Next Article in Journal
Special Issue “Smart Urban Lighting Systems”
Next Article in Special Issue
Impact of Different Photovoltaic Models on the Design of a Combined Solar Array and Pumped Hydro Storage System
Previous Article in Journal
Study of the “Oxidation-Complexation” Coordination Composite Ionic Liquid System for Dissolving Precious Metals
Previous Article in Special Issue
Allothermal Gasification of Peat and Lignite by a Focused Light Flow
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Study on a Correlation-Based Anti-Islanding Method under Wider Frequency Trip Settings for Distributed Generation

Kongju National University, Gongju-si 330-717, Korea
Appl. Sci. 2020, 10(10), 3626; https://doi.org/10.3390/app10103626
Submission received: 29 April 2020 / Revised: 20 May 2020 / Accepted: 22 May 2020 / Published: 24 May 2020
(This article belongs to the Special Issue Environmental Friendly Technologies in Power Engineering)

Abstract

:

Featured Application

Grid Connected Inverter.

Abstract

Islanding phenomenon of distributed generation (DG), such as photovoltaic (PV) generation, is undesirable because it causes safety issues for utility service personnel and power system equipment. Many anti-islanding methods have been studied since DG appeared in electric power systems (EPSs). Most anti-islanding methods focus on disconnecting DG from the grid using functionality to detect islanding under narrow frequency trip settings, because safety issues have a higher priority. However, as DG plays a key part of an EPS, a significant loss of DG due to a short disturbance could result in a reliability issue for the EPS. Corresponding to this matter, new international standards, such as IEEE standard 1547–2018, require more sophisticated and complex functionalities for grid-connected DGs by adopting ride-through technologies and wider voltage/frequency trip settings. Since most anti-islanding functions of inverter-based DG have been based on the frequency of the inverter voltage, it is more difficult to detect islanding under wider frequency trip settings. This paper presents a correlation-based anti-islanding method (AIM) without depending on the frequency trip of inverter-based DGs. Simulation results are provided to verify the performance of the correlation-based anti-islanding method. As a result, the proposed method detects islanding at 0.116 s under wider frequency trip setting by the IEEE Std. 1547–2018 test condition, while the popular active frequency drift method with positive feedback does not detect islanding using the same current disturbance.

1. Introduction

Distribution generation (DG) based on renewable energy resources provides power to local loads in coordination with the main power grid [1,2,3]. DG is now commonly installed in electric power systems (EPSs) [4]. At present, EPSs have become increasingly complex in terms of their operation and controls because of the significant penetration of DGs [5]. The islanding phenomenon of DG has been regarded as one of the major issues of increased DGs in EPSs. Islanding is defined as a condition in which a portion of the utility with a DG and load remains energized even though that portion is disconnected from the remainder of the utility system, as shown in Figure 1 [6]. Since islanding causes safety issues for both utility service personnel and power system equipment, it is desirable that it is prevented [7]. However, as the utilization of DG has increased rapidly in EPSs, a possible significant loss of DG due to a short disturbance could potentially aggravate the problem and cause a wide-spread blackout.
As a result of this issue, new requirements for grid-connected technology, including ride-through and anti-islanding technology, which are more sophisticated and complex, have been recently proposed [8,9]. According to these new requirements, ride-through is the ability to withstand voltage and frequency disturbances, whereas trip is the cessation of output without immediate return to service. As trip requirements are related to the islanding of DG, a requirement for anti-islanding within two seconds is applied when DG is isolated from the upstream part of the area EPS. To date, as shown in Figure 2, a variety of anti-islanding methods (AIMs), including local techniques and remote techniques, have been developed and implemented. Remote methods depend on communication techniques between DG and the EPS but tend to be more costly than local methods [10]. Local methods are usually implemented into the grid-connected inverter of DG and they are typically classified as passive and active methods. Passive methods, based on power mismatches between DG power and local loads, detect islanding only by monitoring several system parameters such as voltage magnitude [11], frequency [12], phase jump [13], and harmonic detection [14]. On the other hand, active islanding methods perturb the DG inverter current in order to break the power balance between DG and local loads in the form of frequency drifting [15,16] and reactive power drifting [17,18]. In addition, neural network, pattern recognition and machine learning-based AIMs have been proposed [19,20]. Since most anti-islanding functions of inverter-based DG have been based on the frequency of the inverter voltage, it is more difficult to detect islanding under wider frequency trip settings. To solve this technical barrier, this paper is based on a correlation technique [21].
In this paper, study of a correlation-based AIM under wider frequency trip settings for distributed generation is presented. A non-detection zone (NDZ) by frequency trip settings is analyzed under IEEE Std. 1547–2018, compared with the previous settings under IEEE Std. 1547–2003. Then, a newly proposed correlation-based AIM method is presented with a corresponding simulation for its verification.

2. NDZ Comparisons

In the early days of the dissemination of DG, safe energy generation of the EPS was important. For voltage and frequency variation, which are indicators of EPS accidents such as blackouts, the focus was on disconnecting the DG from the EPS. As DG has been implemented in EPSs with large capacities, a significant loss of DG due to a short disturbance could cause another reliability issue for the EPS. As a result, new international standards, such as IEEE standard 1547–2018, require more sophisticated and complex requirements for grid-connected DGs. For short voltage and frequency disturbances, the ride-through capability was adopted to continue the operation of DG, as shown in Figure 3. These wider voltage and frequency trip windows allow DG to generate electric power even though there is a slight voltage and frequency disturbance. On the other hand, islanding of DG should be prevented in an EPS because it may cause safety issues. Thus, IEEE Std. 1547–2018 requires islanding detection within 2 s without compromise. However, since most anti-islanding methods are based on frequency trip windows, there have been concerns about the reduced effectiveness of anti-islanding under the new standard requirements.
The relationship between reactive power mismatch ΔQ and frequency threshold can be obtained by [22]:
Q f [ 1 ( f f m i n ) 2 ] < Δ Q P i n v < Q f [ 1 ( f f m a x ) 2 ]
Q f = R C L = | Q L | | Q C | P R
where Pinv is the active power of the DG inverter; ΔQ is the reactive power flow from the grid; f is the grid frequency; fmin and fmax are the under and over frequency thresholds, respectively; and Qf is a quality factor. The quality factor is defined as the measure of the resonance strength of the islanding test load, as shown in Figure 1a [23].
With the limit values of the frequency specified in Table 1, the corresponding NDZ was derived. This quantitative NDZ is the basis to calculate the amount of frequency perturbation of the DG inverter, which causes the harmonic distortion of the current. It has been one of the main research targets for detecting islanding with high power quality and low harmonics.
As shown in Table 1, the islanding test conditions changed to reduce the effect on the EPS by decreasing Qf from 2.5 to 1. Additionally, the frequency relay settings were changed in a wider direction to prevent nuisance trips. Table 1 shows that NDZ varies by Equation (1) according to the set value of the frequency trip settings and the value of Qf. Among the NDZ ranges of the three different standards, IEEE Std. 1547–2018 shows the largest NDZ because it has the widest frequency trip settings. Under the wide range of frequency trip settings, the current disturbance command of AIM must increase to make the frequency move out of the range when islanding occurs. Since this disturbance appears as the current distortion, harmonic components increase or displacement power factor decreases, resulting in poor power quality. Thus, this paper presents a correlation-based AIM that does not depend on the frequency trip.

3. The Proposed AIM

As one of the most used AIMs, the active frequency drift (AFD) method with positive feedback has been studied often [24,25,26]. Accordingly, this method was applicable to be implemented in a commercial photovoltaic (PV) inverter to meet the requirements of IEEE Std. 1547–2003. As shown in Figure 4, the AFD method uses the chopping fraction, cf, as a frequency perturbation parameter, which is defined as the ratio of zero time (tz) to half of the period of voltage waveform (T1/2) as follows:
c f = t z ( T 1 / 2 )
where tz is zero time of the inverter current and T1 is a period of voltage waveform.
Without the AFD method, the current is controlled to be in phase with the voltage waveform, which results in a unity power factor control. When the AFD method is applied, the frequency of the DG inverter is maintained by the grid voltage when the grid is connected, so there is no frequency variation due to zero time of the AFD reference current. It is important to design an appropriate cf value because harmonic components are generated by the injected AFD current command. When the DG inverter is disconnected from the grid, the AFD current command makes the frequency drift to the frequency trip set value, and the inverter stops [24,25,26].
If an AFD current disturbance with a fixed cf can be canceled by local load adjustment, the chopping fraction is usually modified with a positive feedback as follows [24]:
c f [ k ] = c f [ k 1 ] + K p ( F r e q [ k ] F r e q [ k 1 ] )
where k is the present status, Kp is a proportional coefficient, and Freq is the measured frequency of the voltage.
Since the displacement factor (DPF) is 1, the power factor (PF) and the reactive power can be expressed as follows [27]:
P F = P S = P P 2 + Q 2 = 1 1 + T H D i 2
Q P = T H D i
Since total harmonic distortion of current (THDi) is directly proportional to cf, the amount of reactive power variation (Q/P) in Equation (6) can be determined by cf. The previous research showed the relationship between cf and THDi through some experiments [27]. The allowable limit of THDi (5%) by the standard sets the maximum cf about 5% [27,28]. In the case of the new IEEE Std. 1547–2018, the amount of perturbation (ΔQ/Pinv) increases dramatically, as shown in Table 1. Consequently, a higher cf of the AFD method is required to prevent islanding. Thus, it is difficult to use the conventional AFD with positive feedback (AFDPF) by IEEE Std. 1547–2018 because the corresponding THDi is around 12.77% which is higher than the standard limit [28]. Since NDZs, as shown in Table 1, are valid only when AIMs depend on the frequency trip settings, this paper presents a novel method using a correlation parameter without depending on the frequency trip settings.
C p [ k ] = n = 0 n = N ( c f [ k n ] c f [ k n 1 ] ) × ( f r e q [ k n ] f r e q [ k n 1 ] )
where k is the present status and N is the number of line frequency for Cp calculation.
As shown in Equation (7), this paper presents the correlation parameter Cp as an islanding detection indicator without depending on the frequency trip setting. The proposed method uses the fact that the frequency of the DG inverter voltage has a strong correlation with the current frequency deviation after islanding. As shown in Figure 5, when the grid is connected, the inverter voltage of the DG is dominated by the rigid grid voltage source and has a weak correlation with the proposed AFD frequency perturbation. Thus, CP is maintained to be almost zero before t0. On the other hand, after islanding, CP starts to increase after t0 and reaches CP,set, and islanding is prevented.
For the AFDPF method, the key design parameter of cf is the positive feedback gain Kp, which accelerates cf deviation as frequency changes. Kp was designed and chosen by trial-and-error simulations for short frequency trip settings, 59.3 and 60.5 Hz from IEEE Std. 1547–2003. For IEEE Std. 1547–2018, the frequency trip settings, 56.5 and 62 Hz, are wider. Thus, if AFDPF method is used, Kp for IEEE Std. 1547–2018 should be larger than Kp for IEEE Std. 1547–2003, which increases the harmonic components. In this paper, Kp 0.02, which is designed for 59.3 and 60.5 Hz, is also used to show the feasibility for 56.5 and 62 Hz by using the proposed AIM. In summary, the proposed method does not depend on the frequency trip settings and is based on the correlation between the rate of change of the input current perturbation and the rate of change of the corresponding frequency. This means that islanding can be detected using the proposed correlation parameter with less cf perturbation under IEEE Std. 1547–2018.

4. Simulation Results

The performance of the proposed method was verified using PSIM software under the conditions of IEEE Std. 1547–2018. The key parameters for islanding test are shown in Table 2 and simulation circuit is shown in Figure 6. The local load was chosen as a unity power quality factor for a 3 kW DG inverter system. By adjusting tunable RLC local load, a test condition was implemented for the worst case, the power balance condition between DG generation and local load consumption. The threshold value of the correlation factor was chosen to be 0.0013, which was derived from the value of cf for IEEE Std. 1547–2003. This is to show that the designed cf for IEEE Std. 1547–2003 can also be applied to IEEE Std. 1547–2018 using the proposed method. In other words, the lower cf value, which was designed for IEEE Std. 1547–2003, can be used for IEEE Std. 1547–2018.
Figure 7 shows islanding test results when no AIM is applied. When the local loads are almost matched with DG power generation and the grid is disconnected at 0.5 s, the measured frequency is almost maintained to be 60 Hz. Thus, islanding is not detected at all. Figure 8 shows anti-islanding test results when the conventional AFD method with 5% cf is used. Before islanding occurs, the inverter output current is clearly distorted by cf, as shown in Figure 8. Once islanding occurs, the frequency of inverter voltage stays still around 60 Hz, because DG source and load power are balanced under the constant cf disturbance. Thus, islanding is not prevented in this case. In the same way, Figure 9 shows anti-islanding test results when AFDPF method is used. Before islanding occurs, it is hard to recognize the distortion of the inverter output current as shown in Figure 9, because the initial value cf for AFDPF method is 1%. After islanding at 0.5 s, the frequency is drifted by cf over 60.5 Hz and then stabilized under 62 Hz. Even though cf is increased by the positive feedback, the frequency variation after islanding is not enough to detect islanding by depending on frequency trip settings. This means that AFDPF method may meet the requirements of anti-islanding under IEEE Std. 1547–2003, whose frequency trip setting is at 60.5 Hz. However, this AFDPF method does not meet the requirement of IEEE Std. 1547–2018 because its frequency trip point is 62 Hz.
Figure 10 shows anti-islanding test results when the proposed method is used. Before islanding occurs, the distortion of the current is small like the AFDPF method since the initial value cf is 1%. In addition, before islanding, the proposed correlation parameter CP is maintained to be almost zero because frequency is dominated by the rigid grid voltage source, not the chopping fraction. In other words, there is little correlation between cf and frequency before islanding. However, after islanding, the frequency is determined by the chopping fraction with positive feedback. Therefore, the proposed correlation factor starts to increase to be over 0.0013. Therefore, islanding can be prevented by the proposed islanding indicator, CP.
The simulation results are summarized in Table 3. When the grid is connected to DG, the THDi values of AIM methods are assessed. In the conventional AFD method, THDi increases to 5.53% as the cf value increases from 1% to 5%. Both the AFDPF method and the proposed method show low THDi, which is 3.18%, because the initial value cf 1% is only inserted when the grid is connected. For AFD method, islanding is not prevented because DG source and load power were balanced. For AFDPF method, islanding is also not prevented, because the frequency deviation is not enough by using low Kp gain 0.02. In case of the proposed method, islanding is prevented with the same Kp gain of AFDPF method, because this method does not depend on the frequency trip settings.

5. Conclusions

This paper presents a correlation-based AIM under wider frequency trip settings for DG. Since a significant loss of DG due to a short disturbance could cause another reliability issue for an EPS, wider frequency trip settings were introduced in IEEE Std. 1547–2018. Under these conditions, the conventional AIM might not detect islanding with lower current distortion. Thus, the proposed method presents an islanding detection indicator as the correlation parameter between current disturbance and the corresponding frequency, and shows high islanding-detection capability with less current distortion through simulation results. According to the simulation results, the proposed AIM method detects islanding under the IEEE Std. 1547–2018 test condition within 2 s, which meets the standard requirement, and it has around 3.18% THDi, which is relatively lower compared with the conventional AFD method having 5% cf.

Funding

This work was supported by the National Research Foundation of Korea (NRF) grant funded by the Korea government (MSIP) [grant number 2019R1H1A1080039].

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Chen, G.; Lewis, F.L.; Feng, E.N.; Song, Y. Distributed optimal active power control of multiple generation systems. IEEE Trans. Ind. Electron. 2015, 62, 7079–7090. [Google Scholar] [CrossRef]
  2. Huang, W.; Zhang, N.; Yang, J.; Wang, Y.; Kang, C. Optimal Configuration Planning of Multi-Energy Systems Considering Distributed Renewable Energy. IEEE Trans. Smart Grid 2019, 10, 1452–1464. [Google Scholar] [CrossRef]
  3. Cady, S.T.; Dominguez-Garcia, A.D.; Hadjicostis, C.N. A distributed generation control architecture for islanded AC microgrids. IEEE Trans. Control. Syst. Technol. 2015, 23, 1717–1735. [Google Scholar] [CrossRef]
  4. Tan, Y.; Wang, Z. Incorporating unbalanced operation constraints of three-phase distributed generation. IEEE Trans. Power Syst. 2019, 34, 2449–2452. [Google Scholar] [CrossRef]
  5. Massignan, J.A.D.; Pereira, B.R.; London, J.B.A. Load flow calculation with voltage regulators bidirectional mode and distributed generation. IEEE Trans. Power Sys. 2017, 32, 1576–1577. [Google Scholar]
  6. Makwana, Y.M.; Bhalja, B.R. Experimental Performance of an Islanding Detection Scheme Based on Modal Components. IEEE Trans. Smart Grid. 2019, 10, 1025–1035. [Google Scholar] [CrossRef]
  7. Raipala, O.; Makinen, A.S.; Jarventrausta, P. An anti-islanding protection method based on reactive power injection and ROCOF. IEEE Trans. Power Deliv. 2017, 32, 401–410. [Google Scholar] [CrossRef]
  8. IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces; IEEE Std. 1547–2018; IEEE Standard Association: Piscataway, NJ, USA, 2018.
  9. Recommended Settings for Voltage and Frequency Ride-Through of Distributed Energy Resources. EPRI Report, Product Id: 3002006203. Available online: https://www.epri.com/#/pages/product/3002006203/ (accessed on 25 April 2020).
  10. Pouryekta, A.; Ramachandaramurthy, V.K.; Mithulananthan, N.; Arulampalam, A. Islanding Detection and Enhancement of Microgrid Performance. IEEE Syst. J. 2018, 12, 3131–3141. [Google Scholar]
  11. Liu, S.; Zhuang, S.; Xu, Q.; Xiao, J. Improved voltage shift islanding detection method for multi-inverter grid-connected photovoltaic systems. IET Gener. Transm. Distrib. 2016, 10, 3163–3169. [Google Scholar] [CrossRef]
  12. Guha, B.; Haddad, R.J.; Kalaani, Y. Voltage ripple-based passive islanding detection technique for grid-connected photovoltaic inverters. IEEE Power Energy Technol. Syst. J. 2016, 3, 143–154. [Google Scholar] [CrossRef]
  13. Raza, S.; Mokhlis, H.; Arof, H.; Laghari, A.; Mohamad, H. A sensitivity analysis of different power system parameters on islanding detection. IEEE Trans. Sustain. Energy 2016, 7, 461–470. [Google Scholar] [CrossRef]
  14. Liu, N.; Diduch, C.; Chang, L.; Su, J. A reference impedance-based passive islanding detection method for inverter-based distributed generation system. IEEE J. Emerg. Sel. Top. Power Electron. 2015, 3, 1205–1217. [Google Scholar] [CrossRef]
  15. Kim, B.; Sul, S. Stability-Oriented Design of Frequency Drift Anti-Islanding and Phase-Locked Loop Under Weak Grid. IEEE J. Emerg. Sel. Top. Power Electron. 2017, 5, 760–774. [Google Scholar] [CrossRef]
  16. Wen, B.; Boroyevich, D.; Burgos, R.; Shen, Z.; Mattavelli, P. Impedance-Based Analysis of Active Frequency Drift Islanding Detection for Grid-Tied Inverter System. IEEE Trans. Ind. Appl. 2016, 52, 332–341. [Google Scholar] [CrossRef]
  17. Pourbabak, H.; Kazemi, A. Islanding detection method based on a new approach to voltage phase angle of constant power inverters. IET Gener. Transm. Dis. 2016, 10, 1190–1198. [Google Scholar] [CrossRef] [Green Version]
  18. Chen, X.; Li, Y. An Islanding Detection Method for Inverter-Based Distributed Generators Based on the Reactive Power Disturbance. IEEE Trans. Power Electron. 2016, 31, 3559–3574. [Google Scholar] [CrossRef]
  19. Khan, M.A.; Kurukuru, V.S.B.; Haque, A.; Mekhilef, S. Islanding Classification Mechanism for Grid-Connected Photovoltaic Systems. IEEE J. Emerg. Sel. Top. Power Electron. 2020. [Google Scholar] [CrossRef]
  20. Faqhruldin, O.N.; EL-Saadany, E.F.; Zeineldin, H.H. A universal islanding detection technique for distributed generation using pattern recognition. IEEE Trans. Smart Grid. 2014, 5, 1985–1992. [Google Scholar] [CrossRef]
  21. Yu, B. An Improved Active Frequency Drift Anti-Islanding Detecting Module for Multiple PV Micro-Inverter Systems and Detecting Method Using the Same; No. 10-1530207: Seoul, Korea, 2014. [Google Scholar]
  22. Ye, Z.; Kolwalkar, A.; Zhang, Y.; Du, P.; Walling, R. Evaluation of anti-islanding schemes based on nondetection zone concept. IEEE Trans. Power Electron. 2004, 19, 1171–1176. [Google Scholar] [CrossRef]
  23. Utility-Interconnected Photovoltaic Inverters-Test Procedure of Islanding Prevention Measures; IEC 62116:2014; International Electrotechnical Commission: Geneva, Switzerland, 2014.
  24. Ropp, M.E.; Begovic, M.; Rohatgi, A. Analysis and performance assessment of the active frequency drift method of islanding prevention. IEEE Trans. Energy Convers. 1999, 14, 810–816. [Google Scholar] [CrossRef]
  25. Vahedi, H.; Mehdi, K.; Gharehpetian, G.B. Accurate SFS Parameter Design Criterion for Inverter-Based Distributed Generation. IEEE Trans. Power Deliv. 2016, 31, 1050–1059. [Google Scholar] [CrossRef]
  26. Sun, Q.; Guerrero, J.M.; Jing, T.; Vasquez, J.C.; Yang, R. An Islanding Detection Method by Using Frequency Positive Feedback Based on FLL for Single-Phase Microgrid. IEEE Trans. Smart Grid. 2017, 8, 1821–1830. [Google Scholar] [CrossRef] [Green Version]
  27. Jung, Y.; Choi, J.; Yu, G. A novel active anti-islanding method for grid-connected photovoltaic inverter. J. Power Electron. 2007, 7, 64–71. [Google Scholar]
  28. IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Systems; IEEE Std. 929-2000; IEEE Standard Association: Piscataway, NJ, USA, 2000.
Figure 1. Description of islanding phenomenon: (a) grid-connected mode; (b) islanding mode.
Figure 1. Description of islanding phenomenon: (a) grid-connected mode; (b) islanding mode.
Applsci 10 03626 g001
Figure 2. Classification of anti-islanding method.
Figure 2. Classification of anti-islanding method.
Applsci 10 03626 g002
Figure 3. A simplified ride-through capability required in IEEE Std. 1547–2018: (a) voltage ride-through profile; (b) frequency ride-through profile (default setting).
Figure 3. A simplified ride-through capability required in IEEE Std. 1547–2018: (a) voltage ride-through profile; (b) frequency ride-through profile (default setting).
Applsci 10 03626 g003
Figure 4. Active frequency drift (AFD) reference current waveform compared with the voltage waveform.
Figure 4. Active frequency drift (AFD) reference current waveform compared with the voltage waveform.
Applsci 10 03626 g004
Figure 5. Operational waveform of the proposed anti-islanding method.
Figure 5. Operational waveform of the proposed anti-islanding method.
Applsci 10 03626 g005
Figure 6. Simulation circuit for islanding test.
Figure 6. Simulation circuit for islanding test.
Applsci 10 03626 g006
Figure 7. Islanding test results when no anti-islanding method is used.
Figure 7. Islanding test results when no anti-islanding method is used.
Applsci 10 03626 g007
Figure 8. Anti-islanding test results when active frequency drift method (cf = 5%) is used.
Figure 8. Anti-islanding test results when active frequency drift method (cf = 5%) is used.
Applsci 10 03626 g008
Figure 9. Anti-islanding test results when active frequency drift method with positive feedback is used.
Figure 9. Anti-islanding test results when active frequency drift method with positive feedback is used.
Applsci 10 03626 g009
Figure 10. Anti-islanding test results when the proposed method is used.
Figure 10. Anti-islanding test results when the proposed method is used.
Applsci 10 03626 g010
Table 1. Historical frequency trip settings of the distributed generation (DG) inverter.
Table 1. Historical frequency trip settings of the distributed generation (DG) inverter.
StandardOver
Frequency [Hz]
Under
Frequency
[Hz]
Clearing TimeConditionNon Detection Zone
as   Δ Q P
IEEE Std.
929–2000
60.559.36 [cycles]≤ 10 [kW],
Qf = 2.5
5.94 % Δ Q P 4.12 %
IEEE Std.
1547–2003
60.559.30.16 [s]≤ 30 [kW],
Qf = 1
2.37 % Δ Q P 1.65 %
IEEE Std.
1547–2018
62.056.50.16 [s]Default setting,
Qf = 1
12.77 % Δ Q P 6.35 %
Table 2. DG’s key parameters for simulation.
Table 2. DG’s key parameters for simulation.
ParameterValue
Local load R, L, C powerQuality factor Qf = 1PR = 3 kW
QL = 3 kVar
QC = 3 kVar
Single DG inverter nominal power, Pinv3 kW
Threshold value of correlation parameter, CP,set0.0008 (when N = 5, Kp = 0.02)
Frequency trip settingOF: 62 Hz, UF: 56.5 Hz
OF: 62 Hz, UF: 56.5 Hz56.5 < f < 62 Hz
Nominal grid voltage, frequency, Vgrid220 V, 60 Hz single phase
Table 3. Performance comparison among AIMs.
Table 3. Performance comparison among AIMs.
AIMAFD Method
(Fixed cf)
AFDPF Method
(Varying cf)
The Proposed Method
(Varying cf)
Parameter
cf [%]12345 c f [ k ] = c f [ k 1 ] + K p ( F r e q [ k ] F r e q [ k 1 ] )
Kp- (No need)0.020.02
Anti-islanding detection time [s]
at ΔP and ΔQ   0
No detectionNo detection0.116
THDi [%]
before islanding
3.183.193.534.105.533.183.18

Share and Cite

MDPI and ACS Style

Yu, B. Study on a Correlation-Based Anti-Islanding Method under Wider Frequency Trip Settings for Distributed Generation. Appl. Sci. 2020, 10, 3626. https://doi.org/10.3390/app10103626

AMA Style

Yu B. Study on a Correlation-Based Anti-Islanding Method under Wider Frequency Trip Settings for Distributed Generation. Applied Sciences. 2020; 10(10):3626. https://doi.org/10.3390/app10103626

Chicago/Turabian Style

Yu, Byunggyu. 2020. "Study on a Correlation-Based Anti-Islanding Method under Wider Frequency Trip Settings for Distributed Generation" Applied Sciences 10, no. 10: 3626. https://doi.org/10.3390/app10103626

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop