3.1. Circuit Specifications
The specifications, circuit diagram and outer appearance of the actual circuit created to verify the proposed control method are presented in
Table 1 and
Figure 5, respectively. The output power of the
Vout1 and
Vout2 sides are expressed as
Pout1 and
Pout2, respectively. The maximum value of the total output power,
Pout1 +
Pout2, was set to 1 kW and the maximum value of
Pout2 was set to 500 W. The input voltage
Vin was set to 300 V, whereas the target values of the output voltages
Vout1 and
Vout2 were set to 48 V and 12 V, respectively. The minimum and maximum switching frequencies,
fmin and
fMAX, were set to 50 kHz and 100 kHz, respectively and the FPGA used was a XC7K70T-1FBG484C with a clock frequency (
fCLK) of 200 MHz (
TCLK = 5 ns). When substituting the values of
fmin,
fMAX and
TCLK into Equation (5),
αT can take values between 2000 and 4000. As
αT is an integer,
ftx and |
Zout2| could take 2001 possible values under the verification control conditions. Proportional gains and time constants of PI
1 and PI
2 were
K1 = 2.5,
K2 = 0.5,
τ1 =3 µs,
τ2 = 8 µs, respectively.
The input capacitor
Cin was an aluminum electrolytic capacitor of 330 μF, the switching devices of the primary side H-bridge circuit (S1 to S4) were SiC MOSFET (SCT3030AL, ROHM) and the eight diodes of the secondary side diode bridge were SiC Schottky barrier diodes (FFSH4065A, ON Semiconductor). Because this circuit was designed to verify the proposed control method, the breakdown voltage and current capacity of these devices were substantially larger than necessary. The turn ratio of the transformer was 20:5. The parameters of the elements of the series resonant filter,
Lsr and
Csr, were 4.5 μH and 560 nF, respectively. The output smoothing inductors were
Lout1 = 7.3 μH and
Lout2 = 7.0 μH, the output capacitor Cout1 was 88 μF with four ceramic capacitors of 22 μF in parallel and
Cout2 was 188 μF with four ceramic capacitors of 47 μF in parallel. The values of
Cin,
Cout1 and
Cout2 are nominal values and the values of
Lsr,
Lout1 and
Lout2 are calculated by using the following equation:
In the above, di/dt is the rate of current change and V is the voltage across the inductor. Both di/dt and V are obtained by the experimental measurement. The data range both parameters are constant is used for the calculation.
The resonant frequency of the series resonant filter,
f0, could be calculated as 100.3 kHz according to the following equation:
Each value of
Table 1 was substituted into Equations (1) and (2) to calculate
Zsr and
Zsm, which were then substituted into Equation (3). The result is presented in
Figure 6. In this case, it was assumed that Rout2 → ∞. As indicated in
Figure 6, the resonant frequency of the
Vout2-side circuit was approximately 100 kHz. It can be observed that this value was the resonant frequency of the resonant filter and it was not affected by the output smoothing LC filter. This is because the resonant frequency of the output smoothing LC filter (
Lout2,
Cout2) was approximately 4.4 kHz, which was far from 100.3 kHz. Moreover, the
Q value of the output smoothing LC filter was less than 10% of the
Q value of the series resonant filter (assuming that both filters had the same line resistance). As the resonant frequency required for control was approximately 100 kHz, in the operating frequency range between 50 kHz and 100 kHz, the impedance of the
Vout2-side circuit decreased monotonically as the frequency of the transformer voltage (
ftx) increased, which enabled
Vout2 to be controlled by
ftx, as mentioned previously. The reason for the monotonic decrease instead of an increase is that the volume of
Lout1 and
Lout2 could be reduced with higher frequency when a large current passed (
Zout2 was small).
As described above, the change rate of impedance by the frequency change and resonant frequency can be calculated using Equation (3) and
Figure 6. The resonant frequency is the upper or lower limit of the operating frequency. Furthermore, the number of possible frequency values is defined by Equation (5). If the operating frequency is too high, the core losses and switching losses increase, whereas if it is too low, the volume of the magnetic core increases. Moreover, if the change rate of the impedance relative to the frequency change is excessively high and an FPGA without a high clock frequency is used, the impedance values that it can take are not continuous and the control resolution decreases. However, if the change rate of the impedance relative to the frequency change is excessively small, the control resolution increases but if the operating frequency range is not expanded, the power range that can be controlled by the
Vout2-side circuit becomes narrower. Therefore, for the proposed control method to work as intended, it is necessary to select the most appropriate resonant frequency, operating frequency range, frequency–impedance characteristics and FPGA.
3.2. Static Characteristics
Figure 7 presents the output voltages
Vout1 and
Vout2 and output currents
Iout1 and
Iout2, with a total output of 1,037 W (
Pout1 = 461 W and
Pout2 = 576 W), from power-up until reaching a steady state. The measurement devices used in the actual verification are listed in
Table 2.
The voltage and current of both outputs were adjusted to constant values and steady operation was established within 0.5 s following power-up. The averages of the adjusted voltages Vout1 and Vout2 were 48.0 V and 12.0 V, respectively, as per the target values. The ripple voltages in the steady state, Vout1 and Vout2, were both ±0.6 V, whereas the ripple currents, Iout1 and Iout2, were ±0.2 A and ±0.8 A, respectively. The ripple current Iout2 was larger because the resolution of TCP303 used to measure Iout2 was lower than that of the TCP312A used to measure Iout1. These results indicate that the proposed control method can produce an output of 1 kW in an actual circuit.
The manner in which the voltage and current increased in this experiment was not a result of the proposed control method but rather, because of the voltage increase slew rate of the DC power supply ZX-1600H used in the verification. Furthermore, the control parameters of the proposed method (proportional gain of the time constant of the PI calculation part) were only optimized for the disturbance response, which is detailed later. This is because, if this circuit is used as designed, load changes will occur more frequently than power increases. The control of a circuit with a power supply voltage applied from the start is a topic for future research.
3.4. Analysis of Steady Operation
In the simulation, the waveform of each part of the circuit in steady operation was calculated and an analysis was performed on each operation point. PSIM (v. 12.04) was used for the simulation.
Table 3 lists the specifications of simulation circuit. The values displayed in
Table 3 were same as the experimental specifications listed in
Table 1 except for the switching devices. All of the switching devices and the transformer were ideal and there were no parasitic resistance, inductance and capacitance in the simulation circuit.
These analysis results refer to the operation mode of the secondary side circuit when Pout2 was maintained constant and Pout1 was changed (operation points #01, #02, #03, #04, #05 and #06) and when Pout1 was maintained constant and Pout2 was changed (operation points #01, #07, #12 and #16).
Figure 9 indicates the voltage and current direction of each part used to define the operation modes, whereas
Table 4 lists the operation modes of the secondary side circuit in the half cycle in a steady state based on the voltage and current directions of
Figure 9. As shown in
Table 4, the operation modes were defined by the secondary side voltage and current of the transformer (
Vtxs and
Itxs), the current from the transformer to the diode bridge on the
Vout1-side circuit (
IrecA and
IrecB), the current of
Lout1 (
ILout1), the return current of the
Vout1-side circuit (
Iret1), the currents of the series resonant filters (
IsrA and
IsrB), the current of
Lout2 (
ILout2), the return current of the
Vout2-side circuit (
Iret2) and the circulating current (
Icir) that flowed between the GND of both outputs. In
Table 4, “+” represents the positive direction, “−” denotes the negative direction and “0” is the condition of no voltage applied or no current flowing.
There were a total of 11 operation modes for the operation points of the analysis.
Table 5 lists the possible operation modes for each operation point as indicated in
Table 5, for each operation point, several modes were used and others were not, which created a large variety of current paths. As an example,
Figure 10 depicts the simulation waveform of
Vtxs and each current at operation points #04 and #12. The both waveforms of #04 and #12 are divided into 8 modes based on the definition of
Table 4, respectively. The operation modes 3, 6 and 9 were not used at operation point #04 and the modes 4, 5 and 8 were not used at #12 as shown in
Table 5. Therefore, it is difficult to explain the circuit operation by the 11 operation modes. However, by focusing on the charging condition of
Lout1, the 11 operation modes could be categorized into three groups (A, B and C). The changes in
Dtx and
ftx caused by the changes in the operation points can be explained by these three operation modes.
In this mode,
Vtxs is positive. As an example,
Figure 11a presents the current path in mode 2. The transformer voltage works as the voltage source and
Lout1 is charged by the following path: Transformer → D11 →
Zsm1 → D14 → Transformer.
In this mode,
Vtxs is zero and
Iret1 is flowing. As an example, the current path in mode 7 is illustrated in
Figure 11b. When
Lout1 is discharged, its discharge current returns along the following path:
Zsm1 → D14 → Transformer → D11 →
Zsm1.
Figure 11c depicts the current path of mode 10. In this mode,
Iret1 and
IrecB are zero. The return current from
Zsm1 becomes a circulating current (
Icir) and moves around the return current of the
Vout2 side (
Iret2). This circulating current
Icir flows because the GND of the
Vout1-side and
Vout2-side circuits are common and the return path of the
Vout2-side circuit contains
ZsrA or
ZsrB. The circulating current of this mode flows according to the state of
ZsrA and
ZsrB. The current path involved in
Lout1 is
Zsm1 → D22 →
ZsrA → D11 →
Zsm1. When the both-end voltage of
ZsrA (
VsrA) exhibits the relationship of
VsrA >
Vout1,
Lout1 is charged by
ZsrA and when
VsrA <
Vout1,
Lout1 discharges.
Figure 12 presents the occupancy time and corresponding frequencies of these three modes at each operation point. When
Pout2 was constant and
Pout1 changed (
Figure 12a), the time occupied by mode A increased (
Dtx increased) and
ftx decreased (
Ttx increased) as
Pout1 increased. The increase in
Dtx was caused by the increase in
Pout1 and the decrease in
ftx occurred to prevent an increase in the power supply to the
Vout2-side circuit caused by the increase in
Dtx. However, when
Pout1 was constant and
Pout2 changed (
Figure 12b),
Pout2 increased as
Ttx decreased (
ftx increased) but few changes occurred in the percentages of the three operation modes (changes in
Dtx), regardless of the changes in
Pout2. This indicates that the impedance change of the
Vout2-side circuit caused by the frequency change played a dominant role in the changes in
Pout2.
3.5. Comparative Evaluation of Simulation and Measured Results
Figure 13 depicts the measured and simulation waveforms of each part at operation points #01, #06 and #16 in steady operation. From the top,
Figure 13 presents the voltages of the primary and secondary sides of the transformer (
Vtxp and
Vtxs), the currents of the primary and secondary sides of the transformer (
Itxp and
Itxs), the both-end voltages of D11 and D12 (
Vd11 and
Vd12), the
Lout1 current and output current (
ILout1 and
Iout1), the series resonant filter currents (
IsrA and
IsrB), the series resonant filter voltages (
VsrA and
VsrB), the both-end voltages of D21 and D22 (
Vd21 and
Vd22), the
Lout2 current and output current (
ILout2 and
Iout2) and the circulating current (
Icir). According to
Figure 13, the measured and simulation waveforms of #01, #06 and #16 were all very close, which confirms that the verification circuit operated as designed. The errors in
Dtx and
ftx, the voltage surge that only appeared in the measured waveforms and the ringing resulting from it were all caused by wiring resistance, parasitic inductance and floating capacitance, which were not included in the simulation.
Figure 14 and
Figure 15 present the relationships between
Dtx and
Pout1 and
ftx and
Pout2, respectively, in steady operation for the measurement and simulation. In addition, the difference between the experimental results and the simulation results for
Figure 14 and
Figure 15 are depicted in
Figure 16.
Figure 14,
Figure 15 and
Figure 16 indicate the experimental tests are operated by larger
Dtx and lower
ftx than the simulation tests under all load conditions. The reason for the larger
Dtx is that
Dtx compensates for
Vout1 decreased by the conduction losses of parasitic resistance in the actual circuit and the reason for the lower
ftx is that
ftx controls increasing
Vout2 with increasing
Dtx. Although these errors appeared, it can be observed that the values of
Dtx and
ftx at all operation points in steady operation were close to the simulation results. Therefore, the verification circuit also operated as per the simulation analysis at other operation points that are not shown in the waveforms of
Figure 13. This is a further demonstration of the efficacy of the proposed control method.