Energies 2018, 11(1), 112; https://doi.org/10.3390/en11010112

Impacts of Water Flow Rate on Freezing Prevention of Air-Cooled Heat Exchangers in Power Plants

Key Laboratory of Condition Monitoring and Control for Power Plant Equipments of Ministry of Education, School of Energy Power and Mechanical Engineering, North China Electric Power University, Beijing 102206, China
*
Author to whom correspondence should be addressed.
Received: 13 November 2017 / Revised: 13 December 2017 / Accepted: 25 December 2017 / Published: 3 January 2018
Full-Text   |   PDF [11237 KB, uploaded 3 January 2018]   |  

Abstract

Under cold ambient conditions, the freezing risk of air-cooled heat exchangers, especially the frontal finned tube bundles, has been a critical concern in power plants. Based on the freezing conditions of the cooling deltas under windy conditions, the flow and heat transfer characteristics of natural draft dry cooling system (NDDCS) with 30%, 40% and 50% increased water flow rates are investigated in this work, and the outlet circulating water temperatures of the easily freezing cooling deltas and sectors are obtained. The results show that the deltas in the middle front and rear sectors become free from freezing at all wind speeds when the circulating water flow rate is increased. For the frontal sector with increased water flow rate, the outlet water temperatures of deltas increase conspicuously at 4 m/s and 8 m/s, while as the wind speed rises to 16 m/s, these deltas still face serious freezing risks due to the huge heat rejection to ambient air. Therefore, freezing prevention of air-cooled NDDCS heat exchangers can be achieved by increasing the water flow rates at small wind speeds, while as the wind speed becomes high, the water flow redistribution is suggested for the frontal and middle sectors due to their big performance difference. View Full-Text
Keywords: NDDCS air-cooled heat exchanger; cooling delta; anti-freezing; water flow rate; outlet water temperature NDDCS air-cooled heat exchanger; cooling delta; anti-freezing; water flow rate; outlet water temperature
Figures

Figure 1a

This is an open access article distributed under the Creative Commons Attribution License which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited (CC BY 4.0).
SciFeed

Share & Cite This Article

MDPI and ACS Style

Guo, Y.; Wei, H.; Yang, X.; Wang, W.; Du, X.; Yang, L. Impacts of Water Flow Rate on Freezing Prevention of Air-Cooled Heat Exchangers in Power Plants. Energies 2018, 11, 112.

Show more citation formats Show less citations formats

Note that from the first issue of 2016, MDPI journals use article numbers instead of page numbers. See further details here.

Related Articles

Article Metrics

Article Access Statistics

1

Comments

[Return to top]
Energies EISSN 1996-1073 Published by MDPI AG, Basel, Switzerland RSS E-Mail Table of Contents Alert
Back to Top