed to determine the start-up criterion for controlled islanding. This model works through prompt stability status judgment with ELM and selective result amendment with TF to ensure that the assessment is both efficient and accurate. Moreover, a splitting surface searching algorithm, subject to minimal power disruption, is proposed for determination of the controlled islanding implementing locations. A highlight of this algorithm is a proposed modified electrical distance concept defined by active power magnitude and reactance on transmission lines that realize a computational burden reduction without feasible solution loss. Finally, the simulation results and comparison analysis based on the New England 39-bus test system validates the implementation effects of the proposed controlled islanding strategy.

1. Introduction

A modern power system operates close to its technical limits because of expansions in scale and load demand. This operation makes a power system more vulnerable to serious disturbances. To prevent blackouts evolved from rotor angle instability conditions, system separation measures are implemented and show an effect in certain scenarios [1]. With advances in the development of measuring and controlling techniques, controlled islanding strategies adapted to different scenarios are of increasing interest [2,3,4].
For controlled islanding [5], the splitting initiation criterion, an algorithm for splitting surface determination and stability control for an isolated sub-group system, are necessary in the implementation and are usually discussed separately in the literature. Moreover, determining when and where to separate the power system is primarily studied because of the crucial impact of these factors on the success rate of controlled islanding. Splitting initiation criterion usually relies on prompt transient stability status judgment of the power system, which can be categorized into two types according to which physical model is considered. Rapid time-domain simulation [6] and transient energy function methods [7] are representatives of model-based methods.
With widely-configured advanced metering infrastructure [8], dynamic data during a power system transient period can be obtained within milliseconds. On this basis, the use of model-free methods has expanded rapidly because of their acceptable accuracy and accredited high processing speed. On one hand, implicit information in trajectories, e.g., the rotor angle trajectory and the active power trajectory of a generator, is excavated from the aspect of physical [9,10,11] and mathematical [12,13] characteristics. In [9,10], post-disturbance dynamics are analyzed on phase planes Δω–Δδ and P–Δδ to realize stability assessment. These methods rely on correct mapping of an actual power system, the complexity of which increases vastly with the expansion of the power system scale. In [12,13], a curve extrapolation technique, including Taylor series expansion and a pattern recognition method, is applied for fast stability assessment. These methods demonstrate promising performance in short-term assessment; however, their results in long-term assessment are questionable because they do not account for power system non-linear characteristics in a dynamic process. On the other hand, machine learning techniques, including artificial neural networks (ANN) [14,15], support vector machine (SVM) [16], decision tree (DT) [17,18], and extreme learning machine (ELM) [19], have been widely utilized for transient stability assessment, showing promising performance. In [18], an adaptive controlled islanding measure assisted by the DT method is proposed to solve the problem of “when to island”. However, the accuracy of these machine learning based methods is closely related to the training sample scale and quantity, as well as the training method.
Three types of methods are used to determine the splitting surface. Slow coherency theory is the theoretical support for the first type [2,20,21,22]. This type of method reduces the feasible solution space by identifying, in advance, slowly coherent groups of generators with which the dynamic behavior of each generator is considered. However, the time-consuming problem caused by evaluation of higher order states of the system and iterative calculations is noteworthy. The second type of method relies on graph theory [23,24,25]. These methods consider the power system as an undirected graph, and cut sets of splitting lines are determined by satisfying certain constraints. Although these methods achieve an increase in computing efficiency, problems with respect to feasible solution loss in the graph reduction process and rationality of the computing results deserve further research. In [23], breadth first search (BFS) and depth first search (DFS) were applied to searching for the optimal solution with minimal power imbalance. In [24], a three-phase method based on an ordered binary decision diagram (OBDD) highlighted the superiority of graph theory. In [25], the calculation complexity is considerably reduced with spectral clustering; however, the procedure on generator coherency constraint processing is controversial [26]. The third type of method is based on an intelligent optimal solving algorithm, which can help to speed up the calculations and determine globally-optimal solutions that are as close to the truly optimal solutions as practically possible [27,28].
In most of the relevant literature, research on controlled islanding strategies are conducted from the aspect of either the start-up criterion or optimal splitting surface determination. However, a complete controlled islanding strategy should include both aspects in practical implementation. Moreover, increased configuration of phasor measurement unit (PMU) devices enables a situational awareness capability of a power system, and an efficient data-processing method is necessary to achieve such a capability.
Therefore, the main objective of this paper is to propose a controlled islanding strategy with high efficiency and reliability. For the start-up criterion, a transient stability assessment model aimed at maximizing the benefits of model-free methods is constructed by integrating machine learning and the trajectory fitting (TF) method. Furthermore, an optimal splitting surface determining algorithm based on graph theory is proposed; this algorithm avoids feasible solution loss using the modified network reduction method.
The remainder of this paper is organized as follows: In Section 2, key issues about controlled islanding strategy design is discussed. The transient stability assessment model for the start-up criterion and the searching algorithm for the optimal splitting surface are presented in Section 3 and Section 4, respectively. The implementing structure and process of the proposed controlled islanding strategy is explained in Section 5. Case studies and the conclusions are presented in Section 6 and Section 7, respectively.

2. Controlled Islanding Strategy Design

In contrast with conventional passive islanding, controlled islanding is an online, centralized, and globalized implementation method for system separation. This method determines the splitting locations rapidly with globally obtained operation information and constraints, e.g., power imbalance and power-flow disruption. Hence, controlled islanding always shows outstanding performance.
Determining both when and where to separate the power system is essential for controlled islanding. The splitting action occasion is influential on the dynamics of post-splitting systems. The splitting surface selection determines the operational state of the isolated system and the subsequent control measures.
Regarding the task of “when”, prompt transient stability assessment is an effective tool. Model-based transient stability assessment methods, e.g., time simulation and transient energy function, are restricted by excessive computing time or high complexity in the analysis of a large-scale power system. Machine learning-based methods have been widely applied in stability assessment, exhibiting good performance. Among these machine learning methods, the ELM algorithm has been demonstrated to be useful for transient stability assessment because of its high training efficiency and preferable accuracy. In [19], the ELM was verified to provide incorrect judgments at relatively high possibility, if its output is within a certain interval. This result indicated that the accuracy of the ELM-based transient stability assessment model could be enhanced further with specifical amendments. In this paper, the TF method in [13] is adopted as the enforcement tool for amendments. Hence, the start-up criterion for controlled islanding strategy is determined using a transient stability model constructed based on the ELM and the TF method. The model realizes a balance between computing speed and accuracy through a proposed coordinating mechanism.
Regarding the task of “where”, it aims to determine a suitable islanding surface to ensure the stability of the post-splitting subgroup system. In this paper, “suitable solution” corresponds to the splitting surface with minimal power imbalance and power-flow disruption, where minimal power imbalance is regarded as the objective function in the optimal splitting surface calculation. Theoretically, the searching algorithm requires a large calculation quantity because of the extensive possibility of splitting line sets; this situation is known as a typical NP-hard (non-deterministic polynomial) problem. For either graph theory-based methods or slow coherency theory-based methods, determining the splitting surface is intended to search for generator groups with weak connections. Hence, the possible solution space can be pre-filtered with an evaluation of the electrical connection strength. The electrical distance with line reactance only is such an evaluation index; however, this index’s static feature may lead to loss of feasible solutions in the network reduction. In this paper, a modified electrical distance defined by the ratio of the transmission line reactance and the active power measurements (xij/Pij) is proposed for solution space reduction.

3. Hybrid Transient Stability Assessment Model for Activation Criterion

Conventional passive islanding relies on local electrical information to function. Controlled islanding makes a decision based on global system information, and its action state depends on transient stability assessment results.
In this part, a hybrid transient stability assessment model based on the ELM and the TF method is constructed, as shown in Figure 1. The proposed model can provide support for making a controlled islanding decision with post-disturbance system stability assessment results. If the assessment result is stable, then subsequent measures for controlled islanding (e.g., splitting surface searching and splitting actions) will not be triggered. Otherwise, the splitting surface searching algorithm will be initiated at once with generator grouping information.

3.1. ELM Theory

The ELM is a single hidden layer feed-forward neural network algorithm proposed by Huang [29]. Compared with a conventional neural network algorithm, the ELM algorithm determines the parameters of hidden nodes using a random assignment and inverse calculation process, rather than the time-consuming tuning process using the gradient descent method, thereby guaranteeing its high training speed.
Training samples with N sets can be represented as follows:
N = { ( x i , t i ) | x i R n , t i R m } i = 1 N
where xi is a n × 1 input vector, and ti is a m × 1 target vector. A single-hidden layer network with activation function θ(x) can be modeled as:
i = 1 N ˜ β i ϑ i ( w i , b i , x j ) = o j , j = 1 , , N
where N ˜ represents the number of hidden nodes, w i = [ w i 1 , w i 2 , , w i n ] T and bi are parameters of the hidden nodes, and β i = [ β i 1 , β i 2 , , β i n ] T is the weighting vector connecting the i-th hidden nodes and the output nodes. The structure of the ELM algorithm is shown in Figure 2.
For each training sample, the calculated outputs are expected to remain the same as the actual results, which can be represented as j = 1 N o j t j = 0 . Therefore, β i , b i , w i is to be determined to satisfy i = 1 N ˜ β i ϑ i ( w i , b i , x j ) = t j , j = 1 , , N , which can be written in matrix form as follows:
H β = T
where:
H ( w 1 , , w N ˜ , b 1 , , b N ˜ , x 1 , , x N ˜ ) = [ ϑ ( w i , b i , x 1 ) ϑ ( w N ˜ , b N ˜ , x 1 ) ϑ ( w i , b i , x N ) ϑ ( w N ˜ , b N ˜ , x N ) ] N × N ˜ , β = [ β 1 T β N ˜ T ] N ˜ × m T = [ t 1 T t N T ] N × m
Hence, the training process is to determine βi, wi, and bi. For the ELM training algorithm, the parameters wi and bi are fixed before training with random values. βi is the only undetermined parameter. If the number of hidden neurons is equal to the number of training samples, then βi can be calculated easily [29]. Although the number of hidden neurons is less than the number of training samples, generally, precise values of βi, wi. and bi, may not exist. The mathematical model can be transformed to minimize the cost function given below, where β i , b i , w i (the optimal approximate solution) are to be determined:
E = j = 1 N ( i = 1 L β ˜ i ϑ ( w ˜ i X j + b ˜ i ) t j ) 2
For fixed w ˜ i , b ˜ i , β ˜ i the approximate solution can be easily determined [29].
The ELM-based transient stability assessment model is constructed through three main steps. First, historical samples and offline simulation samples, which consist of system features, are collected for feature selection. The recorded actual data can be used to supplement the prior knowledge base to ensure the adaptation to a practical power system. Second, Fisher discrimination is implemented to determine the features that are closely related to the system transient stability status from the initial features with samples in the prior knowledge base. In this manner, the required data scale is reduced and the computing efficiency is improved.
In this paper, the initial features (listed in Table 1) can be obtained by PMU measurements.
Finally, the selected features are regarded as significant features and applied for training of the ELM-based classifier. Once the classifier is established, the ELM transient stability assessment model is constructed. In practical implementation, the transient stability status is judged by the assessment model according to the PMU measurements of the significant features within a short time delay.

3.2. ELM-Based Transient Stability Assessment Model

As mentioned above, the accuracy of a machine learning technique-based method is greatly influenced by the scale and quality of the training samples, as well as the training approach. To improve the accuracy, the TF method [13] is applied to amend the outputs of the ELM-based stability assessment model in certain cases; this approach indicates a coordination mechanism exists in the hybrid transient stability assessment model. The TF method can be constructed using the following two steps:
  • Generator rotor angle trajectories in various scenarios are collected from simulation and historical samples and comprise the prior sample database for one certain generator. The difference between samples is measured by the vector distance and is defined as follows:
    f ( x i , T , x j , T ) = ( t = 0 T 1 ( x i , t x j , t ) 2 ) 1 2
    where xi,T, xj,T are samples i and j with data of T moments. The samples are considered approximate if the vector distance between them is less than a certain threshold.
  • Approximate trajectory samples are grouped using the hierarchical clustering algorithm. The trajectory having the minimum vector distance with other trajectories is defined as the standard trajectory of the group. Standard trajectories comprise the standard trajectory pattern library, and the measured trajectory is subsequently matched with pattern trajectories in this pattern library to predict the rotor angle trajectory tendency. If the rotor angle of any generator is beyond 180° with the predicted trajectory, then it is judged as a transient instability. Otherwise, it is stable in the transient process.
As the essential component of the hybrid transient stability assessment model, the coordination mechanism is designed for sampling time and result amendment. The ELM- and the TF-based assessment model require five cycles and 15–20 cycles of sampling time, respectively. If the measurements are sufficient in quantity and quality, then the assessment model is initiated immediately. With the conclusion that output of the ELM-based model is problematic in a certain interval in [19], the result amendment procedure is triggered if the output of the ELM-based model is in an unreliable interval. In this case, the TF-based method is used for this amendment procedure and determines the final transient stability assessment result. The determined result is taken as the start-up criterion to decide whether to start up the controlled islanding surface searching algorithm and the splitting action.

4. Optimal Splitting Surface Search Algorithm

The splitting surface searching approach is always used to determine weakly-connected generator groups, among which an out-of-synchronization state typically occurs. In this section, a modified electrical distance index is used to determine those nodes having vague connection with separated generator groups, which could significantly simplify the solution space without feasible solution loss. The ‘optimal’ algorithm involves satisfying some other constraints and considering an active power imbalance of the isolated system as the objective function in the proposed searching algorithm.

4.1. Nodes Classification

Conventionally, a power system is considered to be an undirected graph with edge weight and the accumulated value of the edge weights between nodes is regarded as the electrical distance. In most cases, the reactance of lines is defined as the edge weight for network simplification, and nodes in the electrical network can be divided into two types. Nodes near one certain group of coherent generators in electrical distance are labeled as normal nodes (NN). Otherwise, if nodes share a similar connection with multiple groups of coherent generators, then they are classified as public nodes (PN).
However, considering reactance only in the electrical distance is not complete, theoretically. The detailed analysis of a specific case is shown below:
Figure 3 shows a structure of a simple power system, where the reactance of two lines is equal, i.e., x1 = x2, and the load on buses m and n are S1 = 2S2, where S1 = 2S2, i.e., the active power transmitted between node i and m is twice as much as that between node i and n. Therefore, the electrical distance between nodes i and m is equal to that between nodes i and n when only reactance is considered in the electrical distance. However, this approach neglects the effect of transmitted power on the lines. In this paper, the ratio of the reactance and the active power of the lines is considered as the edge weight to evaluate the electrical distance. We take the IEEE-9 test system as an example to show the advantage of this approach as follows:
The effect of the edge weight on the results of determining the splitting surface is analyzed on the IEEE-9 test system [25]. Figure 4 shows the edge weight defined with xij and xij/Pij of the IEEE-9 test system in (a) and (b), respectively. The minimum accumulating value of the edge weight from node 9 to nodes 1 and 3 are calculated, as summarized in Table 2.
Table 2 indicates that edge weight defined with xij has smaller weight value from node 9 to 1, i.e., node 9 is closer to node 1 than to node 3. While nodes 9 to 3 have relatively stronger connections for the edge weight defined by xij/Pij. This difference may lead to a loss of feasible solutions in network reduction for the reactance-only scenario. Hence, further research is necessary to consider reactance not only in the electrical distance.
In this paper, xij/Pij is defined as the edge weight of the undirected graph-model. Reduction of the islanding solution space is executed using the following steps:
  • Calculating the minimum accumulative edge weight among nodes using the Floyd algorithm. The electrical distance between the load nodes and the coherent generator groups can be written as:
    D i m = 1 N m j = 1 N m W i j
    where Nm is the number of generators in coherent group m, and Wij is the minimum accumulative edge weight between load node i and generator node j in group m.
  • The difference in the electrical distance between load node i and two generator groups m1 and m2 can be estimated as:
    γ = D i m 1 D i m 2
A threshold ε is pre-determined according to statistical data and operational experience, with the public nodes occupying approximately 20% of the whole nodes. Node i is defined as the public node of the two generator groups when | γ | < ε . If | γ | > ε , then node i is defined as a normal node and node i is classified as a closely connected generator group according to the positive-negative value of γ.

4.2. Optimal Splitting Surface Searching Algorithm

On basis of node classification, a normal node is assigned to a corresponding generator group. The essence of searching the optimal splitting surface becomes distribution of the public nodes into suitable generator groups. To determine the optimal splitting surface, the minimum active power imbalance and the minimal power-flow disruption are applied as the objective functions in Equations (8) and (9), respectively:
min Δ P = | P G P L |
min i V 1 , j V 2 | P i j |
where PG and PL denote the active power of the generators and the loads in the isolated system respectively, and Pij is the active power transmitted between nodes i and j. The minimum active power imbalance of the isolated system determines whether the isolated system can recover from load-generation imbalance. Minimum power-flow disruption can reduce the disruption caused by variation of the power-flow dispatch. In this paper, the minimum active power imbalance of the isolated system is taken as the objective function. The set of public nodes is distributed into suitable generator groups using the Breadth First Search (BFS) algorithm for optimal splitting location determination.

5. Controlled Islanding Implementing Strategy

The problems of when and where to separate the power system are solved by implementing the proposed strategy. In this strategy, the splitting action is supposed to be executed once the splitting location is determined by the optimal splitting surface searching algorithm. The implementation of the proposed controlled islanding strategy is shown in Figure 5; the details of the steps are as follows:
Step 1:
Start the prediction program after a disturbance is detected.
Step 2:
Capture the PMU measurements required by the hybrid transient stability assessment model. Note that the sampling time is different for the ELM- and for the TF-based models in this hybrid assessment model.
Step 3:
Initiate the splitting criterion-deciding procedure using the hybrid transient stability assessment model. In this model, the amending procedure using the TF model is activated if the output of the ELM model shows uncertainty.
Step 4:
Judge whether to start the optimal islanding surface searching algorithm according to the splitting criterion, i.e., the system stability status. If the power system tends to lose stability, then go to step 5; otherwise, go to step 1.
Step 5:
The optimal splitting surface searching program starts. Series procedures, including system undirected graph construction, nodes classification, and optimal solution calculating, are conducted.
Step 6:
The optimal splitting surface is determined, and the splitting action is immediately executed. The program ends, and the next round begins.
It can be inferred from Figure 5 that the hybrid transient stability assessment model and the optimal splitting surface searching algorithm are essential parts of the proposed strategy. In the hybrid model, the ELM method output assessment result is taken in most cases and the TF method amendment is taken in certain cases to realize optimization of the combination of computing speed and accuracy. Moreover, the splitting surface with a minimized active power imbalance can be determined rapidly via reduction of the possible solution space. Sequentially, fast and reliable detection of transient instability and determination of the optimal splitting surface is realized, thereby achieving the purpose of the proposed strategy.

6. Case Study

The New England 39-bus test system is used as the testbed for validation of the proposed controlled islanding strategy. To construct the transient stability assessment model, 10,000 samples are generated using the Monte Carlo method; 9000 of these samples are applied for training and trajectory clustering, and the rest are applied for testing. The transient stability status will be determined to be unstable as soon as the rotor angle of any generator exceeds 180° compared with the reference generator.
Initial features for feature selection are summarized in Table 1. These initial features are processed via Fisher discrimination to determine the significant features. Figure 6 shows the importance value for each feature, and the top 100 features of the total are chosen as the inputs for the ELM classifier training.
Figure 6 shows that most significant features are dynamic information, e.g., voltage magnitude and phase angle variation, generator rotor angle variation, and fault information. These significant features are used as the ELM training and model inputs. Examinations on the ELM-based transient stability assessment model show that accuracy can reach 97.46% with 1350 hidden nodes at maximum.
Misjudged cases of the ELM-based transient stability assessment model are small in quantity, but are inevitable. The distribution of the output value for correct and incorrect assessment of the ELM-based model is further studied, as shown in Figure 7.
This finding indicates that the output value for the most misjudged case is within a specific interval ranging from 0 to 1.0, which is defined as the unreliable interval. In this paper, the unreliable interval is set as (0, 0.8).
In the hybrid transient stability assessment model, the TF method is applied to amend the ELM assessment results in the unreliable interval. When number of hidden nodes of the ELM algorithm is set as 500, the accuracy is improved from 94.1% (ELM only model) to 100% (hybrid model). The results show that 355 sets of 1000 test samples with problematic outputs are processed using the TF-based model. The TF method rectifies the ELM-based model assessment results 63 times, 45 of which are corrected from the stable condition to the unstable condition. The expected computing time for each test sample increases from 0.041 s (ELM only model) to 0.136 s (hybrid model). Compared with the ELM-only method, the computing time is a slightly longer, but the accuracy is highly improved.

6.1. Case 1: Assessment by ELM Model is Reliable

In this case, a three-phase short circuit fault is set to occur at 0 s in the middle of lines 23–24 and is cleared at 0.4 s. The generators form two coherent groups: {33, 34, 35, 36} and {30, 31, 32, 37, 38, 39}, in which generators 33–36 are the critical crew. Identification of the instability using the ELM-based transient stability assessment model requires 0.036 s. On the basis of the node classification mentioned above, the evaluation value for the electrical distance between load nodes and two generator groups are listed in Table 3.
The threshold ε is set as 0.035. Therefore, nodes 2, 3, 10, 11, 12, 13, 14, and 25 are defined as public nodes. Normal nodes 15, 16, 17, 18, 19, 20, 21, 22, 23, and 24 belong to the generator group {33, 34, 35, 36}. The calculated optimal splitting surface solution is shown in Figure 8 with the red dashed line (Scheme 1).
It can be inferred from Table 3 that node 27 has a shorter electrical distance from the generator group {30, 31, 32, 37, 38, 39} than from {33, 34, 35, 36}. In the algorithm defining the reactance as the edge weight, node 27 is classified into the generator group {33, 34, 35, 36}, and the final splitting solution is shown in Figure 8 with the green solid line (Scheme 2). To show the strength of the proposed algorithm, the algorithm defining reactance as the edge weight is contrasted from the aspect of active power imbalance and power-flow disruption in Table 4.
The table indicates that algorithm considering only reactance in electrical distance may lead to loss of feasible solutions and, thus, affect the final optimal solution. In this condition, power flow disruption is higher than the result found using the proposed algorithm.
Figure 9 and Figure 10 show the trajectories of the critical generator group {33, 34, 35, 36} using the two islanding strategies. Variation of the generator rotor angle shows that the islanding solution presented in this paper retains system stability better.

6.2. Case 2: ELM Output Located in the Unreliable Interval

In this case, a three-phase short circuit fault occurs at 0.1 s at the middle of line 6–7 and continues for 0.4 s until it is cleared. This fault leads to desynchronization between the generator group {31, 32} and the remaining generators. It takes approximately 0.3 s of computing time to ensure an accurate assessment using the TF method because the ELM output is located in the unreliable interval [0, 0.8].
The optimal splitting solution is shown in Figure 11, marked with the red dashed line (Scheme 1). The solution is contrasted with the results (Scheme 2 in Figure 11) determined by the algorithm presented in the literature [30], whose objective function is the minimum power-flow disruption; a comparison of the results is shown in Table 5.
It is apparent that the algorithm that determines the minimum cut ensures the minimum power-flow disruption. Compared with this algorithm, the proposed algorithm in this paper can also avoid high power-flow disruption by taking active power on transmission lines into consideration in the concept of the electrical distance. Using the proposed algorithm, the solution space is reduced based on the electrical distance, resulting in a reduced computing time while providing a consistent (nearly identical) result.
The validation results illustrate that the ELM-based transient stability assessment model is computationally efficient. The TF method is able to amend the problematic results of the ELM-based assessment model; however, this amendment requires a slightly longer computing time. The algorithm proposed for optimal splitting location determination reduces the solution space using the modified electrical distance concept while not losing any feasible solutions.

7. Conclusions

In this paper, a controlled islanding strategy consisting of prompt transient stability assessment and optimal splitting surface determination was described.
(1).
A hybrid transient stability assessment model based on the ELM and TF methods was constructed to determine the start-up criterion. In this model, the ELM method is used for prompt stability assessment, and the TF method is employed to enhance the reliability of the assessment results.
(2).
A rapid algorithm comprised of network reduction and optimal solution searching was proposed to determine the splitting surface. In this algorithm, feasible solution loss in the network reduction process is avoided by modifying the evaluation index of the electrical distance.
Using the proposed method, both the start-up criterion and the optimal splitting surface can be determined online with high reliability. The results showed that the proposed controlled islanding strategy is effective in preventing transient instability. As the scenarios considered in this work were designed optimally, the sample generation problem and data acquisition risks in a realistic scenario were ignored. Further research can be dedicated to these problems to achieve reliable performance of the proposed controlled islanding strategy in a practical implementation.

Acknowledgments

This work was supported in part by the National Science Foundation of China under grants 51577030 and 61503197, Science and Technology Project of SGCC (XT71-16-032), and the National Key Research and Development Program of China in Basic Research Class under grant 2017YFB0903000.

Author Contributions

Yi Tang and Qi Wang contributed in developing the concepts of this research study. Feng Li and Chenyi Zheng performed this research study. Yingjun Wu provided technical support in the simulations of this research study. All of the authors read and approved the final manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Taylor, C.W.; Erickson, D.C. Recording and analyzing the July 2 cascading outage. IEEE Comput. Appl. Power 1997, 10, 26–30. [Google Scholar] [CrossRef]
  2. You, H.; Vittal, V.; Wang, X. Slow Coherency-Based Islanding. IEEE Trans. Power Syst. 2004, 19, 483–491. [Google Scholar] [CrossRef]
  3. Senroy, N.; Heydt, G.T. A conceptual framework for the controlled islanding of interconnected power systems. IEEE Trans. Power Syst. 2006, 21, 1005–1006. [Google Scholar] [CrossRef]
  4. Franco, R.; Sena, C.; Taranto, G.N.; Giusto, A. Using synchrophasors for controlled islanding—A prospective application for the Uruguayan power system. IEEE Trans. Power Syst. 2013, 28, 2016–2024. [Google Scholar] [CrossRef]
  5. Li, L.; Liu, Y.; Mu, H.; Yu, Z. Out-of-Step splitting scheme based on PMUs. In Proceedings of the 3rd International Conference on Deregulation and Restructuring and Power Technologies (DRPT 2008), Nanjing, China, 6–9 April 2008. [Google Scholar]
  6. Wang, S.; Lu, S.; Zhou, N.; Lin, G.; Elizondo, M.; Pai, M.A. Dynamic-feature extraction, attribution, and reconstruction (DEAR) method for power system model reduction. IEEE Trans. Power Syst. 2014, 29, 2049–2059. [Google Scholar] [CrossRef]
  7. Bhui, P.; Senroy, N. Real-Time Prediction and Control of Transient Stability Using Transient Energy Function. IEEE Trans. Power Syst. 2017, 32, 923–934. [Google Scholar] [CrossRef]
  8. Bian, D.; Kuzlu, M.; Pipattanasomporn, M.; Rahman, S. Analysis of communication schemes for Advanced Metering Infrastructure (AMI). In Proceedings of the 2014 IEEE Power and Energy Society General Meeting, National Harbor, MD, USA, 27–31 July 2014. [Google Scholar]
  9. Shrestha, B.; Gokaraju, R.; Sachdev, M. Out-of-Step protection using state-plane trajectories analysis. IEEE Trans. Power Deliv. 2013, 28, 1083–1093. [Google Scholar] [CrossRef]
  10. Hazra, J.; Reddi, R.K.; Das, K.; Seetharam, D.P.; Sinha, A.K. Power grid transient stability prediction using wide area synchrophasor measurements. In Proceedings of the 2012 3rd IEEE PES Innovative Smart Grid Technologies Europe (ISGT Europe 2012), Berlin, Germany, 14–17 October 2012. [Google Scholar]
  11. Gurusinghe, D.R.; Rajapakse, A.D. Post-disturbance transient stability status prediction using synchrophasor measurements. IEEE Trans. Power Syst. 2016, 31, 3656–3664. [Google Scholar] [CrossRef]
  12. Ohura, Y.; Suzuki, M.; Yanagihashi, K.; Yamaura, M.; Omata, K.; Nakamura, T.; Mitamura, S.; Watanabe, H. A predictive out-of-step protection system based on observation of the phase difference between substations. IEEE Trans. Power Deliv. 1990, 5, 1695–1704. [Google Scholar] [CrossRef]
  13. Liu, X.D.; Li, Y.; Liu, Z.J.; Huang, Z.G.; Miao, Y.Q.; Jun, Q.; Jiang, Q.Y.; Chen, W.H. A novel fast transient stability prediction method based on PMU. In Proceedings of the 2009 IEEE Power and Energy Society General Meeting, Calgary, AB, Canada, 26–30 July 2009. [Google Scholar]
  14. Sobajic, D.J.; Pao, Y.-H. Artificial neural-net based dynamic security assessment for electric power systems. IEEE Trans. Power Syst. 1989, 4, 220–228. [Google Scholar] [CrossRef]
  15. Amjady, N.; Majedi, S.F. Transient stability prediction by a hybrid intelligent system. IEEE Trans. Power Syst. 2007, 22, 1275–1283. [Google Scholar] [CrossRef]
  16. Zhou, Y.; Wu, J.; Yu, Z.; Ji, L.; Hao, L. A hierarchical method for transient stability prediction of power systems using the confidence of a SVM-based ensemble classifier. Energies 2016, 9, 778. [Google Scholar] [CrossRef]
  17. Amraee, T.; Ranjbar, S. Transient instability prediction using decision tree technique. IEEE Trans. Power Syst. 2013, 28, 3028–3037. [Google Scholar] [CrossRef]
  18. Vittal, V.; Senroy, N.; Heydt, G.T. Decision Tree Assisted Controlled Islanding. IEEE Trans. Power Syst. 2006, 21, 1790–1797. [Google Scholar] [CrossRef]
  19. Xu, Y.; Dong, Z.Y.; Meng, K.; Zhang, R.; Wong, K.P. Real-time transient stability assessment model using extreme learning machine. IET Gener. Transm. Distrib. 2011, 5, 314–322. [Google Scholar] [CrossRef]
  20. Yusof, S.B.; Alden, R.T.H.; Rogers, G.J. Slow coherency based network partitioning including load buses. IEEE Trans. Power Syst. 1993, 8, 1375–1382. [Google Scholar] [CrossRef]
  21. Yang, B.; Vittal, V.; Heydt, G.T. Slow-coherency-based controlled islanding—A demonstration of the approach on the August 14, 2003 blackout scenario. IEEE Trans. Power Syst. 2006, 21, 1840–1847. [Google Scholar] [CrossRef]
  22. Song, H.; Wu, J.; Wu, K. A wide-area measurement systems-based adaptive strategy for controlled islanding in bulk power systems. Energies 2014, 7, 2631–2657. [Google Scholar] [CrossRef]
  23. Wang, X.M. Slow Coherency Grouping Based Islanding Using Minimal Cut Sets and Generator Coherency Index Tracing Using the Continuation Method. Ph.D. Thesis, Iowa State University, Ames, IA, USA, 2005. [Google Scholar]
  24. Sun, K.; Zheng, D.Z.; Lu, Q. Splitting strategies for islanding operation of large-scale power systems using OBDD-based methods. IEEE Trans. Power Syst. 2003, 18, 912–923. [Google Scholar] [CrossRef]
  25. Ding, L.; Gonzalez-Longatt, F.M.; Wall, P.; Terzija, V. Two-step spectral clustering controlled islanding algorithm. IEEE Trans. Power Syst. 2013, 28, 75–84. [Google Scholar] [CrossRef]
  26. Lin, Z.Z.; Wen, F.S. Discussion on “two-step spectral clustering controlled islanding algorithm”. IEEE Trans. Power Syst. 2014, 29, 413. [Google Scholar] [CrossRef]
  27. El-Zonkoly, A.; Saad, M.; Khalil, R. New algorithm based on CLPSO for controlled islanding of distribution systems. Int. J. Electr. Power Energy Syst. 2013, 45, 391–403. [Google Scholar] [CrossRef]
  28. Liu, L.; Liu, W.; Cartes, D.A.; Chung, I.Y. Slow coherency and Angle Modulated Particle Swarm Optimization based islanding of large-scale power systems. Adv. Eng. Inform. 2009, 23, 45–56. [Google Scholar] [CrossRef]
  29. Huang, G.-B.; Zhu, Q.-Y.; Siew, C.-K. Extreme learning machine: Theory and applications. Neurocomputing 2006, 70, 489–501. [Google Scholar] [CrossRef]
  30. Tang, F.; Jia, J.; Wang, B.; Liao, Q.; Wang, J.; Zhu, Z.; Liu, Y. Study on a fast controlled partition scheme based on improved Dinic max-flow strategy. In Proceedings of the 2015 IEEE Power and Energy Society General Meeting, Denver, CO, USA, 26–30 July 2015. [Google Scholar]
Figure 1. Construction and work-flow of the hybrid transient stability assessment model.
Figure 1. Construction and work-flow of the hybrid transient stability assessment model.
Energies 11 00143 g001
Figure 2. Structure of the single hidden layer feed-forward neural network.
Figure 2. Structure of the single hidden layer feed-forward neural network.
Energies 11 00143 g002
Figure 3. A simple power system for illustration.
Figure 3. A simple power system for illustration.
Energies 11 00143 g003
Figure 4. Graph-model of the IEEE-9 test system. (a) edge weight with xij index; (b) edge weight with xij/Pij index.
Figure 4. Graph-model of the IEEE-9 test system. (a) edge weight with xij index; (b) edge weight with xij/Pij index.
Energies 11 00143 g004
Figure 5. Flowchart of the proposed controlled islanding implementation strategy.
Figure 5. Flowchart of the proposed controlled islanding implementation strategy.
Energies 11 00143 g005
Figure 6. Features selection with Fisher discrimination.
Figure 6. Features selection with Fisher discrimination.
Energies 11 00143 g006
Figure 7. ELM-based stability assessment model output distribution with testing samples.
Figure 7. ELM-based stability assessment model output distribution with testing samples.
Energies 11 00143 g007
Figure 8. Optimal islanding surface (case 1).
Figure 8. Optimal islanding surface (case 1).
Energies 11 00143 g008
Figure 9. Variation of the generator rotor angles (strategy 1).
Figure 9. Variation of the generator rotor angles (strategy 1).
Energies 11 00143 g009
Figure 10. Variation of the generator rotor angles (strategy 2).
Figure 10. Variation of the generator rotor angles (strategy 2).
Energies 11 00143 g010
Figure 11. Optimal islanding surface (case 2).
Figure 11. Optimal islanding surface (case 2).
Energies 11 00143 g011
Table 1. Initial features for Fisher discrimination evaluation.
Table 1. Initial features for Fisher discrimination evaluation.
NotationDescription
δirotor angle variation of generator i
Vi, θivoltage amplitude and phase angle variation of bus i
Pin,i, Qin,iactive and reactive power injection variation of bus i
PL,i, QL,iactive and reactive power flow of line i
Finfo (ftime and fduration)fault information (fault time and fault duration)
L, Lnodeload level
Table 2. Minimum edge weight cumulative summation.
Table 2. Minimum edge weight cumulative summation.
Edge Weight DefinitionMinimum Accumulating Edge Weight Value
Node 9 to 1Node 9 to 3
xij0.14960.2286
xij/Pij0.40860.3620
Table 3. Difference of the minimum edge weights cumulative summation.
Table 3. Difference of the minimum edge weights cumulative summation.
NodesγNodesγNodesγ
10.0392110.033221−0.0749
20.0276120.031822−0.0772
30.0221130.031823−0.0859
40.0369140.029524−0.0790
50.037915-0.0699250.0300
60.037216-0.0721260.0442
70.037217−0.0663270.0442
80.037918−0.0587280.0545
90.054719−0.0764290.0551
100.032720−0.0803
Table 4. Comparison of the islanding surface searching algorithms.
Table 4. Comparison of the islanding surface searching algorithms.
Islanding StrategyActive Power Imbalance (p.u.)Power-Flow Disruption (p.u.)
14–15, 3–18, 17–270.329/0.1300.805
14–15, 17–18, 26–270.901/1.3604.913
Table 5. Comparison of islanding surface searching algorithms.
Table 5. Comparison of islanding surface searching algorithms.
Islanding StrategyPower-Flow Disruption (p.u.)Time (ms)
3–4, 9–39, 14–151.2733≈11
3–4, 8–9, 14–151.2678≈40

Share and Cite

MDPI and ACS Style

Tang, Y.; Li, F.; Zheng, C.; Wang, Q.; Wu, Y. PMU Measurement-Based Intelligent Strategy for Power System Controlled Islanding. Energies 2018, 11, 143. https://doi.org/10.3390/en11010143

AMA Style

Tang Y, Li F, Zheng C, Wang Q, Wu Y. PMU Measurement-Based Intelligent Strategy for Power System Controlled Islanding. Energies. 2018; 11(1):143. https://doi.org/10.3390/en11010143

Chicago/Turabian Style

Tang, Yi, Feng Li, Chenyi Zheng, Qi Wang, and Yingjun Wu. 2018. "PMU Measurement-Based Intelligent Strategy for Power System Controlled Islanding" Energies 11, no. 1: 143. https://doi.org/10.3390/en11010143

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop