3.5.1. Comparison and Analysis of the Pressure Pulsation
The relative peak-to-peak amplitude of pressure pulsation reflects the intensity of pressure pulsation. In the turbine mode, the water sequentially passed through the sv, sgv, gv monitor points around the vanes, the RP1A to RP1H (or RS1A to RS1H) monitor points in the runner, and reached monitor points dt7 to dt1 in the draft tube. By recording the peak-to-peak values of all operation points and converting into water head, the relative peak-to-peak value of the monitor point was derived after division by the operating head, as shown in
Figure 13,
Figure 14 and
Figure 15.
Figure 13 shows the peak-to-peak values at the vane positions, where Series 1, 2, 3, and 4 represent four phases with an interval of 90°. In addition, the Ave. curve represents the average value of pressure pulsations for each set of monitor points. The pressure pulsation trends of both operation conditions, TH0.9P0.72 and TH1.0P0.92, were almost the same. The flow at operation points of the sv and sgv series was stable, with relative peak-to-peak values at a lower level. The gv operation point was located at the vaneless area, its peak-to-peak value rose sharply compared to the upstream sgv operation points, and the relative peak-to-peak value of the low-head operating condition was slightly larger than that of the high-head operating condition. The peak-to-peak values under different phase angles were slightly different, but the differences from the average value were all less than 2%.
In
Figure 14a, for the long blade pressure side channel point RP1, apart from the RP1A monitor point, the peak-to-peak values of the two cases show a downward trend along the flow direction from RP1B to RP1H.
Figure 14b shows the long blade suction side channel points. Apart from the RS1A monitor point, it shows a downward trend, and the relative peak-to-peak value under the low-head case TH0.9P0.72 at RS1D and RS1E was much larger than that under the case TH1.0P0.92. Comparing
Figure 14a,b, the peak-to-peak pressure amplitude at the RS1A monitor point was smaller than that at the RP1A. Combined with the flow fields in
Figure 8 and
Figure 11, the velocity at the RS1A point was generally larger than that at RP1A; that is, on the suction side of the long blade at the runner inlet, peak-to-peak amplitude of pressure pulsation was lower at the position with a larger circumferential speed.
In
Figure 15, the peak-to-peak values at the monitor points of the draft tube are generally lower, and the relative peak-to-peak values are represented in permille (‰). Along the flow direction from dt7 to dt1, the peak-to-peak values show a gradually decreasing trend. The relative peak-to-peak values of most monitor points under the low-head case TH0.9P0.72 were larger than those under the case of TH1.0P0.92, indicating that the draft tube was greatly affected by the runner and the pressure pulsation was more intense under the low-head condition.
In summary, the pulsations at the vanes’ sv and sgv points were low with stable variation; the peak-to-peak values were the highest at gv points in the vaneless area, far higher than other monitor points, and the pressure pulsations were the most intense; the pulsation situation at the rotating monitor points in the runner channel was more complex, and the relative peak-to-peak values at the vaneless area showed abnormal phenomena. The relative peak-to-peak values in the channel on the suction side of the long blade under low head were much larger than the values under high head, corresponding to a complex flow situation in the runner. Compared with other monitor points on the entire flow passage, the pressure pulsation peak-to-peak value in the draft tube was the lowest.
3.5.2. Pressure Pulsation Spectrum Analysis
From the previous analysis, it could be concluded that the pressure pulsation in the vaneless area was the most intense, the flow and pulsation characteristics in the runner channel were the most complex, and there was vortex in the draft tube. Therefore, the gv series monitor points in the vaneless area, the RP1 and RH1 series monitor points in the runner channel, and the points on the draft tube cone were selected for spectrum analysis, by taking advantage of the Fast Fourier Transform (FFT) method. According to the methodology stated in
Section 2.2, the sampling frequency was 100 times that of the runner rotation frequency
fn, by which 1000 samples in total were equally recorded from 10 runner rotations for spectrum analysis.
As shown in
Figure 16, the main frequency of pressure pulsation was 6
f/
fn (six times the rotation frequency) in both cases of TH1.0P0.92 and TH0.9P0.72, which was half of the blade passing frequency, and also equaled the number of long blades. Other frequencies with large amplitudes are multiples of the frequency 6
f/
fn. Apart from the blade frequency and its multiples, all the remaining frequencies together contributed little, indicating that under the turbine mode, the pressure pulsation in the vaneless area was mainly affected by RSI. However, compared with the case TH1.0P0.92, the main frequency 6
f/
fn had a smaller amplitude under the low-head case TH0.9P0.72, while the secondary frequency 12
f/
fn had a larger amplitude. This indicates that, with the increase in efficiency and head, the influence of the blade frequency 12
f/
fn on the vaneless area declined, and the influence of splitter blade frequency 6
f/
fn was strengthened.
Figure 17b,c shows the pressure pulsation spectrum in the RP1 channel on the long blade pressure side, and
Figure 17d,e shows the pressure pulsation spectrum in the RS1 channel on the suction side of the long blade. Apart from the RP1A and RS1A points, RSI effect was observed to gradually weaken in the direction away from the vaneless area with a gradually decreased amplitude of 20
f/
fn, while the amplitude of low-frequency components such as 1
f/
fn and 2
f/
fn went up slightly. The low amplitude at RS1A accounted for the low pressure pulsation peak-to-peak value shown in
Figure 14. This point was located at the edge of the runner, where the circumferential speed was high and was not directly affected by RSI.
For the RP1 channel on the pressure side of the long blade, the frequency and amplitude of pressure pulsation were similar under both heads. For the RS1 channel, under the low-head TH0.9P0.72 case, the amplitude of 1
f/
fn and 2
f/
fn at the RS1D and RS1E points were abnormally large, corresponding to the abnormally large peak-to-peak value at the corresponding monitor points in
Figure 14b. The pressure pulsation in the vaneless area was mainly affected by RSI, and the distribution pattern on the four phases along the circumferential direction showed good symmetry. The main frequency component of the vaneless area pulsation was 6
f/
fn, or half of the runner blade frequency, and other frequencies were also multiples of 6
f/
fn. Under low-head conditions, the proportion of blade frequency 12
f/
fn would increase.
For the runner blade channels, the frequency distribution of the RP1 channel was similar under different heads, while there was a sudden increase in the proportion of 1 f/fn and 2 f/fn in the RS1 channel under low head. As the location of monitor points moved away from the vaneless area, the influence of RSI weakened and the proportion of 20 f/fn gradually decreased, except for the RP1 and RS1 points close to the vaneless area, and the proportion of 20 f/fn was relatively low, for the pressure pulsation was closely related to the flow characteristics. The flow state at the runner inlet was stable, so that the pressure pulsation was also weak.
Figure 18b–g are the pressure pulsation spectrum diagrams in the draft tube for two cases, among which the dt7 series points were closest to the runner, following by the dt6 and dt5 series points, as shown in
Figure 18a. The amplitude of pressure pulsation under the TH0.9P0.72 condition in which the vortex band appeared in the draft tube was much larger than that under the case of TH1.0P0.92. The first three orders of frequency under case TH0.9P0.72 were 0.4
f/
fn, 0.7
f/
fn, and 6
f/
fn, while the first three orders of frequency under the case TH1.0P0.92 were 6
f/
fn, 0.1
f/
fn, and 18
f/
fn. In comparison, the TH0.9P0.72 case contained all the frequency components present in case TH1.0P0.92, and had two additional low frequencies, 0.4
f/
fn and 0.7
f/
fn, which occupied a larger proportion. It could be asserted that the appearance of these two low frequencies was due to the presence of the vortex band in the draft tube.
In summary, both cases had an increased proportion of 12 f/fn in the vaneless area, an increased proportion of 1 f/fn and 2 f/fn in the runner blade channels, and an increased proportion of 0.4 f/fn and 0.7 f/fn in the draft tube, resulting in an overall increase in pressure pulsation under the TH0.9P0.72 operating condition.