Next Article in Journal
Identification of Lossy Y-Type Two-Port Circuit Models under Measurement Uncertainties: Closed-Form Solution and Statistical–Perturbative Characterization
Previous Article in Journal
Hydrogen Carriers: Scientific Limits and Challenges for the Supply Chain, and Key Factors for Techno-Economic Analysis
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Performance Evaluation of LiBr-H2O and LiCl-H2O Working Pairs in Compression-Assisted Double-Effect Absorption Refrigeration Systems for Utilization of Low-Temperature Heat Sources

School of Naval Architecture, Ocean and Energy Power Engineering, Wuhan University of Technology, Wuhan 430063, China
*
Author to whom correspondence should be addressed.
Energies 2023, 16(16), 6036; https://doi.org/10.3390/en16166036
Submission received: 11 July 2023 / Revised: 7 August 2023 / Accepted: 15 August 2023 / Published: 17 August 2023
(This article belongs to the Topic District Heating and Cooling Systems)

Abstract

:
To improve the performance of conventional double-effect absorption refrigeration systems (DEARS), new series parallel (SP) and reverse parallel (RP) configurations using LiCl-H2O and LiBr-H2O as working fluids, combined with two vapor compressors (VC), are proposed and thermodynamically evaluated. The effects of the distribution ratio (D) and compression ratio (CR) on the system performance are discussed. The results reveal that both configurations can extend the operation ranges of DEARS effectively at a higher distribution ratio, and the performance for low-grade heat source utilization is improved substantially by the use of VC. The compressor positioned between the evaporator and absorber is superior to that between the high-pressure generator and low-pressure generator because of the better performance improvement and larger operating ranges. In all the examined cases, LiCl-H2O systems perform better than LiBr-H2O systems in terms of the coefficient of performance (COP) and exergetic efficiency. At the higher CR of approximately 2, the compression-assisted DEARS can be driven by heat sources below 100 °C with high levels of COPs above 1.16 for the LiBr-H2O working pair and 1.29 for the LiCl-H2O working pair. The system can operate at the optimum condition by adjusting the CR values according to the characteristics of the heat sources.

1. Introduction

With the constant improvement in the urbanization level, the building sector has become a major consumer of global energy [1]. In China, energy consumption in the building sector accounts for approximately 44.7% of the national total, and it is responsible for approximately 30% of the total CO2 emissions [2,3]. The heating, ventilation, and air-conditioning (HVAC) systems based on mechanically driven vapor compression cooling technology consume approximately 65% of the overall building energy [4]. The HVAC systems are being criticized not only because they consume a large amount of electrical energy but also because the refrigerants used contribute to ozone layer depletion and the greenhouse effect. As an alternative technology, absorption refrigeration systems (ARS) are receiving more and more attention for their ability to be activated by various low-grade heat sources, such as solar [5,6,7], geothermal energy [8,9,10], and waste heat [11,12,13]. Moreover, the working pairs of the ARS can be environmentally friendly.
The most widely used absorbent–refrigerant pair in ARS for air-conditioning applications is LiBr-H2O. To improve the system performance, researchers are still trying to seek better alternative working pairs [14,15]. Among them, LiCl-H2O seems to be an efficient alternative working pair with the advantages of long-term stability, higher internal energy storage capacity, and relatively lower costs [16,17,18]. In recent years, many studies have focused on the performance evaluation of LiCl-H2O ARS. Parham et al. [19] reported that the generation temperature of LiCl-H2O ARS is lower than that for LiBr-H2O ARS under the same condensation and absorption temperatures, and the LiCl-H2O ARS has higher exergetic efficiency than the LiBr-H2O ARS. Gunhan et al. [20] conducted an experimental test and exergy analysis of a solar-assisted LiCl-H2O ARS. The results showed that the exergetic efficiency of the whole system varied from 13.1% to 43.2% as the dead state temperature increased from 30 °C to 42 °C. Patel et al. [21] compared the thermodynamic performance between LiCl-H2O and LiBr-H2O single-effect ARS. Results revealed that the COP and exergetic efficiency of LiCl-H2O ARS were 4–9% and 3–6%, respectively, higher than that for LiBr-H2O ARS. Bellos et al. [22] examined the LiCl-H2O and LiBr-H2O working pairs in a solar absorption cooling system. They concluded that the LiCl-H2O working pair performed better than the conventional LiBr-H2O for all the examined cases, and the optimum heat source temperature for the LiCl-H2O system was lower than that of the LiBr-H2O system. Moreover, Gogoi et al. [17] pointed out that LiCl-H2O ARS was superior to LiBr-H2O ARS under identical operating conditions. Ren et al. [23] simply designed LiCl-H2O and LiBr-H2O water-cooled single-effect absorption chillers and found that the LiCl-H2O ARS could be driven by a lower temperature of hot water compared to the LiBr-H2O ARS, but its operating range was severely restricted by the solution crystallization.
The single-effect ARS is the most commonly studied, but it has relatively low COP and limitations on the utilization of high-temperature heat sources. The performance of ARS usually increases with the number of effects, but it leads to system complexity and investment cost increases. Moreover, the COP gain usually diminishes with the addition of every effect; thus, double-effect absorption refrigeration systems (DEARS) are preferred for commercial use in the refrigeration industry [24,25]. In recent years, a large number of studies on the performance analysis of DEARS have been reported. Farshi et al. [24,25,26] examined the performance of three flow types of LiBr-H2O DEARS (series, reverse, and reverse parallel) with various operating parameters. They demonstrated that the COPs and exergetic efficiencies of the parallel and reverse parallel systems were higher than those of the series system, while the parallel and reverse parallel configurations had wider operating ranges without crystallization risks of those of the series flow system. Bellos et al. [18] examined the performance of a LiCl-H2O DEARS with a parallel flow configuration powered by solar parabolic trough collectors. The results indicated that the solar cooling performance was 8% higher compared to operation with LiBr-H2O. Konwar et al. [27,28] carried out detailed energy and exergy analyses of three configurations of LiCl-H2O DEARS. They confirmed that LiCl-H2O systems performed better than LiBr-H2O systems, with higher COPs and exergetic efficiencies under the same operating conditions, particularly in low LPG and HPG temperature applications.
The conventional absorption systems using LiBr-H2O as a working fluid suffer from a severe corrosion problem in the metal part of the machine at a high operating temperature, mainly occurring in the generator. To lower the heat source temperature while obtaining good performance, researchers have developed compression-assisted ARS by placing vapor compressors between system components. Dixit et al. [29] proposed a compression-assisted LiBr-H2O two-stage ARS and found that it performed better than the conventional system, with an optimized COP of 0.43 and exergetic efficiency of 11.68%. Bouaziz et al. [30] proved that the LiBr-H2O double-stage ARS with a vapor compressor could operate at a lower temperature of approximately 60–120 °C, instead of 100–160 °C for the conventional cycle. Shu et al. [31] investigated a compressor-assisted triple-effect LiBr-H2O absorption cooling cycle coupled with a Rankine cycle. They concluded that the maximum generation temperature was 50 °C lower than that of the traditional triple-effect ARS. Recently, many researchers have extended the compressor-assisted ARS for various alternative working pairs. Ventas et al. [32] studied a single-effect NH3-LiNO3 ARS integrated with a compressor between the evaporator and absorber. They pointed out that this cycle could work at lower driving temperatures than the single-effect ARS, and the capacity rose with the increase in the compressor pressure ratio at the same driving temperature. Sun et al. [33] analyzed the thermodynamic performance of single-effect compression-assisted absorption refrigeration cycles using R1234yf/ionic liquid as working fluids. They concluded that the compression-assisted cycle could effectively improve the cooling performance, reduce the circulation ratio, and extend the operation ranges compared to the single-effect ARS. Wu et al. [34] pointed out that the compression-assisted absorption cycle with an auxiliary compressor positioned between the evaporator and absorber performed better than that between the generator and condenser due to the higher cycle efficiency and lower compressor discharge temperature.
The previous studies indicate that the LiCl-H2O working pair performs better than the conventional LiBr-H2O working pair in the ARS. However, the operating range of the LiCl-H2O ARS is strictly restricted compared to LiBr-H2O ARS. According to the aforementioned research, the parallel and reverse parallel flow arrangements are superior in performance, with lower crystallization probabilities and higher COPs, suggesting that the distribution ratio plays an important role in determining the performance of the DEARS. Moreover, the compressor-assisted ARS proves to be an efficient means to improve the system performance and lower the temperatures of heat sources. Most of the previous studies in this field have focused on the LiBr-H2O working pair, and there is still a lack of knowledge on the LiCl-H2O working pair applied in the compression-assisted DEARS. Considering the research gap, the most important contribution of the study is to propose the compression-assisted DEARS arranged in series parallel and reverse parallel configurations for the application of LiBr-H2O and LiCl-H2O working pairs. In these two configurations, solution distributors are used to lower the concentrations of strong solutions for wider operating ranges, and the vapor compressors are designed for low-temperature heat source utilization and higher system performance. The innovation of this work lies in the performance comparison of the two configurations with these working fluids. Moreover, the effect of the operating conditions on the solution crystallization risk is considered and the salt concentrations of these working fluids are presented. The main objectives of this work can be summarized as follows:
(1)
Proposal of two novel arrangements of compression-assisted DEARS using LiBr-H2O and LiCl-H2O as working pairs;
(2)
Development of mathematical models to evaluate the system performance from a thermodynamic viewpoint;
(3)
Examination of the effects of the compression ratio and distribution ratio on the COP and exergetic efficiency.

2. System Description and Crystallization Conditions

The schematic diagram of the proposed system is depicted in Figure 1. The main components of the compressor-assisted DEARS are a high-pressure generator (HPG), low-pressure generator (LPG), absorber (abs), condenser (con), evaporator (eva), high-temperature heat exchanger (HTHE), low-temperature heat exchanger (LTHE), solution pump (Pu), expansion valve (EV), and vapor compressor (VC).
In the system operation, the weak solution (stream 10) is pumped to the HPG, where it is heated by the heat source to separate the refrigerant vapor from the solution at a high pressure and temperature. Then, the primary refrigerant vapor (stream 12) is compressed by VC1 and flows into the LPG, where it (stream 13) is condensed into a saturated liquid by transferring heat to the weak solution (stream 9). At the outlet of the LPG, the secondary vapor (stream 16) produced from the weak solution, together with the condensed water (stream 18), flows into the condenser and cools down to a saturated liquid. After this, the liquid refrigerant (stream 1) enters the evaporator through an expansion valve (EV1), where it absorbs heat at a low pressure to produce a cooling capacity. The refrigerant vapor (stream 3) leaving the evaporator is compressed by VC2 and flows into the absorber to be absorbed by the strong solution (stream 20).
The path described above is the same for the two systems considered in this study. In both the SP and RP configurations, the weak solution (stream 5) leaving the absorber is divided into two streams after passing through the LTHE. Figure 1a shows the schematic diagram of the SP configuration. As can be seen, one part of the weak solution (stream 8) passes to the HPG via the HTHE to generate a primary vapor, and the other part (stream 7b) is mixed with the medium-concentration solution (stream 14) exiting the HPG before it is routed to the LPG through EV3. The strong solution leaving the LPG (stream 15) flows back to the absorber through the LTHE and EV4 successively. In the RP configuration shown in Figure 1b, the main part of the weak solution (stream 9) passes to the LPG for refrigerant vapor generation, where the medium-concentration solution (stream 15) is produced. The other part of the weak solution (stream 7b) is mixed with the medium-concentration solution exiting the LPG and pumped to the HPG via the HTHE. The strong solution (stream 11) flows through the two solution heat exchangers (HTHE and LTHE) and an expansion valve (EV3) before it finally enters the absorber.
In the SP and RP systems, a shell and tube heat exchanger structure can be used for the generator, absorber, evaporator, and condenser. The generator and absorber are considered to be falling film vertical tube heat exchangers. The condenser and evaporator are regarded as horizontal tube heat exchangers. The double-pipe heat exchanger is applied in the solution heat exchanger. Different types of vapor compressors, such as Roots or vortex blowers, can be chosen according to the pressure and temperature of the refrigerant.
Figure 2 presents the P-T-x diagram of the two compression-assisted systems. When the solution concentration increases or the solution temperature decreases, crystallization is most likely to take place, interrupting machine operation. The greatest probability of crystal formation in the two systems is located between the LTHE and absorber because this is the point of highest concentration and lowest temperature. In this work, the crystallization conditions can be determined using the solubility boundary curve of the LiCl-H2O and LiBr-H2O solutions in Refs. [12,35], so the operating range of each system is obtained in which crystallization does not occur.

3. System Modeling

3.1. Assumptions

To simulate the thermodynamic performance of the compression-assisted DEARS, several assumptions are made in the development of the mathematical model [25,26]:
  • The system is simulated under the steady-state condition;
  • The heat and pressure losses during the whole process are neglected;
  • The refrigerants at the outlet of the condenser and evaporator are saturated;
  • Solutions leaving the HPG, LPG, and absorber are assumed to be saturated in equilibrium conditions at their corresponding device temperatures and pressures;
  • A temperature difference of 5 K is assumed for heat transfer in the LPG;
  • The expansion valves take part in an isenthalpic process;
  • The reference state for the system is 298.15 K and 101.3 kPa;
  • The cooling capacity is set at 300 kW for each system.

3.2. Mathematical Models

For the thermodynamic analysis of the system, the general form of the steady-state governing equations of mass balance, energy balance, and concentration balance for each component can be written as [27]
m in = m out
Q ˙ + m in h in = W ˙ + m out h out
m in x in = m out x out
where m is the mass flow rate, Q ˙ denotes the heat transfer rate, W ˙ represents the work transfer rate, h is the enthalpy of each stream, and x is the mass concentration of salt in the solution.
The distribution ratio (D) is an important parameter for the double-effect series parallel and reverse parallel systems, which is defined as
D = m 7 b m 7
The compression ratio (CR) of each compressor is given by
C R 1 = P 13 P 12
C R 2 = P 4 P 3
where P is the pressure of the fluid.
In the simulation process, the thermophysical properties of the LiBr and LiCl aqueous solutions can be determined by the equations in Refs. [35,36], and the properties of water and vapor are calculated from REFPROP 9.0. The heat loads of the main components can be calculated by the following formulas.
High-pressure generator:
m 10 = m 11 + m 12
m 10 x 10 = m 11 x 11
m 21 = m 22
Q ˙ HPG = m 11 h 11 + m 12 h 12 m 10 h 10 = m 21 ( h 21 h 22 )
Low-pressure generator:
m 9 = m 15 + m 16
m 9 x 9 = m 15 x 15
m 13 = m 17
Q ˙ LPG = m 15 h 15 + m 16 h 16 m 9 h 9 = m 13 ( h 13 h 17 )
Absorber:
m 5 = m 3 + m 20
m 5 x 5 = m 20 x 20
m 27 = m 28
Q ˙ abs = m 4 h 4 + m 20 h 20 m 5 h 5 = m 27 ( h 28 h 27 )
Condenser:
m 1 = m 16 + m 18
m 23 = m 24
Q ˙ con = m 16 h 16 + m 18 h 18 m 1 h 1 = m 27 ( h 24 h 23 )
Evaporator:
m 2 = m 3
m 25 = m 26
Q ˙ eva = m 2 h 3 h 2 m 25 ( h 25 h 26 )
High-temperature heat exchanger:
m 8 = m 10
m 11 = m 14
Q ˙ HTHE = m 8 h 10 h 8 = m 11 ( h 11 h 14 )
The effectiveness of the high-temperature heat exchangers for both series parallel and reverse parallel configurations can be expressed as
ε HTHE = T 11 T 14 T 11 T 8
Low-temperature heat exchanger:
m 6 = m 7
For SP configuration:
Q ˙ LTHE = m 6 h 7 h 6 m 15 ( h 15 h 19 )
ε LTHE = T 15 T 19 T 15 T 6
For RP configuration:
Q ˙ LTHE = m 6 h 7 h 6 = m 14 ( h 14 h 19 )
ε LTHE = T 14 T 19 T 14 T 6
The electricity consumed by vapor compressors can be calculated by
m 4 = m 5
m 12 = m 13
W ˙ VC 1 = m 12 h 13 h 12 = m 12 h is , 13 h 12 η VC
W ˙ VC 2 = m 3 h 4 h 3 = m 3 h is , 4 h 3 η VC
where h is , 13 and h is , 4 are the ideal specific enthalpy after isentropic compression; η VC is the isentropic efficiency of the compressor, which is set at 0.8 [31].
The power consumed by the solution pumps can be estimated by [37,38]
W ˙ Pu 1 = m 5 · P 6 P 5 η Pu · ρ 5
W ˙ Pu 2 = m 8 · P 8 P 7 a η Pu · ρ 7 a
where η Pu is the efficiency of the solution pumps, which is set at 0.95 [24,37,38], and ρ is the density of the solution.
The coefficient of performance (COP) is defined as the ratio of the cooling capacity to the energy supply to the system, shown as follows [29,30]:
COP = Q ˙ eva Q ˙ HPG + W ˙ SP + W ˙ VC 1 + W ˙ VC 2
The exergetic efficiency of the system is the ratio of the exergy produced by the evaporator to the input exergy, which can be written as [37]
η ex = Q ˙ eva 1 T 0 T CS Q ˙ HPG 1 T 0 T HS + W ˙ SP + W ˙ VC 1 + W ˙ VC 2
where T0 is the reference temperature. TCS and THS are the mean temperatures of the cold source (in the evaporator) and the hot source (in the HPG), respectively. The outlet temperature of hot water is assumed at THPG + 8 and the inlet temperature of hot water is assumed at THPG + 18 [37]. The outlet temperature of chilled water is assumed at Teva + 3 and the inlet temperature of chilled water is assumed at Teva + 8 [25,37].

4. Model Validation

Computer programs have been developed in the MATLAB R2018b software to simulate the performance of the proposed system. Model validation is conducted for the LiBr-H2O DEARS with the series flow by comparison with the results in Farshi et al. [24] and Gomri et al. [38], under the same operating conditions in steady state, shown in Table 1. As can be seen, there is good agreement between the present results and the previously reported ones.

5. Results and Discussion

In this section, the simulation results are presented and discussed. The series parallel and reverse parallel systems are examined separately to analyze the effects of the distribution ratio (D) and compression ratio (CR) on system performance. All the cases are simulated at tabs = tcon = 35 °C and teva = 5 °C.

5.1. Effect of Distribution Ratio (D) on the Performance of DEARS

Figure 3a,b illustrate the variations in the COP and exergetic efficiency at different distribution ratio levels (0–0.2–0.4) for the SP and RP systems. As can be seen, for the two configurations, the LiCl-H2O systems perform better than the LiBr-H2O systems for all the examined cases in terms of the COP and exergetic efficiency under identical operating conditions, particularly at the low tHPG. Compared with the LiBr-H2O systems, the LiCl-H2O systems have narrow operating ranges due to the crystallization of strong solutions. As the tHPG rises, the COP for each LiBr-H2O SP or RP system initially exhibits a significant increase and then levels off, while the exergetic efficiency reaches its maximum value and decreases thereafter. Better performance can be obtained at the condition that D = 0.4 for the SP system, in contrast to D = 0 for the RP system. For the LiBr-H2O DEARS, the maximum COPs are approximately 1.304 and 1.299, respectively, for the SP and RP systems, and the maximum exergetic efficiencies occur at the value of tHPG approximately 135 °C, being close to 0.2206 and 0.2213 for the SP and RP systems, respectively.
This can be explained by the following facts. In the SP system, the mass flow rate of the weak solution entering the HPG decreases with the increase in the distribution ratio, resulting in a reduction in the HPG heat load. In consequence, the COP increases under the constant cooling capacity. Differently, in the RP system, the mass flow rate of the medium-concentration solution pumped to the HPG increases as the distribution ratio rises, which eventually leads to an increase in the HPG heat load; thus, the COP declines slightly. However, in both the SP and RP systems, the exergetic efficiencies decline at the higher tHPG, which is attributed to the enhancement in the quality of heat energy input to the HPG.
Another indication in Figure 3 is that a higher distribution ratio is beneficial to the system operating range, which allows for the utilization of heat sources with higher temperatures. Compared to the systems without solution distributors, the increases in operating ranges are approximately 10 °C for the LiBr-H2O systems and 5 °C for the LiCl-H2O systems at D = 0.4. The reason is that the concentration of the medium solution becomes lower upon mixing with the weak solution, leading to a decrease in the concentration of the strong solution flowing out of the HPG (for the RP system) or LPG (for the SP system), as proven in Figure 4. It can be seen from Figure 4a,b that, at a certain tHPG, the concentration difference in the outlet solutions between the HPG (x11) and LPG (x15) becomes smaller as the distribution ratio rises, which means that a system with a high distribution ratio can utilize higher-temperature heat sources without solution crystallization.
For the LiBr-H2O working pair, when the SP and RP systems operate at tHPG = 145 °C, the concentrations of the strong solutions flowing to the absorber are estimated to be 63.66%, 62.92%, and 61.90%, respectively, for the SP system, as well as 64.28%, 63.60%, and 62.63%, respectively, for the RP system, corresponding to the three different distribution ratio levels (0–0.2–0.4). Moreover, the LiCl-H2O working pair has narrow operating ranges for both the SP and RP systems due to the limitation of salt solubility. In the examined cases, the maximum concentrations of the LiCl-H2O strong solutions are 48.12% and 48.39%, respectively, for the SP and RP systems.

5.2. Effect of Compression Ratio of VC1 on the Performance of DEARS

Figure 5 and Figure 6 depict the variations in the COP and exergetic efficiency with tHPG at different CR1 levels (1–1.5–2) for the SP and RP systems. It can be seen that the system performance at a low value of tHPG under 120 °C is improved substantially with the help of VC1. Moreover, for all the cases, the operating ranges are enlarged at a higher distribution ratio. The reason is that the pressure of the HPG reduces with the increase in CR1, leading to an enhancement in the generation process and an increase in the solution concentration in the HPG at the low tHPG, as shown in Figure 7 and Figure 8. As a consequence, the deflation ratio of the HPG rises, which causes the mass flow rate of the solution to decrease, and, eventually, the heat load of the HPG declines. The COPs of the LiBr-H2O and LiCl-H2O systems increase because the reduction in the heat loads in the HPG is greater than the power consumed by VC1. The exergetic efficiencies of the LiBr-H2O systems increase initially to reach their maximum values and thereafter decrease. For the LiBr-H2O SP and RP systems, the values of tHPG corresponding to the maximum exergetic efficiencies in the case of CR1 = 1, 1.5, 2 are 135 °C, 120 °C, and 110 °C, respectively.
Figure 7 and Figure 8 present the variations in solution concentrations with t HPG at different CR1 levels for the SP and RP systems, respectively. As can be seen, the concentrations of the solutions exiting the HPG and LPG rise obviously at a relatively low tHPG. At the condition that tHPG =120 °C and D = 0, the concentrations of the strong solutions are approximately 56.95%, 60.06%, and 62.30%, respectively, for the SP system, as well as 57.0%, 60.33%, and 62.62%, respectively, for the RP system, corresponding to the three different CR1 levels (1–1.5–2). Meanwhile, as the tHPG rises, the concentrations of the strong solutions in the SP and RP systems with D = 0.4 increase more slowly than those in the systems without solution distributors, which indicates that the system can operate at a higher tHPG under the restriction of solution crystallization.

5.3. Effect of the Compression Ratio of VC2 on the Performance of DEARS

The variations in the COP and exergetic efficiency with tHPG at different CR2 levels (1–1.5–2) for the SP and RP systems are illustrated in Figure 9 and Figure 10. It is observed that the use of VC2 can greatly improve the system performance and operating ranges, especially for the LiCl-H2O working pair. It can be seen that the operating temperature of the HPG in the LiCl-H2O SP system ranges from 90 °C to 125 °C when the CR2 = 2 and D = 0.4, compared with that from 115 °C to 125 °C when the CR2 = 1 and D = 0.4. Moreover, the operating ranges of all the systems can be expanded clearly at a higher distribution ratio under the same value of CR2. In particular, as Figure 9 and Figure 10 demonstrate, at a higher CR2 greater than 2, the system can be driven by the low-temperature heat source under 100 °C, while the COP and exergetic efficiency remain at high levels in this condition. Moreover, the maximum values of the COP and exergetic efficiency for each system increase with the CR2 in the operating range. In all the examined cases, the maximum COPs are 1.389 and 1.415, respectively, for the LiBr-H2O and LiCl-H2O systems with the SP configuration at CR2 = 2 and D = 0, while the maximum exergetic efficiencies are 0.2454 and 0.2569, respectively. The corresponding maximum COP and exergetic efficiency are obtained at tHPG = 115 °C and tHPG = 100 °C, respectively, for the LiBr-H2O system, as well as tHPG = 110 °C and tHPG = 95 °C, respectively, for the LiCl-H2O system.
This can be explained by the following facts. For each system, the pressure of the absorber rises with the increase in CR2, which enhances the absorption process in the absorber; thus, the concentration of the weak solution leaving the absorber becomes lower at a fixed absorption temperature. In this instance, the solution concentration differences between the inlet and outlet of both the HPG and LPG are augmented, resulting in the mass flow rates of the solutions in the HPG and LPG decreasing, as well as their heat loads. Consequently, the COP increases with the increase in CR2 under the same operating temperatures because the effect of HPG heat load reduction is dominant over the electric power consumed by VC2.
The variations in the solution concentrations with t HPG at different CR2 levels for the SP and RP systems are shown in Figure 11 and Figure 12, respectively. It is obvious that, as the CR2 rises, the concentrations of the medium solutions for the SP system (x11) and RP system (x15) decrease, while the concentrations of the strong solutions for the SP system (x15) and RP system (x11) increase at the same tHPG. The gap between the concentrations of the medium and strong solutions is narrowed considerably with the increase in the distribution ratio. Furthermore, the SP and RP systems with a higher CR2 could operate at lower solution concentrations compared to the conventional systems without vapor compressors when the tHPG becomes lower. In the operating ranges of the SP system with D = 0.4, the concentrations of the strong solutions range from 49.37% to 65.44% and from 35.83% to 47.79%, respectively, for the LiBr-H2O and LiCl-H2O working pairs at CR2 = 2, while they range from 55.42% to 64.89% and from 42.90% to 47.95%, respectively, at CR2 = 1.
Compared to the SP and RP systems with VC1, the systems adopting VC2 exhibit lower concentrations of the strong solutions at the same HPG temperature and compression ratio. In the condition that tHPG = 110 °C and D = 0.4, the concentrations of the strong solutions are approximately 54.68% and 55.09%, respectively, for the SP and RP systems at CR2 = 2, compared with that of 58.49% and 58.83%, respectively, at CR1 = 2. Therefore, the operating ranges of the SP and RP systems become wider with the help of VC2 because the lower concentrations of the weak and strong solutions are suitable for low-temperature heat source utilization.

5.4. Effect of CR1 and CR2 on the Performance of DEARS

In this section, a set of specific operating conditions are chosen to investigate the effect of CR1 and CR2 on the system performance at D = 0.4. To cover a great range of operating conditions, the system performance is analyzed for three different CR1 levels (1–1.5–2), while the CR2 ranges from 1 to 2. The obtained results for the LiBr-H2O and LiCl-H2O SP systems are shown in Figure 13 and Figure 14. It can be seen that the proposed systems with higher CR1 and CR2 have a great advantage in operating at low tHPG. In the condition that CR1 and CR2 are equal to 2, the LiBr-H2O and LiCl-H2O SP systems can operate at tHPG =75 °C with high COPs and exergetic efficiencies of approximately 1.183 and 0.2330, respectively, for the LiBr-H2O working pair, as well as 1.310 and 0.2504, respectively, for the LiCl-H2O working pair. This fact means that the proposed systems can be driven by low-temperature heat sources below 100 °C at relatively higher values of CR1 and CR2 with satisfactory performance.
It can be seen from Figure 13 that, at a constant CR1, the COP for each LiBr-H2O and LiCl-H2O SP system rises with the increase in CR2 under the same operating temperatures, while the exergetic efficiency reaches its maximum value with the variation in tHPG, as shown in Figure 14. At a constant CR2, the maximum values of the COP and exergetic efficiency decrease slightly for the systems as CR1 increases. The maximum COPs for the LiBr-H2O SP systems are obtained at CR2 = 2, which are close to 1.389, 1.86, and 1.384, respectively, for the three incremental CR1 levels, corresponding to the tHPG of 115 °C, 100 °C, and 95 °C, respectively. Similarly, the maximum COPs for the LiCl-H2O SP systems reach 1.415, 1.405, and 1.398, respectively, for these three CR1 levels, corresponding to the tHPG of 110 °C, 95 °C, and 90 °C, respectively. It is clear that the optimum system performance can be achieved by adjusting the values of CR1 and CR2 according to the heat source temperature.
Figure 15 and Figure 16 present the effects of CR1 and CR2 on the COP and exergetic efficiency for the LiBr-H2O and LiCl-H2O RP systems. It is apparent that, as CR1 and CR2 increase, the LiBr-H2O and LiCl-H2O RP systems exhibit better performance at lower values of tHPG. The LiBr-H2O and LiCl-H2O RP systems can operate at a low tHPG of approximately 75 °C with COPs of 1.164 and 1.295, respectively, and the exergetic efficiencies of 0.2310 and 0.2489, respectively, when CR1 and CR2 are equal to 2. This means that the compression-assisted systems could utilize low-temperature heat energy efficiently, and the LiCl-H2O working pair is more suitable than the LiBr-H2O working pair in this situation due to the higher COP and exergetic efficiency. As the tHPG rises, the COP for each RP system increases sharply at first and then maintains a certain level, while the exergetic efficiency increases initially to reach its peak and then declines rapidly. For almost all the cases, the maximum COP and exergetic efficiency could be obtained at the condition that CR2 = 2, and they are calculated to be 1.371 and 0.2420, respectively, for the LiBr-H2O RP systems, as well as 1.40 and 0.2515, respectively, for the LiCl-H2O RP systems.

6. Conclusions

In this study, new series parallel and reverse parallel configurations for compression-assisted DEARS are investigated. Performance comparisons between the LiCl-H2O and LiBr-H2O working pairs are conducted under various values of the compression ratio (CR) and distribution ratio (D) considering the crystallization problem. The main conclusions are drawn as follows.
(1) The SP and RP systems with higher distribution ratios are conducive to extending the operation ranges and utilizing the heat energy with higher temperatures. As the distribution ratio rises, the COP and exergetic efficiency increase slightly in the SP system, but decrease in the RP system. In the comparison of the two configurations, the series parallel flow has an advantage in the operating range, but the reverse parallel flow shows a slightly higher COP and exergetic efficiency.
(2) The compression-assisted systems improve the performance substantially at lower HPG temperature conditions, which means that low-temperature heat energy could be utilized efficiently. The compressor placed between the evaporator and absorber is more effective than that between the HPG and LPG in the aspect of lowering the heat source temperature and improving system performance.
(3) In all the examined cases, LiCl-H2O is the working pair with better performance in terms of COP and exergetic efficiency, especially in low-temperature heat source utilization. The operating range of the LiCl-H2O system is extended obviously at a higher CR2 with a distribution ratio of 0.4, which is feasible for the LiCl-H2O working pair in practical application.
(4) The proposed system at relatively higher CR1 and CR2 values could utilize low-temperature heat sources below 100 °C with satisfactory performance. In the condition that the CR1 and CR2 are equal to 2, the LiBr-H2O and LiCl-H2O systems could operate at a low tHPG of approximately 75 °C with high levels of COP and exergetic efficiency above 1.16 and 0.231, respectively, for the LiBr-H2O working pair, as well as 1.29 and 0.248, respectively, for the LiCl-H2O working pair.
(5) At a certain value of CR1, the maximum values of the COP and exergetic efficiency for the LiBr-H2O and LiCl-H2O systems rise with the increase in CR2. For all the examined cases, the maximum values of the COP and exergetic efficiency occur in the SP configuration at CR2 = 2 and D = 0.4, which are 1.389 and 0.2454, respectively, for the LiBr-H2O working pair, as well as 1.415 and 0.2569, respectively, for the LiCl-H2O working pair.

Author Contributions

Formal analysis, T.L.; validation, T.L.; writing—original draft preparation, T.L.; project administration, Z.Q.; supervision, Z.Q.; software, J.R.; methodology, J.R.; investigation, J.R.; writing—review and editing, J.R. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Hubei Province Technological Innovation Special Fund, grant number 2019BKJ002.

Data Availability Statement

The data presented in this study are available on request from the corresponding author. The data are not publicly available due to privacy.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

hspecific enthalpy (kJ·kg−1)evaevaporator
mmass flow rate (kg·s−1)exexergy
Q ˙ heat load (kW)HSheat source
Ttemperature (K)HTHEhigh-temperature heat exchanger
ttemperature (°C)HPGhigh-pressure generator
W ˙ power (kW)isisentropic
xmass concentration of solutionLTHElow-temperature heat exchanger
Subscripts and AbbreviationsLPGlow-pressure generator
0reference pointPusolution pump
absabsorberRPreverse parallel
concondenserSPseries parallel
COPcoefficient of performanceVCvapor compressor
CRcompression ratio
CScold sourceGreek Letters
Ddistribution ratioηefficiency
EVexpansion valveεheat exchanger effectiveness

References

  1. Somu, N.; Gauthama Raman, M.R.; Ramamritham, K. A hybrid model for building energy consumption forecasting using long short term memory networks. Appl. Energy 2020, 261, 114131. [Google Scholar] [CrossRef]
  2. Chi, F.; Xu, L.; Peng, C. Integration of completely passive cooling and heating systems with daylighting function into courtyard building towards energy saving. Appl. Energy 2020, 266, 114865. [Google Scholar] [CrossRef]
  3. Tan, X.; Lai, H.; Gu, B.; Zeng, Y.; Li, H. Carbon emission and abatement potential outlook in China’s building sector through 2050. Energy Policy 2018, 118, 429–439. [Google Scholar] [CrossRef]
  4. Chi, F.; Liu, Y.; Yan, J. Integration of Radiative-based air temperature regulating system into residential building for energy saving. Appl. Energy 2021, 301, 117426. [Google Scholar] [CrossRef]
  5. Alobaid, M.; Hughes, B.; Calautit, J.K.; O’Connor, D.; Heyes, A. A review of solar driven absorption cooling with photovoltaic thermal systems. Renew. Sustain. Energy Rev. 2017, 76, 728–742. [Google Scholar] [CrossRef]
  6. Asadi, J.; Amani, P.; Amani, M.; Kasaeian, A.; Bahiraei, M. Thermo-economic analysis and multi-objective optimization of absorption cooling system driven by various solar collectors. Energy Convers. Manag. 2018, 173, 715–727. [Google Scholar] [CrossRef]
  7. Xu, Z.Y.; Wang, R.Z. Comparison of CPC driven solar absorption cooling systems with single, double and variable effect absorption chillers. Sol. Energy 2017, 158, 511–519. [Google Scholar] [CrossRef]
  8. Mahmoudi, S.M.S.; Akbari Kordlar, M. A new flexible geothermal based cogeneration system producing power and refrigeration. Renew. Energy 2018, 123, 499–512. [Google Scholar] [CrossRef]
  9. Han, B.-C.; Cheng, W.-L.; Nian, Y.-L.; Yang, L.; Zhao, R. Evaluation of an ammonia-water absorption long-distance cooling/heating system for enhanced geothermal resources. Energy Convers. Manag. 2019, 192, 346–358. [Google Scholar] [CrossRef]
  10. Yilmaz, C. Thermodynamic and economic investigation of geothermal powered absorption cooling system for buildings. Geothermics 2017, 70, 239–248. [Google Scholar] [CrossRef]
  11. Ebrahimi, K.; Jones, G.F.; Fleischer, A.S. Thermo-economic analysis of steady state waste heat recovery in data centers using absorption refrigeration. Appl. Energy 2015, 139, 384–397. [Google Scholar] [CrossRef]
  12. Salmi, W.; Vanttola, J.; Elg, M.; Kuosa, M.; Lahdelma, R. Using waste heat of ship as energy source for an absorption refrigeration system. Appl. Therm. Eng. 2017, 115, 501–516. [Google Scholar] [CrossRef]
  13. Cui, P.; Yu, M.; Liu, Z.; Zhu, Z.; Yang, S. Energy, exergy, and economic (3E) analyses and multi-objective optimization of a cascade absorption refrigeration system for low-grade waste heat recovery. Energy Convers. Manag. 2019, 184, 249–261. [Google Scholar] [CrossRef]
  14. Arshi Banu, P.S.; Sudharsan, N.M. Review of water based vapour absorption cooling systems using thermodynamic analysis. Renew. Sustain. Energy Rev. 2018, 82, 3750–3761. [Google Scholar] [CrossRef]
  15. Sun, J.; Fu, L.; Zhang, S. A review of working fluids of absorption cycles. Renew. Sustain. Energy Rev. 2012, 16, 1899–1906. [Google Scholar] [CrossRef]
  16. Fong, K.F.; Lee, C.K.; Chow, C.K.; Yuen, S.Y. Simulation–optimization of solar–thermal refrigeration systems for office use in subtropical Hong Kong. Energy 2011, 36, 6298–6307. [Google Scholar] [CrossRef]
  17. Gogoi, T.K.; Konwar, D. Exergy analysis of a H2O–LiCl absorption refrigeration system with operating temperatures estimated through inverse analysis. Energy Convers. Manag. 2016, 110, 436–447. [Google Scholar] [CrossRef]
  18. Bellos, E.; Tzivanidis, C.; Pavlovic, S.; Stefanovic, V. Thermodynamic investigation of LiCl-H2O working pair in a double effect absorption chiller driven by parabolic trough collectors. Therm. Sci. Eng. Prog. 2017, 3, 75–87. [Google Scholar] [CrossRef]
  19. Parham, K.; Atikol, U.; Yari, M.; Agboola, O.P. Evaluation and optimization of single stage absorption chiller using (LiCl + H2O) as the working pair. Adv. Mech. Eng. 2013, 5, 683157. [Google Scholar] [CrossRef]
  20. Gunhan, T.; Ekren, O.; Demir, V.; Hepbasli, A.; Erek, A.; Sahin, A.S. Experimental exergetic performance evaluation of a novel solar assisted LiCl–H2O absorption cooling system. Energy Build. 2014, 68, 138–146. [Google Scholar] [CrossRef]
  21. Patel, J.; Pandya, B.; Mudgal, A. Exergy based analysis of LiCl-H2O absorption cooling system. Energy Procedia 2017, 109, 261–269. [Google Scholar] [CrossRef]
  22. Bellos, E.; Tzivanidis, C.; Antonopoulos, K.A. Exergetic and energetic comparison of LiCl-H2O and LiBr-H2O working pairs in a solar absorption cooling system. Energy Convers. Manag. 2016, 123, 453–461. [Google Scholar] [CrossRef]
  23. Ren, J.; Qian, Z.; Yao, Z.; Gan, N.; Zhang, Y. Thermodynamic evaluation of LiCl-H2O and LiBr-H2O absorption refrigeration systems based on a novel model and algorithm. Energies 2019, 12, 3037. [Google Scholar] [CrossRef]
  24. Garousi Farshi, L.; Seyed Mahmoudi, S.M.; Rosen, M.A.; Yari, M. A comparative study of the performance characteristics of double-effect absorption refrigeration systems. Int. J. Energy Res. 2012, 36, 182–192. [Google Scholar] [CrossRef]
  25. Garousi Farshi, L.; Seyed Mahmoudi, S.M.; Rosen, M.A. Analysis of crystallization risk in double effect absorption refrigeration systems. Appl. Therm. Eng. 2011, 31, 1712–1717. [Google Scholar] [CrossRef]
  26. Garousi Farshi, L.; Mahmoudi, S.M.S.; Rosen, M.A.; Yari, M.; Amidpour, M. Exergoeconomic analysis of double effect absorption refrigeration systems. Energy Convers. Manag. 2013, 65, 13–25. [Google Scholar] [CrossRef]
  27. Konwar, D.; Gogoi, T.K. Performance of double effect H2O–LiCl absorption refrigeration systems and comparison with H2O–LiBr systems, Part 1: Energy analysis. Therm. Sci. Eng. Prog. 2018, 8, 184–203. [Google Scholar] [CrossRef]
  28. Konwar, D.; Gogoi, T.K. Performance of double effect H2O–LiCl absorption refrigeration systems and comparison with H2O–LiBr systems, Part 2: Exergy analysis. Therm. Sci. Eng. Prog. 2018, 8, 171–183. [Google Scholar] [CrossRef]
  29. Dixit, M.; Arora, A.; Kaushik, S.C. Thermodynamic and thermoeconomic analyses of two stage hybrid absorption compression refrigeration system. Appl. Therm. Eng. 2017, 113, 120–131. [Google Scholar] [CrossRef]
  30. Bouaziz, N.; Lounissi, D. Energy and exergy investigation of a novel double effect hybrid absorption refrigeration system for solar cooling. Int. J. Hydrogen Energy 2015, 40, 13849–13856. [Google Scholar] [CrossRef]
  31. Shu, G.; Che, J.; Tian, H.; Wang, X.; Liu, P. A compressor-assisted triple-effect H2O-LiBr absorption cooling cycle coupled with a Rankine Cycle driven by high-temperature waste heat. Appl. Therm. Eng. 2017, 112, 1626–1637. [Google Scholar] [CrossRef]
  32. Ventas, R.; Lecuona, A.; Zacarías, A.; Venegas, M. Ammonia-lithium nitrate absorption chiller with an integrated low-pressure compression booster cycle for low driving temperatures. Appl. Therm. Eng. 2010, 30, 1351–1359. [Google Scholar] [CrossRef]
  33. Sun, Y.; Di, G.; Wang, J.; Wang, X.; Wu, W. Performance analysis of R1234yf/ionic liquid working fluids for single-effect and compression-assisted absorption refrigeration systems. Int. J. Refrig. 2020, 109, 25–36. [Google Scholar] [CrossRef]
  34. Wu, W.; Leung, M.; Ding, Z.; Huang, H.; Bai, Y.; Deng, L. Comparative analysis of conventional and low-GWP refrigerants with ionic liquid used for compression-assisted absorption cooling cycles. Appl. Therm. Eng. 2020, 172, 115145. [Google Scholar] [CrossRef]
  35. Conde, M.R. Properties of aqueous solutions of lithium and calcium chlorides: Formulations for use in air conditioning equipment design. Int. J. Therm. Sci. 2004, 43, 367–382. [Google Scholar] [CrossRef]
  36. Pátek, J.; Klomfar, J. A computationally effective formulation of the thermodynamic properties of LiBr–H2O solutions from 273 to 500K over full composition range. Int. J. Refrig. 2006, 29, 566–578. [Google Scholar] [CrossRef]
  37. Gomri, R. Second law comparison of single effect and double effect vapour absorption refrigeration systems. Energy Convers. Manag. 2009, 50, 1279–1287. [Google Scholar] [CrossRef]
  38. Gomri, R.; Hakimi, R. Second law analysis of double effect vapour absorption cooler system. Energy Convers. Manag. 2008, 49, 3343–3348. [Google Scholar] [CrossRef]
Figure 1. Schematic diagram of the compression-assisted DEARS for the (a) series parallel configuration; (b) reverse parallel configuration.
Figure 1. Schematic diagram of the compression-assisted DEARS for the (a) series parallel configuration; (b) reverse parallel configuration.
Energies 16 06036 g001
Figure 2. P-T-x diagram of the compression-assisted DEARS for the (a) series parallel configuration; (b) reverse parallel configuration.
Figure 2. P-T-x diagram of the compression-assisted DEARS for the (a) series parallel configuration; (b) reverse parallel configuration.
Energies 16 06036 g002
Figure 3. Performance indicators of the series parallel and reverse parallel configurations with the variation in t HPG at different distribution ratio levels. (a) COP; (b) exergetic efficiency.
Figure 3. Performance indicators of the series parallel and reverse parallel configurations with the variation in t HPG at different distribution ratio levels. (a) COP; (b) exergetic efficiency.
Energies 16 06036 g003
Figure 4. Variations in solution concentrations with t HPG at different distribution ratio levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Figure 4. Variations in solution concentrations with t HPG at different distribution ratio levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Energies 16 06036 g004
Figure 5. Variation in COP with t HPG at different CR1 levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Figure 5. Variation in COP with t HPG at different CR1 levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Energies 16 06036 g005
Figure 6. Variation in exergetic efficiency with t HPG at different CR1 levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Figure 6. Variation in exergetic efficiency with t HPG at different CR1 levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Energies 16 06036 g006
Figure 7. Variations in solution concentrations with t HPG at different CR1 levels in series parallel configuration. (a) D = 0; (b) D = 0.4.
Figure 7. Variations in solution concentrations with t HPG at different CR1 levels in series parallel configuration. (a) D = 0; (b) D = 0.4.
Energies 16 06036 g007
Figure 8. Variations in solution concentrations with t HPG at different CR1 levels in reverse parallel configuration. (a) D = 0; (b) D = 0.4.
Figure 8. Variations in solution concentrations with t HPG at different CR1 levels in reverse parallel configuration. (a) D = 0; (b) D = 0.4.
Energies 16 06036 g008
Figure 9. Variation in COP with t HPG at different CR2 levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Figure 9. Variation in COP with t HPG at different CR2 levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Energies 16 06036 g009
Figure 10. Variation in exergetic efficiency with t HPG at different CR2 levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Figure 10. Variation in exergetic efficiency with t HPG at different CR2 levels for the (a) series parallel configuration; (b) reverse parallel configuration.
Energies 16 06036 g010
Figure 11. Variations in solution concentrations with t HPG at different CR2 levels in series parallel configuration. (a) D = 0; (b) D = 0.4.
Figure 11. Variations in solution concentrations with t HPG at different CR2 levels in series parallel configuration. (a) D = 0; (b) D = 0.4.
Energies 16 06036 g011
Figure 12. Variations in solution concentrations with t HPG at different CR2 levels in reverse parallel configuration. (a) D = 0; (b) D = 0.4.
Figure 12. Variations in solution concentrations with t HPG at different CR2 levels in reverse parallel configuration. (a) D = 0; (b) D = 0.4.
Energies 16 06036 g012
Figure 13. Effect of CR1 and CR2 on the COP in SP configuration for the (a) LiBr-H2O system; (b) LiCl-H2O system.
Figure 13. Effect of CR1 and CR2 on the COP in SP configuration for the (a) LiBr-H2O system; (b) LiCl-H2O system.
Energies 16 06036 g013
Figure 14. Effect of CR1 and CR2 on the exergetic efficiency in SP configuration for the (a) LiBr-H2O system; (b) LiCl-H2O system.
Figure 14. Effect of CR1 and CR2 on the exergetic efficiency in SP configuration for the (a) LiBr-H2O system; (b) LiCl-H2O system.
Energies 16 06036 g014
Figure 15. Effect of CR1 and CR2 on the COP in RP configuration for the (a) LiBr-H2O system; (b) LiCl-H2O system.
Figure 15. Effect of CR1 and CR2 on the COP in RP configuration for the (a) LiBr-H2O system; (b) LiCl-H2O system.
Energies 16 06036 g015
Figure 16. Effect of CR1 and CR2 on the exergetic efficiency in RP configuration for the (a) LiBr-H2O system; (b) LiCl-H2O system.
Figure 16. Effect of CR1 and CR2 on the exergetic efficiency in RP configuration for the (a) LiBr-H2O system; (b) LiCl-H2O system.
Energies 16 06036 g016
Table 1. Comparison of the simulation results obtained from this work with those reported in the literature for the LiBr-H2O DEARS at the same operating conditions (tHPG = 130 °C, tLPG = 80 °C, teva = 4 °C, tabs = tcon = 35 °C, ε HTHE = ε HTHE = 0.7, Q ˙ eva = 300 kW).
Table 1. Comparison of the simulation results obtained from this work with those reported in the literature for the LiBr-H2O DEARS at the same operating conditions (tHPG = 130 °C, tLPG = 80 °C, teva = 4 °C, tabs = tcon = 35 °C, ε HTHE = ε HTHE = 0.7, Q ˙ eva = 300 kW).
ParameterRef. [24]Ref. [38]Present Study
Heat load of HPG (kW)252.394252.407252.417
Heat load of condenser (kW)167.190167.205166.892
Heat load of evaporator (kW)300.000300.000300.000
Heat load of absorber (kW)385.203385.236384.714
COP1.1881.1891.189
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Lei, T.; Qian, Z.; Ren, J. Performance Evaluation of LiBr-H2O and LiCl-H2O Working Pairs in Compression-Assisted Double-Effect Absorption Refrigeration Systems for Utilization of Low-Temperature Heat Sources. Energies 2023, 16, 6036. https://doi.org/10.3390/en16166036

AMA Style

Lei T, Qian Z, Ren J. Performance Evaluation of LiBr-H2O and LiCl-H2O Working Pairs in Compression-Assisted Double-Effect Absorption Refrigeration Systems for Utilization of Low-Temperature Heat Sources. Energies. 2023; 16(16):6036. https://doi.org/10.3390/en16166036

Chicago/Turabian Style

Lei, Tong, Zuoqin Qian, and Jie Ren. 2023. "Performance Evaluation of LiBr-H2O and LiCl-H2O Working Pairs in Compression-Assisted Double-Effect Absorption Refrigeration Systems for Utilization of Low-Temperature Heat Sources" Energies 16, no. 16: 6036. https://doi.org/10.3390/en16166036

APA Style

Lei, T., Qian, Z., & Ren, J. (2023). Performance Evaluation of LiBr-H2O and LiCl-H2O Working Pairs in Compression-Assisted Double-Effect Absorption Refrigeration Systems for Utilization of Low-Temperature Heat Sources. Energies, 16(16), 6036. https://doi.org/10.3390/en16166036

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop