Next Article in Journal
A Review of Design Optimization Methods for Electrical Machines
Previous Article in Journal
Energy-Efficient Subcarrier Pairing and Power Allocation for DF Relay Networks with an Eavesdropper
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Asynchronous Fault Location in Transmission Lines Considering Accurate Variation of the Ground-Mode Traveling Wave Velocity

1
School of Electrical and Power Engineering, China University of Mining and Technology, Xuzhou 221116, China
2
Power and Energy Group, University of Queensland, Brisbane, QLD 4072, Australia
*
Author to whom correspondence should be addressed.
Energies 2017, 10(12), 1957; https://doi.org/10.3390/en10121957
Submission received: 23 October 2017 / Revised: 17 November 2017 / Accepted: 20 November 2017 / Published: 24 November 2017

Abstract

:
This paper proposes a grounding fault location method in transmission lines based on time difference of arrival (TDOA) of ground-mode and aerial-mode traveling waves (TWs). The frequency-dependent characteristics of transmission lines cause different frequencies to have different attenuations and phase lags of different frequency components in traveling waves, which leads to the change of TWs velocities with different propagation distances. Due to these different propagation paths, the wave velocity variations of ground-mode should be considered as a main variable while the velocity of aerial-mode can be seen as a constant factor. A quadratic function that can illustrate the tendency of variation of ground-mode wave velocity is proposed by considering the relation between the wave velocity and fault distance. The least squares method is used to solve the quadratic function of different lines. Combining the quadratic formula and the incident TWs of each mode detected at both terminals of the line, a novel fault location method is proposed. First, according to the maximum and minimum ground-mode velocities, a fault scope can be acquired. Then, more accurate fault scopes and ground-mode velocities can be obtained by iteration computation. Finally, an accurate fault position is acquired when the fault scope is sufficiently small. PSCAD/EMTDC software is used to conduct fault simulations in order to verify the feasibility and accuracy of the method.

1. Introduction

In many countries, the energy base is far from the power load center so long transmission lines are necessary for power transmission. These transmission lines are hundreds of kilometers in length and can be damaged by severe weather and human activities. The traditional fault location is based on the line protection action. Numerous methods have been proposed for transmission line protection [1], with no consideration of the exact fault location, causing the need for time-consuming line patrols. It is necessary to find the exact fault location in transmission lines. Locations of faults on overhead power lines for the repair purposes is still a subject of great interest to researchers and utilities personnel, which dates back to the eighties [2,3].
Currently, there are mainly two kinds of fault location methods: (a) steady-state method and (b) transient-state methods [4]. The steady-state methods do not need high sampling frequency and can be realized by existing measurements [5]. However, these methods is susceptible to line parameters, fault resistances, load swing, etc. Steady-state methods are not suitable for long transmission lines with many changeable factors such as line transposition, load swing, etc. [6,7,8]. The transient-state methods are more stable with respect to these factors and have a better accuracy and robustness. In [9], a current frequency component based method for cable fault location was proposed. It was verified by PSCAD/EMTDC that the method had high accuracy and strong robustness. However, it needs a higher sampling frequency [10,11,12,13,14,15]. For long transmission lines which are of great importance to power companies, transient-state methods have been widely used for their reliability.
Within the category of transient-state method, representative traveling wave-based methods can be further divided into two different types: single-ended and double-ended methods [16]. On the one hand, single-ended methods only need data from one terminal of the line, which is independent from the synchronization and communication equipment [17]. The difficulties of these methods lie in identifying the TWs reflected wave from a fault location. However, the reflected wave is often disturbed by the waves reflected or refracted from other line terminals. In [18], a wavelet transform is employed in order to construct the traveling wave propagation waveform. By comparing the constructed and real recorded waveforms, the reflection wave of the fault point can be identified. Lin proposed a single-ended fault location method based on the time-frequency characteristics of traveling waves [19]. This method is used for calculation of the zero-mode velocity and identification of the reflected wave font. How to ensure the computational accuracy of the Lipschitz exponent is a challenging question. On the other hand, the double-ended method needs data from double terminals and synchronization [20,21]. In [20], Global Positioning System (GPS) is utilized to obtain synchronized transient voltage measurements from all of the receiving ends. A traveling wave based fault location algorithm is presented for hybrid multi-terminal transmission systems which consists of one onshore overhead line and multiple offshore submarine cables. Similarly, GPS and Artificial Neural Network approaches are used to synchronize voltage and current signals at both ends of the transmission line [21].
Based on the above TW methods, more improved asynchronous fault location methods have been proposed [22,23,24,25,26], which are independent from the effect of wave velocities. Most of these methods are in the time domain. The time stamp of transient traveling wave arrival is critical, which is related to the velocity of the transient traveling wave. Attenuation should be considered due to the fact that the TWs on long transmission lines are changeable and related to the characteristics of the traveling wave, especially when the ground-mode TWs are used. In [22], the time stamps of different modes, arrived at measuring points are utilized. According to the fault location formula and based on a time difference of different modes at both ends, this method eliminates the influence of traveling wave velocity from the formula and does not need synchronization. However, the authors ignored that the velocities of ground-mode TWs have various values depending on the fault position. Due to the traveling wave characteristics, when a fault is not in the middle of a transmission line, the velocities of ground-mode at both sides of the fault point are different, which cannot be eliminated. The fault location error is directly proportional to the distance between the fault point and the middle of line. This is a easily neglected problem. Reference [23] gives a method for identifying the reflected wave from a fault point, which is based on the fault position estimation proposed by [26]. The communication system latency is considered to create a fault area to make sure the time stamp of the reflected wave from the fault point can be correctly identified. The time synchronization system between two terminals is necessary for auxiliary pre-estimations of a fault location. Reference [24] analyses the traveling wave propagation characteristic with a distributed parameter model. To tackle the key problem of ground-mode velocity estimation, an iterative method based on prior knowledge is proposed. However, there are deviations when the ground-mode velocities are calculated by the center pseudo-frequency of wavelet transform. In [25], the author considered the dispersion effect of traveling wave and proposed a compensation method for a better fault location result but the synchronization is still required.
As analyzed above, there are few fault location methods that thoroughly considers the traveling wave characteristics, which play important roles in the fault location detection, especially when the ground-mode traveling wave is used. The ground-mode velocity is vital for accurate fault location in long transmission lines where the attenuation is severe. To address this problem, this paper first analyzes the characteristics of traveling waves. Then, to analyze the velocity of the ground-mode, which changes severely with different fault distances, a formula is proposed based on theoretical analysis and experimental results. Combing the derived formula with the fault location method, a novel fault location method has been proposed to determine an actual ground-mode velocity. Considering the fact that the traveling wave measuring device are available and the synchronization technology is not available in some lines, the proposed method uses a double-ended transient voltage traveling wave without synchronization and identifies the second traveling wave head. Finally, PSCAD/EMTDC simulations have been carried out under different fault conditions to verify the reliability and accuracy of the proposed method.

2. Analysis of the Traveling Wave Characteristics

2.1. Frequency-Dependent Characteristics of Traveling Wave

Current and voltage propagating in transmission lines are in the forms of electromagnetic waves. The wave equations are generally given as below:
d 2 U x 2 = Z Y U d 2 I x 2 = Y Z I
U and I are the phasor voltage and current values in frequency domain. Z and Y are the series impedance and parallel admittance matrix of the transmission line, respectively:
Z = R + j ω L Y = G + j ω C
R, L, G, C are the resistance, inductance, conduction and capacitance of transmission line, respectively. The Karrenbauer transform [27] shown in Equation (3) is used to transform the coupled three phases to independent modes 0, 1, 2 where the mode 0 is the ground-mode and the modes of 1 and 2 are the aerial-modes in engineering [9]. The transform is applicable for the current and voltage traveling waves.
[ U 0 U 1 U 2 ] = 1 3 × [ 1 1 1 1 1 0 1 0 1 ] [ U A U B U C ]
when a fault occurs in a transmission line, just like an equivalent reverse voltage step pulse applied at the fault point, which is equal to the pre-fault phase voltage. The step pulse is a band-width signal, including a broad frequency band from Hz to MHz. Thus, the transient traveling waves of the current and voltage are produced and propagated to both sides of the line as shown in Figure 1.
Equation (1) shows the propagation of traveling waves in the frequency domain, which can be transformed into the time domain as in Equation (4). The traveling waves of the current and voltage signals have the similar expressions.
I ( x , t ) = 2 I + e α ( ω ) x cos ( ω t β ( ω ) x + ϕ + ) + 2 I e α ( ω ) x cos ( ω t + β ( ω ) x + ϕ )
where α(ω) is the attenuation factors and β(ω) is the phase distortion factors of line. The propagation coefficient of line is defined as γ = α + j β .
Equation (4) shows that a traveling wave consists of a forward wave and a backward wave. The traveling wave attenuates exponentially with distance. The propagation coefficient plays an important role in the propagation of the traveling wave.
For any line, the propagation coefficient of each mode is decided by the line parameters. As shown in Equation (5), m = 0 is the ground-mode and m = 1, 2 is the aerial-mode.
γ m = α m ( ω ) + j β m ( ω ) = Z m Y m = ( R m ( ω ) + j ω L m ( ω ) ) ( G m ( ω ) + j ω C m ( ω ) )
The terms Rm(ω), Lm(ω), Gm(ω) and Cm(ω) are the resistance, inductance, conductance and capacitance of transmission lines, respectively. Considering the frequency dependent characteristic of the lines, these parameters are the frequency-dependent. Among them, the Rm( ω ) and Lm(ω) change more obviously with frequency comparing to Gm(ω) and Cm(ω). The α m and β m in frequency domain are expressed in Equations (6) and (7).
According to Equations (6) and (7), Figure 2 gives the characteristics of curves α m ( ω ) , β m ( ω ) in frequency. For α m ( ω ) , it is in proportion to the frequency. Due to the different propagation path, α 0 ( ω ) is greater than α 1 ( ω ) , α 2 ( ω ) . The reason is that the impendence of earth is higher than the lines. The attenuation factor of aerial-mode is relatively small and changeless, and that of ground-mode is great and frequency-dependent in comparison:
α m ( ω ) = 1 2 [ R m ( ω ) G m ω 2 L m ( ω ) G m + ( R 2 m ( ω ) + ω 2 L 2 m ( ω ) ) ( G 2 m + ω 2 C 2 m ) ]
β m ( ω ) = 1 2 [ ω 2 L m ( ω ) C m R m ( ω ) G m + ( R 2 m ( ω ) + ω 2 L 2 m ( ω ) ) ( G 2 m + ω 2 C 2 m ) ]
Ignoring the attenuation factors, the traveling waves propagate along in the transmission lines with a certain speed, which is:
v = ω β ( ω )
According to the Equations (7) and (8), the relationship curve of velocities and frequencies is shown in Figure 3 which indicates that the ground-mode velocity is approximately linear with respect to frequency and the aerial-mode velocity is constant at high frequency (above 1 kHz). Different frequency signals have different speeds for ground-mode traveling waves. The measuring velocity of traveling wave depends on the highest frequency signal which can be detected.
As analyzed above, the velocity of traveling wave is vital for many fault location algorithms. When a fault occurs, the transient TWs contain high frequency signals. If there are no attenuation factors, the velocity of traveling wave is equal to the speed of the light. As signals with different frequencies have different attenuation factors and velocities, some high frequency signals are immeasurable at measuring points and the measuring velocity of a fault-traveling wave is uncertain within different fault distances.

2.2. The Change of Traveling Wave Velocity with Fault Distance

Equation (8) gives the expression of velocity that does not take the attenuation factor into account. The attenuation factor plays an important role in measuring velocities at measuring points. Equation (4) illustrates that the amplitude of traveling wave attenuates exponentially. The amplitude of first detected transient traveling wave head can be seen as the amplitude superimposition of the highest frequency signals in one sampling interval:
A = i e x α i f i ( t )
where fi(t) is the amplitude of the component in traveling waves with frequency i and A is the detected amplitude of traveling wave head at a measuring point.
As shown in Figure 1, supposing the amplitude of measured traveling wave at x1 is A1, the amplitude of measured traveling wave at x2 is A2 and sampling time is ∆t. The highest frequency signal components combined with A1 have the strongest attenuation when travelling toward x2. As a result, some of those frequencies are attenuated severely and the traveling wave fault location equipment cannot be triggered. Then, the measured signals of x2 are composed of subsequent lower frequency signals. The dominant frequency of x2 is lower than that of x1. According to Figure 3, the velocity of traveling wave at x2 is smaller than that of x1. The initial traveling wave is a pulse signal with continuous frequency spectrum. The attenuations of the traveling wave in different frequencies have exponential decay characteristics and the velocity is approximately linear with respect to the frequency. The variation tendency of traveling wave velocity affected by fault distance can be described as a monotonic function.
Based on Figure 1, the LGJ-240/30 line has been used for verifying the assumption. The length of the line is 500 km. Figure 4 shows the tendency of ground-mode velocity and aerial-mode velocity.
The attenuation factors are different with the different propagation paths. The ground-mode traveling wave has relatively higher factors of decay. The change of ground-mode velocity is more dramatic than that of the aerial-mode. Without loss of generality, the velocity of ground-mode can be seen as a constant factor which is changed slightly in a finite length line. The ground-mode velocity shows an obviously monotonic descent with the increase of the fault distance. It is inappropriate to take the ground-mode velocity as a known quantity with the unknown fault distance. A monotonic function of ground-mode velocity can benefit the fault location results.
In order to fit the relationship between the ground-mode wave velocity and fault distance, fault simulations and calculations are carried out in the following steps: (1) 14 measurement points denoted as M1, M2, , M14 are installed along the line with the distances l1, l2, , l14 from the local terminal respectively; (2) a fault is simulated at the local terminal of the line at t0; (3) the ground-mode traveling wave signal acquired at each measurement point is analyzed by wavelet transform and the corresponding arrival time stamp ti is extracted based on wavelet modulus maximum; (4) the ground-mode velocity of each location where the measurement point is mounted can be calculated according to the following equation:
v 0 i = l i t i t 0 ( i = , 2 , , 14 )
(5) The exponential function, logarithmic function and quadratic function are used to fit the relationship between v0 and lx. The flowchart of the above steps are illustrated in Figure 5.
From the above steps, it should be noted that it is of great essence to determine the arrival time stamps by wavelet transform, the details of which are shown as follows:
First, the initial traveling wave signal to be analyzed was imported in Matlab Wavelet Tookit. Next, the signal was decomposed into four levels by a Daubechies 6 wavelet. Then, the detailed and approximate coefficients were exported. Finally, the modulus maximum value of detailed coefficients of d1 level was calculated to identify the arrival time stamp of the traveling wave.
The numerical results of Figure 6 are shown in the following Table 1. Three-phase current signals can be transformed into aerial-mode and ground-mode by Karrenbauer transform shown in Equation (3). The arrival time of ground-mode current traveling wave is computed based on Wavelet transform modulus maximum. At last, the ground-mode velocity can be calculated by Equation (10).
As previously analyzed, the initial traveling wave with sufficiently high frequencies has higher attenuation factor, which causes a stronger change of velocity than that from a further distance. The trend of measured velocity is that the closer to the fault point the faster the changes. Therefore, an exponential function, logarithmic function and quadratic polynomial function with the above tendency have been used for the velocity fitting. The result is shown in Figure 5. The fitting functions and the goodness of fit (R2) are:
  • Exponential function: v 0 = 28.7 × e 0.0047 x , R 2 = 0.883 ;
  • Logarithmic function: v 0 = 0.037 ln ( x ) + 2.98 , R 2 = 0.9622 ;
  • Quadratic function: v 0 = 1 × 10 6 x 2 9 × 10 4 x + 2.956 , R 2 = 0.9783 ;
Using this method, MATLAB (MathWorks, Natick, MA, USA) program fits different lines with different lengths. The goodness of fit R2 is given in Table 2.
From Table 2, we can see that each selected function can fit the tendency of the ground-mode velocity. However, the quadratic function fits better than the others and performs better in calculating the velocity along the transmission lines. Thus, the quadratic function is used for describing the relation between the ground-mode velocity and the fault distance.
Based on the above analysis, for any transmission line, the general quadratic function about the ground-mode velocity and the fault distance is defined as below:
v 0 = A x 2 + B x + C
A, B, C are the unknown coefficients determined by the lines; x is the fault distance from measured points; v0 is the corresponding ground-mode velocity.
Acquiring the quadratic function by MATLAB fitting, it is necessary to have significant fault data and information, collected along the lines, which is impossible for operating lines. The least squares method [28] can be used, which only needs more than three points. Therefore, some ground-mode velocities can be found based on the simulation model in PSCAD/EMTDC (Manitoba HVDC Research Centre, Winnipeg, Canada) and using the actual parameters of line. However, the error between the simulation and actual lines is inevitable. In order to correct the error, few velocities achieved by the circuit breakers can be used for the least square method. The breakers commonly have a certain distance between each other, which the fitting correction of tendency can benefit from:
[ A B C ] = C 1 X T v
Among them, C = X T X , X = [ x 1 2 x 1 1 x 3 2 x 2 1 x n 2 x n 1 ] , v = [ v 0 1 v 0 2 v 0 n ] .

3. Fault Location Method

3.1. Fault Location Based on the Time Difference of Modes

Figure 7 depicts a time-space diagram for a line monitored at two terminal lines, where tL0, tL1, tR0, tR1 are the arrival time stamps of incident earth and aerial-mode TWs at buses L and R; v1 is the aerial-mode TW propagation velocity, which doesn’t change along the line; vL0 and vR0 are the ground-mode TW propagation velocities at two-terminal measurements respectively; x is the fault distance and l is the line length.
For the terminal L:
{ x = ( t L 1 t 0 ) v 1 x = ( t L 0 t 0 ) v 0
Eliminating the initial fault time, t0:
x = Δ t L v 1 v L 0 v 1 v L 0
For the terminal R:
l x = Δ t R v 1 v R 0 v 1 v R 0
Among them: Δ t L = t L 0 t L 1 , Δ t R = t R 0 t R 1 .
The accurate time-tap of transient traveling wave head arrived at the measurement is important for the fault location algorithm. In long High Voltage Transmission Lines, a typical method is to use a secondary signal of a current transformer (CT) to detect the wave front of the transient TWs. The detection of the current traveling waves needs TWs detecting devices in each line of a substation, which complicates the fault location system and has higher hardware requirements. The voltage traveling wave method only needs to measure the voltage in the bus. Coupling capacitor voltage transformers (CCVT) is a measuring transforming that is widely used in transmission line for voltage measurement and can be used for the extraction of transient signals. In reference [29], it is pointed out that CCVT may have several resonant models and the frequency response may present obvious bandstop and bandpass characteristics due to the stray capacitances in CCVT. To this problem, some substations have additional sensors set up to measure transient voltage traveling waves and some improved CCVTs with good high-frequency response for traveling wave are used [30]. In the proposed method, the arrival time-stamp of transient traveling wave head can be obtained by detecting the singularity and abrupt change point in the signal. Reference [31] proves that the CCVT has a good performance in transforming the singularity and abrupt change point in the voltage signal.
According to [32,33,34], the performance of wavelet transform is great in capturing the transient wave-head. Thus, the Daubechies 6 (db6) wavelet is used to compose the transient wave-head into four levels. The arrival time of modulus maximum detail coefficients at the first level (d1) is used as calibration time. The frequency band of d1 corresponds to 250 kHz–500 kHz at the 1 MHz sampling frequency. The frequency band of d1 is the highest frequency TWs which decides the propagation velocity of transient TWs.
In Equations (14) and (15), the propagation velocities of ground-mode v L 0 and v R 0 are uncertain with different fault distances. Considering the quadratic function about the relation between ground-mode velocity and fault distance, a more accurate fault location algorithm can be obtained.

3.2. Proposed Method

The proposed method estimates the accurate fault location by iteratively calculating the actual ground-mode velocity according to the fitted relationship. The method can be divided into two stages: off-line ground-mode velocity fitting and on-line fault location. The core ideas of the proposed method are described below and Figure 8 shows the iteration procedure of the method.
The ground-mode velocity in a transmission line changes within a certain range. In other words, if the velocity measured is denoted as v max and v min with a fault occurring at the local and remote terminals respectively, the measuring velocities at both terminals should stay in the range ( v min , v max ) wherever the fault occurs on the other locations of the line. In this paper, the relationship between the ground-mode velocity and fault distance is fitted off-line by the general quadratic function shown in Section 2.2. Therefore, v max and v min can be determined directly by setting the fault distance to be 0 and l in the fitted curve.
When a fault is detected in the transmission line, the following on-line fault location steps are conducted. First, the time difference Δ t L and Δ t R at the local and remote terminals can be computed by applying a wavelet transform to the ground-mode and aerial-mode traveling waves acquired at the two terminals. Next, substituting v min and v max into Equations (18) and (19) with the time difference Δ t L and Δ t R , four fault distances lL_min, lL_max, lR_min and lR_max are obtained and two fault ranges ( l L _ min _ 1 , l L _ max _ 1 ) and ( l R _ min _ 1 , l R _ max _ 1 ) can be determined. The intersection of the two fault ranges is taken as the fault range ( l min _ 1 , l max _ 1 ) for the first iteration, which lie within range of the line as analyzed in Section 3.3. Then, according to the fitted relationship between ground-mode velocity and fault distance, the ground-mode velocities v L _ min _ 1 , v L _ max _ 1 and v R _ min _ 1 , v R _ max _ 1 corresponding to l min _ 1 and l max _ 1 can be determined. Last, the steps mentioned above are repeated until the stopping criterion defined in Equation (16) is satisfied and the final fault location Pf after n time iterations is computed using Equation (17):
Δ l = l max _ n l min _ n
P f = ( l min _ n + l max _ n ) 2
The fault location process is shown in Figure 8.

3.3. Convergence of Proposed Method

In order to achieve the fault points, the convergence of proposed method should be guaranteed. Figure 9 is the iteration diagram.
As shown in the analysis, the ground-mode velocity is decreasing with the increase in fault distance. After iterating n times, the fault range is ( l min _ n , l max _ n ) . The velocities for n + 1 are v min _ n , v max _ n . The iteration fault scope of n + 1 is:
l min _ n + 1 = ( t L 0 t L 1 ) v 1 v min _ n v 1 v min _ n = ( t L 0 t L 1 ) v 1 v 1 v min _ n 1
l max _ n + 1 = ( t L 0 t L 1 ) v 1 v max _ n v 1 v max _ n = ( t L 0 t L 1 ) v 1 v 1 v max _ n 1
According to Equations (18) and (19), if the smaller ground-mode velocity vmin_n is substituted in Equation (18), a smaller calculated fault distance than actual fault distance could be obtained. Otherwise, a larger calculated fault distance could be acquired. Four fault distances lL_min, lL_max, lR_min and lR_max could be computed by substituting the arrival time differences ∆tL and ∆tR between ground-mode and aerial-mode travelling waves detected at both terminals of the line. The minimum distance scope composed by lL_min, lL_max, lR_min and lR_max could be selected for calculating the new ground-mode velocities vmin_n+1 and vmax_n+1. Repeating the above steps would result in the converged fault distance Pf. To clarify the process of iteration, a numerical example (a fault 167 km away from the local terminal) is displayed in Table 3 below.
When only one-end of data is used, such as L, the situation of l L _ max > l may occur when the fault is near the terminal R. In this situation, the l R _ min calculated by the data of terminal R is on the line. As shown in Figure 10, the intersection of lscope is always on the transmission line and the velocities for the next iteration always exist.

4. Simulation and Test Results

4.1. The Model of Simulation

PSCAD/EMTDC software is used to construct a 500 kV AC transmission system model as Figure 7. The length of the transmission lines is 500 km. The sampling rate is 1 MHz and the 16 bits A/D resolution is used. The type of lines is 4 × LGJ-400/35 and earth resistively is 150 Ω m . Figure 11 shows the model of the towers.

4.2. Example Analysis

4.2.1. The Quadratic Function of Ground-Mode Velocity

According to the model, some velocities along the transmission line are simulated. Benefiting from the reclosing devices, few actual ground-mode velocities can be obtained, which will modify the results. Using Equation (12), the quadratic function of this line is:
v 0 = 8.49 × 10 7 x 2 7.93 × 10 4 x + 2.954
Figure 12 compares the actual ground-mode velocity curve and the calculated velocity curve. It can be seen that the proposed fitting method has a great performance and the maximum error is less than 0.2%, which meets the demand of engineering application. For this transmission line, the maximum ground-mode velocity is v max = 2.954 × 10 5 km/s and the minimum ground-mode velocity is v min = 2.796 × 10 5 km/s. The aerial-mode velocity is a constant value of 2.994 × 10 5 km/s.

4.2.2. Validation of Proposed Fault Location Method

A single-phase ground fault is set at the distance of 167 km from terminal L. The wavelet transform is used to capture the arrival time of each mode. Figure 13 shows the time differences of ground-mode and aerial-mode at each end. An appropriate adjustment is adopted on TWs amplitude for easily observation and analysis, which does not affect the time difference of aerial-mode and ground-mode. The time differences at L, R are Δ t L = 29 μs, Δ t R = 84 μs separately. Figure 14 gives the results of each iteration.
Figure 14 shows that the proposed method has quick convergence and high accuracy. After iterating five times, the calculated fault scope is 166.806 km–167.245 km and Δ l = 0.439 km, 500 × 0.5 % Δ t R when the iteration process is over. The fault location is 167.026 km from terminal L, which only deviates slightly from the actual situation. Though the iteration is used, the complexity of proposed method is low. The process of fault location can be accomplished instantaneously.

4.3. Fault Location Results

The Equation (21) is used to calculate the relative error:
d % = | l x _ m e a l x _ r e a l | l 100 %
where l x _ r e a l is the actual fault distance, l x _ m e a is the distance of location result and the l is the length of the transmission line.
Table 4 shows effect of fitting error of velocities on the fault location results. From Figure 12, the tendency of fitted ground-mode velocity conforms to the actual situation, which ensures the convergence of the proposed method. Although there are errors between the fitted and actual velocities, the small errors cannot change the tendency. For a fault, the fitted velocities around fault point play an important role in the accuracy of fault location. The fitting error in other places will not affect the fault location result. The fitted ground velocity fully satisfies the requirements of engineering applications, so the proposed method has a great robustness.
In order to verify the adaptability of the proposed method, different faults have been simulated. Table 5 and Table 6 show the influences of fault resistance and fault angle on the fault location method. From Table 5 and Table 6, it can be concluded that the fault location error is increasing with the rise of fault resistance when the fault inception angle keeps constant. On the other hand, when the fault resistance remains constant, the fault location error is minimum with a 90° fault inception angle. Under different fault conditions, the maximum error and minimum error of the accurate fault location using this method are 0.37 km and 0.01 km, which well meets the requirement of practical engineering application.
In order to show the advantages of the proposed method, we compare in Table 7 several methods published in recent years with the presented method.
The results reveal that: (1) the proposed method has great performance no matter where the faults occur along the transmission line. The absolute error is less than 0.37 km and the relative error is less than 0.2%, which meets the requirement of practical applications; (2) with respect to the traditional synchronized method in [21], the proposed method has better accuracy and does not need synchronization. Due to the effect of different angles and fault resistances on the voltage amplitude of the initial transient TWs, the fault location results fluctuate slightly but do not affect the accuracy of the measurement; (3) compared with the single-ended method [19], the proposed method is fast and has much less computation time and can be completed quickly when a fault occurs. Due to the attention of TWs, the computational accuracy of Lipschitz exponent is decreased with the increase of the fault distance which affects the fault location. The positioning accuracy of proposed method is independent from the fault distance; (4) comparing with the method given in [21], the proposed method has a great fault location result performance, which illustrates that the change of ground-mode velocity is important in fault location when the ground-mode TWs are used. As the attenuation factors cannot be ignored, the proposed quadratic function can describe the change tendency of ground-mode velocity with fault distance, which improve the accuracy of fault location greatly; (5) although the method described in reference [23] is asynchronous, the second reflected wave front must be detected, which brings difficulty to accurate fault location since it is usually hard to detect the second reflected wave front. However, the presented method only utilizes the arrival time stamps of the first wave fronts of the modulus traveling waves which are easily detected. In addition, the presented method does not require synchronization, it is independent of line parameters, and has high fault location accuracy.

5. Conclusions

The inaccuracy of the ground-mode velocity is an important issue for fault location detection based on the ground-mode TWs. To address this problem, this paper thoroughly investigated the relation between fault distance and ground-mode velocity. The measured velocity is based on the phase distortion factors and frequency while it is also affected by the attenuation factors. Based on the fundamental cause of the ground-mode velocity change, the general trend of the velocity change can be obtained. Comprehensive simulations have been carried out and the quadratic function performed very well in describing the change of ground-mode velocity. The change tendency of velocity can benefit the fault location algorithm using the ground-mode velocity.
The proposed fault location method neither need synchronization nor identification of a second wave font, which is a cost-effective. The fault location results are slightly affected by the fault phase and resistance. The accuracy of the fault location can be as high as the synchronized two-ended TWs fault location method with strict time synchronization.
Nowadays, traveling wave fault location devices are widely installed on HV transmission lines, which is convenient for applying the proposed fault location method.

Acknowledgments

The research was supported by the Fundamental Research Funds for the Central Universities (Grant No. 2017XKQY033).

Author Contributions

Rui Liang conceived and designed the algorithms. Zhi Yang and Nan Peng developed the simulation environment and performed the simulations. Chenglei Liu and Firuz Zare implemented the comparative studies and drew the conclusions. All authors have contributed to the writing, editing, and proofreading of this paper.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Uthe phasor voltage
Ithe phasor current
Zthe series impedance matrix of the transmission line
Yparallel admittance matrix of the transmission line
R, Rm (ω)the resistance of transmission line
L, Lm (ω)the inductance of transmission line
G, Gm (ω)the conduction of transmission line
C, Cm (ω)the capacitance of transmission line
α(ω)the attenuation factors of line
β(ω)the phase distortion factors of line
γthe propagation coefficient of line
fi(t)the amplitude of the component in traveling waves with frequency i
Athe detected amplitude of traveling wave head at a measuring point
∆tsampling time
xthe fault distance from measuring points
v0ground-mode velocity
tL0the arrival time of incident ground-mode TWs at buses L
tL1the arrival time of aerial-mode TWs at buses L
tR0the arrival time of incident ground-mode TWs at buses R
tR1the arrival time of aerial-mode TWs at buses R
v1the aerial-mode TW propagation velocity
vL0the ground-mode TW propagation velocities at L-terminal measurements
vR0the ground-mode TW propagation velocities at R-terminal measurements
lthe line length
lxfault distance from the local terminal
t0the initial fault inception time
tLthe time difference of ground-mode and aerial-mode traveling wave detected at the local terminal
tRthe time difference of ground-mode and aerial-mode traveling wave detected at the remote terminal
vmaxThe maximum ground-mode velocity in a certain transmission line
vminThe minimum ground-mode velocity in a certain transmission line
lmin_1the minimum fault distance by first iteration
lmax_1the maximum fault distance by first iteration
lL_minthe minimum fault distance calculated from L-terminal
lL_maxthe maximum fault distance calculated from L-terminal
lR_minthe minimum fault distance calculated from R-terminal
lR_maxthe maximum fault distance calculated from R-terminal
lL_min_1the minimum fault distance calculated from L-terminal of first iteration
lL_max_1the maximum fault distance calculated from L-terminal of first iteration
lR_min_1the minimum fault distance of calculated from R-terminal first iteration
lR_max_1the maximum fault distance calculated from R-terminal of first iteration
vL_min_1the minimum ground-mode velocity calculated from L-terminal of first iteration
vL_max_1the maximum ground-mode velocity calculated from L-terminal of first iteration
vR_min_1the minimum ground-mode velocity calculated from R-terminal of first iteration
vR_max_1the maximum ground-mode velocity calculated from R-terminal of first iteration
Pfthe fault distance from the local terminal
nthe number of iterations
vf0the velocity at fault location
lL_scopethe intersection of the L-terminal maximum fault distance and the L-terminal minimum fault distance
lR_scopethe intersection of the R-terminal maximum fault distance and the R-terminal minimum fault distance
lscopethe intersection of lL_scope and lR_scope
lx_realthe actual fault distance
lx_meathe distance of fault location result

References

  1. Xue, S.; Lian, J.; Qi, J.; Fan, B. Pole-to-Ground fault analysis and fast protection scheme for HVDC based on overhead transmission lines. Energies 2017, 10, 1059. [Google Scholar] [CrossRef]
  2. Ibe, A.O.; Cory, B.J. A Traveling Wave-Based Fault Locator for Two-and Three-Terminal Networks. IEEE Power Eng. Rev. 1986, PER-6, 55. [Google Scholar] [CrossRef]
  3. Ziegler, G. Fault Location in H.V. Power Systems. IFAC Proc. 1980, 13, 121–129. [Google Scholar] [CrossRef]
  4. Institute of Electrical and Electronics Engineers (IEEE). IEEE Guide for Determining Fault Location on AC Transmission and Distribution Lines; IEEE Std.: New York, NY, USA, 2015; pp. 1–76. ISBN 978-0-7381-9421-9. [Google Scholar]
  5. Das, S.; Santoso, S.; Gaikwad, A. Impedance-base fault location in transmission networks: Theory and application. IEEE Access 2014, 2, 537–557. [Google Scholar] [CrossRef]
  6. Al-Mohammed, A.H.; Abido, M.A. An adaptive fault location algorithm for power system networks based on synchrophasor measurements. Electr. Power Syst. Res. 2014, 108, 153–163. [Google Scholar] [CrossRef]
  7. Jamali, S.; Bahmanyar, A. A new fault location method for distribution networks using sparse measurements. Electr. Power Syst. Res. 2016, 81, 459–468. [Google Scholar] [CrossRef]
  8. Hosseini, S.A.; Sadeh, J.; Mozafari, B. Robust wide-area impedance-based fault location method utilizing LAV estimator. IET Gener. Transm. Distrib. 2016, 10, 2475–2485. [Google Scholar] [CrossRef]
  9. Zhao, P.; Chen, Q.; Sun, K.; Xi, C. A current frequency component-based fault-location method for voltage-source converter-based high-voltage direct current (VSC-HVDC) cables using the S transform. Energies 2017, 10, 1115. [Google Scholar] [CrossRef]
  10. Lopes, F.V.; Neves, W.L.A.; Femandes, D., Jr. A Traveling-wave Detection Method Based on Park’s Transformation for Fault Locators. IEEE Trans. Power Deliv. 2013, 28, 1626–1633. [Google Scholar] [CrossRef]
  11. Ahmadimanesh, A.; Shahrtash, S.M. Transient-Based Fault-Location Method for Multiterminal Lines Employing S-Transform. IEEE Trans. Power Deliv. 2013, 28, 1373–1380. [Google Scholar] [CrossRef]
  12. Liang, R.; Wang, F.; Fu, G. Wide-area fault location based on optimal deployment of the traveling wave recorders. Int. Trans. Electr. Energy Syst. 2015, 26, 1667–1672. [Google Scholar] [CrossRef]
  13. Feizifar, B.; Haghifam, M.R.; Soleymani, S. Application of continuous wavelet transform for fault location in combined overhead line and cable distribution networks. Electr. Electron. Eng. 2011, 14, 142–146. [Google Scholar]
  14. Peyman, J.; Majid, S.-P. A Traveling-Wave-Based Protection Technique Using Wavelet/PCA Analysis. IEEE Trans. Power Deliv. 2010, 25, 588–599. [Google Scholar]
  15. Ding, J.; Li, L.; Zheng, Y. Distributed traveling-wave-based fault location without time synchronization and wave velocity error. IET Gener. Transm. Distrib. 2017, 11, 2085–2093. [Google Scholar] [CrossRef]
  16. Wang, P.; Yang, Z.; Su, Z.; Xu, Z. Analysis of Traveling Wave Fault Location. In Proceedings of the 2012 Asia-Pacific Power and Energy Engineering Conference, Shanghai, China, 27–29 March 2012. [Google Scholar]
  17. Spoor, D.; Zhu, J.G. Improved single-ended traveling-wave fault-location algorithm based on experience with conventional substation transducers. IEEE Trans. Power Deliv. 2006, 21, 1714–1720. [Google Scholar] [CrossRef]
  18. Chen, Y.; Liu, D.; Xu, B.Y. Travelling Wave Single End Fault Location Method based on Network Information. Prz. Elektrotech. 2012, 88, 205–209. [Google Scholar]
  19. Lin, S.; He, Z.Y.; Li, X.P.; Qian, Q.Q. Travelling wave time-frequency characteristic-based fault location method for transmission lines. IET Gener. Transm. Distrib. 2012, 6, 764–772. [Google Scholar] [CrossRef]
  20. Hamidi, R.J.; Livani, H. Traveling-Wave-Based Fault-Location Algorithm for Hybrid Multiterminal Circuits. IEEE Trans. Power Deliv. 2017, 32, 135–144. [Google Scholar] [CrossRef]
  21. Shaik, A.G.; Pulipaka, R.R.V. A new wavelet based fault detection, classification and location in transmission lines. Int. J. Electr. Power Energy Syst. 2015, 64, 35–40. [Google Scholar] [CrossRef]
  22. Lopes, F.V. Settings-Free Traveling-Wave-Based Earth Fault Location Using Unsynchronized Two-Terminal Data. IEEE Trans. Power Deliv. 2016, 31, 2296–2298. [Google Scholar] [CrossRef]
  23. Lopes, F.; Dantas, K.; Silva, K.; Costa, F.B. Accurate Two-Terminal Transmission Line Fault Location Using Traveling Waves. IEEE Trans. Power Deliv. 2017. [Google Scholar] [CrossRef]
  24. Chen, X.; Yin, X.; Deng, S. A novel method for SLG fault location in power distribution system using time lag of travelling wave components. IEEJ Trans. Electr. Electron. Eng. 2017, 12, 45–54. [Google Scholar] [CrossRef]
  25. Jia, H. An Improved Traveling-Wave-Based Fault Location Method with Compensating the Dispersion Effect of Traveling Wave in Wavelet Domain. Math. Probl. Eng. 2017, 2017, 1019591. [Google Scholar] [CrossRef]
  26. Lopes, F.V.; Silva, K.M.; Costa, F.B.; Neves, W.L.A.; Fernandes, D. Real-time traveling-wave-based fault location using two-terminal unsynchronized data. IEEE Trans. Power Deliv. 2015, 30, 1067–1076. [Google Scholar] [CrossRef]
  27. Zhang, H.; Zhang, Q.; Gao, W. A Novel Transformation Matrix Based on Karrenbaure Transformation. Appl. Mech. Mater. 2014, 521, 260–263. [Google Scholar] [CrossRef]
  28. Azizi, S.; Sanaye-Pasand, M.; Abedini, M.; Hasani, A. A traveling-wave-based methodology for wide-area fault location in multiterminal DCsystems. IEEE Trans. Power Deliv. 2014, 29, 2552–2560. [Google Scholar] [CrossRef]
  29. Vermeulen, H.J.; Dann, L.R.; van Rooijen, J. Equivalent circuit modelling of a capacitive voltage transformer for power system harmonic frequencies. IEEE Trans. Power Deliv. 1995, 10, 1743–1749. [Google Scholar] [CrossRef]
  30. Raoofat, M.; Mahmoodian, A.; Abunasri, A. Fault location in transmission lines using neural network and wavelet transform. In Proceedings of the 2015 International Congress on Electric Industry Automation (ICEIA 2015), Shiraz, Iran, 24–25 September 2015. [Google Scholar]
  31. Xia, Y.J.; Yin, X.G.; Wang, Z.H.; Yang, J.C.; Zhang, X.B. A novel fault location scheme using voltage traveling-wave of CVTs. In Proceedings of the 39th International Universities Power Engineering Conference (UPEC 2004), Bristol, UK, 6–8 September 2004; pp. 768–772. [Google Scholar]
  32. Lai, T.M.; Snider, L.A.; Lo, E.; Sutanto, D. High-impedance fault detection using discrete wavelet transform and frequency range and RMS conversion. IEEE Trans. Power Deliv. 2005, 20, 397–407. [Google Scholar] [CrossRef]
  33. Liang, R.; Fu, G.; Zhu, X.; Xue, X. Fault location based on single terminal traveling wave analysis in radial distribution network. Electr. Power Energy Syst. 2015, 66, 160–165. [Google Scholar] [CrossRef]
  34. Zhang, X.; Zeng, X.; Lei, L. Fault Location using Wavelet Energy Spectrum Analysis of Traveling Waves. In Proceedings of the 8th International Power Engineering Conference, Singapore, 3–6 December 2007; pp. 1126–1130. [Google Scholar]
Figure 1. The propagation of a traveling wave.
Figure 1. The propagation of a traveling wave.
Energies 10 01957 g001
Figure 2. Relationship curve of α m ( ω ) , β m ( ω ) with respect to frequency.
Figure 2. Relationship curve of α m ( ω ) , β m ( ω ) with respect to frequency.
Energies 10 01957 g002
Figure 3. The relationship between velocity and frequency.
Figure 3. The relationship between velocity and frequency.
Energies 10 01957 g003
Figure 4. The tendency of ground-mode velocity and aerial-mode velocity.
Figure 4. The tendency of ground-mode velocity and aerial-mode velocity.
Energies 10 01957 g004
Figure 5. A flowchart of fitting the relationship between v0 and lx.
Figure 5. A flowchart of fitting the relationship between v0 and lx.
Energies 10 01957 g005
Figure 6. The fitting for ground-mode velocity.
Figure 6. The fitting for ground-mode velocity.
Energies 10 01957 g006
Figure 7. A time-space diagram for a line monitored at two line terminals.
Figure 7. A time-space diagram for a line monitored at two line terminals.
Energies 10 01957 g007
Figure 8. The fault location process.
Figure 8. The fault location process.
Energies 10 01957 g008
Figure 9. Diagram of iteration.
Figure 9. Diagram of iteration.
Energies 10 01957 g009
Figure 10. Intersection of two scopes.
Figure 10. Intersection of two scopes.
Energies 10 01957 g010
Figure 11. The tower model.
Figure 11. The tower model.
Energies 10 01957 g011
Figure 12. Error of fitting.
Figure 12. Error of fitting.
Energies 10 01957 g012
Figure 13. Time difference at terminals. (a) Terminal L (b) Terminal R.
Figure 13. Time difference at terminals. (a) Terminal L (b) Terminal R.
Energies 10 01957 g013
Figure 14. The results of each iteration.
Figure 14. The results of each iteration.
Energies 10 01957 g014
Table 1. The Numerical results of ground-mode velocity for fitting.
Table 1. The Numerical results of ground-mode velocity for fitting.
Velocity v0 (105 km/s)Fault Distance lx (km)Velocity v0 (105 km/s)Fault Distance lx (km)
2.950102.817200
2.928202.805250
2.914502.794300
2.888702.784350
2.8611002.771400
2.8471502.770450
2.8281702.762480
Table 2. The R2 of different lines with different length.
Table 2. The R2 of different lines with different length.
Line TypesLGJ-240/30LGJ-500/45LGJ-800/70
Length (km)Goodness of Fit ( R 2 )
ExponentialLogarithmQuadraticExponentialLogarithmQuadraticExponentialLogarithmQuadratic
3000.8980.9450.9710.9520.9230.9860.9220.9660.987
5000.8830.9620.9780.9410.9520.990.910.9750.983
7000.9080.9570.9830.8870.9430.9770.8920.9480.969
10000.9470.9610.9860.8540.9010.9880.9060.9210.992
Table 3. Iteration result of the fault location at 167 km.
Table 3. Iteration result of the fault location at 167 km.
Iteration TimesvR_minvR_maxvL_minvL_maxLRR-L < 0.5% × L
12.76982.9542.76982.954107.266189.298no
22.77352.78962.83432.8787156.770183.583no
32.78182.78812.83702.8505159.433170.194no
42.78242.78482.84362.8492166.807167.246yes
Table 4. The influence of fitting error on the fault location results.
Table 4. The influence of fitting error on the fault location results.
Fault Distance (km)69172268339420479
Fitted velocity(×108 m/s)2.90322.84272.80252.78282.77072.769
Actual velocity(×108 m/s)2.90182.84292.80242.78362.77232.7668
Relative error of velocity (%)0.050.010.000.030.060.08
Fault location(km)69.18172.12268.05339.09420.14179.21
Relative error of location (%)0.0360.0240.010.0180.0280.042
Table 5. The fault location results by 0.1 Ω fault resistance.
Table 5. The fault location results by 0.1 Ω fault resistance.
Fault Distance/kmFault Angle/( ° )Fault Location/km
Proposed
10309.88
909.92
25030250.05
90250.01
48530484.89
90485.07
Table 6. The fault location results by 90° by fault angle.
Table 6. The fault location results by 90° by fault angle.
Fault Distance/kmFault Resistance/( Ω )Fault Location/km
Proposed
100.19.92
30010.37
2500.1250.01
300250.21
4850.1485.07
300485.33
Table 7. A comparison with the state-of-the-art fault location methods.
Table 7. A comparison with the state-of-the-art fault location methods.
YearMethodMin Error (km)Max Error (km)Synchronization
2012[19]0.162.52no
2015[21]0.0214.32yes
2017[23]0.0310.067no
2017Proposed method0.010.37no

Share and Cite

MDPI and ACS Style

Liang, R.; Yang, Z.; Peng, N.; Liu, C.; Zare, F. Asynchronous Fault Location in Transmission Lines Considering Accurate Variation of the Ground-Mode Traveling Wave Velocity. Energies 2017, 10, 1957. https://doi.org/10.3390/en10121957

AMA Style

Liang R, Yang Z, Peng N, Liu C, Zare F. Asynchronous Fault Location in Transmission Lines Considering Accurate Variation of the Ground-Mode Traveling Wave Velocity. Energies. 2017; 10(12):1957. https://doi.org/10.3390/en10121957

Chicago/Turabian Style

Liang, Rui, Zhi Yang, Nan Peng, Chenglei Liu, and Firuz Zare. 2017. "Asynchronous Fault Location in Transmission Lines Considering Accurate Variation of the Ground-Mode Traveling Wave Velocity" Energies 10, no. 12: 1957. https://doi.org/10.3390/en10121957

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop