1. Introduction
HVDC and MVDC links are taking over AC transmission and distribution because of some favorable factors. First of all, HVDC converters are becoming as reliable as power transformers but featuring much more flexibility and efficiency, even at EHV levels. Second, cable can transmit and distribute energy over longer distances, but with lower losses (for conductor and insulation). In addition, interconnections of AC networks through DC links are easier [
1,
2,
3,
4,
5,
6,
7,
8,
9,
10]. The integration of renewable energy sources into the electrical grid is crucial for global sustainability [
11,
12,
13,
14,
15]. The usage of HVDC cable systems is making the whole grid smarter by promoting flexibility and sustainability through the grid connection of renewable energy sources which, in general, are present in remote locations far from large consumption areas. Even in power distribution networks, MVDC technology is becoming a preferable option because of its high power transfer capacity, superior controllability, and operational flexibility [
16].
So far so good, but a big question mark overshadows this fast-developing framework. While for AC there is a span of many decades of feedback from the field as regards cable design, performance, maintenance, and reliability, very little is available for DC cables, especially those using polymeric insulation [
17]. Return on investment, ROI, relies upon expected cable system life, maintenance plans, outage rate, and operation effectiveness; thus, possessing design and diagnostic models and tools is fundamental for evaluating the long-term impact of HVDC investment and associated sustainability. In this picture, involving thermoplastic, recyclable insulation over oil–paper insulation can be seen as a must, rather than an option. This is due to their advantages, such as being environmentally friendly (no oil leakage and partially or totally recyclable), lower maintenance costs, higher maximum service temperature, and simpler cable jointing [
18,
19,
20,
21,
22].
This paper focuses on key features for HVDC (and MVDC) cable system sustainability and ROI, from design to condition maintenance.
Section 2 deals with life modeling, able to provide a fundamental tool for an effective design even when voltage transients can be foreseen during cable operation (as energization and voltage polarity inversion). The model can account for extrinsic aging phenomena, which are deleterious for insulation reliability, such as partial discharges (PDs).
Section 3 unravels a hidden issue for long-term cable reliability that is posed by variation with time under stress (operation) of a key property for DC insulation, i.e., conductivity. Since under DC the electric field distribution is driven by conductivity, if this quantity varies with aging and non-uniformly along insulation volume, the electric field profile can also change, determining increased risks of intrinsic and extrinsic accelerated aging.
Section 4 introduces the concept of PD-free design, using an innovative procedure that allows the inception voltage of PDs, both in internal defects and on insulation surfaces/interfaces, to be estimated. According to the so-called three-leg approach, cable design can account for intrinsic aging, evaluating and minimizing the risk of extrinsic PD aging, even when conductivity variations are expected to affect both intrinsic and extrinsic life.
Section 5 faces the aspect of insulating materials, from the use of thermoplastics, which are fully recyclable and feature a long life cycle, to that of nano–micro filling to improve cable endurance even when PDs may incept and occur steadily or intermittently. The concept of reliability redundancy, at least for cable accessories, is introduced.
Eventually,
Section 6 addresses the fundamental point of cable health condition evaluation and the diagnostic quantities that can be monitored during cable operation in order to carry out effective maintenance plans. In the case of PD-based diagnostics and condition maintenance, it is essential not only to measure signals corresponding to PDs but also to identify the type of defect that has generated the PD [
23,
24,
25]. Diagnostic studies, which include a series of assessments ranging from residual life estimation to health condition or health index, can be effective following the proper identification of the typology of the PD source. Considering these aspects, a new definition of dynamic health index, DHI, is discussed, with a derivation focusing on PD-associated markers as diagnostic quantities. An application on accelerated cable aging under PDs is shown.
2. Dependence of Life on Voltage and Current Transients
Power flow direction can be managed by inverting voltage polarity with line commutated converters (LCC) or reversing the direction of the current with voltage source converters (VSC). In the case of LCC, the insulation system is subjected to slow voltage transients at energization and at voltage polarity inversion, while the latter are absent cables fed by VSC.
Each voltage transient changes electric field distribution in insulation, from conductivity (DC steady state) to permittivity driven, during transients. At the beginning of each energization or voltage polarity inversion, the electric field profile can therefore differ considerably from that in steady state, on which cable design is generally based. This electric field variation can last hours or days, depending on insulating material characteristics and insulation volume, being the time constant,
, of the electric field transient (response to an ideal step voltage),
where
rs,
req, and
ceq are the equivalent circuit parameters depending on insulation system volume/surface and material characteristics (such as surface conductivity
σs, bulk conductivity
σb, and absolute permittivity
ε0εrb). Specifically,
is the insulation surface layer resistance,
and
are the equivalent resistance and capacitance values for bulk insulation (or the combination of the bulk layer of insulation and cavity in the case of internal discharges) [
17]. Calculations show that, as mentioned above,
can go from hundreds of seconds for surface insulation to many hours for internal cavities.
As shown in the literature [
17], partial discharges generally incept under AC at a lower voltage than in DC; that is, the partial discharge inception voltage in AC, PDIV
AC < PDIV
DC. Therefore, even for a DC insulation system that is PD-free at nominal voltage, partial discharges can be incept during energization and voltage polarity inversion, with magnitude and repetition rate that increase with voltage slew rate [
17].
Such behavior must be taken into account when designing insulation systems that are fed by LLC or VSC.
Life specs in cable design are met using, mostly, the inverse power model at constant electrical and thermal stress [
26,
27,
28],
where
E is the electrical stress (maximum field),
n is the so-called voltage endurance coefficient (VEC),
is the reference electric field, and
is the corresponding life. Equation (2) provides a straight lifeline in a log-log plot, whose inverse slope is
n. Parameter values depend on temperature, and, in general, their values at maximum operating temperature are chosen for design (conservative approach). To establish an electrical stress life model, two parameters are required, i.e., n and (
ER and
tR), which is a point of the lifeline (generally corresponding to high-stress aging). Accelerated life tests are carried out to estimate model parameters for a given cable material and design, and extrapolation of the lifeline is used, at specified failure probability, to estimate the maximum design field corresponding to the specified life (e.g., 30 years).
It must be remembered that Equation (2) is generally used for intrinsic aging, that is, the type of aging that occurs globally in an insulation system and determines insulation design parameters (
ED,
LD, i.e., design field and life). However, it also works in the presence of extrinsic aging, as that occurs under PDs. In the latter case, in general, the voltage endurance coefficient
n and reference life point (
ER, tR) are lower than for intrinsic aging (as shown later in
Table 1).
In order to take into account voltage transients, thus a time dependence of electrical stress, an expression accounting for the superposition of DC and energization/voltage polarity inversion (based on the superposition effect, thus of the Miner law [
29]) is as follows:
where
is part of the lifetime during which aging occurs under constant DC stress and
is the relevant life;
is, likewise, operating time under-voltage transients and
life under permanent transients.
and
are provided by Equation (2) as follows:
where
,
and and
and
are reference fields and relevant lifetimes considering the life model with DC and AC parameters, respectively. The underlying assumption is that during voltage transients, since the electric field is driven by permittivity and it is time variable, failure time obeys the same life law as for AC sinusoidal, thus subscript
t could be replaced by
AC.
and
, or
, correspond to the voltage endurance coefficient in DC and AC, respectively, where suffix
x indicates (as for
ER and
tR) the absence or presence of PDs during that specific portion of life. Hence, the general model can feature
and
when PDs are absent,
and
when PDs are present, or a combination of them. The same holds for
ERDC and tRDC and
ERDC and tRDC.
The total life, accounting for DC regime and transients, is given by the following:
is unknown, since it depends on the number of expected voltage transients during life. Having preliminary information at the design stage of the expected transient rate,
, besides the transient duration,
,
t2 can be expressed as follows:
and
in Equation (4) becomes the following:
Coefficient h in Equation (7) can be taken, in general, <1 because the main contribution of transients to life reduction (with and without PDs) occurs in the first part of them, where is larger; thus, it could be assumed, e.g., that 0.1 < h < 0.5 (depending on transient slew rate). For the cases shown, h was considered as 0.1.
Examples of the effect of field transients on life reduction for DC cable in relation to the specified life (30 years at failure probability 1%), obtained by applying Model (4), are shown in
Figure 1 and
Figure 2. Model parameters are summarized in
Table 1. They include the cable design field,
ED, obtained from Model (2) with
L =
LD, i.e., specified life.
Figure 1 addresses the case of a cable supplied in DC in steady state without PDs (intrinsic aging) and subjected to voltage transients (energization or voltage polarity inversion) with PDs (extrinsic aging due to PDs). The curves represent the decrease in life, compared to specification, when transient rate per day (
) and field time constant,
, increase.
Figure 2 refers to the same case as
Figure 1, but when PDs also occur in the DC steady state. As can be seen, life can decrease considerably in the presence of PDs, both in transient and in steady state, with reference to design specifications, as the number of transients per day and the electric field time constant increase. For example, life drops down to 7.5 years at a probability of 1% (from 30 years) when PDs are present in a steady state and very few voltage transients occur, but it will further drop to 3 years for 1 transient/day and a time constant of 100 min.
The risk of triggering extrinsic aging during transients and/or in a steady state can be predicted based on AC and DC PDIV measurements on cable models or estimation, as described in the next section. If PDIV values under AC (relevant to transients) or DC (steady state) are lower than cable nominal voltage, actions shall be taken at the design stage to match specifications. They can include changing the design (of cable and accessories, e.g., increasing insulation thickness and reducing electric field at accessory interfaces), materials (PD-resistant materials, see
Section 5), and using life model (Equation (4)) to reach the expected life and reliability even if, and when, PD might be present under cable operation (depending on transient rate and duration).
3. Insulation Aging Impact on Conductivity and Cable Field Distribution
Since electric field distribution in DC insulation is driven by conductivity, and maximum field in cable insulation must be lower than design field
ED determined by life modeling, knowledge of conductivity dependence on electric field and temperature is a key point for correct cable design. An approximate expression of such dependence is given by [
23] the following:
where
and
are the temperature and electric field coefficients and
is the reference volume conductivity (theoretically at
and
).
Contrarily to AC (where the field is driven by permittivity which has negligible dependence on field and temperature), significant variations in electric field profile along insulation thickness with cable load (i.e., temperature gradient) are expected in DC [
30,
31,
32], which may impact on the intrinsic aging rate and on extrinsic aging (due to PD inception) [
33]. This can be taken into account at the design stage including a time variation in electrical stress (field)
E in model (4).
An expression, based on the superposition effect and Equation (2), that considers stress time variation as the approximated summation for the stress-time convolution integral, is as follows:
where the first summation (from left) relates to the types of stresses, e.g., electrical and thermal
, (thus to each relevant life model,
), the second to their time variation (
,
), being
the number of stress typologies and
the discretized time-variation in stress magnitude
. This can account also for the type of supply voltage as regards electrical stress, e.g., AC sinusoidal, DC, transient DC (Equation (4)), thus including the presence of PDs.
However, since aging mechanisms and their rate for HV and MV DC cables are not fully known, design should also take into account the possibility that insulation properties/parameters may vary with cable operation and aging, which could have a non-negligible impact on cable system reliability. Considering that electric field distribution, which drives intrinsic and extrinsic aging, depends significantly on conductivity, Equation (8), this becomes the main insulation property that should be watched carefully as a function of cable aging. Indeed, if conductivity value and its dependence on temperature and field would vary with aging time, unpredicted values of the maximum electric field in insulation, viz at interfaces, on cable surface and at bulk defects, may be generated, which could increase the intrinsic aging rate and cause inception of PDs at nominal voltage. Cable life and reliability could not, therefore, be achieved anymore.
As shown in reference [
33], conductivity measurements performed at various electric fields and temperatures on specimens cut from HVDC polymeric cable laboratory-aged for 1 year, indicated clearly that conductivity can display large variations with time under stress (operation time). An example is shown in
Figure 3, where the quasi-steady state value (that used to provide the conductivity value) varies around 3 times from unaged and aged specimens.
The consequence can involve both intrinsic and extrinsic aging. As regards the former, it might occur that, due to inhomogeneous variation in conductivity along cable thickness (see
Figure 4), the electric field distribution in aged cable insulation differs from that for unaged cable, which was used for the design. If the maximum field would increase in the aged cable, as shown in
Figure 5 which is relevant to the same aged cable of
Figure 3, considering full load and, hence, a temperature gradient of 30 °C (from 95 °C on the conductor to 65° on the outer semiconductor), life can be reduced, according to Models (2) or (4). As an example, considering the maximum field of
Figure 5, constant with time, and based on Equation (2) referred to the maximum field, life would diminish considerably due to the increase in the maximum field caused by conductivity variation with aging, as obtained from the lab accelerated life test. Using Equation (2) with model parameters provided by
Table 1, life could decrease to an extent that can go up to ≈60% compared to design life. These, however, are just qualitative numbers, based on the assumptions that the value of a maximum field of
Figure 5 is applied from the beginning of cable operation (while it increases progressively with aging) and that life is associated with the maximum field (even in the presence of a field gradient as in
Figure 5). Even if a more complex life model than (2) should be used to consider the progressive variation in the maximum field with time (e.g., a general model as (9)), this result indicates that the intrinsic aging rate can increase with time under operation, due to conductivity inhomogeneous variation in insulation bulk. This could cause noticeable life reduction with respect to specifications.
As regards extrinsic aging, that is, partial discharges, since they are promoted by electric fields it is evident that electric field variation with aging can impact the voltage at which PDs incept, i.e., PDIV, for both bulk defects (cavities generating internal discharges) and surface triple points/interfaces (as at accessories). Recently, a deterministic PD inception model, valid for both internal and surface discharges, has been proposed and validated for different insulation systems under AC and DC supply (see, e.g., references [
34,
35]). It can be written as follows:
where PDIE is the inception field,
is the critical reduced field,
is pressure,
and
are known parameters related to discharge physics, and
is a scale factor that localizes PD inception probability around the volume/surface where the electric field is maximum (e.g., triple points).
can be calculated from the field profile at the defect location (
for internal defects and uniform surface field distribution). Hence, the only unknown parameter in Equation (10) is
l, that is, the distance from the triple point on the surface (between the HV and ground electrode) or cavity height. Notably, parameter values change for internal or surface discharges. The parameter values in Equation (10) are known for both surface and internal discharges, having been estimated empirically by a wealth of experiments performed on insulation systems with artificial defects of different shapes and locations. The voltage at which the inception field calculated by Equation (10) matches the value of the maximum electric field in the defect is the partial discharge inception voltage, PDIV.
Devising a type of defect, its size and location, in any insulation system (such as DC cables dealt with here), calculating the electric field, and matching with Equation (10) would allow mean PDIV estimation for both internal and surface insulation sub-systems to be achieved. As an example,
Figure 6 displays estimated values of PDIV
DC for cables having the same geometry as that simulated for intrinsic aging evaluation, with a cavity of radius
placed near the inner semiconductor (1 mm far) and in the middle of insulation. The full-load condition is considered the same as in
Figure 5. As can be seen, the PDIV
DC of aged specimens is lower than those of unaged, particularly when the cavity is in the middle of the insulation. This may indicate that in the presence of manufacturing or structural defects, an initially PD-free design can turn into an operation mode that is affected by PDs, likely depending on load conditions. For instance, a cable with a
conductor and 16 mm insulation thickness has PDIV
DC = 174 kV when unaged (with a defect located in the central part of insulation thickness and full load), while PDIV
DC = 134 kV is the expected value after the accelerated aging causing the conductivity variation discussed above. Similar results are obtained by considering interfaces and surface defects.
The message here is that when counting on a PD-free insulation system for all operating life, the possible conductivity evolution with aging must be evaluated and properly taken into account. The other takeaway is that since such conductivity increase with aging is likely caused by diffusion of contaminants from semiconductors, care should be taken in the HVDC selection of semiconductive materials. The aspect of PD-free design is developed in the next section.
4. Extrinsic Aging-Free Cable Design
While intrinsic aging can be accounted for by appropriate modeling in order to provide the specified life and reliability, the risk of extrinsic aging could be minimized at the design stage knowing the impact of bulk defects and surface insulation triple points on PDIV. The PD inception field and voltage model is now available, Equation (10), and it can be used in the so-called “three-leg approach” framework holding for any type of voltage and insulation system. This approach is valid for both AC and DC systems, and it is based on three steps (the “legs”), which are as follows:
Electric field simulation of the insulation system/object under study;
Modeling of the PD inception field and voltage, PDIE and PDIV, respectively;
Perform PD measurements to validate the results predicted by leg 2.
Legs 1 and 2 were, in practice, mentioned above when defining the PD inception model (10), i.e., leg 2, and the need to calculate the electric field distribution at the defect, leg 1, in order to estimate the PDIV. Leg 3 is, indeed, validation of the PDIV estimate by PD detection and analytics, which must be able to identify the type of defect-generating PDs (a crucial point for the sake of proper design and condition maintenance) [
35].
Figure 7 shows examples of PDIV
DC estimation for a DC cable with surface and internal defects, as mentioned above and described in [
35]. The mean measured values are also reported, showing the good capabilities of the three-leg approach to predict PDIV under DC supply (actually, the accuracy under sinusoidal AC and modulated has been verified).
Through this innovative approach, any type of internal defect (e.g., cavities that can be too small to be detected by other quality control tools like RX, or butt gaps in laminated DC cables, interfaces, joint field deflectors, etc.) can be simulated, and the relevant expected PDIV calculated so that the final design would be PD-free. To account for conductivity variation, the electric field distribution (leg 1) must be calculated on the basis of the estimated conductivity variations and in the worst conditions for temperature gradient (load).
5. Materials
Cable insulating materials have been transitioning from oil-impregnated paper to polymeric tapes, mixed polymeric-paper tapes, and extruded polymers. Polymers are, typically, HDPE or XLPE (high-density or cross-linked polyethylene) and, recently, thermoplastic polypropylene, PP [
36], the latter displaying the interesting sustainability feature of a long life cycle.
New types of polymeric materials are being developed, and some of those made available commercially contain micron or nano inorganic fillers [
37]. Since partial discharges damage insulating material through polymer chain bond breakdown, with energies up to 100 eV [
38], inorganic particles cannot be attached by PDs, having larger bond energy. This delays the PD aging rate or, in other words, will increase the
nDCPD to values close to those related to intrinsic aging (
nDC in
Table 1). Commercially, these new materials were named “corona resistant” because improperly PDs were confused with corona discharges. More appropriately, they should be defined as PD-resistant materials.
Figure 8 displays the results of accelerated life tests performed on commercially available PD (or corona) resistant polyimide, i.e., Kapton CR, compared with the same material free of microfilters (Kapton NCR). Electrical lifelines, at a failure probability of 1%, are reported and obtained upon applying model (2) by least square regression fitting (those lines that, properly extrapolated, would provide the design field). As can be seen, the slope (inversely proportional to
n) of the lifeline with and without PDs is almost the same for Kapton CR, but much lower when PDs are continuously present for Kapton NCR.
If using CR material for a whole HVDC cable insulation might be too expensive and needless (bulk defects are generally uncommon) and since most failures occur in accessories, thinking of manufacturing joints and terminations with PD-resistant materials can be a significant upgrade for delivering the specified life and reliability.
Relying upon such innovative materials, a new concept for insulation system design can be introduced, i.e., that of reliability redundancy.
The concept of reliability redundancy is quite simple. It can occur that real stresses in service could be larger than those considered for design, that electrothermal and mechanical aging change insulating material characteristic values (as for conductivity), as well as create or grow defects (at interfaces). Eventually, environmental changes can occur during operation, and there is always the risk that the on-field assembly of cable accessories is flawed. All of this can cause unexpected, or not-controllable, extrinsic accelerated aging, as provided by PD inception, failing life specification. Here is where the PD-resistant materials can help. Using insulating materials that have a large value of n, even if PDs are permanently or sporadically active (nPD), the design is more robust in terms of extrinsic aging endurance, thus providing additional reliability or reliability redundancy. Indeed, specifications can be fulfilled even if PDs are permanently or sporadically active, while in the absence of PDs during service life, the design will result in being conservative; thus, life will be even longer than specs (or reliability larger).
6. Diagnostics and Health Condition Evaluation
Extrinsic aging in DC cables has a much slower rate than under AC, since the PD repetition rate in DC is generally much smaller than in AC [
17,
23], and the magnitude can be slightly higher or equivalent. Indeed, the PD global damage is proportional to the product magnitude per repetition rate, such as the following:
where
is damage density per unit time,
/
and
mean repetition rate and amplitude, in relative value,
is a coefficient accounting for probability and effectiveness that an electron involved in a PD with a certain amplitude exceeding an energy level, e.g., 8 eV for most polyolefins, and causing permanent and irreversible degradation (for Polyethylene
≈ 0.02, according to [
38]). As an example, from PD measurements performed on a model cable with an internal defect as in
Figure 7,
= 0.2 in DC and 89.6 in AC.
Therefore, while for HVAC cables the presence of PD, if internal, calls for immediate maintenance, under DC PDs can be withstood for a longer time. This is highlighted by
Figure 2, where life drops to 7.5 years, from 30, when DC PDs are permanently occurring under service, while in AC, at the same maximum field, life would drop to 115 h, based on
nACPD,
ERACPD, and
tRACPD values of
Table 1.
As regards MV, oil–paper insulation and polymeric cables can last a significant time before failure in the presence of some internal discharges of limited amount, and for even large surface discharges, both in DC and AC. In addition, the large number of MV asset components and the cost of maintaining or replacing them when PDs appear suggest that maintenance actions must be planned based on real cable health conditions and failure risk. Any action could be taken, then, only when strictly needed, possibly avoiding catastrophic failures, reaching an optimum condition for ROI, and associated cable asset sustainability.
As a consequence, both HV and MV DC cable typologies would benefit from condition maintenance based on health index algorithms, which will allow maintenance costs to be minimized while increasing ROI and operation costs, and decreasing environmental risk.
A general definition of dynamic health index (DHI) was developed, e.g., in reference [
39]. The main difference compared to other contributions in the literature (e.g., references [
40,
41]) is that the logic OR condition in the buildup of the HI algorithm replaces the logic AND in order to attribute more importance (weight) to the extrinsic aging effect of PD occurrence and variation as regards health condition worsening. As an example, if a cable has significant internal PD activity, but other markers such as insulation temperature, sheath current, dissipation factor, etc., are good, cable condition would be seen as satisfactory (high health index) through AND logic, while maintenance would be required likely very fast (as portrayed by the new DHI). In summary, an expression for DHI evolution with time is given by the following:
where
is the reliability of each subcomponent
i, given by the following:
and are the maximum and minimum score (magnitude) values for the diagnostic marker j, for the subcomponent , and takes into account the weight of such marker on the aging rate (higher weight means that the property diagnoses a stronger aging mechanism). The significance of a specific aging mechanism is defined as a combination of a diagnostic marker magnitude, or score, Si,j,k (e.g., PD amplitude or repetition rate) and its weight, Wi,j,k (related to the type of defect, in the case of PDs). The latter expresses the harmfulness of the degradation process associated with the diagnostic quantity.
Equations (12)–(14) hold for any type of diagnostic quantity (and voltage waveshape), and (12) can include other information that can be useful to define a global DHI, such as results of previous forensic inspections, history of previous failures/outages, and environmental conditions [
39].
If PDs are the only diagnostic quantity,
j = 1, and considering one sub-system, i.e., i = 1, only one component is present in (13), (14). Since the main factors associated with PDs as a diagnostic quantity are amplitude
A, repetition rate
RR, and the PD typology (i.e., whether internal or surface type of discharge, the former being more harmful than the latter, at the same amplitude and repetition rate), a new score algorithm was proposed [
42], that is the following:
where
signs are the sign of the quantity vs. time slope, that is, =1 if increasing, =−1 if decreasing.
is a reference PD amplitude, and
is a reference repetition rate.
is the likelihood percentage provided by the identification of the PD typology (through an approach to PD analytics as that described in [
35]), being
k = 1, 2, that is,
P1 = likelihood of surface,
P2 = likelihood of internal. Weight can be expressed by the following:
The final expression of DHI, referring to PDs as monitored diagnostic properties, becomes, from Equation (12), the following:
Figure 9 and
Figure 10 show a case of accelerated aging of DC cable with surface discharges, where PD monitoring is carried out online till breakdown. As can be seen from
Figure 9, PD amplitude,
A, and repetition rate,
RR, vary in a non-monotone way with time under stress. As often occurs, PD magnitude does not increase with aging even before breakdown (in this case, however, the repetition rate grows constantly, but sometimes even this quantity has no clear trend). Such behavior would not support the use of PDs as a diagnostic quantity, referring only to magnitude,
A, or
RR. However, using the
DHI algorithm of Equation (17),
Figure 10 is obtained.
DHI decreases with time under stress, whatever the time trend of PDs and repetition rate, which means that it can constitute a valid diagnostic marker. Extrapolating the
DHI trend and establishing endpoints, maintenance times can be automatically selected. As an example,
Figure 10 highlights three zones: green (no action) for
DHI down to 75%, yellow (action to be planned) for 0.75 ≤
DHI < 0.25, and maintenance to be executed as soon as possible for
DHI ≤ 0.25.
This can be the basis for a thorough condition assessment and maintenance approach for DC cables, which can be extended to any quantity that can have relations with aging and cable reliability. Planning maintenance before failures and relevant outages would be beneficial for a sustainable, reliable, and safe approach to DC cable management.
7. Conclusions
The main purpose of this paper was to provide a picture of potential issues and remedies for proper design and maintenance of HV (and MV) DC cables, focusing on polymeric insulation and in light of better sustainability of cable asset investment. Oil–paper insulation is considered, indeed, to have higher reliability, but the risk, in case of failure, of fire and fluid oil spilling does not make them environmentally friendly and sustainable.
It is shown that innovative life modeling, accounting for both extrinsic and intrinsic aging, design, based on the three-leg approach, and diagnostics, where a global health condition index has been developed, can likely increase confidence in this new, and yet unavoidable, technology. Indeed, HV and MV polymeric DC cables will be key players in renewable generation and T&D, as well as in electrified transportation.
This DHI methodology can possibly be implemented in large-scale HVDC networks, as well as in critical MV links and networks. It requires effective online diagnostic monitoring and AI-based predictive analytic techniques able to provide automated alerts, which can potentially enable grid operators to prioritize maintenance action accordingly.
Having the possibility to plan maintenance effectively before major damages to cable systems impacting the environment, human safety, and energy service quality is a must for the sustainability of this technology. In addition, this would contribute to reducing management costs that will reflect on energy prices and, globally, on improving ROI.
The views expressed are those of the author and do not reflect the official policy or position of the Department of Defense or the U.S. Government.