Next Article in Journal
A Closed-Loop Control Strategy for Air Conditioning Loads to Participate in Demand Response
Next Article in Special Issue
Synergetic Effect between Lighting Efficiency Enhancement and Building Energy Reduction Using Alternative Thermal Operating System of Indoor LED Lighting
Previous Article in Journal
Investigation of the Promotion of Wind Power Consumption Using the Thermal-Electric Decoupling Techniques
Previous Article in Special Issue
Study of Power Flow Algorithm of AC/DC Distribution System including VSC-MTDC
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Energy Efficiency Indicators for Assessing Construction Systems Storing Renewable Energy: Application to Phase Change Material-Bearing Façades

by
José A. Tenorio
1,*,
José Sánchez-Ramos
2,†,
Álvaro Ruiz-Pardo
3,†,
Servando Álvarez
2,† and
Luisa F. Cabeza
4,†
1
Eduardo Torroja Institute-CSIC, Serrano Galvache 4, Madrid 28030, Spain
2
Thermal Engineering Group, School of Engineering, University of Seville, Camino de los Descubrimientos s/n, Seville 41092, Spain
3
School of Engineering, University of Cadiz, C/Chile, 1, Cádiz 11002, Spain
4
Department of Computer and Industrial Engineering, University of Lleida, C/Jaume II, 69, Lleida 25001, Spain
*
Author to whom correspondence should be addressed.
These authors contributed equally to this work.
Energies 2015, 8(8), 8630-8649; https://doi.org/10.3390/en8088630
Submission received: 30 June 2015 / Revised: 1 August 2015 / Accepted: 3 August 2015 / Published: 13 August 2015
(This article belongs to the Special Issue Energy Conservation in Infrastructures)

Abstract

:
Assessing the performance or energy efficiency of a single construction element by itself is often a futile exercise. That is not the case, however, when an element is designed, among others, to improve building energy performance by harnessing renewable energy in a process that requires a source of external energy. Harnessing renewable energy is acquiring growing interest in Mediterranean climates as a strategy for reducing the energy consumed by buildings. When such reduction is oriented to lowering demand, the strategy consists in reducing the building’s energy needs with the use of construction elements able to passively absorb, dissipate, or accumulate energy. When reduction is pursued through M&E services, renewable energy enhances building performance. The efficiency of construction systems that use renewable energy but require a supplementary power supply to operate can be assessed by likening these systems to regenerative heat exchangers built into the building. The indicators needed for this purpose are particularly useful for designers, for they can be used to compare the efficiency or performance to deliver an optimal design for each building. This article proposes a series of indicators developed to that end and describes their application to façades bearing phase change materials (PCMs).

Graphical Abstract

1. Introduction

Lowering the amount of energy needed to maintain indoor thermal comfort is an objective shared by all advanced societies, driven both by rising energy costs and environmental considerations such as the reduction of carbon footprint.
Building consumption levels cannot be lowered to under certain thresholds with strategies based solely on insulation or ventilation control. Renewable energies and natural sinks are also needed. The timing of the demand for renewable energies is at odds with the timing of supply, however. One of the most promising techniques for solving that mismatch is the storage of thermal energy.
Many papers have been published on thermal energy storage (TES) systems. Dinçer and Rosen [1] studied such systems in general, contending that they induce energy savings through the use of renewables. Storage may involve the sensible heat absorbed by or from building construction elements, water, or rocks, or the latent heat in PCMs, capitalizing on the high enthalpy attendant upon phase changes. The use of PCMs in building construction has been studied by Mehling and Cabeza [2] and more recently by other authors [3,4,5,6].
A broad spectrum of PCMs is available. Cabeza et al. [7] compiled and classified a full list, analyzing the requirements, problems, and solutions for their use in buildings. Assessment of their performance calls for suitable simulation methods. Any number of articles have been written on simulation, most dealing with detailed methods [8,9,10,11,12,13,14,15].
In another vein, while solar energy may be passively absorbed and harnessed via construction systems in buildings or the environment as a means of obtaining cost-free cooling, this approach often requires an external source of energy; classical examples are Trombe walls and other derived structures that preheat outdoor air for ventilation.
Assessment of the performance of these systems calls for a series of indicators to aid design and provide information on their integration in the building. If the aim is for the building to absorb, exchange, or accumulate energy, designers must have suitable tools for assessing system operation. In the case of PCMs, such indicators must ensure the accurate quantification of the amount of material needed and the operating conditions for each application in keeping with specific building use and the potential of the climate where it is sited.
These indicators constitute an innovation in the field of building energy given the technology involved, although benchmarking is generally accepted as a useful endeavor. The regenerative efficiency indicator or the use factor of the amount of energy stored is one of the parameters most relevant to the design of regenerative heat exchangers (also known as regenerators), for instance [16,17]. Some papers [18,19] on efficiency describe simplified methods derived from detailed methods for calculating indicators from energy accumulation system design parameters.
The indicators defined in this article are generally applicable to any construction element in a building’s envelope or interior that harnesses renewable energy. They were developed specifically for PCM-bearing façades, however, and are adapted to analyzing night-time cooling. Their development forms part of the first author’s Ph.D. dissertation.

2. Phase Change Material (PCM)-Bearing Façade

The suitability of using PCMs in ventilated façades was studied under a research project entitled MECLIDE. The aim was to develop PCM-based night-time cooling solutions able to meet a significant fraction of a building’s cooling needs and identify the circumstances under which residential needs could be fully covered [20,21,22,23].
The PCM-bearing façade studied here comprises three parts: an outer element, an air chamber housing the PCM-bearing fins, and an inner element or wall. A plan view diagram of the façade is shown in Figure 1.
Figure 1. Façade diagram: plan view: (1) Outer element; (2) the fins; and (3) the inner element.
Figure 1. Façade diagram: plan view: (1) Outer element; (2) the fins; and (3) the inner element.
Energies 08 08630 g001
The vertical air chamber runs along the entire façade. The rectangular membranes forming the fins bear PCMs. Air flows upward in the chamber.
During the night the outdoor air circulates through the chamber, cooling the PCM fins. During the day the warm indoor air melts the PCMs and flows back into the building at a cooler temperature. Demand starts when the exterior air temperature is higher than 26 °C and continues until the outlet air temperature from the chamber exceeds Tmax = 25 °C.
Consequently, as discussed in a later section on indicators, the building is dually impacted by the chamber. On the one hand, it is cooled by the ventilation system during the day, using the cooling power accumulated during the night in the PCMs, and on the other it benefits from the thermal barrier formed.
Façade operation is illustrated in Figure 2. Its operating range foreseeably lies between the maximum and minimum temperatures defined, Tmin = 15 °C and Tmax = 25 °C. The orientation considered is south. Façade daily operation is shown in Figure 3.
Figure 2. Façade operation: (a) Storage; (b) Standby; (c) Release.
Figure 2. Façade operation: (a) Storage; (b) Standby; (c) Release.
Energies 08 08630 g002
Figure 3. Daily façade operation temperatures.
Figure 3. Daily façade operation temperatures.
Energies 08 08630 g003
The façade described acts as a cooling and a thermal stabilization element. The larger the number of energy storage and release cycles, the greater is façade efficiency.
Elements of this type depend directly on climate and the building’s energy needs. If the element is used for cooling, energy can only be released if it was previously stored. By the same token, its operation is only effective if the energy released is needed. In other words, weather conditions must be appropriate for operation, with cool nights and warm days, as is normally the case in Mediterranean summers.
PCMs are characterized in terms of effective heat capacity vs. temperature. This simplification of material (RT 22, Rubitherm, Berlin, Germany) behavior is sufficiently accurate according to the model proposed [24] (Figure 4).
Figure 4. Effective heat capacity.
Figure 4. Effective heat capacity.
Energies 08 08630 g004

3. Description of Indicators Proposed

As noted earlier, the indicators are generally applicable to other construction systems. Nonetheless, the façade described above is used here as an example to facilitate discussion.
The first indicator defined, the global efficiency indicator, determines the amount of energy actually delivered by a system relative to the energy needed.

3.1. Global Building Efficiency (GBE) Indicator

Global building efficiency (GBE) is designed to provide insight into system behavior as part of a building.
It is defined as the ratio of the energy saved in a building attributable to the installation of a PCM-based façade ( Δ D ) to the energy needed to achieve such savings ( C vent ).
The GBE indicator may be analyzed in terms of energy demand, independently of HVAC systems:
G B E = Δ D C vent

3.2. Global Façade Efficiency (GFE) Indicator

The performance of façades or other elements bearing PCMs depends primarily on climate, façade orientation, and the building’s cooling load. Such performance can be analyzed independently of the building, i.e., likening it to a renewable air conditioning system.
Global façade efficiency (GFE) is defined as the ratio between the variation in energy consumption attained by installing PCMs in the façade and the energy consumed in the process. As an indicator separate from the building, it affords no information on energy savings. The difference is related both to daytime ventilation (free night-time cooling) and the thermal barrier formed by the air chamber in the façade. Evaluating this indicator calls for a model that can be simplified by dividing the façade into sections:
G F E = E V + E C C vent
where EV is the energy delivered during the day for cooling and Ec is the difference between heat loss in the inner-most wall with and without PCM. Fan energy consumption (Cvent) may differ in GBE and GFE, although both indicators are similar to coefficient of performance (COP) and provide a measure of a façade’s thermal performance. Ev and EC are calculated with the equation described in Section 4.2.

3.3. Partial Indicators

The further factors of Equation (3) can be defined to analyze façade behavior, all of them being non-dimensional, namely the ventilation factor, fV, and the chamber factor, fc (Figure 5):
f V = E V E Design   ;   f C = E C E Design
GFE can therefore be expressed as follows:
G F E = E Design C vent ( f V + f C )
Figure 5. Façade energy diagram. PCM: phase change materials.
Figure 5. Façade energy diagram. PCM: phase change materials.
Energies 08 08630 g005
For the intents and purposes of design, an installation factor Equation (5), fI, and a design factor, fD, can also be defined. The installation factor is the ratio between actual fan consumption and consumption, assuming operation under design conditions:
f I = C vent C vent . Design
Lastly, the design factor is:
f D = E Design C vent . Design
This factor, which depends exclusively on design conditions, is the ratio between the theoretical renewable energy stored by the system and theoretical consumption.
GFE can therefore be expressed as follows:
G F E = f D · f V + f C f I
After analyzing system performance independently of the building (GFE), a suitable tool can be used to define a factor to link GBE and GFE, thereby integrating the system into the building to optimize design.

3.4. Supplementary Indicators

Supplementary indicators can be used to analyze how energy is stored and released.
As noted above, maximum storage capacity depends on the amount of PCM in the system and element inertia. This storage capacity cannot be exceeded, but neither does it need to be activated in all cycles. For the system to store energy, energy must have been previously released, just as for energy to be released, it must have been previously stored.
Partial indicators can be defined to separately analyze the developments affecting storage and release. If the study is confined to the system’s main purpose, namely ventilation, the following non-dimensional indicators can be defined:
f V = E V E Design = E V E V . Max   ·   E V . Max E Str   · E Str E Str . Max   · E Str . Max E Design = f U · f B · f RS · f DS
where: fU is the use factor or the ratio between the ventilation energy delivered and the maximum transferrable energy; fB is the balance factor or the ratio between the maximum transferrable energy and the energy stored by the system; fRS is the real storage factor or the ratio between the energy stored and the maximum storable energy; and fDS is the design storage factor or the ratio between the maximum storable energy and the design energy.
A detailed study of these factors is useful for understanding façade behavior. The aforementioned indicators are designed to study the façade system as a cooling element, although as general factors they can be adapted to other elements and redefined for application to heating. These indicators can be combined or can be estimated and used as weighting factors.

4. Estimates and Models

4.1. Estimates

Construction systems that absorb renewable energy can be likened to regenerators. Regenerative heat exchangers operate by extracting thermal energy from a hot fluid and conveying it to a matrix. In a second cycle the energy stored in the matrix is released to a cold fluid. The similarity to storage systems is obvious. Models often use two non-dimensional parameters to characterize this process; Λ and Π in Equation (10):
Λ = h c · A m ˙ f · C f   ;   Π = h c · A ( P L v ) m m · C m
where hc is the convective heat transfer coefficient; A is area; m ˙ f is the mass air flow rate; Cf is the heat capacity of the air; P is period; L is length; v is air speed; mm is matrix mass; and Cm is matrix heat capacity. These parameters are extremely useful for analyzing the results, particularly for Λ.
Regenerative heat efficiency can be calculated from the inlet and exit air temperatures during storage and consumption:
η = T out T in T PCM T in
As losses have a heavier impact on consumption than on storage, efficiency is more stable in the latter and can be calculated theoretically.
Moreover, regenerator efficiency varies with time because the temperatures involved are not constant.
Façades may be likened to regenerators and studied using parameters Λ and Π, modifying the definition of Π as in Equation (11). Here the term L/P is regarded as negligible and hence dropped and Cm is not constant:
Π = h c · A ·   τ m PCM ·   λ T PCM T in
where τ and λ are storage time and latent heat, respectively.

4.2. Models

A number of simulation models were developed to study the façade described. A detailed model calibrated with empirical tests was described by Ruiz-Pardo et al. [21]. In his Ph.D. thesis, Tenorio [25] developed two simplified models, one based on an analogy with electricity and the other on the direct estimation of performance as a regenerator.
In the first simplified model, the façade is divided into three sections, representing the indoor and outdoor walls with three resistors and two capacitors each. Any combination of building elements can be simulated with this scheme.
Radiation between the inner surfaces inside the air chamber and PCM-bearing fins is factored into the model. Radiation heat transfer between inner surfaces inside the air chamber is neglected in light of the distance involved and the existence of PCM fins in the chamber. Radiation heat transfer among the PCM-bearing fins is likewise neglected. In contrast, the model includes convection heat transfer between all surfaces and the air (Figure 6).
Figure 6. Simplified model.
Figure 6. Simplified model.
Energies 08 08630 g006
Air temperature is calculated from the energy balance in each section. Certain simplifications were adopted for the model, including the assumption of a constant temperature in each section and of a uniform temperature in the fins, as well as the use of the average of the inlet and exit air temperatures in each section. PCMs were characterized in terms of effective thermal capacity vs. temperature.
Variables used in indicators can be calculated from the simplified model with the following equations:
E V = τ m ˙ f · C f   ( T out ( t ) T in ( t ) ) d t
E Str = τ m ˙ f · C f   ( T out ( t ) T in ( t ) ) d t
E façade = m PCM · λ + m f a ç a d e · C p   ( T + 273 )   d T
E V . max = E Max E façade   ( initial   release   conditions )
E Str . max = E Max E façade   ( initial   storage   conditions )
E Design = m PCM · λ + m f a c a d e · C p   ( T m a x T m i n )   d T m P C M · λ
EC is the difference between heat loss in the inner-most wall with and without PCM, therefore can be calculated using an overlapping model without PCM, in the same conditions.
The model was calibrated against experimental data and the more detailed model described in [23] to very satisfactory results. The correlation coefficients obtained are given in Table 1.
Table 1. Correlation coefficients between simplified model, experimental data and detailed simulation.
Table 1. Correlation coefficients between simplified model, experimental data and detailed simulation.
Correlated withToutTPCM (Section 1)TPCM (Section 2)TPCM (Section 3)
Experimental data0.9870.9890.9770.973
Detailed model0.9880.9860.9700.978
In the second simplified model, system behavior was assessed for theoretical efficiency by solving the following four-equation system:
Air:
T out ( t ) T in ( t ) =   [ T PCM T in ( t ) ] ( 1 e h · A ( t ) / m ˙ · C p )
PCM:
d M d t = Q ( t ) λ = m ˙ · C p · ( T PCM T in ( t ) ) λ · ( 1 e h · A ( t ) / m ˙ · C p )
Change in effective area exposed to the phase change:
d A d t = A 0 M 0 · d M d t
Efficiency:
η = τ ( T out ( t ) T in ( t ) ) d t τ ( T PCM T in ( t ) ) d t
In façades, the value of Λ generally ranges from 0 to 5. The η values estimated with the model are shown in Figure 7.
Figure 7. Regenerator efficiency.
Figure 7. Regenerator efficiency.
Energies 08 08630 g007

5. Discussion

Tenorio [25] ran the first model described for a number of configurations of PCM-bearing façades to study the functional dependence of the indicators on variations in the basic variables (insulation, mass, weather, amount of PCM, and air speed).
The variations in the indicators observed with variations in the weather and the amount of PCM are discussed here by way of example. The figures below illustrate the utility of indicators in determining façade performance. They compare performance of a standard façade with 70 kg/m2 of PCM in different climates and the same façade in Madrid with PCM contents ranging from 10 kg/m2 to 100 kg/m2.
Figure 8 shows the results of the simulation for several climates in Spain, Figure 9 shows the variation with different amounts of PCM, and Figure 10 shows the ventilation energy delivered in July and August.
Figure 8. Indicators in different climates: (a) fV; (b) fC; (c) fI; (d) GFE.
Figure 8. Indicators in different climates: (a) fV; (b) fC; (c) fI; (d) GFE.
Energies 08 08630 g008
Figure 9. Indicators for different amounts of PCM: (a) fV; (b) fC; (c) fI; (d) GFE.
Figure 9. Indicators for different amounts of PCM: (a) fV; (b) fC; (c) fI; (d) GFE.
Energies 08 08630 g009
Figure 10. Ventilation energy delivered in July and August: (a) different climates; (b) different amounts of PCM.
Figure 10. Ventilation energy delivered in July and August: (a) different climates; (b) different amounts of PCM.
Energies 08 08630 g010
Similarly, an analysis of supplementary indicators fU·fB·fRS·fDS for different façade configurations in different climates revealed the following:
  • Use factor fU provides information on the use of energy in the system and fewer losses. A high fU value means efficient release with fewer losses; efficiency can be improved with façade insulation and the speed of release.
  • Balance factor fB compares release capacity to storage capacity. A high fB value implies small loss during inactivity. This factor depends (inversely) on the maximum temperatures (greatest loss) and speed of release and directly on the outer insulation.
  • Real storage factor fRS reflects operation during storage. A high fRS means good storage performance. It depends directly on the maximum and minimum temperatures, but more on the high temperatures, and on speed of release and insulation.
  • Design storage factor fDS provides information on cooling potential relative to climate. A high fDS is symptomatic of design suited to the climate at issue. It depends directly on minimum temperatures and storage speed, and, inversely, on the amount of PCM. It is affected slightly, likewise inversely, by inertia.
  • Façade performance can also be estimated with the theoretical model (second simplified model) using non-dimensional parameters Λ and Π.
  • The energy stored in an air medium can be calculated from the following expressions in Equations (22)–(24):
    E Str = τ m ˙ f · C f   ( T out ( t ) T in ( t ) ) d t
    E Str = m ˙ f · C f   τ ( T out ( t ) T in ( t ) ) d t τ ( T PCM T in ( t ) ) d t τ ( T PCM ( t ) T in ( t ) ) d t
    E Str = m ˙ f · C f · η · C C P
    where CCP is climate cooling potential (Kh) in degree-hours over a given night-time storage period.
While as a rule EV < EStr, where Λ is not overly small it may be regarded as roughly similar and used to estimate fV.
The advantage of the method is that it can be used to estimate façade behavior from the perspective of regenerator efficiency and to obtain Λ and Π, which define the main variables. The amount of PCM, air speed, and energy delivered can consequently be predesigned to the climate in question.
Comparison with a regenerator and the theoretical values defined are only valid for highly insulated façades; otherwise, losses distort the results. Nonetheless, as the above example shows, the difference is not large.
Both the simulations and the theoretical values showed that the façade behaved much like a regenerator. Note that the Π values ranged from 0.8 to 2.1 in this approach.
Figure 11 shows the energy stored and released (kWh/m2) in July and August in façades with different amounts of PCM. The figure also shows the energy stored as estimated from η and CCP.
Figure 11. Energy stored, energy delivered for ventilation, and estimated energy storage in July and August.
Figure 11. Energy stored, energy delivered for ventilation, and estimated energy storage in July and August.
Energies 08 08630 g011
As the figure shows, PCM-bearing ventilated façades can deliver substantial amounts of renewable energy for use in air conditioning.
System behavior as a heat exchanger merits comment. In the simulation, at high values of Λ, which denote low air speed, η normally fluctuates around 1 (Figure 12). That GFE and η increase with the amount of PCM is another finding of interest. While GFE is greater in cold climates, heat exchanger efficiency, η, is higher in warm climates. The reason is that façades perform better when the cooling potential is high (cold nights), even if regenerator use is less intense. Values of η greater than 1 mean that the façade is active in both the latent and the sensible ranges because of the mass from the indoor wall, which is more relevant in warm than in cold climates.
Figure 12. Efficiency as a regenerator: (a) different climates; (b) different amounts of PCM.
Figure 12. Efficiency as a regenerator: (a) different climates; (b) different amounts of PCM.
Energies 08 08630 g012
The results of applying the model to different façade configurations (Table 2) are given in Table 3. The drawings in the table represent the insulation, the ventilation chamber, and the masonry wall typical of construction in Spain, as appropriate. The example is based on Madrid’s climate and a PCM content of 60 kg/m2.
Table 2. Façade configurations.
Table 2. Façade configurations.
CaseConfiguration
Case 1Lightweight outer element, lightweight inner element
Case 2Lightweight outer element, heavy inner element with insulation on the chamber side
Case 3Lightweight outer element, heavy inner wall
Case 4Heavy outer element, lightweight inner element
Case 5Heavy outer heavy element, heavy inner element with insulation on the chamber side
Case 6Heavy outer element with insulation on the chamber side, heavy inner element with insulation on the chamber side
Case 7Heavy outer element, heavy inner wall
Case 8Heavy outer element with insulation on the chamber side, heavy inner wall
Table 3. Results obtained in different façade configurations.
Table 3. Results obtained in different façade configurations.
Case12345678
Outer Energies 08 08630 i001inner Energies 08 08630 i002 Energies 08 08630 i003 Energies 08 08630 i004 Energies 08 08630 i005 Energies 08 08630 i006 Energies 08 08630 i007 Energies 08 08630 i008 Energies 08 08630 i009
fU Use factor0.910.920.920.910.910.980.90.97
fB Balance factor0.9910.971.11.11.081.031.04
fRS Real storage factor0.820.820.820.730.730.760.760.78
fDS Design storage factor0.840.840.830.840.840.850.830.84
fV Ventilation factor0.620.630.610.610.610.680.590.66
fC Chamber factor0.120.10.170.020.020.110.090.19
fI Installation factor0.540.540.540.530.540.540.550.55
fD Design factor7.547.547.877.957.957.548.287.87
GFE Global façade efficiency indicator10.3810.1611.269.319.231110.3212.24
A yearly performance graph for one of the façades (case 1) is reproduced in Figure 13, by way of illustration. The thermal stabilization afforded by the façade is clearly visible.
As noted, climate is a key factor in this type of systems. The ability to estimate the amount of energy available for use is directly related to CCP in degree-hours (Kh), which can be readily calculated for a given climate and prevailing conditions.
Figure 14 contains a temperature diagram for the cities where the studies were conducted. The horizontal lines represent the time of day from 0:00 to 24:00 and the vertical lines (from top down) the days of the year. The diagrams stand as proof of the substantial cooling power that can be derived from the thermal sink comprising the low night-time summer temperatures.
Figure 13. Façade temperatures over a 12-month period.
Figure 13. Façade temperatures over a 12-month period.
Energies 08 08630 g013
Figure 14. Hourly temperatures in the cities studied over a one-year period.
Figure 14. Hourly temperatures in the cities studied over a one-year period.
Energies 08 08630 g014
Climate potential can be fairly simply assessed from the following expression, which depends on the phase change temperature:
C C P = τ ( T PCM ( t ) T in ( t ) ) d t
Given the hourly temperatures for a climate, its CCP can be estimated for a specific phase change temperature. The findings for 22 °C in the climates selected are given in Table 4.
Table 4. Climate cooling potential (CCP) values for selected climates.
Table 4. Climate cooling potential (CCP) values for selected climates.
CCP (Kh Degree-Hours)JuneJulyAugustSeptember
Cuenca3324169517143255
Madrid19606467091909
Lleida17577467141854
Granada2311130713022281
Cáceres1520427432801
Seville1120445378698
Insight into the natural cooling power that can be drawn from energy stored during the night can be obtained by comparing those values to the degree-hours of cooling in the respective climates. The data in Table 5, provided by way of indication only, were calculated for a temperature of 26 °C.
Table 5. Degree-hours of cooling in selected climates.
Table 5. Degree-hours of cooling in selected climates.
Degree-hours of coolingJuneJulyAugustSeptember
Cuenca84827707222
Madrid248973832209
Lleida3501175868318
Granada68216521533699
Cáceres65117121415798
Seville925220121261081
Note that the storage potential in Cuenca is very high compared to its cooling needs. Madrid and Lleida yield similar values, although the summer is warmer in the latter. Granada has high cooling potential as well as high cooling needs. Cáceres and Seville exhibit much lower potential than needs, particularly in July and August.

6. Conclusions

Ventilated facades containing PCMs have been shown to help reduce buildings’ energy consumption, contributing to energy savings. Spain’s climate is particularly well adapted to reducing or eliminating energy consumption for air conditioning by deploying the cooling power stored overnight in PCMs.
The suitability of system design depends on needs-driven efficiency. Indicators furnish the information on performance required to analyze and compare different solutions. They may also be used to standardize technical specifications. In simplified models, non-dimensional parameters such as defined for regenerators (Λ and Π) stabilize the results and facilitate their analysis by condensing all the basic variables in a single value.
Likening PCM storage to regenerator behavior is a useful approach to capitalize fully on climate potential. Regenerator efficiency contributes to global system efficiency.
Preliminary estimates and simplified modeling are useful for determining system behavior, for by saving on calculation time they optimize the design of new solutions.
As the findings show, very high façade efficiency values are obtained for both lightweight and heavy elements.
Cooling potential is very high in continental climates and high in temperate Mediterranean climates.
Solutions should be designed in keeping with the aims pursued respecting the amount and duration of energy release, while energy storage depends upon the potential available.

Acknowledgments

The present paper draws from some of the findings of a project entitled “MECLIDE-Soluciones estructurales con materiales especiales para la climatización diferida de edificios” (structural solutions with special materials for deferred environmental control in buildings) co-funded by Corporación Tecnológica de Andalucía and DETEA. Luisa F. Cabeza would like to thank the Catalan Government for the quality accreditation given to her research group (2014 SGR 123).

Author Contributions

These authors contributed equally to this work. José A. Tenorio introduced the idea of indicators and wrote the draft; José Sánchez-Ramos and Álvaro Ruiz-Pardo worked in the second simplified model and in detailed model; Servando Álvarez contributed in concepts, managed and supervised the research works and Luisa Cabeza managed also the research and provided experimental issues. All of them have together contributed in developing the ideas, improving the manuscript, and they have read as well as approved the manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

Abbreviations

CCP
Climate cooling potential
COP
Coefficient of performance
C′vent
Fans energy consumption in the operation of the façade
Cvent
Theoretical fans energy consumption in the operation of the façade (without building)
Cvent.Design
Fans energy consumption assuming operation under design conditions
Cf
Heat capacity of the air
Cm
Matrix mass capacity
Cp
Heat capacity of the façade
ΔD
Theoretical energy saved in a building attributable to the installation of a PCM façade
EDesign
Energy stored in the façade due to increase temperature between Tmin and Tmax
Ev
Energy delivered for cooling in a period of time
EC
Energy saved attributable to the PCM façade as thermal barrier
EStr
Energy stored
fB
Balance factor
fC
Chamber factor
fD
Design factor
fDS
Design storage factor
fI
Design factor related to fans consumption
fU
Use factor
fRS
Real storage factor
fV
Ventilation factor
GBE
Global building efficiency indicator
GFE
Global façade efficiency indicator
hc
Convective heat transfer coefficient
L
Length (regenerative heat exchangers)
λ
PCM latent heat
Λ
Reduced length (regenerative heat exchangers)
m ˙ f
Mass air flow rate
mfaçade
Façade mass
mm
PCM mass
mPCM
Matrix mass (regenerative heat exchangers)
η
Efficiency (regenerative heat exchangers)
P
Period (regenerative heat exchangers)
Π
Reduced period (regenerative heat exchangers)
Tin
Inlet air temperature
Tmin
Minimum temperature range defined in the air chamber
Tmax
Maximum temperature range defined in the air chamber
Tout
Outlet air temperature
TPCM
Phase change temperature
τ
Storage time (regenerative heat exchangers)
v
Air speed (regenerative heat exchangers)

References

  1. Dinçery, I.; Rosen, M.A. Thermal Energy Storage: Systems and Applications; John Wiley and Sons: Chichester, UK, 2010. [Google Scholar]
  2. Mehlingy, H.; Cabeza, L.F. An up to date introduction into basics and applications. In Heat and Cold Storage with PCM; Springer: Berlin/Heidelberg, Germany, 2008; pp. 217–295. [Google Scholar]
  3. Tyagiy, V.V.; Buddhi, D. PCM thermal storage in buildings: A state of art. Renew. Sustain. Energy Rev. 2007, 11, 1146–1166. [Google Scholar] [CrossRef]
  4. Sharma, A.; Tyagi, V.V.; Chen, C.R.; Buddhi, Y.D. Review on thermal energy storage with phase change materials and applications. Renew. Sustain. Energy Rev. 2009, 13, 318–345. [Google Scholar] [CrossRef]
  5. Wang, X.; Zhang, Y.; Xiao, W.; Zeng, R.; Zhang, Q.; Di, F.H. Review on thermal performance of phase change energy storage building envelope. Chin. Sci. Bull. 2009, 54, 920–928. [Google Scholar] [CrossRef]
  6. Soares, N.; Costa, J.J.; Gaspar, A.R.; Santos, P. Review of passive PCM latent heat thermal energy storage systems towards buildings’ energy efficiency. Energy Build. 2013, 59, 82–103. [Google Scholar] [CrossRef]
  7. Cabeza, L.F.; Castell, A.; Barreneche, C.; de Gracia, A.; Fernández, A.I. Materials used as PCM in thermal energy storage in buildings: A review. Renew. Sustain. Energy Rev. 2011, 15, 1675–1695. [Google Scholar] [CrossRef]
  8. Crawley, D.B.; Lawrie, L.K.; Winkelmann, F.C.; Buhl, W.F.; Huang, Y.J.; Pedersen, C.O.; Strand, R.K.; Liesen, R.J.; Fisher, D.E.; Witte, M.J.; et al. EnergyPlus: Creating a new-generation building energy simulation program. Energy Build. 2001, 33, 319–331. [Google Scholar] [CrossRef]
  9. Ibáñez, M.; Lázaro, A.; Zalba, B.; Cabeza, L.F. An approach to the simulation of PCMs in building applications using TRNSYS. Appl. Therm. Eng. 2005, 25, 1796–1807. [Google Scholar] [CrossRef]
  10. Pedersen, C.O. Advanced zone simulation in Energyplus: Incorporation of variable properties and phase change material (PCM) capability. In Proceedings of the 10th International IBPSA Conference, Beijing, China, 3–9 September 2007.
  11. Kuznik, F.; Virgone, J.; Johannes, K. Development and validation of a new TRNSYS type for the simulation of external building walls containing PCM. Energy Build. 2010, 42, 1004–1009. [Google Scholar] [CrossRef]
  12. Kośny, J.; Yarbrough, D.; Miller, W.; Shrestha, S.; Kossecka, E.; Lee, E. Numerical and Experimental Analysis of Building Envelopes Containing Blown Fiberglass Insulation Thermally Enhanced with Phase Change Material (PCM). In Proceedings of the 1st Central European Symposium on Building Physics, Cracow, Poland, 13–15 September 2010; pp. 13–15.
  13. Tetlow, D.; Su, Y.; Riffat, S.B. Energy Plus simulation analysis of incorporating microencapsulated PCMs (Phase Change Materials) with internal wall insulation (IWI) for hard-to-treat (HTT) houses in the UK. In Proceedings of the 10th International Conference on Sustainable Energy Technologies, Istanbul, Turkey, 4–7 September 2011.
  14. Tabares-Velasco, P.C.; Christensen, C.; Bianchi, M. Verification and validation of EnergyPlus phase change material model for opaque wall assemblies. Build. Environ. 2012, 54, 186–196. [Google Scholar] [CrossRef]
  15. Mazo, J.; Delgado, M.; Marin, J.M.; Zalba, B. Modeling a radiant floor system with Phase Change Material (PCM) integrated into a building simulation tool: Analysis of a case study of a floor heating system coupled to a heat pump. Energy Build. 2012, 47, 458–466. [Google Scholar] [CrossRef]
  16. Willmott, J.A. Dynamics of Regenerative Heat Transfer; CRC Press: New York, NY, USA, 2001. [Google Scholar]
  17. Ackermann, R.A. Cryogenic Regenerative Heat Exchangers; Springer Science & Business Media: New York, NY, USA, 2013. [Google Scholar]
  18. Tay, N.H.S.; Belusko, M.; Bruno, F. An effectiveness-NTU technique for characterising tube-in-tank phase change thermal energy storage systems. Appl. Energy 2012, 91, 309–319. [Google Scholar] [CrossRef]
  19. Nellis, G.F.; Klein, S.A. Regenerative heat exchangers with significant entrained fluid heat capacity. Int. J. Heat Mass Transf. 2006, 49, 329–340. [Google Scholar] [CrossRef]
  20. De Gracia, A.; Navarro, L.; Castell, A.; Ruiz-Pardo, Á.; Álvarez, S.; Cabeza, L.F. Thermal analysis of a ventilated facade with PCM for cooling applications. Energy Build. 2013, 65, 508–515. [Google Scholar] [CrossRef]
  21. Ruiz-Pardo, A.; Sánchez, F.J.; Sánchez Ramos, J.; de Gracia, A.; Cabeza, L.F. Numerical simulation of a ventilated facade with PCM inside the air channel. In Proceedings of the 12th International Conference on Energy Storage, Lleida, Spain, 16–18 May 2012.
  22. De Gracia, A.; Navarro, L.; Castell, A.; Cabeza, L.F. Numerical study on the thermal performance of a ventilated facade with PCM. Appl. Therm. Eng. 2013, 61, 372–380. [Google Scholar] [CrossRef]
  23. Alvarez, S.; Cabeza, L.F.; Ruiz-Pardo, A.; Castell, A.; Tenorio, J.A. Building integration of PCM for natural cooling of buildings. Appl. Energy 2013, 109, 514–522. [Google Scholar] [CrossRef]
  24. Lamberg, P.; Lehtiniemi, R.; Henell, A.-M. Numerical and experimental investigation of melting and freezing processes in phase change material storage. Int. J. Therm. Sci. 2004, 43, 277–287. [Google Scholar] [CrossRef]
  25. Tenorio, J.A. Energy Saving in Buildings through Structural Storage with Phase Change Materials; Seville University: Seville, Spain, 2014. [Google Scholar]

Share and Cite

MDPI and ACS Style

Tenorio, J.A.; Sánchez-Ramos, J.; Ruiz-Pardo, Á.; Álvarez, S.; Cabeza, L.F. Energy Efficiency Indicators for Assessing Construction Systems Storing Renewable Energy: Application to Phase Change Material-Bearing Façades. Energies 2015, 8, 8630-8649. https://doi.org/10.3390/en8088630

AMA Style

Tenorio JA, Sánchez-Ramos J, Ruiz-Pardo Á, Álvarez S, Cabeza LF. Energy Efficiency Indicators for Assessing Construction Systems Storing Renewable Energy: Application to Phase Change Material-Bearing Façades. Energies. 2015; 8(8):8630-8649. https://doi.org/10.3390/en8088630

Chicago/Turabian Style

Tenorio, José A., José Sánchez-Ramos, Álvaro Ruiz-Pardo, Servando Álvarez, and Luisa F. Cabeza. 2015. "Energy Efficiency Indicators for Assessing Construction Systems Storing Renewable Energy: Application to Phase Change Material-Bearing Façades" Energies 8, no. 8: 8630-8649. https://doi.org/10.3390/en8088630

Article Metrics

Back to TopTop