1. Introduction
Urban agriculture has been developed throughout history, particularly during times of crisis, where residents have come to grow fruits and vegetables in community or personal gardens to access a direct food source [
1]. The COVID-19 pandemic is a good example of such a world crisis that triggered food insecurity in cities [
2,
3]. Urban agriculture has emerged to address these issues and allow the production of fresh and local goods to avoid disruptions to global food supply chains. While this reduces food insecurities and increases social well-being, this agricultural method is associated with high costs and constraints [
4]. A citizen’s socioeconomic status and access to land on which personal gardening is possible are two important constraints that make personal gardens only affordable for a small proportion of the population [
5]. Therefore, social companies, community-based organizations and municipal initiatives play a key role in improving food security in unprivileged districts [
6], considering the development of social economy initiatives can contribute to food security in neighborhoods.
Greenhouses are becoming increasingly popular for agriculture due to their high output, which is 10–20 times greater per unit area than outdoor production [
7]. However, maintaining a controlled temperature in these environments induces significant energy costs. To avoid damaging plants, the air temperature must remain within a specific range, with temperature variations smaller than 5–7 °C [
8]. As a result, the majority of the energy consumed for greenhouse operations goes toward heating the building, while the rest is used to provide electrical apparatus and food transportation [
9]. These factors reveal a significant challenge for greenhouse growers in cold regions who must find affordable solutions.
Climate change and global warming due to anthropogenic nature are major societal concerns where CO
2 emissions must be reduced [
10]. Hence, the transition toward sustainable renewable energies is important for decarbonising the energy sector. It is therefore critical to provide energy to urban greenhouses according to (1) renewable energy sources, which have a lower carbon footprint compared to traditional fossil fuels; (2) lower energy dependence, where operators will reduce their vulnerability to cost fluctuations and energy supplies disruptions [
11]; and (3) social acceptance, where using renewable energies can enhance the public image and reputation of environmentally responsible food producers.
Ground-source heat pump systems (GSHP) account for most of the geothermal applications in direct use, with 71.6% of the installed capacity and 59.2% of annual energy consumption reported in 2020 [
7]. However, these systems have higher installation costs compared to traditional heating systems [
12]. There are two main types of geothermal heat exchangers: open loops (groundwater or surface water) and closed loops. The open loops installed in aquifers or surface water circulate water from an aquifer, lake, or pond to the heat pump; however, this method is less common, as it requires a nearby water source or specific hydrogeological conditions. Ground-coupled heat pumps commonly use closed-loop heat exchangers installed in boreholes or trenches, given they can be installed everywhere.
Slinky-coil horizontal ground heat exchangers (HGHEs) can be a cost-effective method for reducing GSHP system installation costs, given they only require shallow excavations instead of borehole drilling. However, this type of HGHE requires a decent amount of space to bury the heat exchange pipes, which are exposed to land area problems when a building is located in a limited space. However, optimization techniques can be employed to reduce the land area needed. For example, the geothermal system can be combined with another type of heating system or the heat exchange rate per unit of the land area can be improved by optimizing the system design [
13,
14,
15]. Greenhouses can be compatible with such hybrid geothermal systems relying on HGHEs, given their floors are often made of unconsolidated soils, which facilitate installation.
Chong et al. [
16] developed a slinky HGHE numerical model using the ANSYS Fluent software, testing five different setting configurations of 0.25 m, 0.5 m, 1.0 m, 2.0 m and 3.0 m with a diameter of 0.8 m, 1 m and 1.2 m. The results suggested that reducing the coil pitch could improve the system’s overall performance, reduce the system’s thermal resistivity by 20%, and decrease the overall excavation costs by 15%. They also concluded that local ground thermal and hydraulic properties highly influenced the system’s performance.
Tang et al. [
17] modeled a numerical slinky-coil HGHE involving an atmosphere–soil–HGHE interaction, validating the model with a local temperature probe and comparing measured temperatures to a simulated temperature. Their work demonstrated that there is no significant difference in the outlet fluid temperature when the depth of the HGHE is increased from 0.5 m to 1 m. The study points out that numerical simulations are important in the case of an atmosphere–soil–HGHE interaction.
Larwa et al. [
18] suggest that slinky-type ground heat exchangers can be modeled using a one-dimensional model. They carried out experimental investigations of heat transfer between hot water flowing through a slinky-coil heat exchanger and the surrounding ground. Using an analytical solution based on the ring source model, they analyzed the measurements taken on a slinky-coil HGHE at a depth of 0.5 m for 3 days. They concluded that when the pitch is small, the temperature distribution in the surrounding ground can be approximated using a one-dimensional method. This simplification assumes that the heat transfer in the ground is similar to that of a flat slab. Here, using a one-dimension model simplifies the problem by neglecting any variations in temperature in other directions.
Wu et al. [
19] investigated the thermal performance of a slinky-coil HGHE coupled to a GSHP system for different coil diameters and slinky interval distances. They validated experimental measurements with 3D numerical simulations of such systems using ANSYS Fluent software. The results show that the COP decreased with the running time and changed with ambient environmental conditions. Numerical simulations demonstrated that there is no significant difference caused by variations in the coil diameter in the specific heat extraction of the slinky heat exchanger.
Xing et al. [
20] studied different approaches to simulating under-building HGHEs installed under building foundations by comparing an analytical and a numerical model with experimental measurements. The analytical model is based on a superposition of line sources and sinks, while the numerical model uses a two-dimensional finite volume based on a superposition developed in the HVACSIM+ environment. To assess the impact of ambient temperature and environment on the performance of such a system, they operated both models at six different sites across the USA. The results show that, while the analytical models are associated with excessive errors, numerical models are time-consuming. They recommended the use of a one-dimensional ground temperature numerical model, which would require little computation time.
Fujii et al. [
13,
14] numerically modeled a slinky HGHE and the surrounding soil using the finite-element software FEFLOW [
21]. A comparison between the numerical model and a thermal response test (TRT) experiment on the HGHE was made to validate the simulation approach. The results obtained from their HGHE thin-plate numerical simulations revealed that when using the thin plate model, pipe and fluid thermal conductivity of 0.025 W m
−1 K
−1 to 0.045 W m
−1 K
−1, respectively, tends to reproduce TRT data and the in-situin-situ operation conditions. This present study used the same approach as that developed by Fujii et al. [
13,
14] since slinky-coil HGHEs are difficult to model. The heat exchange rate per unit length of the straight horizontal heat exchange pipes is significantly lower than that obtained with a vertical ground heat exchanger because shallow ground temperature is affected by seasonal air temperature variations, and dry soils near the ground surface have relatively low thermal conductivity. Using slinky-coil heat exchange pipes instead of straight pipes is, therefore, a good alternative to optimize the HGHEs’ design and reduce trench length, which can facilitate the development of such a system, even in cases of limited land availability [
14].
This work provides a comprehensive assessment of the heating and cooling capacity of HGHEs in the context of urban greenhouse systems. By considering different scenarios and incorporating a sensitivity analysis, we offer a deeper understanding of the different interactions between the building and the HGHE. The work achieved also explored the use of HGHEs for greenhouses, for which limited has been made. The practical aspect of this study is also noteworthy, providing insights for practitioners aiming to improve sustainability of heating and cooling. Our work finally showed that a finite-element simulator such as FEFLOW [
21] could be used in such practical cases for HGHE under a greenhouse, which is not initially covered by the software.
In urban areas, there is little land space to install HGHEs. Therefore, it seems important to know if HGHEs installed under the limited surface of a building, such as a greenhouse, can cover significant heating and cooling loads. It is assumed that HGHEs covering a limited area located under a greenhouse can be attractive to users because of their reduced installation cost but would likely not cover the full heating or cooling loads of the greenhouse when installed in a continental humid climate like that of Quebec, Canada, where the heating demand is high in winter. Thus, numerical simulations using FEFLOW [
21] were made following the work conducted by Fujii et al. [
13,
14] to evaluate the percentage of greenhouse heating and cooling loads that can be covered with an HGHE of limited surface area installed under a greenhouse. This approach combines Fujii’s model [
13,
14] with an actual greenhouse energy consumption profile, allowing for the testing and evaluation of the system’s potential through a 5-year simulation. This methodology serves as a valuable practical application tool, providing insights and data for assessing the system’s performance similar to real-world scenarios.
It is important to assess the effect of the greenhouse on such a system, considering local ground thermal properties, ambient and greenhouse air temperature and building energy consumption. A field site was chosen and characterized for this study, aiming to provide information and guidance to integrate HGHEs in greenhouses located in a cold continental humid climate such as Quebec. The Cégep de La Pocatière is planning to build an enclosed greenhouse and complementary research buildings (
Figure 1). The project aims to demonstrate that such a research complex can be air-conditioned mainly with renewable energy sources, such as geothermal heat pump systems. A hybrid heating system is envisioned, and the HGHE would be installed below the greenhouse to minimize installation costs, knowing that the system can only fulfill part of the heating and cooling needs. Auxiliary heating and cooling sources would be needed to cover the full heating and cooling loads of the greenhouse. This site was consequently chosen to conduct the study, although obtained conclusions can provide guidelines for other greenhouses in a similar setting.
4. Results
The results for Scenario 1 show that the constant temperature of the greenhouse above the HGHE influences the temperature in the first underground meters (
Figure 8 and
Figure 9). Here, the constant temperature seems to affect mainly the zone directly below the greenhouse. The results are presented for the months of February and July for both the first and fifth simulation years. February and July represent and will be referred to as the heating and cooling seasons.
The numerical simulations provide results in the form of fluid temperature for the inlet and the outlet. The following graph shows the EFT for every case, compared with the LFT (
Figure 10). The bigger the difference between the EFT and LFT, the better the system’s performance. The LFT (blue line) of 34 °C is for the cooling period, while the LFT of −4 °C is for the heating period.
The highest temperature difference between the LFT and EFT during heating periods is observed for Scenario 2, followed by Scenario 1, Scenario 4 (1 m), Scenario 3, Base case and Scenario 4 (2 m). These intermediate results show that the greenhouse has a positive effect on the heating performance. On the other hand, the Base case shows the highest temperature difference during the cooling periods, followed by Scenario 2, Scenario 1, Scenario 3, Scenario 4 (1 m) and Scenario 4 (2 m), which implies that the HGHE is less performant during the cooling periods. The performance of the heat exchanger varies among scenarios at different times of the month. Some scenarios, such as Scenario 4, exhibit a better performance at the beginning of the month, while others perform better toward the end. Hence, evaluating the best scenario based on fluid temperature alone is challenging. To have a better understanding of the results, the fluid temperature can therefore be converted into the percentage of the total heating and cooling covered by the system. The following results focus on the months of February for the heating season and July for the cooling season (
Table 7;
Figure 11). During the other months, the system covers a higher percentage of the heating and cooling demand.
The COP values shown in
Table 7 are higher than the Base case for every scenario in the heating mode, while they are lower in the cooling mode. There is a 0 to 0.18 increase for the month of February, while the values decrease between 0.05 to 0.27 for the month of July when comparing every scenario with the Base case. In the heating mode, Scenario 2 has a higher improvement on the heat pump’s COP. The results show that incorporating a greenhouse structure above the HGHE enhances the heating efficiency while deteriorating the cooling efficiency.
The results for the peak months of February and July demonstrate that the presence of a greenhouse above the HGHE improves the system’s performance for heating but slightly lowers the percentage covered during the cooling phases. The following comparisons between scenarios and the Base case are made for the same year to make the comparisons lighter. Scenario 1 increases the load covered in February by around 15% while it reduces the load covered in June by around 2%. Scenario 2, which implies installing the HGHE at a 1 m depth, increases the load covered in February by 23% to 25% and increases it by 0.5% in July. Scenario 3, which implies installing the HGHE at a depth of 2 m, increases the load covered by around 12% during February while lowers it by 3% during July. Scenario 4, which combines Scenarios 2 and 3, improves both heating and cooling by 28% and 6%, respectively. When looking only at the heating demand, Scenario 4 covers the highest percentage of the total heating load, followed by Scenario 2, Scenario 1, Scenario 3 and the Base case. When looking only at the cooling demand, Scenario 4 covers the highest percentage of the total cooling load, followed by Scenario 2, the Base case, Scenario 1 and Scenario 3.
Figure 11 illustrates that the system exhibits better performance in terms of heating during the fifth year, whereas it performs better in terms of cooling during the first year. For the heating season, there is a 6%–8% increase between the first and the fifth years. In contrast, total cooling generally decreases by 8%–10% between the first and fifth years. This can be attributed to a warming ground temperature, either caused by an HGHE unbalanced heat injection versus extraction and temporal propagation of the thermal front from the greenhouse floor toward the subsurface. It can be assumed that the greenhouse constant temperature increases the subsurface temperature over time.
5. Sensitivity Analysis
The COP values are shown for the Base case and for Scenario 1 (
Table 8 and
Table 9). These tables only display values for the months of February and July, which are representative of the highest and lowest yearly temperatures. It is important to note that the data presented in those tables do not represent the other months.
When compared with the Base case, the results (
Table 8) show that raising and reducing ground temperature and changing the ground thermal properties do not significantly impact the COP in the heating mode. There is also no significant change during the first year in the cooling mode. During the fifth year in the cooling mode, raising and lowering the surface ground temperature, respectively, results in 0.44 and −0.03 variations, while deteriorating and enhancing the ground thermal properties results in −0.62 and 0.16 COP variations.
When compared with Scenario 1, the results (
Table 9) show that raising and reducing the ground temperature and changing the ground thermal properties do not significantly impact the COP values in the heating mode. There is also no significant change during the first year in the cooling mode. During the fifth year in the cooling mode, raising and lowering the surface ground temperature, respectively, results in 0.66 and 0.01 variations, while deteriorating and enhancing the ground thermal properties results in −0.86 and 0.65 COP variations.
Those results show that, over a prolonged operation period, raising the surface ground temperature as well as reducing and enhancing ground thermal properties has a greater impact on the COP for Scenario 1 compared to the Base case. Since the observed differences are increasing through years of operation, it can be assumed that sustained fluctuations in ambient temperature would be required to impact the system’s performance. The results can also be seen in the form of percentages of the total heating and cooling loads covered by the HGHE (
Figure 12 and
Figure 13).
In the Base case (
Figure 12), variations in the surface ground temperature and thermal properties have a small impact on load coverage in the heating mode during the first year (−0.3% to 2.1%) and the fifth year (−0.9% to 1.3%). In the cooling mode, variations have a larger impact than in the heating mode during the first (−2.4% to 2.2%) and fifth years (−4% to 2%).
In Scenario 1 (
Figure 13), variations in the surface ground temperature have small effects on load coverage during the first year in the heating mode (0.1%) but larger effects during the fifth year (−0.3% to 0.8%). Variations in the ground thermal properties have a more important impact on both the first and the fifth years (−4.8% to 5.5%). In the cooling mode, variations in the surface ground temperature have a smaller effect on both the first and the fifth years (−1.5% to 1.3%), while the thermal properties have a larger impact on both the first and the fifth years (−4.8% to 4.2%).
Those numbers indicate that an ambient temperature has a smaller influence on the system’s performance if a greenhouse with a constant temperature is located above it. In this case, ground thermal properties play an important role in the HGHE’s performance, especially during the cooling phases. In the Base case’s situation, ambient temperature and ground thermal properties are both equally significant.
6. Discussion
This study explores the coupling of greenhouses with HGHEs in a particular context and investigates their heating and cooling performances in urban agriculture. However, these findings may have limited generalizability due to factors such as the short simulation period, constant input parameters, and simplified LFT assumptions. Thus, interpretations of the results should consider the following. Surface water infiltration was not considered; therefore, rain and greenhouse plant watering were assumed to have a negligible impact on the heat transport simulations. The temperature profile used only includes the constant average temperature for every month, which does not represent real-life conditions with hourly fluctuations. The energy consumption monthly values were considered constant according to the energy consumption monthly profile. However, energy consumption varies instantly throughout the day, depending on the building’s energy demand. A simplified LFT was therefore assumed using a constant LFT of −4 °C (heating periods) and 34 °C (cooling periods), while it should vary several times within a day. The model has limitations belonging to its simplifications resulting in assumptions, lack of validation and the homogeneity of the materials. To overcome these limitations, attention should be focused on incorporating more realistic scenarios, validating the models against experimental data, considering a higher range of variables, and addressing the heterogeneity and variability of relevant factors.
In order to make the study and model applicable for worldwide usage, it would be essential to consider a broader range of geographic locations, climate conditions and greenhouse types. Using local data, conducting sensitivity analyses while varying different parameters, assessing economic feasibility and considering the model’s adaptability can make simulations more applicable on a global scale.
This study followed Fujii’s approach [
14] using the same pipe diameter for the HGHEs and did not explore alternative HGHE configurations. Fujii et al. [
14] developed a specific method tailored to the conditions encountered in their TRT study. However, it is important to note that the parameters they utilized may yield different values when applied to a different soil type. Covering a higher building load with a similar system could be achieved by using thermally improved pipes or reducing the pitch, as Chong et al. [
16] indicated. Using pipes with a larger diameter can increase the heat transfer efficiency between the circulating fluid and the ground, as the overall thermal conductivity would increase, and it would be beneficial to the system’s performance.
Fujii’s work [
14] was conducted to simulate TRT for a two-week period using a horizontal HGHE, which means that the numerical simulations were only realized for a 2-week time lap. Their work shows that the simulation is well calibrated to the experimental data and that boundary conditions and input parameters are constant with those used in the experiment. Simulating the same system for 5 years can therefore differ from their experiment, given that such a comparison between the numerical and experimental models was not made with different parameters and boundaries. An HGHE simulation for a 5-year period can provide more information on the long-term performance of the system under different environmental conditions; however, small errors or inaccuracies in the model may accumulate over time and result in a deviation from the system’s true behavior. Air temperature, humidity and solar radiation can vary significantly over time; however, this study assumed constant values for these input parameters used in the numerical models.
The purpose of the sensitivity analysis was to assess the system’s response to changes in key parameters and assess their relative importance. We acknowledge that changing the ground thermal properties values may deviate from the conditions under which the model was calibrated. This variation can affect the accuracy of the results and undermine their validity. Therefore, it is essential to interpret the results of the sensitivity analysis with caution. It should be considered as a step towards understanding the behavior of an HGHE system under certain conditions rather than a validation of the model for a larger range of conditions. Future studies should also focus on model validation under a wider range of conditions, including ground thermal properties and ambient temperature.
Installing the system beneath the greenhouse offers several advantages. HGHEs are close to the surface and are impacted by air temperature and seasonal variations. Cold temperatures will increase the viscosity of the propylene glycol/water mixture, thereby reducing thermal conductivity and heat transfer [
31]. In cities like Montréal, Québec and La Pocatière, which experience cold winters, the ground temperature near the surface can fall below 0 °C. The inlet fluid temperature, or heat pump LFT, must be lower than the ground temperature to produce heat, which increases the fluid viscosity. Additionally, the fluid can freeze depending on its water proportion. Also, greenhouses are typically constructed on ground level; thus, excavating the area and installing the system directly beneath the structure is easier compared to conventional residential or commercial buildings. This arrangement is also associated with potentially low installation costs.
Our results show that an HGHE with a restricted surface area underneath a greenhouse can provide partial base loads for heating and cooling a greenhouse in a cold continental climate such as Quebec. The different scenarios show that there are strategies to increase the system’s heating efficiency; however, they are still not enough to only rely on the HGHE and the heat pump system. An auxiliary system should be considered in an urban setting, where the area covered by the HGHE is limited, and peak energy demands need to be delivered to the building. Olabi et al. [
32] suggested using hybrid geothermal systems, like solar energy systems and cooling towers, coupled with the geothermal system. The former implies that solar collectors, such as photovoltaic thermal hybrid systems, could be used to generate additional heating to cover any deficit from the geothermal system. This would allow the GHE to act as a seasonal energy storage. Such a system is difficult to install on the roof of a greenhouse, as it would prevent the sun from penetrating the building and heating the interior. Otherwise, the coupling of a cooling tower to a geothermal system aims to increase the COP by improving the system’s cooling efficiency with cold water circulation, which allows the hybrid system to maintain a soil thermal balance throughout the year. This type of system can also be coupled with borehole GHEs. Zhou et al. [
33] designed a system combining a borehole GHE and an HGHE to reduce the cost of conventional borehole GHE heat pump systems by determining the optimal shape factors, building load distribution scheme and the length of the hybrid GHE.
Géotherma Solutions Inc’s study [
23] showed that an HGHE underneath the greenhouse would not provide enough energy to cover the building’s total energy consumption. Using analytical solutions, they showed that the HGHE must be four to nine times greater than the surface area of the greenhouse to do so. This method did not take into consideration the effect of the greenhouse’s constant air temperature on the system’s performance. The ground thermal properties chosen for their studies were also lower when compared to this study. Using sizing calculations, Léveillée-Dallaire et al. [
15] showed that 30% to 40% of the heating and cooling peak loads could be covered by an HGHE of the same size as a small greenhouse in Montreal without considering the effect of the greenhouse’s constant temperature. Even though the current study used a numerical approach, the other study’s results are similar to what was obtained in the Base case, which suggests that the system can cover 7.1% of the heating and 26.5% of the cooling loads during the coldest and hottest months. It should be noted that previous studies did not include the effect of the greenhouse above the HGHE.
A comparison between the results for the Base case and Scenario 1 during February and July indicates that installing the HGHE under a greenhouse can double the heating loads covered by the system while slightly lowering the cooling loads covered. This shows that the greenhouse constant temperature has a positive effect on heat extraction. A comparison between scenarios 1, 2 and 3 demonstrates that the closer the system is to the surface (Scenario 2), the better the heat extraction. However, installing a deeper HGHE does not seem to improve either the heating or the cooling performance of the system. Furthermore, Scenario 4 appears to be the best in terms of heating and cooling performance, covering an additional 30% of heating and 6% of cooling compared to the Base case in the short term. Hence, for space optimization, it would be worth choosing this scenario to cover the maximum amount of heating and cooling possible, while further studies need to be completed to evaluate if the extra costs outweigh the system’s benefits.
Between the first and the fifth year of simulation for each scenario, the system’s capacity for heating increases while cooling decreases. In regions with cold climates, heating demand generally outweighs cooling demand, causing the local ground temperature to decrease slightly over time. However, the situation in this study slightly differs and produces contrasting results. The HGHE coupled to a heat pump does not entirely cover the building’s heating and cooling requirements. The objective of this project was to calculate the percentage of a greenhouse’s heating and cooling coverage provided by an HGHE limited in size. As a result, heat production and injection from the HGHE may not follow the building’s consumption needs. Additionally, maintaining a constant temperature in the building could contribute to this increase in the ground temperature over time. Therefore, the incomplete coverage of heating and cooling loads and the building’s constant temperature can create deviations from typical results in cold climates.
The sensitivity analysis indicates that the greenhouse’s constant air temperature reduces the system’s dependence on the ground surface temperature variations for both heating and cooling, even though cooling is less efficient. Hence, there is a notable advantage for heating periods and a small disadvantage for cooling periods. It can therefore be assumed that using such a system has an overall positive effect on the HGHE’s performance in cold regions such as Quebec. The analysis results show the importance of accurately estimating ground thermal properties either by performing a TRT or at least by analyzing ground samples. This shows that a system’s performance can vary according to different types of geological materials and thermal property values. These specific HGHE percentages of total heating and cooling loads covered are obviously expected to differ for HGHEs located in different environments; however, the results can be used as guidelines for greenhouses in a cold continental climate.
7. Conclusions
In conclusion, installing a greenhouse over an HGHE can increase the heating capacity of the system; however, the cooling efficiency tends to decrease. Heating and cooling performances vary according to the depth of the HGHE installation. Additionally, the system had an improved heating performance while the cooling capacity decreased over time, where the HGHE removed heat more efficiently in the cooling phase than during the heating phase. Overall, these results indicate that coupling greenhouses and HGHEs can be an efficient way to improve heating efficiency under some conditions; however, care should be taken to assess their effect on cooling capacity. Considering heating only, Scenario 4 covers the highest percentage of total heating demand between all scenarios, followed by Scenario 2, Scenario 1, Scenario 3 and the Base case.
The sensitivity analysis shows that a change in ground surface temperature affects the system’s performance with increasing operation time, while the ground thermal properties play an important role in the performance of the HGHE, especially during the cooling phases. In addition, ground surface temperature variations seem to play a smaller role in the system’s capacity, with a constant temperature greenhouse located above it when compared to standard HGHEs. The results also indicate the importance of measuring ground thermal properties before installing such a system.
Therefore, the study confirms that a minimum of 7.1% and 26.5% of a small greenhouse’s total heating and cooling loads can be covered in the first year of operation by an HGHE at a 1.5 m depth with no greenhouse above it (Base case). In contrast, installing this same HGHE under a greenhouse with a constant temperature of 21 °C (scenario 1) raises the heating loads covered to 22.8% but decreases the cooling loads covered to 24.2%.
The significance of this study lies in the exploration of coupling greenhouses with HGHEs for improved heating efficiency in urban agriculture. This knowledge is important for urban greenhouse farmers and policymakers seeking sustainable methods to address heating and cooling demands while minimizing energy consumption and costs. Understanding the trade-off between heating and cooling efficiency is essential for decision-making. The insights gained can inform the design of greenhouse-HGHE systems in various urban settings for specific geographic locations.
Following this study, the results could be improved by developing numerical models, including the effect of vertical fluid flow to represent precipitation and/or plant watering, which most likely impacts underground heat transport. Simulations should also be conducted with a complete energy consumption profile, which should be determined hourly to represent the actual heating and cooling demands. An LFT simulation should consider hourly consumption and select temperatures based on the time of day. Further investigations could also explore the economic feasibility of such systems in more standard geographic settings, considering factors such as the system’s maintenance and cost-effectiveness. Future studies could explore the potential of incorporating new numerical models representing different types of HGHEs, such as spiral-coil HGHEs [
34] or cylindrical-finned HGHEs [
35].