Next Article in Journal
Semi-Supervised Learning for Defect Segmentation with Autoencoder Auxiliary Module
Next Article in Special Issue
FCS–MPC with Nonlinear Control Applied to a Multicell AFE Rectifier
Previous Article in Journal
Sensor Fault Diagnostics Using Physics-Informed Transfer Learning Framework
Previous Article in Special Issue
Application of a Control Scheme Based on Predictive and Linear Strategy for Improved Transient State and Steady-State Performance in a Single-Phase Quasi-Z-Source Inverter
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Derivative-Free Power Flow Solution for Bipolar DC Networks with Multiple Constant Power Terminals

by
Ángeles Medina-Quesada
1,*,
Oscar Danilo Montoya
2,3,* and
Jesus C. Hernández
1
1
Department of Electrical Engineering, University of Jaén, Campus Lagunillas s/n, Edificio A3, 23071 Jaén, Spain
2
Grupo de Compatibilidad e Interferencia Electromagnética, Facultad de Ingeniería, Universidad Distrital Francisco José de Caldas, Bogotá 110231, Colombia
3
Laboratorio Inteligente de Energía, Facultad de Ingeniería, Universidad Tecnológica de Bolívar, Cartagena 131001, Colombia
*
Authors to whom correspondence should be addressed.
Sensors 2022, 22(8), 2914; https://doi.org/10.3390/s22082914
Submission received: 22 March 2022 / Revised: 5 April 2022 / Accepted: 8 April 2022 / Published: 11 April 2022

Abstract

:
This paper analyzes the power flow solution in bipolar direct current networks with radial structures considering multiple monopolar and bipolar constant power loads. The electrical configuration of the bipolar DC grid considers that the reference pole is non-grounded along the feeder, which produces important neutral currents and voltage imbalances along the DC grid. The power flow problem is formulated through the triangular-based representation of the grid topology, which generates a recursive formulation that allows determining the voltage values in the demand nodes through an iterative procedure. The linear convergence of the triangular-based power flow method is tested through multiple load variations with respect to the nominal grid operative condition. Numerical results in the 21- and the 85-bus grids reveal the relevant variations in the voltage profiles and total grid power losses when the neutral cable is solidly grounded or not.

1. Introduction

Recently, the direct current (DC) distribution network has gained attention in the research and industrial communities since they do not require generation synchronization, have better voltage profiles, present lower power and energy losses, and in these grids, reactive power and frequency concepts are nonexistent [1,2]. Additionally, the accelerated advances in power electronic converters make these grids attractive for integrating multiple distributed energy resources such as photovoltaic generation, battery energy storage systems, and fuel cells, since these operate directly with DC technology, reducing the number of converters required in comparison with classical alternating current (AC) networks [3,4,5].
Electrical distributions with DC technologies can be constructed with two possible configurations: monopolar and bipolar [6,7]. The former is the most typical structure, where a positive and a neutral pole are used to provide constant voltage to multiple loads connected in the feeder [8]. The latter, i.e., bipolar, is composed of three cables that work as positive, neutral, and negative poles, respectively [9,10]. The main characteristic of the bipolar connection is that it allows the transfer of double the power to the loads in comparison to the monopolar connection solely by including a new cable. Further, under a perfectly balanced load case, the neutral cable can be eliminated, which reduces about 33% of the total investment costs in conductors [11]. An additional advantage of the bipolar connection is that for certain special loads, it is possible to duplicate the voltage profile provided to the load by interconnection between the positive and negative poles [12].
To examine the DC distribution under steady-state conditions, even if this works with monopolar or bipolar configurations with multiple constant power loads, it is mandatory to implement the power flow methodologies owing to the nonlinearities introduced by the constant power terminals [13,14]. In the case of monopolar configurations in the current literature, multiple approaches based on derivative-free and derivative-based methods are found, such as backward/forward, successive approximations, triangular-based, Newton–Raphson, and Taylor-based power flow methods [15]. For bipolar DC grids, few works have recently been developed for power flow and optimal power flow analyses in these networks, some of which are discussed below. Authors of [9] proposed a mixed-integer linear multi-objective optimization model for phase-swapping in the bipolar DC grids; however, they do not consider the existence of constant power loads, which is an oversimplification of the power flow model. Authors of [16] presented an optimal power flow formulation for bipolar DC networks with multiple constant power loads, including dispersed generators; additionally, they incorporated the effect of the neutral pole and its resistance in their analysis. The objective of this work was to compute the locational marginal prices of the network; however, to obtain these, the authors have linearized the hyperbolic constraints regarding constant power loads, which implies that the power flow problem was again simplified, as in the previous work. Authors of [17] illustrated an admittance nodal formulation to solve the power flow problem in bipolar DC grids with constant power terminals. A numerical evaluation into a three-bus system is made using the PSCAD/EMTDC software; however, they do not present any analysis of the model complexity or convergence test under load variations, only altering the constant power terminals for controlled current sources and leaving the complications of the solution to a power system analyzer tool. In reference [18], the authors studied the optimal power flow problem in DC bipolar distribution networks considering high load unbalanced. The authors proposed a linearized optimal power flow model to determine the effect of the grid congestion on the local marginal prices per node. Numerical results in two example test feeders show the effectiveness of the proposed approach; however, the authors do not make any comparison with other alternative optimal power approaches. Authors of [10] presented an optimal power flow formulation with multiple load unbalances by applying the current injection method. Numerical results showed the effectiveness of the proposed formulation by using a sensitivity analysis based on the Jacobian matrix to determine the costs of the total grid unbalance. Their numerical achievements were verified with the help of the PSCAD/EMTDC software.
Owing to the existing gap in the current literature regarding numerical methodologies in solving the power flow problem in bipolar DC grids with constant power terminals, this research proposes the extension of the triangular-based power flow method expounded initially in [16] for bipolar configurations, considering that the neutral pole can or cannot be solidly grounded in all the nodes of the network. A recursive power flow formula is derived, and it can be easily applied for systems with multiple monopolar loads and pure bipolar loads even if high imbalances are present. The numerical results in the 21- and the 85-bus systems portray the negative effect of non-grounding the neutral cable, since important voltage values appear in the neutral pole added with important increments in the total power losses. Moreover, to show the linear convergence properties of the proposed power flow method, multiple load scenarios were considered.
This document is organized as follows: Section 2 presents the derivation of the recursive power flow formula based on the upper-triangular matrix representation; Section 3 unveils the iterative procedure to solve the power flow problem in bipolar DC grids; Section 4 reveals the main characteristics of the 21-bus and the 85-bus grid system. Section 5 details the numerical validations and their analyses and discussions. Finally, Section 6 describes the main concluding remarks and some possible future works derived from this research.

2. Power Flow Formulation

A bipolar DC distribution network with multiple constant power loads can be analyzed through a recursive formulation that allows the determining of the final voltage profile in the positive p, neutral o, and negative n poles from an initial voltage value provided in the first iteration [19]. To illustrate the formulation of the triangular-based bipolar power flow method, let us consider a small bipolar network composed of three nodes, depicted in Figure 1 [12].
Figure 1 shows that the nodes can be connected with multiple constant power terminals. Note that in an arbitrary node k, it is possible to have loads connected between the positive and neutral poles, i.e., p d k , p o , loads between the negative and neutral poles, i.e., p d k , n o , and also pure bipolar loads named p d k , p n . It is worth mentioning that the index d is used in referring to demand nodes.
Now, if the first Kirchhoff’s law is applied to each node, where the current through the line l is named j l , p o n = [ j l , p , j l , o , j l , n ] and the demanded current at node k is defined as i d k , p o n = [ i d k , p , i d k , o , i d k , n ] T , the following set of linear equations are formed:
j a , p j a , o j a , n j b , p j b , o j b , n = 1 0 0 1 0 0 0 1 0 0 1 0 0 0 1 0 0 1 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 i d 2 , p i d 2 , o i d 2 , n i d 3 , p i d 3 , o i d 3 , n ,
which can be easily compacted in a matricial structure with the form defined in Equation (2).
J l , p o n = T l l , p o n I d , p o n ,
where J l , p o n R 3 l × 1 is the vector that contains all the branch currents, i d , p o n R 3 ( b 1 ) × 1 is the vector that comprises all of the demanded currents (b being the total number of nodes/buses the network), and T l l , p o n R 3 l × 3 l is defined as the triangular matrix that relates branches with demand currents. Note that the triangular-based formulation defined in (2) is only applicable to DC bipolar networks with radial structures and a unique voltage controlled source (slack node).
Now, if the second Kirchhoff’s law is applied to each closed-loop trajectory from the slack node to each demand node, then the following set of linear equations is obtained:
v d 2 , p v d 2 , o v d 2 , n v d 3 , p v d 3 , o v d 3 , n = 1 0 0 0 1 0 0 0 1 1 0 0 0 1 0 0 0 1 v s , p v s , o v s , n 1 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 1 0 0 1 0 0 0 1 0 0 1 0 0 0 1 0 0 1 e a , p e a , o e a , n e b , p e b , o e b , n ,
which can be compacted in its matricial form as follows:
V d , p o n = A d s V s , p o n T l l , p o n E l , p o n ,
where V d , p o n R 3 ( b 1 ) × 1 is the vector that contains all the voltage profiles in the positive, neutral, and negatives poles for the demand nodes, V s , p o n R 3 s × 1 is the vector with the voltage outputs in the slack source (known voltage values), E l , p o n R 3 l × 1 is the vector that consists of all the voltage drops in the grid branches, and A d s R 3 ( b 1 ) × 3 is a tri-diagonal matrix composed of identity diagonal matrices that relate each demand node with the substation.
To relate branch current and branch voltage drops, Ohm’s law is applied to each branch l, which produces the following set of linear equations:
e a , p e a , o e a , n e b , p e b , o e b , n = r a , p 0 0 0 0 0 0 r a , o 0 0 0 0 0 0 r a , n 0 0 0 0 0 0 r b , p 0 0 0 0 0 0 r b , o 0 0 0 0 0 0 r b , n j a , p j a , o j a , n j b , p j b , o j b , n ,
which can be compacted as defined in Equation (6)
E l , p o n = R l l , p o n J l , p o n ,
where R l l , p o n R 3 l × 3 l is a diagonal matrix that contains all the resistive effects of the grid branches.
Now, if Equation (2) is substituted in Equation (6) and its result is replaced in Equation (4), consequently, the triangular-based power flow formula for bipolar DC networks is obtained as defined in (7).
V d , p o n = A d s V s , p o n T l l , p o n R l l , p o n T l l , p o n I d , p o n ,
For simplicity in the formulation, the resistance-like nodal matrix, R d d , p o n , as T l l , p o n R l l , p o n T l l , p o n , is defined to convert Equation (7) into (8).
V d , p o n = A d s V s , p o n R d d , p o n I d , p o n .
Note that Equation (8) is indeed a linear relation between demanded voltages and currents; however, due to the presence of multiple constant power terminals, this equation transformed into a general nonlinear non-convex equation. From Figure 1, it is possible to define the current demanded in an arbitrary node k for each pole as follows [17]:  
i d k , p = p d k , p o v d k , p v d k , o + p d k , p n v d k , p v d k , n ,
i d k , o = p d k , p o v d k , o v d k , p + p d k , n o v d k , o v d k , n ,
i d k , n = p d k , n o v d k , n v d k , o + p d k , p n v d k , n v d k , p .
To arrive at a compact formula for the calculation of the demand current at each node, as defined in Equations (9)–(11), let us define the auxiliary variables that measure the voltage difference between poles as follows: v d k , p o = v d k , p v d k , o , v d k , p n = v d k , p v d k , n , and v d k , n o = v d k , n v d k , o , which can be grouped into a vector as Δ v d k , p o n = [ v d k , p o , v d k , p n , v d k , n o ] . With these definitions, the demanded current in the k node can be calculated as presented below:
I d k , p o n = H diag 1 Δ v d k , p o n P d k , p o n ,
where
I d k , p o n = i d k , p i d k , o i d k , n , H = 1 1 0 1 0 1 0 1 1 , P d k , p o n = p d k , p o p d k , p n p d k , n o .
It is worth mentioning that in finding all the demanded voltages with Equation (8), it is necessary to use an iterative procedure since the demanded currents at each node k defined in (12) are a function of the demanded voltages, which implies that in order to know these voltages, it is necessary to have known them previously, which is only solvable through a recursive implementation, as will be presented in the next section [19].

3. Iterative Solution

To solve the power flow problem in bipolar DC grids with multiple constant power loads, the iterative procedure implemented is presented in Algorithm 1.
In Algorithm 1, the parameter ζ is the convergence error between two consecutive voltages, which is defined as recommended in [19] as 1 × 10 10 . Note that once the power flow problem is solved by implementing the Algorithm 1, the total grid power losses in all the branches of the network can be determined as follows:
p loss = J l , p o n R l l , p o n J l , p o n ,
Algorithm 1: Power flow solution using the triangular-based formulation for multiple constant power loads.
Sensors 22 02914 i001

4. Test Feeders

To evaluate the efficiency of the proposed triangular-based power flow approach for bipolar DC grids with multiple constant power loads, two test feeders are employed. The characteristic of each one of these test feeders is presented below.

4.1. 21-Bus System

The 21-bus system was adapted from [19] to include loads connected to the positive and negative poles with respect to the neutral as well as pure bipolar loads. The electrical configuration of this grid is depicted in Figure 2.
For this test feeder, the slack bus works in the positive and negative poles with ± 1 kV. All the electrical parameters regarding branches and loads are reported in Table 1. Notably, in this research, we assume that all the poles, including the neutral, were constructed with the same caliber.

4.2. 85-Bus System

The 85-bus system is a DC bipolar adaptation of the IEEE 85-bus system presented in [20] to locate and size fixed-step capacitor banks. This system is operated with 11 kV per pole, and it has radial configuration, i.e., 84 distribution lines. The electrical configuration of this test feeder is depicted in Figure 3.
The complete parametric information for the 85-bus grid with bipolar structure is presented in Table 2.

5. Numerical Validations

The numerical implementation of the proposed triangular-based bipolar power flow method was executed in the MATLAB programming environment using the researcher’s own scripts. For this implementation, 2021 b was used on a PC with an AMD Ryzen 7 3700 2.3 GHz processor and 16.0 GB RAM, running on a 64-bit version of Microsoft Windows 10 Single language.

5.1. Results in the 21-Bus System

To demonstrate the effectiveness of the proposed method on addressing the power flow solution in bipolar DC grids with multiple constant power loads, we consider two simulation cases regarding the neutral pole: (i) this pole is solidly grounded at each one of the nodes of the network; and (ii) this pole is only solidly grounded at the substation bus.
Table 3 exhibits the voltage in the positive and negative poles when both cases are simulated.
The numerical data provided in Table 3 permit noting the following: (i) in the first simulation case when the neutral is solidly grounded, the positive pole presents some nodes with voltage regulations more than 10%, presenting a minimum voltage at node 17 with a magnitude of 890.1027 V, which implies that the grid regulation is about 10.99 % . Conversely, for the negative pole, the worst regulation voltage appears at node 18 with a value of 9.14 % . The voltage unbalance between the positive and negative poles is caused by the load disequilibrium, since the positive pole has about 554 kW of constant power consumption while the negative pole has only 445 kW of the same. (ii) In the second case, when the neutral pole is not connected to the electrical ground at each node, it is possible to observe that nodes 15 to 18 have voltages higher than 18 V, which can cause the misoperation of some devices in the adjacent areas, especially when sensitive to voltage variations on the reference point. Additionally, the non-grounded neutral pole can worsen the voltage profile in some nodes of the network, as seen for the positive voltage profile at node 17, where the voltage has decreased 1.8433 V with respect to the first simulation case.
The main issue when the neutral pole is not solidly grounded in all the nodes corresponds to the total grid power losses since these are increased with respect to the solidly grounded case. For example, in the 21-bus system for the first simulation case, the total power losses are 91.2701 kW, while for the second, this number increased to 95.4237 kW. These values indicate that there is about 4.1536 kW that is transformed into heat owing to the currents flowing through the neutral cable.
As evidence of the convergence properties of the studied triangular-based bipolar power flow method, we plot the logarithm value of the convergence error, i.e., log ϵ (where ϵ = max V d , p o n t + 1 V d , p o n t ), for the worst operative case (i.e., non-grounded simulation scenario) considering that the load varies from 60% to 180% of their nominal values listed in Table 1. The convergence rate is depicted in Figure 4. Note that the 100% corresponds to the benchmark case of the network where the load takes its nominal value.
The numerical performance of the triangular-based method for bipolar DC grids in the 21-bus system depicted in Figure 4 detail the following: (i) the load variations directly impact the total number of iterations to reach the desired convergence. For example, when the load is 60% of the nominal value, 10 iterations are required, whereas in the benchmark case, 13 iterations are used, and when the load is 1.8 times the nominal value, 26 iterations are employed to solve the power flow problem. (ii) For all the load increments, it is observed that the convergence rate of the triangular-based bipolar power flow is linear, implying that under normal operating conditions, this method can ensure convergence to the power flow solution. However, this is only possible if the system is operated far from the voltage collapse point.

5.2. Results in the 85-Bus Grid

After the implementation of the proposed triangular-based method for bipolar DC grids in the 85-bus system under the nominal operating conditions, we found that (i) when the neutral wire is solidly grounded in all the nodes of the grid, then the total power losses is 452.2981 kW, i.e., 6.76% of the total power consumption, while when the neutral wire is non-grounded, the total power increases to 489.5759 kW, i.e., 7.32% of the net power consumption; (ii) the total number of iterations was about 10 for the solidly-grounded case and 13 for the non-grounded case.
On the other hand, in Figure 5 are presented the voltage profiles in the 85-bus system for the positive and negative poles considering solidly-grounded and non-grounded operation cases.
Voltage profiles in Figure 5 show that (i) for the solidly-grounded operative costs, the minimum voltage in the positive pole is 0.9189 pu at node 54, and for the negative pole it is 0.8950 pu at the same node; and (ii) in the non-grounded scenario, these values are 0.9204 pu for the positive pole, and 0.8925 pu for the negative pole.
Note that when positive and negative voltage profiles are compared (see Figure 5), it is observed that the positive pole has similar behavior to the negative pole, which is very similar to the reflection of the voltage profile with respect to the axis of nodes; even if the system is perfectly balanced, v p must be equal to the absolute value of v n .

5.3. Complementary Analysis

The following results were also obtained for both test feeders:
In the solidly grounded scenario after 1000 consecutive evaluations of the power flow methodology, the average processing times for the 21- and 85-bus grids were 0.6498 ms and 6.4858 ms, respectively. In the non-grounded case, these times were 0.7318 and 6.7226 ms. Note that the increments in these times are expected since the number of iterations increases in the non-grounded neutral wire simulation scenario.
Comparative simulations with the classical backward/forward power flow method adapted for bipolar DC grids demonstrated that both methodologies reach the same voltage profiles and power losses calculations. However, the main advantage of the triangular-based power flow method is the processing time required, since for both tests feeders were 20 % faster than the backward/forward power flow method, which confirmed the results presented by authors of [15] in the case of monopolar DC grid equivalents.

6. Conclusions and Future Works

The power flow problem in bipolar DC grids with multiple constant power loads was addressed in this research through the application of the triangular-based power flow formulation. The proposed formulation is applicable in radial configurations, considering the possibility that the neutral cable is or is not grounded in all the nodes of the system. The numerical results in the 21-bus system demonstrate that when the neutral pole is solidly grounded, the maximum voltage regulation bound under normal operative conditions was about 10.99 % and total grid power losses about 91.2701 kW; conversely, for the non-grounded simulation case, the voltage regulation of the network was 11.17 % and total grid losses increased to 95.4237 kW. Numerical evaluations where the total load was incremented from 60% to 180% of the nominal value illustrated that the convergence of the triangular-based power flow method is linear, and the effect of the load increments is transferred to the number of iterations.
In the case of the 85-bus grid, the minimum voltage profile occurs in the negative pole for the solidly-grounded and non-grounded operative scenarios with magnitudes of 0.8950 pu and 0.8925 pu, respectively; while in the case of the power losses, the solidly-grounded case has a total power loss of 452.2981 kW, which increased to 489.5759 kW in the non-grounded scenario.
For future research, it will be possible to execute the following works: (i) propose a recursive power solver for bipolar DC grids by linearizing the demanded currents around the initial voltage values and then updating this point until the desired convergence error is reached; (ii) determine via metaheuristic or convex optimization the optimal subset of nodes where the neutral cable must be solidly grounded to reduce the total grid power losses; and (iii) design an experimental scenario where the power flow methodologies for DC bipolar networks can be validated.

Author Contributions

Conceptualization, methodology, software, and writing—review and editing, O.D.M., Á.M.-Q. and J.C.H. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported in part by the Centro de Investigación y Desarrollo Científico de la Universidad Distrital Francisco José de Caldas under grant 1643-12-2020 associated with the project: “Desarrollo de una metodología de optimización para la gestión óptima de recursos energéticos distribuidos en redes de distribución de energía eléctrica”.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

No new data were created or analyzed in this study. Data sharing is not applicable to this article.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Mackay, L.; Blij, N.H.v.d.; Ramirez-Elizondo, L.; Bauer, P. Toward the universal DC distribution system. Electr. Power Components Syst. 2017, 45, 1032–1042. [Google Scholar] [CrossRef] [Green Version]
  2. Montoya, O.D. Numerical Approximation of the Maximum Power Consumption in DC-MGs With CPLs via an SDP Model. IEEE Trans. Circuits Syst. II Express Briefs 2019, 66, 642–646. [Google Scholar] [CrossRef]
  3. Parhizi, S.; Lotfi, H.; Khodaei, A.; Bahramirad, S. State of the Art in Research on Microgrids: A Review. IEEE Access 2015, 3, 890–925. [Google Scholar] [CrossRef]
  4. Siraj, K.; Khan, H.A. DC distribution for residential power networks—A framework to analyze the impact of voltage levels on energy efficiency. Energy Rep. 2020, 6, 944–951. [Google Scholar] [CrossRef]
  5. Li, B.; Wang, W.; Liu, Y.; Li, B.; Wen, W. Research on power flow calculation method of true bipolar VSC-HVDC grids with different operation modes and control strategies. Int. J. Electr. Power Energy Syst. 2021, 126, 106558. [Google Scholar] [CrossRef]
  6. Zhu, H.; Zhu, M.; Zhang, J.; Cai, X.; Dai, N. Topology and operation mechanism of monopolarto-bipolar DC-DC converter interface for DC grid. In Proceedings of the 2016 IEEE 8th International Power Electronics and Motion Control Conference (IPEMC-ECCE Asia), Hefei, China, 22–26 May 2016. [Google Scholar] [CrossRef]
  7. Guo, C.; Wang, Y.; Liao, J. Coordinated Control of Voltage Balancers for the Regulation of Unbalanced Voltage in a Multi-Node Bipolar DC Distribution Network. Electronics 2022, 11, 166. [Google Scholar] [CrossRef]
  8. Garces, A. Uniqueness of the power flow solutions in low voltage direct current grids. Electr. Power Syst. Res. 2017, 151, 149–153. [Google Scholar] [CrossRef]
  9. Chew, B.S.H.; Xu, Y.; Wu, Q. Voltage balancing for bipolar DC distribution grids: A power flow based binary integer multi-objective optimization approach. IEEE Trans. Power Syst. 2018, 34, 28–39. [Google Scholar] [CrossRef] [Green Version]
  10. Lee, J.O.; Kim, Y.S.; Moon, S.I. Current Injection Power Flow Analysis and Optimal Generation Dispatch for Bipolar DC Microgrids. IEEE Trans. Smart Grid 2021, 12, 1918–1928. [Google Scholar] [CrossRef]
  11. Rivera, S.; Lizana, R.; Kouro, S.; Dragičević, T.; Wu, B. Bipolar dc power conversion: State-of-the-art and emerging technologies. IEEE J. Emerg. Sel. Top. Power Electron. 2020, 9, 1192–1204. [Google Scholar] [CrossRef]
  12. Litrán, S.P.; Durán, E.; Semião, J.; Barroso, R.S. Single-Switch Bipolar Output DC-DC Converter for Photovoltaic Application. Electronics 2020, 9, 1171. [Google Scholar] [CrossRef]
  13. Javid, Z.; Karaagac, U.; Kocar, I.; Chan, K.W. Laplacian Matrix-Based Power Flow Formulation for LVDC Grids with Radial and Meshed Configurations. Energies 2021, 14, 1866. [Google Scholar] [CrossRef]
  14. Simpson-Porco, J.W.; Dorfler, F.; Bullo, F. On Resistive Networks of Constant-Power Devices. IEEE Trans. Circuits Syst. II Express Briefs 2015, 62, 811–815. [Google Scholar] [CrossRef] [Green Version]
  15. Montoya, O.D.; Gil-González, W.; Garces, A. Numerical methods for power flow analysis in DC networks: State of the art, methods and challenges. Int. J. Electr. Power Energy Syst. 2020, 123, 106299. [Google Scholar] [CrossRef]
  16. Montoya, O.D.; Grisales-Norena, L.F.; Gil-Gonzalez, W. Triangular Matrix Formulation for Power Flow Analysis in Radial DC Resistive Grids With CPLs. IEEE Trans. Circuits Syst. II Express Briefs 2020, 67, 1094–1098. [Google Scholar] [CrossRef]
  17. Kim, J.; Cho, J.; Kim, H.; Cho, Y.; Lee, H. Power Flow Calculation Method of DC Distribution Network for Actual Power System. KEPCO J. Electr. Power Energy 2020, 6, 419–425. [Google Scholar] [CrossRef]
  18. Mackay, L.; Guarnotta, R.; Dimou, A.; Morales-Espana, G.; Ramirez-Elizondo, L.; Bauer, P. Optimal Power Flow for Unbalanced Bipolar DC Distribution Grids. IEEE Access 2018, 6, 5199–5207. [Google Scholar] [CrossRef]
  19. Garces, A. On the Convergence of Newton’s Method in Power Flow Studies for DC Microgrids. IEEE Trans. Power Syst. 2018, 33, 5770–5777. [Google Scholar] [CrossRef] [Green Version]
  20. Tamilselvan, V.; Jayabarathi, T.; Raghunathan, T.; Yang, X.S. Optimal capacitor placement in radial distribution systems using flower pollination algorithm. Alex. Eng. J. 2018, 57, 2775–2786. [Google Scholar] [CrossRef]
Figure 1. Schematic representation of a bipolar DC grid.
Figure 1. Schematic representation of a bipolar DC grid.
Sensors 22 02914 g001
Figure 2. Grid configuration of the 21-bus system.
Figure 2. Grid configuration of the 21-bus system.
Sensors 22 02914 g002
Figure 3. Grid topology of the IEEE 85-bus system for bipolar power flow applications.
Figure 3. Grid topology of the IEEE 85-bus system for bipolar power flow applications.
Sensors 22 02914 g003
Figure 4. Convergence rate of the studied method for load variations in the 21-bus system.
Figure 4. Convergence rate of the studied method for load variations in the 21-bus system.
Sensors 22 02914 g004
Figure 5. Voltage behavior for the 85-bus grid considering solidly-grounded and non-grounded neutral wire.
Figure 5. Voltage behavior for the 85-bus grid considering solidly-grounded and non-grounded neutral wire.
Sensors 22 02914 g005
Table 1. Data for the 21-bus system (all powers in kW).
Table 1. Data for the 21-bus system (all powers in kW).
Node jNode k R j k ( Ω ) P d k , p o P d k , n o P d k , p n
120.053701000
130.054000
340.0543640120
450.063400
460.0513600
370.037000
780.07932500
790.072800100
3100.0530100
10110.03845300
11120.07968700
11130.07810075
10140.083000
14150.06522300
15160.06423100
16170.07443060
16180.08134600
14190.0789150
19200.084211050
19210.08221200
Table 2. Data for the 85-bus system (all powers in kW).
Table 2. Data for the 85-bus system (all powers in kW).
Node jNode k R j k ( Ω ) P d k , p o P d k , n o P d k , p n Node jNode k R j k ( Ω ) P d k , p o P d k , n o P d k , p n
120.1080010.07534441.00217.6417.9950
230.16350040.3544450.9115017.6417.995
340.2172828.565045460.9112517.6417.995
450.10810050046470.54677.1410
560.43517.6417.99525.1835480.6370100
670.27208.625048490.1820025
781.19717.6417.99530.2949500.36418.14018.505
890.10817.835040.4650510.4552828.5650
9100.5980100048521.36630015
10110.5442828.565052530.45517.643517.995
11120.5440404553540.546283028.565
12130.598454022.552550.54638048.565
13140.27217.6417.99535.1349560.54674032.14
14150.32617.6417.99520.1759570.2734835.06510
2160.72817.6467.533.4957580.8190500
3170.45556.157.1550.2558590.1821828.56525
5180.8202828.56520058600.5462843.5650
18190.6372828.5651060610.7281828.56530
19200.45517.6417.99515061621.00212.529.0650
20210.81917.6470152.560630.18277.145
21221.54817.6417.9953063640.7280050
19230.182287528.56564650.18212.52537.5
7240.910017.6417.99565660.1824048.56533
8250.45517.6417.9955064670.455000
25260.36402828.56567680.910000
26270.5461107517568691.0921318.56525
27280.2732812528.56569700.4550200
28290.5460507570710.54617.6438.27517.995
29300.54617.64017.99567720.1822813.5650
30310.27317.6417.995068731.1843000
31320.1820175073740.273285028.565
32330.18277.1412.573751.00217.646.2317.995
33340.81900070760.5463848.5650
34350.637005065770.091717.1425
35360.18217.64017.99510780.63728628.565
26370.364283028.56567790.54617.6442.9950
27381.0022828.5652512800.7282828.56530
29390.54602828.56580810.36445075
32400.45517.64017.99581820.0912853.750
40411.002100081831.09212.6432.99562.5
41420.27317.642517.99583841.0026272.20
41430.45517.6417.995013850.819101010
Table 3. Voltage for both simulation cases in the 21-bus system.
Table 3. Voltage for both simulation cases in the 21-bus system.
Node+Pole (V)0 Pole (V)−Pole (V)
Grounded neutral
110000−1000
2996.27610−994.6716
3960.06830−968.4100
4952.37140−962.7830
5952.10670−962.7830
6950.43960−962.7830
7953.74480−964.5412
8951.08670−960.4284
9943.86190−960.7609
10937.48880−948.4698
11930.92200−942.8952
12925.11520−936.9933
13926.94670−939.7613
14916.47150−930.2940
15905.44440−921.0085
16896.14200−913.9505
17890.10270−911.4861
18893.05820−908.6017
19909.95280−924.3558
20905.70610−921.1448
21908.05650−922.5781
Non-grounded neutral
110000−1000
2996.2821−1.6193−994.6628
3959.52059.2157−968.7363
4951.763611.3722−963.1358
5951.495511.6403−963.1358
6949.803013.3327−963.1358
7953.118311.7700−964.8884
8950.429110.3922−960.8213
9943.111017.9963−961.1073
10936.574612.4855−949.0602
11929.925913.6204−943.5464
12924.024713.7095−937.7342
13925.935714.4762−940.4119
14915.162815.9904−931.1532
15903.904018.1140−922.0181
16894.408120.6576−915.0657
17888.259424.3408−912.6002
18891.252218.5786−909.8309
19908.551316.7359−925.2872
20904.261617.8323−922.0939
21906.615816.9276−923.5434
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Medina-Quesada, Á.; Montoya, O.D.; Hernández, J.C. Derivative-Free Power Flow Solution for Bipolar DC Networks with Multiple Constant Power Terminals. Sensors 2022, 22, 2914. https://doi.org/10.3390/s22082914

AMA Style

Medina-Quesada Á, Montoya OD, Hernández JC. Derivative-Free Power Flow Solution for Bipolar DC Networks with Multiple Constant Power Terminals. Sensors. 2022; 22(8):2914. https://doi.org/10.3390/s22082914

Chicago/Turabian Style

Medina-Quesada, Ángeles, Oscar Danilo Montoya, and Jesus C. Hernández. 2022. "Derivative-Free Power Flow Solution for Bipolar DC Networks with Multiple Constant Power Terminals" Sensors 22, no. 8: 2914. https://doi.org/10.3390/s22082914

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop