Next Article in Journal
Framework Conditions and Strategies for Pop-Up Environments in Urban Planning
Next Article in Special Issue
Configurations of Aromatic Networks for Power Distribution System
Previous Article in Journal
Pastoral Population Growth and Land Use Policy Has Significantly Impacted Livestock Structure in Inner Mongolia—A Case Study in the Xilinhot Region
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Fault Classifications in Distribution Systems Consisting of Wind Power as Distributed Generation Using Discrete Wavelet Transforms

by
Theerasak Patcharoen
1 and
Atthapol Ngaopitakkul
2,*
1
Faculty of Industrial Technology, Rajabhat Rajanagarindra University, Chachoengsao 24000, Thailand
2
Faculty of Engineering, King Mongkut’s Institute of Technology Ladkrabang, Bangkok 10520, Thailand
*
Author to whom correspondence should be addressed.
Sustainability 2019, 11(24), 7209; https://doi.org/10.3390/su11247209
Submission received: 21 October 2019 / Revised: 10 December 2019 / Accepted: 11 December 2019 / Published: 16 December 2019
(This article belongs to the Special Issue Smart Energy Grid for Sustainable Cities and Societies)

Abstract

:
This paper proposed a fault type classification algorithm in a distribution system consisting of multiple distributed generations (DGs). The study also discussed the changing of signal characteristics in the distribution system with DGs during the occurrence of different fault types. Discrete Wavelet Transform (DWT)-based signal processing has been used to construct a classification algorithm and a decision tree to classify fault types. The input data for the algorithm is extracted from the three-phase current signal under normal conditions and during fault occurrence. These signals are recorded from the substation, load, and DG bus. The performance of the proposed classifying algorithm has been tested on a simulation system that was modeled after part of Thailand’s 22 kV distribution system, with a 2-MW wind power generation as the DG, connected to the distribution line by PSCAD software. The parameters that were taken into consideration consisted of the fault type, location of the fault, location of DG(s), and the number of DGs, to evaluate the performance of the proposed algorithm under various conditions. The result of the simulation indicated significant changes in current signal characteristics when installing DGs. In addition, the proposed algorithm has achieved a satisfactory accuracy in terms of identifying and classifying fault types when applied to a distribution system with multiple DGs.

1. Introduction

Energy consumption has become a major issue for many governments around the globe in recent decades. The reason for this is limited energy resources in some countries and concern for environmental problems caused by the burning of fossil fuels. This has resulted in the implementation of a new policy that tries to reduce the usage of fossil fuels at every level and research forms of renewable energy. Thus, renewable energy has become a significant topic that has gained much attention from researchers and policymakers. Renewable energy is a natural energy resource that can be replenished over time and exists over a broad geographic location, such as solar, wind, geothermal, hydropower, biomass, and biofuels. It can be used as an alternative energy source to generate electricity, instead of fossil fuels, that is limited to specific regions and depleted over time. Distributed Generation (DG) is a term used to describe the technologies that generate electricity from a renewable energy source at or near the point of use, according to the definition by the International Energy Agency [1]. This type of generation can change the nature of power systems from centralized generation (CG), with a large-scale power plant located at an energy source transmitting power over a long distance to the customer, to distributed generation (DG), that consists of small-scale power generation using renewable energy sources located at the customer level [2].
The rapid rise in the penetration level of DGs in the distribution system can provide a positive benefit in terms of the environment and accessibility to the electrical market for small-scale providers and customers. However, this trend changes the character of the distribution system and affects the performance of the conventional protection system, which designs with the assumption of a specific load–flow direction. The connection of DGs to the distribution system can affect electrical characteristics such as voltage, current, and power during normal conditions and fault occurrence. The reason for this is that, during fault occurrence, DGs can still generate power and feed current into the fault location, resulting in a significant rise in the load current [3]. In addition, DGs that are integrated into a system can affect the electrical grid in other aspects, such as fault contribution, power quality, voltage level, and grid protection [4,5]. This shows that the presence of DGs has a significant impact on the distribution system characteristic during fault occurrence, therefore, a conventional protection scheme might not be adequate to detect and classify faults on the distribution line. Thus, a new approach for the protection system under these changing conditions must be developed, to deal with the new circumstances in distribution systems with DGs [6]. These new approaches need to provide the operator with a quick and accurate response to the abnormal condition, in order to maintain the desired level of reliability in the power system.
Therefore, this paper proposes a fault type classification algorithm based on DWT in a distribution system with multiple DGs. The performance of the proposed algorithm evaluates a distribution system consisting of DGs, that is modeled after part of Thailand’s distribution system using PSCAD software. The wavelet-based signal analysis has been used to process the current signals during the steady-state (normal condition) and transient state (fault condition). The obtained result, in terms of coefficient values, is used to construct a suitable decision tree for fault type classification. The various parameters that affect the performance of the proposed algorithm will be taken into consideration, such as fault types, fault location, DG location and number of DGs, and the result will be described in terms of classification accuracy.
This paper consists of six sections, as follows. Section 3 discusses the distribution system used in the case study, including a diagram of the distribution system and wind power generation from PSCAD software. Section 4 presents the characteristics of the distribution system under fault conditions compared to the normal conditions in cases with and without DGs connected. Section 5 proposes a DWT-based fault type classification algorithm and presents a decision tree. Section 6 shows the results of the applied proposed algorithm on the case study modeled after an actual system located in Thailand under different fault conditions. Finally, the conclusion in Section 7 will summarize the results of the proposed algorithm and discuss its performance.

2. Literature Review

A literature review on the effects of DG, especially wind power generation, on system characteristics under fault conditions, has been carried out [7,8,9,10,11]. The characteristics of the current signals in the system under fault conditions are significantly changed when installing the DG into the system [7]. Wind power generation significantly affects the protection system, causing fault levels, thermal limits of fault currents, failure of reclosing, unnecessary disconnection of a healthy feeder, and prevention of feeder protection operation, as has been discussed [8]. The case study on planning wind power generation in networks with the framework that included feeder reconfiguration and voltage control has been presented [9]. The proposed interconnection planning used binary particle swarm optimization (BPSO) methodology to optimize grid operation to accommodate the increased network DG capacity. Condition monitoring and fault diagnosis in wind turbines, using the HET-P system and Internet-based remote monitoring, was proposed in order to increase the reliability of the system with a DG connection [10]. In [11], the research proposed that faults in the system consist of Doubly fed induction generator (DFIG) wind turbines, due to a new requirement of the grid code. A smart grid system with a high level of renewable energy penetration, especially wind farms, requires accurate and rapid fault location algorithms in order to prevent the tripping of out of wind power generators [12]. These researches have demonstrated a significant change in various aspects of system characteristics in the distribution system with wind power generation as a DG, in both normal conditions and fault states.
Fault diagnosis in the distribution system with DGs is also a crucial requirement for an operator to respond to fault situations quickly and accurately, in order to maintain the reliability of the power system. A literature review in the field of the fault-classification algorithms that have been developed in the past has been performed in this research [13,14,15,16,17,18,19]. The approach towards fault classification in the distribution system consists of DFIG-based wind power generation, which has been previously proposed. The algorithm used a waveshape recognition technique to identify waveshape attributes of the DFIG fault current and classify which fault types currently occur in the system [13]. The fault classification using a power-spectrum theorem, based on information from wide-area measurement systems (WAMS), has shown the ability to classify fault types accurately, especially in multiple terminal transmission systems [14]. The synchronized voltage and current measurement data from both ends of the transmission line have been used for fault detection and classification algorithm [15,16]. The results from the simulation in the case study system have shown a satisfying level of accuracy using only small time windows from captured waveforms, in order to reduce the need for further data. Further research using the monitoring data to classify faults have shown similar accuracy in fault classification in the transmission system [17]. The impedance-based algorithm is another methodology that has been used in fault diagnosis. The evaluation achieved the desired performance when tested on the series capacitor-compensated transmission lines [18,19]. In [20], the decision-tree methodology with a half-cycle discrete Fourier transform was proposed. Testing on double-circuit transmission lines achieved 100% accuracy. However, this methodology was only tested on the conventional transmission line, and the performance cannot be guaranteed to be the same on a system with DG. For the smart grid with interconnected substation and distribution generation, fault detection and classification can be performed using a synchronized three-phase current signal, obtained from the protective relay [21].
Wavelet transform is another signal analysis methodology, similar to Fourier transform. It was suitable for analyzing signals in a transient state, due to its ability to represent both the time and frequency domains [22,23]. Due to this advantage, the wavelet transform has been widely applied to analyze transient states in the power system, including fault analysis in distribution and transmission systems [24,25]. The application of wavelet-based fault diagnosis is discussed in P. Rajaraman et al.’s paper. Discrete Wavelet Transform (DWT) and multi-resolution analysis (MRA) were used to decomposed signals in order to obtain the coefficients of the fault signal. The study evaluates the performance of the Daubechies (db4) mother wavelet, which is a suitable mother wavelet for fault analysis [26]. It can be seen that the wavelet transform has been widely applied in transient analyses, especially in cases of a fault in the power system. The research by A. R. Adly has proposed the fault identification algorithm using wavelet transform and current measurement from only one end of the transmission line [27]. In [28], the fault classification on a transmission line using DWT was proposed. The performance of wavelet-based fault detection is evaluated on the 282-bus radial distribution system. The algorithm can detect, classify, and locate faults with satisfying results [29]. The combined methodology of DWT and traveling waves has also been used to improve the accuracy of the fault detection and analysis algorithm [30,31].
The application of artificial intelligence to wavelet transformations has been recently developed to improve the accuracy of the algorithm. Wavelet transform and artificial neural network (ANN)-based algorithm performance has been tested and evaluated in the Ungrounded Photovoltaic System [32]. Another ANN-based methodology on fault detection algorithms was tested on an ultrafast transmission line [33]. The fault classification in series-compensated transmission lines using norm entropy values, that have advantages in terms of reducing training time in a neural network, was presented [34]. The wavelet transforms and MRA have been used in an extra-high voltage line for real-time fault analysis, as the performance of an algorithm in this system is independent of fault impedance and fault angle [35]. Another case study on the multi-terminal transmission system also showed a similar result terms of accuracy of fault location [36]. These applications of the wavelet-based algorithm and artificial intelligence for fault classification have shown a satisfactory result with potential for application in the protection system. However, many case studies have been tested using the conventional system, without considering the effect of DGs.
The comparison between the proposed methodology in this study and the existing methodologies, in terms of performance in fault classification, is shown in Table 1. From Table 1, it can be seen that other methodologies were only tested on conventional distribution systems without considering factors such as the location and number of DGs in the algorithm, which has a significant impact on the performance of the algorithm, due to its effect on system characteristics. Thus, the fault-classification algorithm may be less efficient when applied to different systems with multiple DGs. However, the proposed algorithm can achieve the best performance in terms of accuracy in classifying fault types.

3. Distribution System

The distribution system used in the study is modeled after part of the 22 kV distribution system connected with wind power generation located in the northern part of Thailand. The simulation is performed using PSCAD software to simulate the characteristics of the distribution system with wind power generation as a DG under both normal conditions and different fault-type occurrences. The simplified diagram of the distribution system under study and the diagram of simulation in the PSCAD software counterpart are shown in Figure 1 and Figure 2, respectively. The case study distribution system consists of a 30 km 22 kV distribution line connected between substation and the load center. The two units of 2 MW wind power generation are connected to the distribution line between the substation and load center. In order to emphasize the effect of the DG on system characteristics, the location and number of DGs will vary along the distribution to create different case studies. Parameter data, such as three-phase voltage, current and power, are obtained from the data recorder located on the substation bus, load bus, and DG bus for further analysis.
The diagram of the 2 MW wind power generator, used in this simulation as a DG in the PSCAD software, is shown in Figure 3. The main components of the system consist of a synchronous generator, AC exciter, wind turbine, governor, wind source, and Transformer. The operation of a wind turbine can be divided into two states. In the transient state, the wind turbine receives a wind speed averaging 13 m/s and a blade pitch angle from the wind governor. This angle is calculated from the loop feedback from the angular speed and the real power of the synchronous generator. The output from the turbine is provided to the synchronous generator and AC exciter for the generation of electrical power. When the system is in a steady state, the wind source can provide the average wind speed, to generate torque by itself. The wind power generation can generate active and reactive power and feed it through a 2 MVA 0.69 kV/22 kV power transformer before being connected to a distribution system.
The simulation of wind power generation used in this study has been carried out to verify the generating power and the correction of the electrical signal. In terms of power generated from the wind power generation in Figure 4, it can be seen that the power fluctuated in the first 3 s after the generator started operating. Then, the system entered the steady state, with a constant output of a 2 MW generating level at an average wind speed of 13 m/s. The result has shown the ability of the wind power generation used in this study as a DG, with a steady 2 MW power generation during the operation.

4. Fault Characteristics

The changing of distribution system characteristics in cases of integration with DGs can impact the performance of the protection system. Thus, this research has studied the impact of DGs on system characteristics, integrating different numbers of DGs with the system, using PSCAD software. The characteristics of the three-phase current signal in the substation, DG, and load bus have been recorded. The example of a current signal from the simulation, in cases of single-phase to a ground fault in phase A, occurs in the distribution system without a DG, with a single DG, and with two DGs. These are shown in Figure 5 and Figure 6, respectively.
The case of single-phase to ground fault in phase A occurs in a single distribution system. The three-phase current from the substation bus in cases of no DG, single DG, and two DGs are shown in Figure 5. It can be seen that, when a fault occurs in the system, the current in the fault phase measured on the substation bus is higher than the normal phase. After installing the single DG in the middle of a distribution line or at a 15 km distance, measured from the substation bus, the current signal from the substation bus is decreased compared to the previous case, due to the DG feeding the current into fault location. In addition, the current in the fault phase from the DG bus is slightly higher compared to the other phases. In the case of two DGs, connected at 3 and 27 km, measured from the substation bus, the results showed similarities in overall signal waveshape. However, the amplitude of the current signal was significantly changed, with the current signal from the substation bus decreasing. This result suggests that the DG injected power and current to the load and fault locations instead of the substation bus.
For the load bus, the three-phase currents from the substation bus in cases without DG, with a single DG, and with two DGs are shown in Figure 6. The current measured on the load bus is lower than under normal conditions, as the current is flowing from the substation bus into the fault location instead of the load bus. When installing the single DG in the middle of a distribution line or at a 15 km distance from the substation bus, the current signal is increased, as a result of the current signal generating from the DG flowing to both the fault location and the load bus. The level of change in amplitude depends on the location of the DG. The DG located near the substation bus will decrease the current amplitude in both the substation and the load bus. The DG located near the load bus will significantly increase the current amplitude on the load bus but reduce the current amplitude on the substation bus. In the case of two DGs, connected 3 and 27 km from the substation bus, the results showed similarities in overall signal waveshape. However, the amplitude of the current signal was significantly changed, with the current signal from the load bus increasing compared to the previous case. This result suggest the current signal generated from two DGs was fed to both the fault location and load bus.
The results from the simulated distribution system with and without DGs illustrate the changing system characteristics of the current signal under fault conditions. They reveal that, with DG installation, the amplitude of the current signal during fault occurrence increased significantly, and this can affect the operation of the conventional protection system. Thus, the proposed fault classification has considered these factors when designing the algorithm and decision tree.

5. Fault-Classification Algorithm

Different fault types occurred on distribution caused by different levels of change to voltage and current signal on the substation bus, load bus, and DG bus compared to normal conditions, according to the characteristic of each fault type. The proposed algorithm only used a current signal obtained from the substation, DG, and the load bus to classify fault types that occurred on the distribution line. Fault current signals with unique characters in each fault type were used to design a fault-classification algorithm. The obtained one-fourth cycle of the three-phase current signal during fault occurrence was analyzed using DWT to extract coefficient value during the transient state. Then, these values were compared with the DWT coefficient of the zero sequence component to create a parameter that determined the fault types in a decision tree. The parameters used in fault type classification have been normalized in the same wavelet scale, in order to simplify the analytical process. The parameters under consideration are listed as follows.

5.1. Maximum Parameter During Fault Occurrence

The proposed algorithm used the maximum coefficient from the DWT of the three-phase current signals during the one-fourth cycle when the distribution system was under the fault condition. The maximum parameter on each phase and zero sequence signal are described as follows:
A max is the maximum coefficient of the phase A component.
B max is the maximum coefficient of the phase B component.
C max is the maximum coefficient of the phase C component.
Z max is the maximum coefficient of the zero sequence component.

5.2. Comparison Parameter

The comparison parameter is used to determine the state of a fault condition in each phase. This parameter will be used as a reference line to detect the phase where the fault occurs when the value is higher than the comparison value. It can be calculated using the maximum coefficient of the component in each phase, divided by the zero sequence component. The comparison parameter on each phase is described as follows:
A c o m   =   A max Z max is the comparison parameter for fault detection in phase A.
B c o m   =   B max Z max is the comparison parameter for fault detection in phase B.
C c o m   =   C max Z max is the comparison parameter for fault detection in phase C.

5.3. Check Parameter

The check parameters are used to determine the fault types in the decision tree. These parameters are obtained from the maximum value of the comparison parameter. The check parameters are described in the following:
P h max is the maximum value from the comparison A c o m , B c o m , C c o m   .
P h min is the minimum value from the comparison A c o m , B c o m , C c o m   .
The fault-classification algorithm will compare the maximum and minimum check parameters to classify the three-phase fault first. After that, the algorithm will determine the phase where the fault occurs using a comparison parameter in each phase if the value is 1.5 times more than the minimum check parameter, or 0.9 times more than the maximum check parameter. For fault to ground, if the zero sequence component—after fault occurrence—is 5 times higher than the normal condition, and the maximum zero sequence component is higher than 10-12, it will indicate a fault to the ground signal. A simplified diagram of the decision tree used in the proposed algorithm is illustrated in Figure 7.
The example of the algorithm operation is illustrated in Figure 8 using the case of a three-phase fault that occurs in the distribution system with two DG. The fault types can be determined by using data only from one bus, but in order to recheck the correction of the fault types classification, the algorithm has been applied to the data obtained from substation bus, wind power generation no. 1, the no. 2 bus and the load bus as shown in Figure 8a–d. From the figure, the operation of the proposed fault classification is as follows: first, the current signal has been applied using DWT to extract a coefficient value on the same wavelet scale. The maximum coefficient value of the three-phase current signal and zero sequence signal are then used to calculate the comparison parameter. These values are the inputs of the decision tree for fault classification. As the example signal indicated, the maximum and minimum value from the comparison is less than 50. This resulted in the algorithm determining that the fault occurs in the distribution system, with two DGs in a three-phase fault. When applied to the data obtained from different buses, the algorithm showed the same result with a three-phase fault.

6. Simulation Results

The proposed fault-classification algorithm using DWT and the decision tree has evaluated the performance of the distribution system modeled after the actual system located in Thailand. The different parameters have been taken into consideration in order to test the performance under different conditions, to verify its ability to achieve the desired result in the actual application on the protection system. The case study consists of the number of DGs, the location of DG, fault location, and fault types, as summarized in Table 2. The number of DGs has been varied in order to illustrate the performance when the system was changing following the installation of DG. The location of DGs has been varied in the case of one DG near the substation bus, the middle of distribution line, and the load bus. In the two DG case, the location has been fixed near to the substation bus and near the load bus. The fault location and fault types have been varied in order to evaluate the performance under different fault conditions.

6.1. Distribution System without DG

The results in the case of the distribution system without DGs revealed the performance of the proposed fault-classification algorithm in terms of average accuracy. The average accuracy from the data obtained from the substation bus and load bus in the case without DGs is shown in Figure 9. It can be seen that the proposed fault classification can correctly classify all of the fault types with 100% accuracy under various system conditions. In terms of the system without DG, the proposed algorithm can perform according to the desired objective.

6.2. Distribution System with a Single DG

The result of the case of the distribution system with a single DG varied along the distribution line is illustrated in Figure 10, Figure 11 and Figure 12. In the case of the DG installed near a substation or 5 km away from the substation bus, the result of the proposed fault-classification algorithm in terms of average accuracy is shown in Figure 10. It can be seen from the result that the proposed algorithm can classify fault types with 100% average accuracy under all conditions. This result from the decision tree has taken the changing coefficient from the connection of the DG into consideration. Thus, the algorithm can clearly detect all the types of faults that occur in the system.
In the case of a single DG installed in the middle of the distribution line, or 15 km away from the substation bus, the result of the proposed fault-classification algorithm in terms of average accuracy is shown in Figure 11. The results reveal that the proposed algorithm can classify fault types with 100% average accuracy under different conditions similar to the previous case. When using data from the substation bus, DG bus, and load bus as inputs for the decision tree, it also achieved the 100% average accuracy.
For the case of a single DG installed near the load bus or 25 km away from substation bus, the result of the proposed fault-classification algorithm, in terms of average accuracy, shown in Figure 12 also shows a similar result as the previous two cases, with 100% fault-type accuracy. It was similarly accurate when using data from the substation bus, DG bus, and load bus. This demonstrates that the impact on a signal characteristic from the DG and its location does not affect the performance of the proposed fault-classification algorithm in terms of average accuracy.

6.3. Distribution System with Two DGs

In the case of two DGs installed on the distribution line at 5 and 25 km away from the substation bus, the results reveal that the proposed fault-classification algorithm can classify fault types with 100% average accuracy under the different conditions, as shown in Figure 13. This level of accuracy can also be achieved using the data from the substation, Dg unit 1, DG unit 2, and load bus. Even though the number of DGs was increased, the effect of the DGs on the signal characteristic did not impact the performance of the proposed algorithm.

7. Conclusions

This paper proposed a DWT-based algorithm and decision tree model for fault classification in a distribution system consisting of DG. This paper also studies the characteristics of the distribution system under fault conditions in cases with and without wind power generation as a DG. The results from the simulation and the character of the fault signals show that the DGs have a significant effect on the amplitude of the current signal of both the substation and load bus, depending on the number and location of DGs. This change can impact the performance of the conventional fault-classification algorithm that is normally installed in the protection system. Thus, the new approach to fault classification has been presented in the study. The proposed algorithm has demonstrated its accuracy in terms of fault types classification, and has consistently performed across all factors that take into consideration the average accuracy over 100%. Factors such as the number of DGs, location of DGs, location of the fault, and fault types do not affect the performance of the proposed algorithm. The algorithm can correctly identify fault types using different data from the substation, DG, or load bus, depending on the availability of the information. The result and methodology proposed in this research can be applied to improve the protective scheme of the distribution system with a rising level of DG penetration, in order to ensure the safety and reliable operation of the power system. Future work can develop a fault-classification algorithm based on the currently proposed methodology, in order to identify types of fault and implement such a system to actual protection systems.

Author Contributions

T.P.—conceptualization, formal analysis and design the experiment; A.N. performed the experiments, investigation and analyzed the data; A.N.—funding acquisition and contributed resources; T.P.—writing; A.N.—review and editing.

Funding

This research was funded by King Mongkut’s Institute of Technology Ladkrabang Research fund, Thailand grant number No.KREF025606.

Acknowledgments

The authors wish to gratefully acknowledge financial support for this research (No. KREF025606) from the King Mongkut’s Institute of Technology Ladkrabang Research fund, Thailand.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. IEA. Distributed Generation in Liberalised Electricity Markets; IEA: Paris, France, 2002. [Google Scholar]
  2. Mehigan, L.; Deane, J.P.; Gallachóir, B.P.Ó.; Bertsch, V. A review of the role of distributed generation (DG) in future electricity systems. Energy 2018, 163, 822–836. [Google Scholar] [CrossRef]
  3. Coster, E.J.; Myrzik, J.M.A.; Kruimer, B.; Kling, W.L. Integration Issues of Distributed Generation in Distribution Grids. Proc. IEEE 2011, 99, 28–39. [Google Scholar] [CrossRef] [Green Version]
  4. Sarabia, A.F. Impact of Distributed Generation on Distribution System. Ph.D. Thesis, University of Aalborg, Aalborg, Denmark, 2011. [Google Scholar]
  5. Coster, E.J.; Myrzik, J.M.A.; Kruimer, B.; Kling, W.L. Effect of DG on Distribution Grid Protection. Distributed Generation; Dattatraya, G., Ed.; Eindhoven University of Technology: Eindhoven, The Netherlands, 2010. [Google Scholar]
  6. Huchel, L.; Zeineldin, H.H. Planning the Coordination of Directional Overcurrent Relays for Distribution Systems Considering DG. IEEE Trans. Smart Grid 2016, 7, 1642–1649. [Google Scholar] [CrossRef]
  7. Jia, K.; Gu, C.; Xuan, Z.; Li, L.; Lin, Y. Fault Characteristics Analysis and Line Protection Design Within a Large-Scale Photovoltaic Power Plant. IEEE Trans. Smart Grid 2018, 9, 4099–4108. [Google Scholar] [CrossRef]
  8. Maki, K.; Repo, S.; Jarventausta, P. Effect of wind power based distributed generation on protection of distribution network. In Proceedings of the Eighth IEE International Conference on Developments in Power System Protection, Amsterdam, The Netherlands, 5–8 April 2004; pp. 327–330. [Google Scholar]
  9. Su, S.Y.; Lu, C.N.; Chang, R.F.; Gutierrez-Alcaraz, G. Distributed Generation Interconnection Planning: A Wind Power Case Study. IEEE Trans. Smart Grid 2011, 2, 181–189. [Google Scholar] [CrossRef]
  10. Chen, X.; Yan, R.; Liu, Y. Wind turbine condition monitoring and fault diagnosis in China. IEEE Instrum. Meas. Mag. 2016, 19, 22–28. [Google Scholar] [CrossRef]
  11. El-Naggar, A.; Erlich, I. Analysis of fault current contribution of Doubly-Fed Induction Generator Wind Turbines during unbalanced grid faults. Renew. Energy 2016, 91, 137–146. [Google Scholar] [CrossRef]
  12. Aly, M.M.A.M.; Sayed, M.A.H.E. Enhanced fault location algorithm for smart grid containing wind farm using wireless communication facilities. IET Gener. Transm. Distrib. 2016, 10, 2231–2239. [Google Scholar] [CrossRef]
  13. Hooshyar, A.; Azzouz, M.A.; El-Saadany, E.F. Three-Phase Fault Direction Identification for Distribution Systems with DFIG-Based Wind DG. IEEE Trans. Sustain. Energy 2014, 5, 747–756. [Google Scholar] [CrossRef]
  14. Chang, H.; Linh, N.V.; Lee, W. A Novel Nonintrusive Fault Identification for Power Transmission Networks Using Power-Spectrum-Based Hyperbolic S-Transform—Part I: Fault Classification. IEEE Trans. Ind. Appl. 2018, 54, 5700–5710. [Google Scholar] [CrossRef]
  15. Dutta, P.; Esmaeilian, A.; Kezunovic, M. Transmission-Line Fault Analysis Using Synchronized Sampling. IEEE Trans. Power Deliv. 2014, 29, 942–950. [Google Scholar] [CrossRef]
  16. Stanojević, V.A.; Preston, G.; Terzija, V. Synchronised Measurements Based Algorithm for Long Transmission Line Fault Analysis. IEEE Trans. Smart Grid 2018, 9, 4448–4457. [Google Scholar] [CrossRef]
  17. Adu, T. An accurate fault classification technique for power system monitoring devices. IEEE Trans. Power Deliv. 2002, 17, 684–690. [Google Scholar] [CrossRef]
  18. Bains, T.P.S.; Sidhu, T.S.; Xu, Z.; Voloh, I.; Zadeh, M.R.D. Impedance-Based Fault Location Algorithm for Ground Faults in Series-Capacitor-Compensated Transmission Lines. IEEE Trans. Power Deliv. 2018, 33, 189–199. [Google Scholar] [CrossRef]
  19. Jamehbozorg, A.; Shahrtash, S.M. A Decision Tree-Based Method for Fault Classification in Double-Circuit Transmission Lines. IEEE Trans. Power Deliv. 2010, 25, 2184–2189. [Google Scholar] [CrossRef]
  20. Chaitanya, B.K.; Yadav, A. An intelligent fault detection and classification scheme for distribution lines integrated with distributed generators. Comput. Electr. Eng. 2018, 69, 28–40. [Google Scholar] [CrossRef]
  21. Mahfouz, M.M.A.; El-Sayed, M.A.H. Smart grid fault detection and classification with multi-distributed generation based on current signals approach. Iet Gener. Transm. Distrib. 2016, 10, 4040–4047. [Google Scholar] [CrossRef]
  22. Robertson, D.C.; Camps, O.I.; Mayer, J.S.; Gish, W.B. Wavelets and electromagnetic power system transients. IEEE Trans. Power Deliv. 1996, 11, 1050–1058. [Google Scholar] [CrossRef]
  23. Wilkinson, W.A.; Cox, M.D. Discrete wavelet analysis of power system transients. IEEE Trans. Power Syst. 1996, 11, 2038–2044. [Google Scholar] [CrossRef]
  24. Kim, C.H.; Aggarwal, R. Wavelet transforms in power systems. I. General introduction to the wavelet transforms. Power Eng. J. 2000, 14, 81–87. [Google Scholar] [CrossRef]
  25. Kim, C.H.; Aggarwal, R. Wavelet transforms in power systems. II. Examples of application to actual power system transients. Power Eng. J. 2001, 15, 193–202. [Google Scholar] [CrossRef]
  26. Rajaraman, P.; Sundaravaradan, N.A.; Meyur, R.; Reddy, M.J.B.; Mohanta, D.K. Fault Classification in Transmission Lines Using Wavelet Multiresolution Analysis. IEEE Potentials 2016, 35, 38–44. [Google Scholar] [CrossRef]
  27. Adly, A.R.; Sehiemy, R.A.E.; Abdelaziz, A.Y.; Ayad, N.M.A. Critical aspects on wavelet transforms based fault identification procedures in HV transmission line. IET Gener. Transm. Distrib. 2016, 10, 508–517. [Google Scholar] [CrossRef]
  28. Choudhury, M.; Ganguly, A. Transmission line fault classification using discrete wavelet transform. In Proceedings of the 2015 International Conference on Energy, Power and Environment: Towards Sustainable Growth (ICEPE), Shillong, India, 12–13 June 2015; pp. 1–5. [Google Scholar]
  29. Alves, H.D.N.; Fonseca, R.N.B. An algorithm based on discrete wavelet transform for fault detection and evaluation of the performance of overcurrent protection in radial distribution systems. IEEE Lat. Am. Trans. 2014, 12, 602–608. [Google Scholar] [CrossRef]
  30. Davydova, N.; Hug, G. Travelling wave protection with disturbance classification for distribution grids with distributed generation. J. Eng. 2018, 2018, 830–835. [Google Scholar] [CrossRef]
  31. Lopes, F.V.; Ribeiro, C.M.S.; Ribeiro, J.P.G.; Leite, E.J.S. Performance evaluation of the travelling wave-based differential protection when applied on Hybrid Transmission Lines. J. Eng. 2018, 2018, 1114–1119. [Google Scholar] [CrossRef]
  32. Karmacharya, M.; Gokaraju, R. Fault Location in Ungrounded Photovoltaic System Using Wavelets and ANN. IEEE Trans. Power Deliv. 2018, 33, 549–559. [Google Scholar] [CrossRef]
  33. Abdullah, A. Ultrafast Transmission Line Fault Detection Using a DWT-Based ANN. IEEE Trans. Ind. Appl. 2018, 54, 1182–1193. [Google Scholar] [CrossRef]
  34. Singh, S.; Vishwakarma, D.N. Faults classification in series compensated lines based on wavelet entropy and neural network. In Proceedings of the 2016 International Conference on Microelectronics, Computing and Communications (MicroCom), Durgapur, India, 23–25 January 2016; pp. 1–6. [Google Scholar]
  35. Ananthan, S.N.; Padmanabhan, R.; Meyur, R.; Mallikarjuna, B.; Reddy, M.J.B.; Mohanta, D.K. Real-time fault analysis of transmission lines using wavelet multi-resolution analysis based frequency-domain approach. IET Sci. Meas. Technol. 2016, 10, 693–703. [Google Scholar] [CrossRef]
  36. Ding, J.; Wang, X.; Zheng, Y.; Li, L. Distributed Traveling-Wave-Based Fault-Location Algorithm Embedded in Multiterminal Transmission Lines. IEEE Trans. Power Deliv. 2018, 33, 3045–3054. [Google Scholar] [CrossRef]
Figure 1. Diagram of the simplified 22 kV distribution line with distributed generation (DG) used in the case study.
Figure 1. Diagram of the simplified 22 kV distribution line with distributed generation (DG) used in the case study.
Sustainability 11 07209 g001
Figure 2. Single line diagram of the distribution system using PSCAD software.
Figure 2. Single line diagram of the distribution system using PSCAD software.
Sustainability 11 07209 g002
Figure 3. Diagram of wind power generation using PSCAD software.
Figure 3. Diagram of wind power generation using PSCAD software.
Sustainability 11 07209 g003
Figure 4. The power generated from wind power generation.
Figure 4. The power generated from wind power generation.
Sustainability 11 07209 g004
Figure 5. Three-phase current signal from the substation bus under the single line to the ground fault condition (Phase A): (a) No Dg; (b) One DG; (c) Two DG.
Figure 5. Three-phase current signal from the substation bus under the single line to the ground fault condition (Phase A): (a) No Dg; (b) One DG; (c) Two DG.
Sustainability 11 07209 g005
Figure 6. Three-phase current signal from the load bus under the single line to ground fault condition (Phase A): (a) No Dg; (b) One DG; (c) Two DG.
Figure 6. Three-phase current signal from the load bus under the single line to ground fault condition (Phase A): (a) No Dg; (b) One DG; (c) Two DG.
Sustainability 11 07209 g006
Figure 7. Fault classification decision tree.
Figure 7. Fault classification decision tree.
Sustainability 11 07209 g007
Figure 8. Maximum coefficient value and comparison value in the case of a three-phase fault on the distribution system with two DGs: (a) Substation bus; (b) Distributed Generation No. 1 bus; (c) Distributed Generation No. 2 bus; (d) Load Bus.
Figure 8. Maximum coefficient value and comparison value in the case of a three-phase fault on the distribution system with two DGs: (a) Substation bus; (b) Distributed Generation No. 1 bus; (c) Distributed Generation No. 2 bus; (d) Load Bus.
Sustainability 11 07209 g008aSustainability 11 07209 g008b
Figure 9. Average accuracy of fault classification in a case without DG.
Figure 9. Average accuracy of fault classification in a case without DG.
Sustainability 11 07209 g009
Figure 10. The average accuracy of fault classification in the case with a DG near substation bus.
Figure 10. The average accuracy of fault classification in the case with a DG near substation bus.
Sustainability 11 07209 g010
Figure 11. The average accuracy of fault classification in the case of a DG in the middle of the distribution line.
Figure 11. The average accuracy of fault classification in the case of a DG in the middle of the distribution line.
Sustainability 11 07209 g011
Figure 12. The average accuracy of fault classification in the case with a DG near load bus.
Figure 12. The average accuracy of fault classification in the case with a DG near load bus.
Sustainability 11 07209 g012
Figure 13. The average accuracy of fault classification in the case of two DG.
Figure 13. The average accuracy of fault classification in the case of two DG.
Sustainability 11 07209 g013
Table 1. Comparative study of the different methodologies in fault classification.
Table 1. Comparative study of the different methodologies in fault classification.
ReferenceMethodIntegration of Distributed GenerationPost-Fault Data RequirementAccuracy
[14]Power-Spectrum-Based hyperbolic S-TransformNo1 Cycle100%
[15]Synchronized SamplingNoNot Reported100%
[17]Combination of Phase Angles and MagnitudesNoNot Reported95%
[19]Decision Tree and Random Forest AlgorithmNo1/4 Cycle100%
[20]Discrete Fourier TransformNo1/2 Cycle100%
[21]Current Signals ApproachYes1/4 CycleNot Reported
[26]Discrete Wavelet TransformNoNot ReportedNot Reported
[34]Wavelet Entropy and Neural NetworkNo1 CycleNot Reported
Proposed AlgorithmYes1/4 Cycle100%
Table 2. Parameters under consideration in the case study.
Table 2. Parameters under consideration in the case study.
ParameterVariation
Number of DGNo DG, 1 DG and 2 DG.
Location of DG5, 15, 25 km measure from substation bus
Fault Location3, 6, 9, 12, 15, 18, 21, 24, and 27 km measure from substation bus
Fault TypesSingle line to ground fault; double line fault; double line to ground fault; three-phase fault; three-phase to ground fault

Share and Cite

MDPI and ACS Style

Patcharoen, T.; Ngaopitakkul, A. Fault Classifications in Distribution Systems Consisting of Wind Power as Distributed Generation Using Discrete Wavelet Transforms. Sustainability 2019, 11, 7209. https://doi.org/10.3390/su11247209

AMA Style

Patcharoen T, Ngaopitakkul A. Fault Classifications in Distribution Systems Consisting of Wind Power as Distributed Generation Using Discrete Wavelet Transforms. Sustainability. 2019; 11(24):7209. https://doi.org/10.3390/su11247209

Chicago/Turabian Style

Patcharoen, Theerasak, and Atthapol Ngaopitakkul. 2019. "Fault Classifications in Distribution Systems Consisting of Wind Power as Distributed Generation Using Discrete Wavelet Transforms" Sustainability 11, no. 24: 7209. https://doi.org/10.3390/su11247209

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop