Next Article in Journal
Sand Particle Transport Mechanisms in Rough-Walled Fractures: A CFD-DEM Coupling Investigation
Previous Article in Journal
Study on Improving International Cooperation Frameworks for Combating Illegal, Unreported, and Unregulated Fishing to Achieve Sustainable Use of Fishery Resources
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Steady-State Reactive Power Capability Analysis of Doubly-Fed Variable Speed Pumped Storage Unit Considering the Unit’s Operating Characteristics

1
School of Water Resources and Hydroelectric Engineering, Xi’an University of Technology, Xi’an 710048, China
2
PowerChina Northwest Engineering Corporation Limited, Xi’an 710065, China
*
Author to whom correspondence should be addressed.
Water 2025, 17(17), 2519; https://doi.org/10.3390/w17172519
Submission received: 11 July 2025 / Revised: 12 August 2025 / Accepted: 19 August 2025 / Published: 24 August 2025

Abstract

Based on the actual data of a 300 MW doubly-fed variable speed pumped storage units (DFVSPSUs) in China, the reactive power characteristics of both the stator side and the grid-side converter are analyzed, and the reactive power regulation capability of the unit is discussed. First, the power coupling relationship is analyzed, demonstrating that the reactive power-regulation capability is jointly composed of the stator side and the grid-side converter, without direct coupling between them. Next, we determine the doubly-fed induction generator (DFIG) capacity, explaining that the capacity of the DFIG exceeds the rated capacity of the unit. Then, we note that the stator-side reactive power regulation capability is limited by prime mover power, stator current, and rotor current, while the grid-side converter regulation capability is influenced by converter capacity and rotor-side real power. Furthermore, the stator-side, grid-side converter and total reactive power-regulation capabilities of the unit under different water heads and real power conditions are determined. The results demonstrate that fully considering the grid-side converter can increase the unit’s reactive power regulation capability by 12% to 26%. Finally, by comparing the reactive power operating ranges of fixed-speed and variable-speed units, the reactive power advantages of the variable-speed unit are quantified.

1. Introduction

With the world’s energy landscape gradually transforming towards clean energy, a large amount of new energy will be introduced into the power grid [1,2]. In the new electric power system, the energy structure has changed, and the introduction of high-proportion new energy grid integration and long-distance power transmission requires the system to have a wider reactive power regulation range [3,4], to address the challenges of load fluctuations and voltage stability [5,6,7,8]. Therefore, pumped storage units (PSUs) are widely adopted due to their flexible operating characteristics, rapid operating-condition-switching capability, and excellent reactive power regulation performance [9,10,11].
Compared with fixed-speed pumped storage units (FSPSUs), doubly-fed variable speed pumped storage units (DFVSPSUs) control output power by adjusting the speed, offering greater flexibility and efficiency [12,13]. The advantages of DFVSPSUs lie in their strong grid support, fast power response, high hydraulic efficiency, and ability to meet the fast power regulation needs of the new power system [14,15,16,17,18]. Additionally, doubly-fed units feature adjustable power under pump conditions and bidirectional power flow between the stator and rotor [19,20,21], making them superior in reactive power regulation. Due to the complex operating characteristics of doubly-fed units, analyzing their reactive power-regulation capability is critical for ensuring the stable operation of the power system, improving power transmission efficiency, and enhancing power quality.
Existing research primarily focuses on simulating and verifying the reactive power capability of doubly-fed induction generators (DFIGs) themselves [22,23,24], without comprehensively considering the operating characteristics of the pump–turbine system or applying them to pumped storage units. Some scholars have proposed that decoupled power control can quickly and accurately absorb reactive power without compromising stability [25,26]. Singh et al. [27] proposed a unified control strategy for a variable-speed pumped storage plant based on a DFIG under different grid conditions; by injecting a low-voltage DC power source during the startup of the stator circuit, slip losses were reduced, and the magnetizing current was lowered, effectively saving electrical energy. Huang et al. [28] analyzed the reactive power capability of a pumped storage unit motor and demonstrated the reactive voltage regulation range under pump conditions. Further, some scholars analyzed the stator-side reactive power characteristics of the DFIG using the V-curve method, exploring the reactive power-regulation capability of the DFVSPSU under different operating conditions, proving that doubly-fed asynchronous machines have reactive power-regulation characteristics similar to synchronous machines [29,30,31]. Chen et al. [32] presented an electromagnetic–electromechanical transient multi-time scale model to determine the operational characteristics of pumped storage units, studying the stable operating range and the response speed of active/reactive power regulation under various conditions. Li et al. [33] established a reactive power balance equation to confirm the strong reactive power-regulation capabilities of DFVSPSUs. However, previous studies have only explored the reactive power boundaries from the DFIG perspective, without considering the pump–turbine system or coupling the two for a comprehensive analysis. Additionally, the grid-side converter’s reactive power-regulation capability is often overlooked. Therefore, current research on the DFVSPSU’s reactive power regulation is still incomplete and lacks in-depth analysis of the unit.
Therefore, this study analyzes, in depth, the reactive power-regulation performance of DFVSPSUs by combining the operating characteristics of pump–turbines. On the basis of adopting a T-equivalent circuit analysis, the power boundary conditions on the generator stator side are derived, and the power operating range is clearly defined in the P-Q diagram. Through measured data and theoretical derivation, the reactive power-regulation capabilities of the stator-side and grid-side converters are quantitatively analyzed, thereby obtaining the overall reactive power regulation range of DFVSPSUs; furthermore, through a comparison with FSPSUs of the same capacity in China, it is first confirmed that variable-speed units can extend the reactive power-regulation range by 12–26%. This core discovery fills the gap in the quantitative evaluation of reactive power performance for variable-speed units, providing critical theoretical support for the stable operation of high-penetration renewable energy power grids.

2. Power Coupling Analysis of the Doubly-Fed Variable Speed Pumped Storage Unit

2.1. Operating Principle of the DFVSPSU

The DFVSPSU is a complex system with strong coupling among hydraulic, mechanical, electrical, and control subsystems. It mainly consists of a water intake system, pump–turbine system and its control system, and DFIG and its control system, as shown in the topology diagram in Figure 1. The stator of the DFIG is directly connected to the power grid, while the rotor is connected to the grid through a converter. Both the stator and rotor can exchange energy with the grid. The DFIG control system adjusts the rotor-side voltage to control the generator’s power output. The pump–turbine control system regulates the flow of the water intake system by changing the guide vane opening, thus controlling the pump–turbine system’s power output. The pump–turbine system is connected to the generator through the shaft, enabling the conversion between mechanical energy and electrical energy. These subsystems cooperate to ultimately achieve energy balance and stable operation of the DFVSPSU.
In Figure 1, we can clearly see the coupling relationship between the three speeds, as shown in (1):
ω s = ω r + ω 2 = ω r + s ω s
In the equation, ωs represents the synchronous speed of the stator rotating magnetic field of the DFIG, ωr represents the rotor speed, ω2 represents the excitation magnetic field speed of the DFIG, and s represents the slip rate of the DFIG. When ωr < ωs and s > 0, the motor operates in a sub-synchronous state; when ωr > ωs and s < 0, the DFIG operates in a super-synchronous state.
Further,
ω s = 60 f 1 / p
ω 2 = 60 f 2 / p
It can be derived that
f 1 = ω r p 60 + f 2
where f1 and f2 are the frequencies of the stator and rotor currents, respectively, and p is the number of pole pairs. During operation, since the synchronous speed ωs remains constant, the rotor speed ωr is adjusted by regulating the frequency of the rotor excitation current f2, thus achieving constant-frequency variable-speed operation of the unit.

2.2. Power Coupling Relationship of the DFVSPSU

The DFVSPSU is capable of both real power output and reactive power output. Based on the topology and operating principles described above, for the real power part, it includes the total real power output P of the unit, the stator real power output Ps, the rotor real power output Pr, and the real power output of the grid-side converter Pc. For the reactive power part, it includes the total reactive power output Q of the unit, the reactive power output from the stator side Qs, the reactive power output from the rotor side Qr, and the reactive power output from the grid-side converter Qc. The power flow directions are shown in Figure 2.
Due to the fact that the DC bus side of the back-to-back converter only exchanges real power, under the assumption of no power loss and line loss, the real power output of the grid-side converter is equal to the real power output of the rotor, as shown in (5). However, there is no equal relationship between the reactive power output of the grid-side converter and the reactive power output of the rotor side (QcQr).
P c = P r
As shown in Figure 2, for the real power output of the unit, the mechanical power output P of the unit is equal to the sum of the stator real power output Ps and the real power output of the grid-side converter Pc. Combining with (5), the following coupling relationship is obtained:
P = P s + P c = P s + P r
In this context, the real power output of the stator and rotor is also coupled with the slip rate:
P r = s P s
Therefore, the mechanical power P of the unit can be directly represented by the stator real power output Ps:
P = ( 1 s ) P s
Regarding the reactive power output of the unit, as described earlier, since the DC bus side of the back-to-back converter only exchanges real power, the reactive power output of the grid-side converter does not equal the reactive power output of the rotor side (QcQr). Furthermore, the total reactive power output Q equals the sum of the stator reactive power output Qs and the grid-side converter reactive power output Qc and is not equal to the sum of the stator reactive power output Qs and the rotor-side reactive power output Qr, as shown in the following equation:
Q = Q s + Q c Q s + Q r
Stator reactive power Qs couples with rotor reactive power Qr, while the grid-side converter’s reactive output Qc remains decoupled from Qs. Qc is constrained solely by the converter capacity and its real power output Pc. Consequently, the unit’s total reactive power Q cannot be derived directly from the stator output, unlike its mechanical power P.
Therefore, to study the reactive power characteristics of the DFVSPSU, it is necessary to analyze the reactive power characteristics of both the stator-side and the grid-side converter.

3. Reactive Power Characteristic Analysis of the Stator Side of the Doubly-Fed Variable Speed Pumped Storage Unit

In studying the reactive power-regulation capability of the stator side of the DFVSPSU, the following steps are taken: first, the operational constraints of the power output of the doubly-fed unit are explored, and then, the capacity of the DFIG is determined based on the pump–turbine data. Next, the reactive power limitation of the stator of the DFVSPSU is derived from the mathematical model, which leads to the P−Q power operating range of the DFVSPSU. Finally, the reactive power limits for both emitting and absorbing are analyzed based on the optimal operating data of the pump–turbine.

3.1. Stator Side Power Operating Constraints of the DFVSPSU

The power operating constraints on the stator side of the DFVSPSU mainly include four factors: prime mover power limitation, stator current limitation, rotor current limitation, and rotor voltage limitation:
  • Prime Mover Power Limitation (Pm):
The prime mover power limitation is primarily constrained by two factors: first, the prime mover’s power limitation usually does not exceed the rated capacity of the DFIG, and it is generally restricted by the rated real power of the machine. Second, the prime mover’s power limitation is also restricted by the pump-turbine, which can be further divided into the following: maximum and minimum output limits in turbine mode; maximum and minimum input limits in pump mode.
2.
Stator Current Limitation (Ismax):
The stator current limitation is determined by the design and materials of the motor, including the stator windings and core heating, which establish the safe operating limits. Under constant stator voltage, the rated capacity of the unit determines the allowable value of the stator current.
3.
Rotor Current Limitation (Irmax):
The rotor current refers to the current flowing through the rotor windings of the motor, which is typically determined by the heating of the rotor. The maximum rotor current Irmax of the DFVSPSU is the current flowing through the rotor windings when the unit is operating at the rated working point.
4.
Rotor Voltage Limitation (Urmax):
The maximum rotor voltage of the DFIG depends on the maximum operating voltage of the rotor and the maximum output voltage of the converter. Additionally, the slip ratio s also affects the rotor voltage. If the design parameters of the unit and converter are appropriate, the power operating range is generally not limited by the maximum rotor voltage.
As mentioned above, in order to obtain the stator-side reactive power characteristics of the DFVSPSU, the first step is to determine the capacity of the DFIG. Then, the study was conducted on the stator current limitation, rotor current limitation, and rotor voltage limitation using an equivalent circuit model.

3.2. Determination of the DFIG Capacity

The rated capacity of a pumped storage unit is determined by its maximum total power, while the capacity of the motor is determined by the maximum stator power output. For synchronous motors, the stator power equals the total power; hence, the motor’s capacity is equivalent to the unit’s rated capacity. However, for the DFIG, the total power is the sum of the rotor and stator powers. According to the operational characteristics of pump–turbines, during turbine modes, the unit operates in a sub-synchronous state, where the rotor power flows in the opposite direction to the total power. As a result, the stator power exceeds the total power, necessitating a DFIG capacity that is greater than the unit’s rated capacity.
This section selects the capacity of a DFIG based on actual data from a domestic 300 MW variable-speed pumped storage unit. Based on the operational characteristics of the pump–turbine for this unit, the real power output on the stator side under turbine mode and pump mode can be obtained, as shown in Figure 3.
From Figure 3, under turbine conditions, stator power increases with both higher reference output at a fixed head and a higher head at fixed output. At a 462 m head and 300 MW reference output (412 rpm), maximum stator power reaches 315.38 MW. For pump conditions, stator power rises with increased reference input at a fixed lift but decreases with a higher lift at fixed input. At a 400 m lift and 330 MW input, the peak stator power is 316.20 MW.
Therefore, the capacity of the DFIG can be selected as the maximum real power output of the stator sides under turbine operating conditions, which is 315.38 MW, rounded to 316 MW. Taking the power factor cosφ as 0.9, the capacity of the DFIG can be calculated as 351.1 MW, which is consistent with the actual situation of a domestic variable-speed unit.

3.3. Voltage and Current Limitations on the Stator Side of the DFVSPSU

To analyze the limiting relationships between different electrical quantities and the operating power during the steady-state process of the unit more clearly, this section mainly uses the conventional T-type equivalent circuit to derive the three reactive power limitations of the stator of the DFIG. These include the stator current limitation (Ismax), rotor current limitation (Irmax), and rotor voltage limitation (Urmax).
The conventional T-type equivalent circuit is a commonly used simplified circuit model that converts complex magnetic field relationships into intuitive circuit models, helping to understand the internal working principles of motors and thereby deriving key operating constraints. The T-type equivalent circuit of DFIG is shown in Figure 4, with the left side representing the stator side, the right side reflecting the rotor side, and the middle part simulating the energy transfer of the air gap magnetic field, where the positive directions of stator and rotor currents point towards the interior of the DFIG and the electrical quantities have been converted to the stator side.
According to Figure 4, the mathematical model of the DFIG can be derived as shown in (10):
E m . = I m . j X m U s . = E m . + I s . R s + j X s U r . / s = E m . + I r . R r / s + j X r I m . = I s . + I r .
In this equation, U s ˙ is the voltage phasor at the stator side of the DFIG, U r ˙ / s is the rotor voltage phasor converted to the stator side of the DFIG, E m ˙ is the induced electromotive force phasor in the air gap magnetic field, I s ˙ is the stator current phasor of the DFIG, I r ˙ is the rotor current phasor converted to the stator side of the DFIG, I m ˙ is the excitation current phasor of the DFIG, Rs is the stator resistance of the DFIG, Xs is the stator leakage reactance of the DFIG, Rr/s is the rotor resistance converted to the stator side of the DFIG, Xr is the rotor leakage reactance converted to the stator side of the DFIG, and Xm is the excitation reactance of the DFIG.
To provide clearer visualization of the operational limitations for the DFVSPSU in the P-Q diagram, the following methodology will be adopted: based on the traditional T-type equivalent circuit model, the active and reactive components of relevant parameters will be decomposed along the d-axis and q-axis. This approach enables the stator-side real power (Ps) and stator-side reactive power (Qs) to intuitively depict the operational constraints for the DFIG—namely the stator current limitation (Ismax), rotor current limitation (Irmax), and rotor voltage limitation (Urmax). The detailed derivation is presented from (11) to (16).
Assuming U s ˙ as the reference quantity, i.e., U s ˙ = U s 0 ° , then the stator and rotor current, as well as the rotor voltage of the DFIG, can be decomposed as follows:
I s . = I ds + j I qs I r . = u I r . = u I dr + j I qr U r . = U r . u = U dr + j U qr / u
where u represents the transformation ratio of the DFIG, I r ˙ is the rotor current phasor of the DFIG, and U r ˙ is the rotor voltage phasor of the DFIG.
The active and reactive power generated by the stator of the DFIG can be represented by the d-q axis components of the stator current, as shown in (12):
P s = Re m U s . I s . = m U s I ds Q s = Im m U s . I s . = m U s I qs
From (12), it can be seen that the decomposed stator current can be represented by the active and reactive power at the stator side. Therefore, the stator current limitation (Ismax) can be directly expressed by the stator-side active and reactive power, as shown in (13):
P s 2 + Q s 2 m U s I smax
where m is the number of stator winding phases and Ismax is the maximum stator current.
By combining (10), (11), and (12), the rotor current limitation (Irmax) can be directly expressed by the stator-side active and reactive power, as shown in (14):
P s 2 + ( Q s + m U s 2 X s + X m ) 2 m U s X m u ( X s + X m ) I rmax
Similarly, the rotor voltage limitation (Urmax) can be obtained as shown in (15), where Urmax is the maximum rotor voltage. The intuitive relationship between rotor voltage and stator-side active and reactive power is shown in (16).
U dr 2 + U ds 2 U rmax
U r = K 1 P s m U s + K 2 Q s m U s + K 3 U S 2 + K 4 P s m U s + K 5 Q s m U s + K 6 U S 2
where
K 1 = R s s ( X s + X m ) R r / X m R s X r s / X m K 2 = s X s R s R r / X m + ( X s + X m ) X r s / X m K 3 = s + X r s / X m K 4 = s X s R s R r / X m + ( X s + X m ) X r s / X m K 5 = R s s + ( X s + X m ) R r / X m + R s X r s / X m K 6 = R r / X m
From (16), it can be observed that the rotor voltage limitation is also affected by the slip rate s. Considering that the slip rate of the DFVSPSU consistently remains below the critical slip value corresponding to the rotor voltage constraint during normal operation, the rotor voltage limitation (Urmax) is omitted in the analysis of its reactive power-regulation capability.
In summary, using actual data from a domestic power station, the operational limits of the stator-side power of the DFVSPSU are reflected in the P-Q power chart, as shown in Figure 5. In the figure, the vertical axis represents real power, the horizontal axis represents reactive power, and the yellow region indicates the normal operating range of the DFVSPSU.
In Figure 5, the four horizontal lines parallel to the reactive power axis represent the prime mover power limitation (Pm). Due to the constraints of the pump–turbine, the maximum output limit under the turbine operating condition is 315.99 MW, while the minimum output limit is set to be not less than 30%, which is 105.33 MW. Under the pump operating condition, the maximum input limit is 344.078 MW, and the minimum input limit is set to be not less than 70%, which is 245.77 MW. According to (13), the stator current limitation (Ismax) is represented as a blue circle with its center at the origin and a radius of mUsIsmax in Figure 5. According to (14), the rotor current limitation (Irmax) is also represented as a red circle. However, due to the iron losses in the motor, the center of the circle is no longer at the origin but is located at a point shifted towards the negative reactive power axis. The maximum rotor current used in this study is Irmax = 6764A.
Although the P-Q diagram of the DFIG shows the stator-side reactive power range, it does not reflect its changes under random operating conditions. In fact, the stator-side reactive power output depends on real power and head (or lift). Therefore, the following section analyzes the actual reactive power limits of the stator side under different operating conditions using optimal pump–turbine data, further investigating its reactive power-regulation capability.

3.4. Reactive Power-Regulation Capability of the Stator Side of the DFVSPSU

This section utilizes the optimal operation data of the pump–turbine to determine the operating conditions under both turbine and pump modes and further combines actual data to derive the reactive power regulation range for the stator side of the DFVSPSU.
By combining the stator-side real power output (shown in Figure 3) with the P-Q power operation limitation diagram (shown in Figure 5), the reactive power output of the stator side under turbine and pump modes can be obtained, as shown in Figure 6 and Figure 7.
From Figure 6, it can be observed that under turbine mode, for the same head, the limits of the stator-side reactive power output and absorption decrease as the reference output increases. When the reference output is 124 MW and the head is between 385 and 462 m, the stator’s maximum reactive power output is 267.16 MVA. When the reference output is 300 MW and the head is 385 m, the minimum reactive power output is 147.74 MVA. When the reference output is 124 MW and the head is 385–462 m, the stator’s maximum reactive power absorption is 324.79 MVA, and when the reference output is 300 MW at a head of 385 m, the minimum reactive power absorption is 153.3 MVA.
From Figure 7, under pump mode, for the same lift, the limits of the stator-side reactive power output and absorption decrease as the reference input increases. When the reference input is 180 MW and the lift is 425 m, the maximum reactive power output of the stator is 242.845 MVA. When the reference input is 330 MW and the lift is 400 m, the minimum reactive power output is 147.37 MVA. When the reference input is 180 MW and the lift is 425 m, the maximum reactive power absorption is 294.08 MVA. When the reference input is 330 MW and the lift is 400 m, the minimum reactive power absorption is 152.61 MVA.

4. Reactive Power Characteristic Analysis of the Grid-Side Converter

The power limits of the grid-side converter are primarily constrained by the converter’s maximum capacity (Scmax):
P c 2 + Q c 2 S cmax 2
where Pc and Qc are the active and reactive power of the grid-side converter and Scmax is the maximum capacity of the grid-side converter. Further transformation of this formula yields the reactive power limitation range for the grid-side converter, as shown in (19):
Q cmin = S cmax 2 P c 2 Q cmax = S cmax 2 P c 2
From (5) and (18), it is clear that to obtain the reactive power characteristics of the grid-side converter, the real power on the rotor side of the DFVSPSU needs to be determined first.

4.1. Determining the Real Power on the Rotor Side of the DFVSPSU

This section uses the actual data of a domestic variable-speed unit as an example. Based on the pump–turbine’s operating characteristics, the real power output on the rotor side under turbine and pump modes can be derived, as shown in Figure 8.
As shown in Figure 8, under turbine mode, for the same head, the rotor power decreases as the reference output increases, but when the reference output reaches 270 MW, the rotor power starts to increase. When the head is between 385 and 462 m and the reference output is 124 MW, the maximum rotor power is −9.34 MW. When the reference output is 310 MW at a head of 385 m, the minimum rotor power is −20.29 MW.
It can be seen that under pump mode, for the same lift, the rotor power increases as the reference input increases. At the same reference input, the rotor power increases with lift. When the lift is 405 m and the reference input is 200 MW, the minimum rotor power is −14.7 MW. When the lift is 470 m and the reference input is 330 MW, the maximum rotor power is 18.87 MW.

4.2. Reactive Power Characteristic Analysis of the Grid-Side Converter in the DFVSPSU

In this study, the maximum capacity of the grid-side converter for a domestic DFVSPSU is 42 MVA. By combining the rotor-side real power output (shown in Figure 8) with the theoretical analysis provided earlier, the reactive power regulation capacity of the grid-side converter under turbine and pump modes is shown in Figure 9 and Figure 10.
From Figure 9, under turbine mode, when the reference output is 124 MW and the head is between 385 and 462 m, the maximum reactive power output of the grid-side converter Qcmax is 41.04 MVA. When the reference output is 270 MW at a head of 462 m, the minimum reactive power output Qcmin is 36.88 MVA. Similarly, when the reference output is 124 MW and the head is between 385and 462 m, the maximum reactive power absorption Qcmax is 41.04 MVA, and at a 270 MW output with a head of 462 m, the minimum absorption Qcmin is 36.88 MVA.
From Figure 10, under pump mode, when the reference input is 260 MW and the lift is 450 m, the maximum reactive power output of the grid-side converter Qcmax is 42.09 MVA. When the reference input is 330 MW at a lift of 470 m, the minimum reactive power output is Qcmin 37.62 MVA. Similarly, when the reference input is 260 MW at a lift of 450 m, the maximum reactive power absorption is Qcmax 42.09 MVA, and when the reference input is 330 MW at a lift of 470 m, the minimum absorption Qcmin is 37.62 MVA.

5. Total Reactive Power Characteristics of the Doubly-Fed Variable Speed Pumped Storage Unit

The total reactive power characteristics of the DFVSPSU consist of two components: the stator-side and grid-side converter’s reactive power characteristics. Combining the conclusions from Section 3 and Section 4, the total reactive power regulation capability is summarized in Figure 11 and Figure 12.
In the figures, the gray surface represents the reactive power output and absorption on the stator side, the yellow surface represents the reactive power output and absorption on the grid-side converter, and the blue surface represents the total reactive power output and absorption of the unit.
Most existing studies focus on the stator side but neglect the grid-side converter. This study incorporates both, finding that considering the grid-side characteristics significantly improves the total reactive power regulation capability of the unit.
From Figure 11, under turbine mode, when the reference output is 124 MW and the head is between 385 and 462 m, the total reactive power output of the unit reaches a maximum value of 308.2 MVA. When the reference output is 300 MW and the head is 385 m, the minimum value of the total reactive power output is 186.7 MVA. When the reference output is 124 MW and the head is between 385 and 462 m, the total reactive power absorption of the unit reaches a maximum value of 365.83 MVA, and when the reference output is 300 MW and the head is 385 m, the minimum value of the total reactive power absorption is 192.28 MVA.
Table 1 takes the maximum and minimum total reactive power output and absorption of the unit under the turbine mode as examples, along with the corresponding head and reference output for the stator-side and grid-side reactive power. The calculation results show that by considering the reactive power characteristics of the grid-side converter, the total reactive power-regulation capability of the unit increases by approximately 12% to 26% compared to considering only the stator-side reactive power.
From Figure 12, under pump mode, when the reference input is 180 MW and the lift is 425 m, the maximum total reactive power output of the unit is 283.24 MVA. When the reference input is 330 MW and the lift is 400 m, the minimum total reactive power output is 187.12 MVA. When the reference input is 180 MW and the lift is 425 m, the maximum total reactive power absorption is 334.48 MVA, and when the reference input is 330 MW and the lift is 400 m, the minimum total reactive power absorption is 192.37 MVA.

6. Comparison of Reactive Power-Regulation Capabilities Between Fixed-Speed Pumped Storage Unit and Doubly-Fed Variable Speed Pumped Storage Unit

To more clearly demonstrate the superiority of variable-speed units in reactive power regulation, this section analyzes the power operating range of fixed-speed pumped storage units (FSPSUs) and compares the reactive power-regulation capabilities of fixed-speed and variable-speed units. The analysis shows that fixed-speed units, due to their fixed speed characteristics, have relatively weaker reactive power-regulation capabilities. In contrast, variable-speed units, by adjusting their speed and power factor, have relatively stronger reactive power-regulation capabilities.

6.1. Power Operating Constraints of the FSPSU

The power operating range of the FSPSU is analyzed similarly to the DFVSPSU. The reactive power operating range of the fixed-speed unit is derived in the P-Q diagram based on its operating constraints, and then, the actual reactive power regulation range of the unit is analyzed under different operating conditions using actual data from a domestic fixed-speed unit.
  • P-Q Power Operating Constraints of the FSPSU:
The power operating range of the FSPSU is constrained by the prime mover power, stator winding temperature, excitation winding temperature, and other factors:
  • Stator winding temperature rise constraint: The stator winding temperature rise depends on the stator current, which is influenced by the generator’s apparent power. The unit’s rated capacity is limited by the thermal capacity of the stator winding and core, ensuring safe operation, represented as a blue circle in the P-Q diagram;
  • Prime mover power constraint: The rated power of the prime mover of a pumped storage unit is usually equal to the rated real power of the generator it is paired with. Therefore, the prime mover power constraint is shown in the P-Q diagram by four horizontal lines. With a rated power factor of cosφ = 0.9, the minimum output constraint for turbine operation is 50%, and the minimum input constraint for pump operation is 75% [34];
  • Excitation winding temperature rise constraint: The excitation winding temperature rise constraint limits the temperature increase during operation, primarily dependent on the excitation current. Due to iron losses, the power circle’s center shifts from the origin to the negative reactive power axis, forming a purple circle;
  • Other constraints: When the excitation electromotive force is constant, the maximum achievable real power and its corresponding power angle represent the static stability constraint. In practice, there is an additional 10–15% margin for the static stability constraint. When the excitation current is zero, the unit is in an excitation loss state, at which point the unit is subject to excitation loss constraints.
Figure 13 illustrates the P-Q diagram of operational limitations for the FSPSU, where the yellow and green areas represent the normal operating ranges under the turbine and pump modes, respectively.
2.
Reactive Power Regulation Range of the FSPSU:
This section provides a detailed analysis using the actual data of the domestic FSPSU, exploring the reactive power regulation range under both turbine and pump modes.
As shown in Figure 14, under turbine mode, the reactive power output and absorption of the fixed-speed unit decrease as the reference output increases at the same head. When the reference output is 150 MW, the maximum reactive power output (absorption) is 209.4 MVA (300.66 MVA). When the reference output is 300 MW, the minimum reactive power output (absorption) is 146.36 MVA (151.3 MVA).
As shown in Figure 15, under pump mode, with the same lift, the real power is non-adjustable. The reactive power output limit is represented by a curve with a downward trend, while the reactive power absorption limit is represented by a curve with an upward trend. When the lift is 400 m and the reference input is 283 MW, the minimum reactive power output (absorption) is 156.09 MVA (181.07 MVA). When the lift is 465 m and the reference input is 249.9 MW, the maximum reactive power output (absorption) is 173 MVA (224.61 MVA).

6.2. Comparison of Reactive Power-Regulation Capabilities Between FSPSU and DFVSPSU

By summarizing the conclusions from Section 5 and Section 6.1, the differences in reactive power-regulation capabilities between two domestic pumped storage units, both with a capacity of 300 MW (one fixed-speed and one variable-speed), are shown in Figure 16 and Figure 17.
As shown in Figure 16, under turbine mode, the DFVSPSU has higher reactive power output and absorption limits than the FSPSU, with a maximum total output of 308.2 MVA and absorption of 365.83 MVA, compared to 209.4 MVA and 300.66 MVA for the FSPSU. Under pump mode (Figure 17), the DFVSPSU’s reactive power regulation range forms a surface, adjustable by speed, while the FSPSU’s range forms a curve, limited by fixed speed.
In order to more clearly illustrate the differences in reactive power-regulation performance between DFVSPSU and FSPSU, the results of Figure 16 and Figure 17 are summarized in a table for comparison, as shown in Table 2.
As shown in Table 2, under turbine and pump modes, the maximum values of reactive power output or absorption by the DFVSPSU are greater than those of the FSPSU. The comparison confirms that the DFVSPSU provides a wider reactive power-regulation range than the FSPSU in both turbine and pump modes, demonstrating superior reactive power-regulation capabilities.

7. Conclusions

This study investigates the reactive power-regulation capability of a 300 MW DFVSPSU in China. The DFVSPSU’s reactive power characteristics are divided into stator-side and grid-side converter components, which are not coupled and should be analyzed separately. The DFIG capacity is often greater than the unit’s rated capacity due to its sub-synchronous operation under turbine mode, providing stronger reactive power regulation. For instance, the 300 MW unit has a rated speed of 412 rpm, with a DFIG capacity of 351.1 MW, exceeding the rated unit capacity. Factors limiting stator-side reactive power regulation include the prime mover power, stator current, and rotor current, with the grid-side converter’s regulation limited by converter capacity and rotor-side real power. Based on the variable-speed characteristic curve, the unit’s reactive power-regulation capability can be improved by 12% to 26% by fully utilizing the grid-side converter. Compared to the FSPSU, the DFVSPSU offers superior reactive power regulation, with higher output and absorption limits under turbine mode and a more flexible regulation range under pump mode.
In summary, this study reveals that DFVSPSUs possess broader reactive power-regulation characteristics than FSPSUs of the same capacity. This capability enables the units to actively absorb excess reactive power during periods of low grid load, effectively improving the operational efficiency of power plants during grid imbalances. Additionally, it provides a foundation for reactive power support and dynamic optimization design for the grid, thereby supporting grid voltage stability. Furthermore, this study has further explored the reactive power-regulation capabilities of grid-side converters, which can effectively support the design of overall reactive power-regulation strategies for DFVSPSUs. Future research can focus on the allocation of reactive power characteristics between grid-side converters and the stator side, thereby optimizing a dynamic control strategy design.

Author Contributions

Conceptualization, B.Y. and C.G.; methodology, C.G. and B.Y.; software, C.G.; validation, Z.Z.; formal analysis, C.G. and S.S.; investigation, Chuang Dong and J.G.; resources, Z.Z.; data curation, J.G.; writing—original draft preparation, C.G. and S.S.; writing—review and editing, B.Y.; visualization, Q.Y.; supervision, B.Y.; project administration, C.D. funding acquisition, Q.Y. All authors have read and agreed to the published version of the manuscript.

Funding

This research is supported by the National Natural Science Foundation of China (grant no. 52179090, grant no. U2443226, grant no. 52439006), Natural Science Basic Research Program of Shaanxi (grant no. 2025JC-YBQN-744), Scientific Research Program Funded by Shaanxi Provincial Education Department (grant no. 23JE011, grant no. 23JE012), and Research Project of Xi’an Postdoctoral Innovation Base (grant no. 2023-15).

Data Availability Statement

Data will be made available on request.

Conflicts of Interest

Authors Bo Yi, Zheyuan Zhang, Chuang Dong, Jiawei Gu and Qiming Yan were employed by the company PowerChina Northwest Engineering Corporation Limited. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Abbreviations

The following abbreviations are used in this manuscript:
DFVSPSUsDoubly-fed variable speed pumped storage units
DFIGDoubly-fed induction generator
PSUsPumped storage units
FSPSUsFixed-speed pumped storage units

References

  1. Du, E.; Zhang, N.; Hodge, B.-M.; Wang, Q.; Kang, C.; Kroposki, B.; Xia, Q. The Role of Concentrating Solar Power Toward High Renewable Energy Penetrated Power Systems. IEEE Trans. Power Syst. 2018, 33, 6630–6641. [Google Scholar] [CrossRef]
  2. Wang, Y.; Qiu, D.; Sun, X.; Bie, Z.; Strbac, G. Coordinating Multi-Energy Microgrids for Integrated Energy System Resilience: A Multi-Task Learning Approach. IEEE Trans. Sustain. Energy 2024, 15, 920–937. [Google Scholar] [CrossRef]
  3. Ye, J.; Tan, L.; Shi, W.; Chen, C.; Francis, E.M. Numerical Simulation of Axial-Flow Pump Cavitation Based on Variable Frequency Speed Regulation. Water 2022, 14, 2757. [Google Scholar] [CrossRef]
  4. Li, H.; Sun, D.; Li, B.; Wang, X.; Zhao, Y.; Wei, M.; Dang, X. Collaborative Optimization of VRB-PS Hybrid Energy Storage System for Large-Scale Wind Power Grid Integration. Energy 2023, 265, 126292. [Google Scholar] [CrossRef]
  5. Qin, Y.; Li, D.; Wang, H.; Liu, Z.; Wei, X.; Wang, X.; Yang, W. Comprehensive Hydraulic Performance Improvement in a Pump-Turbine: An Experimental Investigation. Energy 2023, 284, 128550. [Google Scholar] [CrossRef]
  6. Zhang, J.; Ma, R.; Cao, Y.; Zou, S.; Li, C. Quantitative Assessment of Static Voltage Stability for Power System with High-Penetration Wind Power Based on Energy Function. Energy Rep. 2024, 12, 699–707. [Google Scholar] [CrossRef]
  7. Coban, H.H.; Rehman, A.; Mousa, M. Load Frequency Control of Microgrid System by Battery and Pumped-Hydro Energy Storage. Water 2022, 14, 1818. [Google Scholar] [CrossRef]
  8. Atallah, M.; Mezouar, A.; Fernández–Ramírez, L.M.; Belgacem, K.; Saidi, Y.; Benmahdjoub, M.A.; Brahmi, B. Supervisory Control of Reactive Power in Wind Farms with Doubly Fed Induction Generator-Based Wind Turbines for Voltage Regulation and Power Losses Reduction. Electr. Power Syst. Res. 2024, 228, 110059. [Google Scholar] [CrossRef]
  9. Kougias, I.; Aggidis, G.; Avellan, F.; Deniz, S.; Lundin, U.; Moro, A.; Muntean, S.; Novara, D.; Pérez-Díaz, J.I.; Quaranta, E.; et al. Analysis of Emerging Technologies in the Hydropower Sector. Renew. Sustain. Energy Rev. 2019, 113, 109257. [Google Scholar] [CrossRef]
  10. Wang, R.; Yang, W.; Ji, L.; Li, X.; Zhang, S.; Jing, X. Regulation Intensity Assessment of Pumped Storage Units in Daily Scheduling for Renewable Energy Consumption. Sustain. Energy Technol. Assess. 2023, 56, 103027. [Google Scholar] [CrossRef]
  11. Pugliese, F.; Giugni, M. An Operative Framework for the Optimal Selection of Centrifugal Pumps As Turbines (PATs) in Water Distribution Networks (WDNs). Water 2022, 14, 1785. [Google Scholar] [CrossRef]
  12. Xu, B.; Zhang, J.; Egusquiza, M.; Chen, D.; Li, F.; Behrens, P.; Egusquiza, E. A Review of Dynamic Models and Stability Analysis for a Hydro-Turbine Governing System. Renew. Sustain. Energy Rev. 2021, 144, 110880. [Google Scholar] [CrossRef]
  13. Fu, J.; Yu, X.; Gao, C.; Cui, J.; Li, Y. Nonsingular Fast Terminal Control for the DFIG-Based Variable-Speed Hydro-Unit. Energy 2022, 244, 122672. [Google Scholar] [CrossRef]
  14. Jukić, D.-K.; Kugi, A.; Kemmetmüller, W. Optimal Operation of Pumped Storage Power Plants with Fixed- and Variable-Speed Generators in Multiple Electricity Markets Considering Overload Operation. J. Energy Storage 2024, 88, 111601. [Google Scholar] [CrossRef]
  15. Kadri, A.; Marzougui, H.; Aouiti, A.; Bacha, F. Energy Management and Control Strategy for a DFIG Wind Turbine/Fuel Cell Hybrid System with Super Capacitor Storage System. Energy 2020, 192, 116518. [Google Scholar] [CrossRef]
  16. Ge, X.; Qian, J.; Fu, Y.; Lee, W.-J.; Mi, Y. Transient Stability Evaluation Criterion of Multi-Wind Farms Integrated Power System. IEEE Trans. Power Syst. 2022, 37, 3137–3140. [Google Scholar] [CrossRef]
  17. Tavoosi, J.; Mohammadzadeh, A.; Pahlevanzadeh, B.; Kasmani, M.B.; Band, S.S.; Safdar, R.; Mosavi, A.H. A Machine Learning Approach for Active/Reactive Power Control of Grid-Connected Doubly-Fed Induction Generators. Ain Shams Eng. J. 2022, 13, 101564. [Google Scholar] [CrossRef]
  18. Lei, L.; Li, F.; Kheav, K.; Jiang, W.; Luo, X.; Patelli, E.; Xu, B.; Chen, D. A Start-up Optimization Strategy of a Hydroelectric Generating System: From a Symmetrical Structure to Asymmetric Structure on Diversion Pipes. Renew. Energy 2021, 180, 1148–1165. [Google Scholar] [CrossRef]
  19. Kan, K.; Xu, Z.; Chen, H.; Xu, H.; Zheng, Y.; Zhou, D.; Muhirwa, A.; Maxime, B. Energy Loss Mechanisms of Transition from Pump Mode to Turbine Mode of an Axial-Flow Pump under Bidirectional Conditions. Energy 2022, 257, 124630. [Google Scholar] [CrossRef]
  20. Tang, W.; Hu, J.; Chang, Y.; Liu, F. Modeling of DFIG-Based Wind Turbine for Power System Transient Response Analysis in Rotor Speed Control Timescale. IEEE Trans. Power Syst. 2018, 33, 6795–6805. [Google Scholar] [CrossRef]
  21. Trivedi, T.; Jadeja, R.; Bhatt, P.; Long, C.; Sanjeevikumar, P.; Ved, A. Sliding Mode-Based Direct Power Control of Unified Power Quality Conditioner. Heliyon 2024, 10, e39597. [Google Scholar] [CrossRef] [PubMed]
  22. Jadhav, H.T.; Roy, R. A Comprehensive Review on the Grid Integration of Doubly Fed Induction Generator. Int. J. Electr. Power Energy Syst. 2013, 49, 8–18. [Google Scholar] [CrossRef]
  23. Parida, A.; Chatterjee, D. An Improved Control Scheme for Grid Connected Doubly Fed Induction Generator Considering Wind-Solar Hybrid System. Int. J. Electr. Power Energy Syst. 2016, 77, 112–122. [Google Scholar] [CrossRef]
  24. Schmidt, J.; Kemmetmüller, W.; Kugi, A. Modeling and Static Optimization of a Variable Speed Pumped Storage Power Plant. Renew. Energy 2017, 111, 38–51. [Google Scholar] [CrossRef]
  25. Siniscalchi-Minna, S.; Bianchi, F.D.; Ocampo-Martinez, C.; Domínguez-García, J.L.; De Schutter, B. A Non-Centralized Predictive Control Strategy for Wind Farm Active Power Control: A Wake-Based Partitioning Approach. Renew. Energy 2020, 150, 656–669. [Google Scholar] [CrossRef]
  26. Kadi, S.; Benbouhenni, H.; Abdelkarim, E.; Imarazene, K.; Berkouk, E.M. Implementation of Third-Order Sliding Mode for Power Control and Maximum Power Point Tracking in DFIG-Based Wind Energy Systems. Energy Rep. 2023, 10, 3561–3579. [Google Scholar] [CrossRef]
  27. Singh, R.R.; Baranidharan, M.; Subramaniam, U.; Bhaskar, M.S.; Rangarajan, S.S.; Abdelsalam, H.A.; Collins, E.R.; Senjyu, T. An Energy-Efficient Start-Up Strategy for Large Variable Speed Hydro Pump Turbine Equipped with Doubly Fed Asynchronous Machine. Energies 2022, 15, 3138. [Google Scholar] [CrossRef]
  28. Huang, Y.; Yang, W.; Zhao, Z.; Han, W.; Li, Y.; Yang, J. Dynamic Modeling and Favorable Speed Command of Variable-Speed Pumped-Storage Unit during Power Regulation. Renew. Energy 2023, 206, 769–783. [Google Scholar] [CrossRef]
  29. Gayen, P.K.; Chatterjee, D.; Goswami, S.K. Stator Side Active and Reactive Power Control with Improved Rotor Position and Speed Estimator of a Grid Connected DFIG (Doubly-Fed Induction Generator). Energy 2015, 89, 461–472. [Google Scholar] [CrossRef]
  30. Ghosh, S.; Isbeih, Y.J.; Bhattarai, R.; Moursi, M.S.E.; El-Saadany, E.F.; Kamalasadan, S. A Dynamic Coordination Control Architecture for Reactive Power Capability Enhancement of the DFIG-Based Wind Power Generation. IEEE Trans. Power Syst. 2020, 35, 3051–3064. [Google Scholar] [CrossRef]
  31. Yin, J. Influence of Reactive Power Support Control Strategy on Short-Circuit Current Calculation and Fault Analysis Method of DFIG. Energy Rep. 2021, 7, 5933–5942. [Google Scholar] [CrossRef]
  32. Chen, Y.; Xu, W.; Liu, Y.; Bao, Z.; Mao, Z.; Rashad, E.M. Modeling and Transient Response Analysis of Doubly-Fed Variable Speed Pumped Storage Unit in Pumping Mode. IEEE Trans. Ind. Electron. 2023, 70, 9935–9947. [Google Scholar] [CrossRef]
  33. Li, J.; Guo, W. Optimization of Shafting and Excitation Dual Damping Controller for Combined Pumped Storage and Wind Power System. Energy 2024, 313, 133894. [Google Scholar] [CrossRef]
  34. Li, J.; Liu, X.; Pang, J.; Xu, L. Review on Cavitation Performance of Pump-turbine. Hydropower Pumped Storage 2025, 11, 88–101. [Google Scholar]
Figure 1. Structure of the DFVSPSU.
Figure 1. Structure of the DFVSPSU.
Water 17 02519 g001
Figure 2. Power flow diagram of the DFVSPSU: (a) super-synchronous operation under turbine mode; (b) sub-synchronous operation under turbine mode; (c) super-synchronous operation under pump mode; (d) sub-synchronous operation under pump mode.
Figure 2. Power flow diagram of the DFVSPSU: (a) super-synchronous operation under turbine mode; (b) sub-synchronous operation under turbine mode; (c) super-synchronous operation under pump mode; (d) sub-synchronous operation under pump mode.
Water 17 02519 g002
Figure 3. Real power on the stator side: (a) turbine mode; (b) pump mode.
Figure 3. Real power on the stator side: (a) turbine mode; (b) pump mode.
Water 17 02519 g003
Figure 4. Conventional T-type equivalent circuit.
Figure 4. Conventional T-type equivalent circuit.
Water 17 02519 g004
Figure 5. P-Q diagram of operational limitations for the DFVSPSU (Outputtmax represents the maximum output limit under turbine operating conditions; Outputtmin represents the minimum output limit under turbine operating conditions; Inputpmin represents the minimum input limit under pump operating conditions; and Inputpmax represents the maximum input limit under pump operating conditions).
Figure 5. P-Q diagram of operational limitations for the DFVSPSU (Outputtmax represents the maximum output limit under turbine operating conditions; Outputtmin represents the minimum output limit under turbine operating conditions; Inputpmin represents the minimum input limit under pump operating conditions; and Inputpmax represents the maximum input limit under pump operating conditions).
Water 17 02519 g005
Figure 6. Limit of reactive power output and absorbed by the stator (turbine mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Figure 6. Limit of reactive power output and absorbed by the stator (turbine mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Water 17 02519 g006
Figure 7. Limit of reactive power output and absorption by the stator (pump mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Figure 7. Limit of reactive power output and absorption by the stator (pump mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Water 17 02519 g007
Figure 8. Real power on the rotor side: (a) turbine mode; (b) pump mode.
Figure 8. Real power on the rotor side: (a) turbine mode; (b) pump mode.
Water 17 02519 g008
Figure 9. Limit of reactive power output and absorption by the grid-side converter (turbine mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Figure 9. Limit of reactive power output and absorption by the grid-side converter (turbine mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Water 17 02519 g009
Figure 10. Limit of reactive power output and absorption by the grid-side converter (pump mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Figure 10. Limit of reactive power output and absorption by the grid-side converter (pump mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Water 17 02519 g010
Figure 11. Limit of total reactive power output and absorption by the DFVSPSU (turbine mode): (a) limit of total reactive power output; (b) limit of total reactive power absorbed.
Figure 11. Limit of total reactive power output and absorption by the DFVSPSU (turbine mode): (a) limit of total reactive power output; (b) limit of total reactive power absorbed.
Water 17 02519 g011
Figure 12. Limit of total reactive power output and absorbed by the DFVSPSU (pump mode): (a) limit of total reactive power output; (b) limit of total reactive power absorbed.
Figure 12. Limit of total reactive power output and absorbed by the DFVSPSU (pump mode): (a) limit of total reactive power output; (b) limit of total reactive power absorbed.
Water 17 02519 g012
Figure 13. P-Q diagram of operational limitations for FSPSU (Outputtmax represents the maximum output limit under turbine operating conditions; Outputtmin represents the minimum output limit under turbine operating conditions; Inputpmin represents the minimum input limit under pump operating conditions; and Inputpmax represents the maximum input limit under pump operating conditions).
Figure 13. P-Q diagram of operational limitations for FSPSU (Outputtmax represents the maximum output limit under turbine operating conditions; Outputtmin represents the minimum output limit under turbine operating conditions; Inputpmin represents the minimum input limit under pump operating conditions; and Inputpmax represents the maximum input limit under pump operating conditions).
Water 17 02519 g013
Figure 14. Limit of reactive power output and absorption by the FSPSU in China (turbine mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Figure 14. Limit of reactive power output and absorption by the FSPSU in China (turbine mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Water 17 02519 g014
Figure 15. Limit of reactive power output and absorption by the FSPSU in China (pump mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Figure 15. Limit of reactive power output and absorption by the FSPSU in China (pump mode): (a) limit of reactive power output; (b) limit of reactive power absorbed.
Water 17 02519 g015
Figure 16. Comparison of reactive power total output and total absorption capacity (turbine mode): (a) limit of total reactive power output; (b) limit of total reactive power absorbed.
Figure 16. Comparison of reactive power total output and total absorption capacity (turbine mode): (a) limit of total reactive power output; (b) limit of total reactive power absorbed.
Water 17 02519 g016
Figure 17. Comparison of reactive power total output and total absorption capacity (pump mode): (a) limit of total reactive power output; (b) limit of total reactive power absorbed.
Figure 17. Comparison of reactive power total output and total absorption capacity (pump mode): (a) limit of total reactive power output; (b) limit of total reactive power absorbed.
Water 17 02519 g017
Table 1. Reactive power regulation capability of the DFVSPSU considering Qc (unit: MVA).
Table 1. Reactive power regulation capability of the DFVSPSU considering Qc (unit: MVA).
QQsQc(QQs)/Qs
308.2267.1641.0415.36%
186.7147.7438.9826.37%
365.83324.7941.0412.54%
192.28153.338.9825.43%
Table 2. Comparison of reactive power-regulation capabilities between DFVSPSU and FSPSU (unit: MVA).
Table 2. Comparison of reactive power-regulation capabilities between DFVSPSU and FSPSU (unit: MVA).
Turbine ModePump Mode
The Maximum Reactive Power OutputThe Maximum Reactive Power AbsorptionThe Maximum Reactive Power OutputThe Maximum Reactive Power Absorption
DFVSPSU308.2365.83283.24334.48
FSPSU209.4300.66173224.61
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Yi, B.; Zhang, Z.; Dong, C.; Gao, C.; Sun, S.; Gu, J.; Yan, Q. Steady-State Reactive Power Capability Analysis of Doubly-Fed Variable Speed Pumped Storage Unit Considering the Unit’s Operating Characteristics. Water 2025, 17, 2519. https://doi.org/10.3390/w17172519

AMA Style

Yi B, Zhang Z, Dong C, Gao C, Sun S, Gu J, Yan Q. Steady-State Reactive Power Capability Analysis of Doubly-Fed Variable Speed Pumped Storage Unit Considering the Unit’s Operating Characteristics. Water. 2025; 17(17):2519. https://doi.org/10.3390/w17172519

Chicago/Turabian Style

Yi, Bo, Zheyuan Zhang, Chuang Dong, Chunyang Gao, Sijia Sun, Jiawei Gu, and Qiming Yan. 2025. "Steady-State Reactive Power Capability Analysis of Doubly-Fed Variable Speed Pumped Storage Unit Considering the Unit’s Operating Characteristics" Water 17, no. 17: 2519. https://doi.org/10.3390/w17172519

APA Style

Yi, B., Zhang, Z., Dong, C., Gao, C., Sun, S., Gu, J., & Yan, Q. (2025). Steady-State Reactive Power Capability Analysis of Doubly-Fed Variable Speed Pumped Storage Unit Considering the Unit’s Operating Characteristics. Water, 17(17), 2519. https://doi.org/10.3390/w17172519

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop