Article

Indoor Air Quality in Urban and Rural Preschools in Upper Silesia, Poland: Particulate Matter and Carbon Dioxide

Department of Air Protection, Silesian University of Technology, 22B Konarskiego St., 44-100 Gliwice, Poland
*
Author to whom correspondence should be addressed.
Int. J. Environ. Res. Public Health 2015, 12(7), 7697-7711; https://doi.org/10.3390/ijerph120707697
Submission received: 22 April 2015 / Revised: 8 June 2015 / Accepted: 1 July 2015 / Published: 8 July 2015

Abstract

:
Indoor air quality (IAQ) in preschools is an important public health challenge. Particular attention should be paid to younger children, because they are more vulnerable to air pollution than higher grade children and because they spend more time indoors. Among air pollutants, particulate matter (PM) is of the greatest interest mainly due to its acute and chronic effects on children’s health. In addition, carbon dioxide (CO2) levels indicate ventilation conditions. In this paper, we present the concentrations of PM (PM1, PM2.5, PM10 and total—TSP) and CO2 monitored in four naturally ventilated nursery schools located in the area of Gliwice, Poland. The nursery schools were selected to characterize areas with different degrees of urbanization and traffic densities during the winter season. The results indicate the problem of elevated concentrations of PM inside the examined classrooms, as well as that of high levels of CO2 exceeding 1000 ppm in relation to outdoor air. The characteristics of IAQ were significantly different, both in terms of classroom occupation (younger or older children) and of localization (urban or rural). To evaluate the children’s exposure to poor IAQ, indicators based on air quality guidelines were proposed to rank classrooms according to their hazard on the health of children.

1. Introduction

The current strategic framework for European cooperation in education and training, assumes that, by the year 2020, at least 95% of children between the ages of four and whenever they start compulsory primary education should participate in early childhood education [1].
In Poland, preschool education covers children aged from three to six years old and is fulfilled by nursery schools, preschool branches in schools and in preschool points. Early childhood education in 48.8% of cases is led by nursery schools, from which 67% are located in urban areas. Preschool education involves 1.3 million children, which covers 75.3% of children. Respectively, in urban and rural areas, 84.4% and 58.6% of children attend preschool education [2]. In Poland, the compulsory participation of five-year-olds results in 93.6% contribution levels for early childhood education. The aim of the EU benchmark to achieve the 95% level will be mainly connected with the increase in attendance of four-year-olds (currently 70.7%) and three-year-olds (currently 57.5%).
According to the expected development of early childhood education, particular effort should be paid in order to ensure high quality care, and especially to the indoor environmental quality, which is crucial in relation to children’s health and welfare.
During the past decade, many studies have been conducted to assess IAQ in school environments. A large number of indoor air pollutants have been measured, including volatile organic compounds (VOCs), nitrogen oxides (NOx), sulphur dioxide (SO2), ozone (O3), carbon mon- and dioxide (CO and CO2), bioaerosols and PM [3,4,5,6,7,8,9,10,11,12,13,14], but few authors have reported results on IAQ in preschools [15,16,17,18,19,20,21]. Researchers often encounter problems in gaining access to such institutions as nursery schools as well as in installing the necessary measuring equipment in such a way as to avoid disturbance during the measurement process and to limit children’s curiosity.
The exposure of preschool children to air pollutants could represent a very interesting study for three main reasons: (a) children are particularly vulnerable to the harmful effects of air pollution because of immature lung defences, narrower airways, higher inhalation rates and a higher metabolic rate of oxygen consumption per unit of body weight [17,22,23]; (b) younger children spend more time in preschools than in any other indoor environment besides the home; (c) other factors, such as furnishing, sorptive materials (carpets, toys and bedcovers) and children’s activities influence the concentrations of air pollutants, and thus IAQ in preschools is different from primary school onwards [15,17].
The present authors’ recent project (“Children’s exposure to indoor air pollutants in nursery schools—CHEIN”) concerning IAQ (VOCs, bioaerosols, PM and CO2 concentrations) in urban and rural nursery schools located in the industrial region of Upper Silesia, Poland, clearly indicated the problem of elevated concentrations of PM and CO2 during the winter season.
The Upper Silesia region, compared with other EU countries as well as other Polish regions, is characterized by relatively high levels of PM. A considerable part of the PM comes from anthropogenic sources, such as production processes, coal-based power generation and heat generation industries, as well as traffic and resuspension processes from urban surfaces. However, pollutants emitted from industrial coal combustion processes have been seriously reduced, while the emissions from small-scale combustion utilities, such as domestic boilers, have become particularly dangerous. The hazard of domestic sources originate from low quality of fuels (coal, biomass, culm or even refuse) used for heating during winter.
The aim of the present study is to characterize IAQ in four nursery school buildings located in urban and rural areas of Gliwice, in southern Poland. The study carried out simultaneous PM (indoor: PM1, PM2.5, PM10 and total—TSP; outdoor: PM2.5 and PM10) and CO2 concentration (outdoors and indoor in two classrooms) measurements to evaluate the influence of outdoor emissions on the IAQ of naturally ventilated classrooms occupied by younger or older children. Moreover, in order to rank classrooms according to their hazard levels, integrated indicators were introduced to correlate WHO guidelines and EU legislation values with the PM2.5, PM10 and CO2 concentrations found in these environments.

2. Experimental Section

The study was carried out during the winter season of 2013/2014 at four nursery schools located in the area of Gliwice—a typical city in the industrial region of Upper Silesia, Poland (with 4.5 million people in the region). Two of the nursery schools are located in an urban area and two in a rural area (Figure 1).
Figure 1. Localization of the investigated nursery schools (Map data: 2015© Google, ORION-ME).
Figure 1. Localization of the investigated nursery schools (Map data: 2015© Google, ORION-ME).
Ijerph 12 07697 g001
All the nursery schools are public, and entirely managed with public funds by the municipality authorities and the Ministry of Education.

2.1. Sampling Sites

The first building, labelled SU-1 (Sikornik district, Urban area 1), is located in the residential area of the southwest of the city centre, next to an air quality monitoring station. The second is located in an urban traffic area, and labelled PU-2 (Pszczynska Street, Urban area 2). The front facade of the PU-2 building is located 50 m from the street, with heavy traffic reaching 2400–2800 vehicles per hour. Between the PU-2 building and the street, there is parking space available which enables the flow of air from the traffic in the street. Two more buildings are located in the rural areas in the northeast direction approx. 10 km from Gliwice. The location was selected according to the dominant wind direction (207°) in the region. The PR-3 side (Przezchlebie village, Rural area 3) represents typical rural localization without industrial activity or heavy traffic, while the SR-4 building (Świętoszowice village, Rural area 4) is located 50 m from highway A1 (a section opened since 2011). The building is separated from the highway by highway screens. All the nursery schools are located in detached buildings (Figure 1), all of which underwent the process of thermal efficiency improvement, being completed in 2007 (PU-2), 2008 (SU-1) or summer 2013 (PR-3 and SR-4). During the thermal insulation process, the natural ventilation using the air duct systems of the buildings was left unchanged. Consequently, the IAQ is mostly ensured by means of stack ventilation and airing through open and unsealed windows.
The buildings have kitchens which use gas stoves located on the first (SU-1 and SR-4) or ground floors (PU-2 and PR-3). The urban nursery schools had 100 (SU-1) and 150 (PU-2) children divided by age into four or six different classrooms, respectively. Meanwhile, in the rural buildings, 54 (PR-3) and 56 (SR-4) children were divided into three groups. Generally, in each group there were 21–25 children and 1–2 persons on the nursery school staff. In PR-3, there was one group of four disabled children; this group was not included in the studies. The measurements were conducted in older (I) and younger (II) children classrooms. Table 1 summarizes some of the main important characteristics for IAQ in each studied classroom.
The daytime schedules in all the nursery schools are generally similar. An essential difference between the groups is that the younger children have an afternoon nap from 12:00 to 14:00. In the SU-1 nursery school, children undress, put on pyjamas and - during the resting period—sleep on folding beds covered with their own bedcovers. In other cases, the children rest covered with blankets belonging to the nursery (PU-2) or else themselves (PR-3 and SR-4). During the resting period, they usually watch fairy tales on television - only in PR-3 do the nursery school children rest in another room.
Table 1. Summary of the main characteristics for IAQ analysis in each studied classroom.
Table 1. Summary of the main characteristics for IAQ analysis in each studied classroom.
Nursery SchoolAreaClassroom of ChildrenChildren’s Age (Years)FloorVolume (m3)Occupancy *Period of Occupation
SU-1Urban residentialOlder (I)5–6Ground floor180.921/256:00–17:00
Younger (II)31st floor180.918/258:00–15:00
PU-2Urban city centreOlder (I)5–61st floor210.320/256:30–16:30
Younger (II)3Ground floor210.317/256:30–16:30
PR-3Rural villageOlder (I)5–6Ground floor209.221/256:30–16:00
Younger (II)3–41st floor203.719/258:00–12:30
SR-4Rural highwayOlder (I)5–6Ground floor169.716/246:30–16:00
Younger (II)3–4Ground floor118.614/218:00–12:30
* Median occupancy of children during winter/number of children in group.

2.2. Sampling Method

Indoor (PM1, PM2.5, PM10 and TSP) and outdoor (PM2.5 and PM10) fractions of PM were actively sampled and determined following the reference procedure PN-EN 12341:2014 [24]. Samples were collected between 9 December 2013 and 14 March 2014 both outside on each playground and inside selected classrooms. The sampling time was from Monday to Friday (five-day periods, except for PU-2 (II), which had a four-day sample collection period) between 7:30 and 15:30. Inside the classrooms, the TSP, PM10 and PM2.5 samples were collected on 25 mm Nuclepore membranes (Whatman International Ltd., Maidstone, UK) while PM1 was collected employing 47 mm Teflon filters (Pall International Ltd., New York, NY, USA) using a three-stage impactor with a flow-rate of 30 dm3/min. The average volumes of air aspired by the filters was approximately 72 m3. Outside, parallel samples of PM10 and PM2.5 were collected using 47 mm Whatman QMA filters attached to PNS-15 aspirators (Atmoservice, Poznan, Poland) with flow rates of 2.3 m3/h. The average volume of air aspired outside by QMA filters was approximately 86 m3. Before and after sampling, the membranes and filters were conditioned (temperature 20 ± 1 °C, relative humidity 50 ± 5%) for 48 h and weighted with a microbalance precision of 1 µg. The sampling position in the classrooms was set at the height of an average child’s head (i.e., about 0.8 to 1.0 m above the floor) and away from the door, thus avoiding disturbances resulting from air currents.
Simultaneously, the continuous measurement of CO2 concentrations inside both the (I) and (II) classrooms and outside each building were performed using automatic portable monitors (model 77535, Az Instruments International Ltd., Hong Kong). Each monitor, equipped with a non-dispersive infrared sensor, was connected to a PC with RS232 software installed. The precision of measurements ranged between +0 and +10,000 ppm CO2: ±100 ppm CO2 or ±3% at a concentration below 100 ppm. The monitors displayed and recorded measurements in real-time, allowing for logged data to be downloaded for analysis. The selected sampling interval was 60 s.
Statistical analyses were performed using the statistical package Statistica 10 (StatSoft, Tulsa, OK, USA). The t test for average CO2 concentrations (or the Wilcoxon paired sign rank test for the concentrations of PM fractions) was performed in order to test whether urban and rural concentrations differed significantly, as well as whether the concentrations of compounds in older (I) and younger (II) children’s classrooms differed significantly from one another. A statistical significance level of α = 0.05 was used throughout the study.

2.3. Integrated Indicators based on WHO Guidelines and EU Legislation

Polish legislation [25] specifies a 24-h mean concentration of PM10 in ambient air, which is 50 µg/m3. For PM2.5, there is no corresponding short-term (24-h) limit, but there is an annual level of 25 µg/m3. The World Health Organization (WHO) is more strict in this regard; for PM2.5, it recommends a 24-h average standard of 25 µg/m3 [26] and recommends applying the same guidelines as for ambient air to indoor spaces.
Carbon dioxide concentrations are often used as a surrogate for the rate of outside supply air per occupant. Permissible concentrations of CO2 in confined spaces equal 1,000 ppm. This minimum sanitary requirement is recommended by the European Office of the WHO [27] and by ASHRAE [28]. The Polish Committee for Standardization has established general guidelines concerning the quality of air inside non-residential buildings [29]. This standard was drawn up on the basis of EU directives, as noted in Table 2, through a classification of IAQ, as it is influenced by the CO2 concentration above the outdoor level (ΔCO2). Based on the above-mentioned regulations, the increase of CO2 concentrations in relation to CO2 concentrations in outdoor air (ΔCO2) was measured in both classrooms of each of the buildings under study.
Table 2. Classification of IAQ according to PN-EN 13779 [29].
Table 2. Classification of IAQ according to PN-EN 13779 [29].
CategoryDescription of Indoor Air Quality (IAQ)Increase of CO2 Concentration in Relation to CO2 Concentration in Outdoor Air (∆CO2, ppm)
IDA 1High≤400
IDA 2Medium400–600
IDA 3Moderate600–1000
IDA 4Low≥1000
In order to gain an overall assessment of IAQ in the monitored classrooms, an integrated indicator (Total IAQindex) based on recommended guidelines was proposed. The indicator was obtained analogically to the common average air quality index (CAQI) provided to enable a comparison of air quality in European cities [30].
The PM index (PM IAQindex) was based on the comparison of indoor concentrations with reference concentrations of PM2.5 and PM10 (WHO guidelines). The PM IAQindex (1) of each fraction was calculated by dividing its average concentration by its corresponding reference concentration, namely 25 and 50 µg/m3 for PM2.5 and PM10, respectively.
PM IAQ index = PM concentration WHO guidelines  
The CO2 index (CO2 IAQindex) was created as the fraction of low IAQ (IDA4) during five hours of compulsory preschool education (from 8:00 to 13:00). If the contribution of IDA4 during care/teaching hours was 0%, the CO2 index was assumed to be 1.0, and with the increase of IDA4 contribution the CO2 IAQindex increased above 1.0:
CO 2  IAQ index = 1 + IDA4 contribution
The total IAQ index (Total IAQindex) was calculated to assess the general exposure risk for each monitored classroom as an average of the IAQ indexes (IAQindex) of all the compounds checked at the same sampling side:
Total IAQ index = n IAQ index n
where n - number of compounds.

3. Results and Discussion

The indoor (PM1, PM2.5, PM10 and TSP) and outdoor (PM2.5 and PM10) concentrations of PM were measured at all the nursery schools. The nursery school buildings differ in location, and so it was expected that they would present different quality outdoor air, especially between the urban and rural sites. At the same time, homogeneous age groups and similar internal sources of air pollutants indicate the validity of performing a comparative analysis between the classrooms of older and younger children, as well as controlling the impact of the afternoon nap on air quality inside the classrooms of younger children.

3.1. PM Concentrations

The indoor (PM1, PM2.5, PM10 and TSP) and outdoor (PM2.5 and PM10) concentrations of PM measured at all the sites are listed in Table 3. As with the indoor samples, outdoor samples of PM2.5 and PM10 were collected on playground areas. The lowest outdoor PM2.5 (21.88 µg/m3) and PM10 (22.20 µg/m3) concentrations were collected on the playground located outside the urban (PU-2) building, while the highest were observed at the playground located at the rural site (PR-3) 88.30 µg/m3 (PM2.5) and 92.17 µg/m3 (PM10). The average outdoor PM2.5 concentration exceeded the WHO guidelines at 65% and 132%, correspondingly, at urban and rural sites. The average outdoor concentration of PM10 collected at the urban sites did not exceed the WHO guidelines, while at rural sites the WHO guidelines were on average exceeded by 30%. The outdoor concentrations were higher in rural areas than in urban areas, but not significantly (p = 0.18). Outdoors, during the winter season and in the Upper Silesia region, Rogula-Kozłowska et al. [31,32] received analogous mean concentrations of PM2.5 and PM10. Other worldwide research generally points out higher concentrations of PM at urban sites compared to rural sites [15,17,33]. However, in Poland, during the winter season, domestic sources use low quality coal, biomass or even refuse for heating. Thus, rural areas are often characterized by lower air quality than urban areas.
The highest indoor concentrations of all the determined PM fractions (PM1, PM2.5, PM10 and TSP) were found in the rural (SR-4) nursery school situated next to the highway. Meanwhile, the lowest were observed in the SU-1 building situated at the urban residential site. However, the discrepancies between urban and rural classrooms are not significant (p = 0.10–0.51). The indoor mean concentrations of samples collected in Portuguese preschools were found to be at a similar level, e.g., PM1, PM2.5, PM10 and TSP were 33.08, 34.69, 50.94 and 85.81 µg/m3, respectively [17]. Furthermore, the total (TSP) and respirable fraction (PM10) of PM in Korean preschools were at a similar level, respectively, 66.5 ± 35.1 µg/m3 and 25.9 ± 13.4 µg/m3 [15]. Meanwhile, in Swedish preschools equipped with mechanical ventilation, the PM2.5 concentrations were significantly lower - between 3.2 and 9.3 µg/m3 [21].
Table 3. Average levels of PM fractions (μg/m3) measured during occupancy periods (N = 48); (I) - Older, (II) - Younger children classrooms.
Table 3. Average levels of PM fractions (μg/m3) measured during occupancy periods (N = 48); (I) - Older, (II) - Younger children classrooms.
LocationConcentration, μg/m3
Indoor Outdoor
PM1SDPM2.5SDPM10SDTSPSD PM2.5SDPM10SD
SU-1 (I)51.2125.3470.5930.71117.5742.04134.4346.1235.7315.4936.7116.96
SU-1 (II)25.9712.8541.1717.9168.2624.4173.0525.0642.5518.4545.3720.96
PU-2 (I)78.8939.04106.0646.14149.8153.57163.8156.2064.7228.0770.2632.46
PU-2 (II)33.7016.6749.0621.3479.9228.5896.7833.2021.889.4922.2010.26
PR-3 (I)83.6423.52102.0527.54135.9341.02147.5442.2544.4317.2149.0417.07
PR-3 (II)78.1321.9780.9421.84104.9031.66124.2435.5888.3034.2092.1732.08
SR-4 (I)102.1128.71125.6933.92166.1250.13184.2452.7638.0414.7443.8115.25
SR-4 (II)49.0413.7967.6518.2681.4924.5991.1926.1160.7723.5474.1825.82
Urban47.4423.4766.7229.02103.8937.15117.0240.1441.2217.8743.6320.16
Rural78.2322.0094.0825.39122.1136.85136.8039.1757.8822.4264.8022.55
(I)78.9621.04101.1022.81142.3620.62157.5021.5045.7313.1949.9614.45
(II)46.7123.0459.7017.9983.6415.3596.3221.1953.3728.1958.4830.93
Moreover, in all the nursery schools, PM concentrations were higher in older children’s classrooms (Table 3). The TSP, PM10 and PM2.5 levels were significantly higher in older children classrooms (p < 0.03), while the PM1 levels were higher but not significantly (p = 0.08). Other research reported an analogous relationship between the classrooms of younger and older children [17,33], and indicated a potential reason for this being the cumulative effect of three major conditions: high occupancy, poor ventilation and the intensive activities of children resulting in the PM resuspension phenomenon [7].
From our point of view, it was important to explicate which of the enumerated conditions were most influential in the examined cases. Based on Wilcoxon paired sign rank tests, the PM fractions characteristic of older (I) and younger (II) children’s classrooms were compared. In SU-1 and both rural nursery schools (PR-3 and SR-4), the trend of higher PM levels in the older (I) children’s classroom was not as strong or statistically significant (p = 0.10–0.48). In the PU-2 nursery school, this seemed more important (p = 0.04).
Assuming that that the physical activity level of five-year-old children is higher than that of three-year-old children in all nursery schools, the process of PM resuspension is able to confirm increased PM concentrations in older children’s classrooms. Moreover, in PU-2, the older children’s classroom was located on the second floor, compared to the first floor in the other nursery schools; this probably increased the influence of the inadequate ventilation system.

3.2. Indoor/Outdoor Ratios and PM Size Distribution

To understand the participation of indoor and outdoor sources in IAQ, the I/O ratios’ analysis was restricted to PM2.5 and PM10 levels being obtained for each studied classroom (Table 4). The lowest average I/O ratio 0.92 (PM2.5) was found in PR-4 (II), occupied by younger children who would leave the classroom for their afternoon nap. Meanwhile, the highest, reaching 3.79 (PM10), was in SR-4 (I), occupied by older children. The results underscore the higher contribution of PM2.5 and PM10 levels in older children’s classroom (respectively 2.30 and 2.97) compared with younger (respectively 1.31 and 1.84) children’s classrooms. In order to appropriately protect the health of children, it is important to reduce their exposure to aerosol particles. For example, instead of the carpets, smooth panels can be installed. In addition, every-day wet cleaning of the floor is strongly recommended.
In Portuguese preschools, during children’s occupancy, the I/O ratios of PM10 varied between 2.12 and 13.96 [17], while the PM10 ratios varied from 1.06 to 1.60 in Korea [15]. In one Polish secondary school, during teaching hours in winter, the I/O ratios of PM1, PM2.5 and PM10 were significantly lower at 0.8 ± 0.2, 2.0 ± 0.8 and 2.5 ± 1.7, respectively [6], which might be associated with the reduced physical activity of teenagers.
Table 4. Indoor/outdoor (I/O) ratios and PM size distribution in each studied classroom.
Table 4. Indoor/outdoor (I/O) ratios and PM size distribution in each studied classroom.
Nursery School (Classroom)I/O RatiosPM Size Distribution
PM2.5PM10PM1/PM2.5PM2.5/PM10PM10/TSP
SU-1 (I)1.983.200.730.600.87
SU-1 (II)0.971.500.630.600.93
PU-2 (I)1.642.130.740.710.91
PU-2 (II)2.243.600.690.610.83
PR-3 (I)2.302.770.820.750.92
PR-3 (II)0.921.140.970.770.84
SR-4 (I)3.303.790.810.760.90
SR-4 (II)1.111.100.720.830.89
Generally, the I/O ratios were higher for larger fractions of PM10 and in all the buildings and classrooms located on the first floor. Blondenau et al. [34] have emphasized that the I/O ratios of airborne particles strongly depend on particle size. The larger the particles are in terms of optical diameter, the heavier they are and the more easily they can be deposited on floors and furnishings. Consequently, the influence of re-suspension on indoor particle concentrations increases with particle size. To understand the effect of size distribution on the measured PM concentrations, three different PM size ratios were used to characterize indoor air: PM1/PM2.5, PM2.5/PM10 and PM10/TSP. The PM size distributions calculated for each classroom generally confirm the predominant contribution of larger particles (Table 4). The relationships between older and younger children’s classrooms were not significant (p > 0.33). Larger particles (PM10/TSP) at urban and rural sites revealed similar size distributions (p = 0.93), while smaller particles presented dissimilar distributions. However, the PM2.5/PM10 distribution between urban and rural sites was not as significant (p = 0.05) as for PM1/PM2.5 (p = 0.004).

3.3. Carbon Dioxide

Based on the general guidelines concerning the quality of air inside non-residential buildings (PN-EN 13779, 2008), the increase in CO2 concentrations in relation to CO2 concentration in outdoor air (ΔCO2) was measured during the children’s occupation of both classrooms of each of the studied building. Figure 2 depicts the classification of IAQ in each nursery school building during the children’s occupation during compulsory care/teaching hours (8:00–13:00).
Figure 2. Classification of IAQ (IDA) in nursery school building according to growth of CO2 concentration (ΔCO2).
Figure 2. Classification of IAQ (IDA) in nursery school building according to growth of CO2 concentration (ΔCO2).
Ijerph 12 07697 g002
The indoor concentrations of CO2 revealed inadequate classroom air exchange rates. Most worryingly, during compulsory care/teaching hours, the air in the classrooms was often of low quality (IDA4). The highest contribution of IDA4 (91.0% of compulsory care/teaching time) prevailed in the younger children’s classroom (II) at the SU-1 site (children who sleep in pyjamas during resting time). Meanwhile, the lowest contribution of poor indoor air (IDA4 = 22.6%) was for the younger children’s classroom (II) at the PR-3 site (children who rest in another room). The differences between indoor and outdoor concentrations of CO2 observed in the classrooms of the younger children points to the significance of the afternoon nap.
Recent studies by Gładyszewska-Fiedoruk [18,35] presented CO2 levels in nursery schools located in Białystok, in north-eastern Poland. The measurements were taken prior to the arrival of children and staff, as well as after all the classes had been concluded. These studies classified the quality of the air into IDA1 and IDA2 categories prior to the arrival of staff and children, and noted low IAQ (IDA4) in the afternoons (which is in agreement with our own findings). Generally, studies in Poland [35,36,37] and other countries [15,23,38,39,40,41,42] highlight that CO2 levels often exceed the recommended standards. Its concentrations vary according to the length and level of occupancy of the classrooms, the type and quality of ventilation and room design. Our research confirmed the enumerated conditions, moreover, our results point out differences between older (I) and younger (II) children’s classrooms, which can become more significant if we link inadequate ventilation with the various patterns of children’s activities.

3.4. Integrated Indicator

The IAQindex for each classroom was calculated for PM2.5, PM10 and CO2 (Figure 3). Generally, PM2.5 was found to be the highest single-compound contributor to IAQindex values. Only at the urban SU-1 site in the younger children’s classroom (II) CO2 IAQindex was higher than PM2.5 IAQindex, but not significantly (p = 0.43). The individual IAQindex of each compound was assumed to be additive.
In analogy to the common average air quality index (CAQI) [30], the Total IAQindex was calculated as the arithmetic average of the IAQindex of the individual compounds. Comparing the Total IAQindex for each classroom, the following order of average indicators was found: SR-4(I) > PU-2(I) > PR-3(I) > SU-1(I) > PR-4(II) > SR-3(II) > PU-2(II) > SU-1(II). The presented order clearly indicates the higher indoor exposure of older (five- to six-year-old) than younger (three- to four-year-old) children to the examined air pollutants. The difference in the average Total IAQindex between older (I) and younger (II) children—2.81 and 1.89, respectively—was significant (p = 0.01). The urban and rural Total IAQindex were also different - 2.15 and 2.55, respectively - but not significant (p = 0.38).
The key intent of this study was to estimate whether the overall exposure of children to PM and CO2 differs between locations of nursery schools. The Total IAQindex enabled to order the examined nursery schools from the highest to the lowest exposure of children to poor IAQ. The following order of average indicators for Total IAQindex was found: SR-4 > PR-3 > PU-2 > SU-1 = 2.62 > 2.47 > 2.37 > 1.93, respectively. It should be underlined that the presented IAQ gradation of nursery schools is adequate only for winter season. More research is necessary to verify whether, during the spring season a similar or reverse relation will occur, which is crucial to the health of children.

4. Conclusions

The aim of this study was to assess IAQ in naturally ventilated nursery schools by conducting a PM and CO2 measuring campaign. The quantification of indoor (PM1, PM2.5, PM10 and TSP) and outdoor (PM2.5 and PM10) fractions of PM revealed significant indoor PM contributions. Frequently-monitored, high-levels of CO2 exceeding 1,000 ppm in relation to outdoor air (IDA4) also confirmed low IAQ inside classrooms, which points to the low efficiency of ventilation systems.
The relationship between urban and rural sites revealed elevated concentrations of all PM fractions at rural sites in outdoor as well as indoor air. The IAQ in older and younger children's classrooms confirmed that the classrooms occupied by older children were found to be those with higher PM (PM1, PM2.5, PM10 and TSP) concentrations; meanwhile, the highest CO2 concentration was observed in the classrooms of younger children who slept during the afternoon. In addition to the highest contribution of low IAQ during teaching hours, the role of the afternoon nap seems significant.
Figure 3. Integrated Indicator -IAQ index.
Figure 3. Integrated Indicator -IAQ index.
Ijerph 12 07697 g003
In order to rank sites based on their IAQ, the total IAQ index (Total IAQindex) was used. This simple approach could be a precious tool for the more efficient management of resources, with the aim of mitigating actions, as well as for the estimation of the impact of the indoor activities of children frequenting these environments.
Similar studies should be conducted in order to evaluate whether or not there is a causal relationship between pollutant exposure and health symptoms in nursery schools and whether this may adversely affect children’s attendance.

Acknowledgements

The authors would like to thank the support of the principals and staff of the nursery schools that participated in the study. We are also grateful to Jozef S. Pastuszka, Silesian University of Technology for support and useful comments. The research leading to these results has received funding from the Polish-Norwegian Research Programme operated by the National Centre for Research and Development under the Norwegian Financial Mechanism 2009-2014 in the frame of Project Contract No. Pol Nor/210247/20/2013.

Author Contributions

Anna Mainka had the original idea for the studies in nursery schools. Elwira Zajusz-Zubek was responsible for analysis of trace elements. Anna Mainka prepared the manuscript, which was reviewed by Elwira Zajusz-Zubek. Both authors read and approved the final manuscript.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. EU Commission. Progress towards the Common European Objectives in Education and Training (2010/2011); EU Commission: Brussels, Belgium, 2011. [Google Scholar]
  2. Education in 2013/2014 School Year; Central Statistical Office: Warsaw, Poland, 2014.
  3. Almeida, S.M.; Canha, N.; Silva, A.; Do Carmo Freitas, M.; Pegas, P.; Alves, C.; Evtyugina, M.; Pio, C.A. Children exposure to atmospheric particles in indoor of Lisbon primary schools. Atmos. Environ. 2011, 45, 7594–7599. [Google Scholar] [CrossRef]
  4. Sofuoglu, S.C.; Aslan, G.; Inal, F.; Sofuoglu, A. An assessment of indoor air concentrations and health risks of volatile organic compounds in three primary schools. Int. J. Hyg. Environ. Health 2011, 214, 36–46. [Google Scholar] [CrossRef] [PubMed]
  5. De Gennaro, G.; Farella, G.; Marzocca, A.; Mazzone, A.; Tutino, M. Indoor and outdoor monitoring of volatile organic compounds in school buildings: Indicators based on health risk assessment to single out critical issues. Int. J. Environ. Res. Public Health 2013, 10, 6273–6291. [Google Scholar] [CrossRef] [PubMed]
  6. Zwoździak, A.; Sówka, I.; Krupińska, B.; Zwoździak, J.; Nych, A. Infiltration or indoor sources as determinants of the elemental composition of particulate matter inside a school in Wrocław, Poland? Build. Environ. 2013, 66, 173–180. [Google Scholar] [CrossRef]
  7. Zwoździak, A.; Sówka, I.; Fortuna, M. Influence of PM1, PM2.5, PM10 concentrations in indoor school environment on spirometric parameters in schoolchildren in Polish. Annu. Set Environ. Prot. 2013, 15, 2022–2038. [Google Scholar]
  8. Alves, C.A.; Urban, R.C.; Pegas, P.N.; Nunes, T. Indoor/Outdoor relationships between PM10 and associated organic compounds in a primary school. Aerosol Air Qual. Res. 2014, 14, 86–98. [Google Scholar] [CrossRef]
  9. Demirel, G.; Özden, Ö.; Döǧeroǧlu, T.; Gaga, E.O. Personal exposure of primary school children to BTEX, NO2 and ozone in Eskişehir, Turkey: Relationship with indoor/outdoor concentrations and risk assessment. Sci. Total Environ. 2014, 473–474, 537–548. [Google Scholar] [CrossRef] [PubMed]
  10. Krugly, E.; Martuzevicius, D.; Sidaraviciute, R.; Ciuzas, D.; Prasauskas, T.; Kauneliene, V.; Stasiulaitiene, I.; Kliucininkas, L. Characterization of particulate and vapor phase polycyclic aromatic hydrocarbons in indoor and outdoor air of primary schools. Atmos. Environ. 2014, 82, 298–306. [Google Scholar] [CrossRef]
  11. Mazaheri, M.; Clifford, S.; Jayaratne, R.; Megat Mokhtar, M.A.; Fuoco, F.; Buonanno, G.; Morawska, L. School children’s personal exposure to ultrafine particles in the urban environment. Environ. Sci. Technol. 2014, 48, 113–120. [Google Scholar] [CrossRef] [PubMed] [Green Version]
  12. Turunen, M.; Toyinbo, O.; Putus, T.; Nevalainen, A.; Shaughnessy, R.; Haverinen-Shaughnessy, U. Indoor environmental quality in school buildings, and the health and wellbeing of students. Int. J. Hyg. Environ. Health 2014, 217, 733–739. [Google Scholar] [CrossRef] [PubMed]
  13. Mendell, M.J.; Heath, G.A. Do indoor pollutants and thermal conditions in schools influence student performance? A critical review of the literature. Indoor Air 2005, 15, 27–52. [Google Scholar] [CrossRef] [PubMed]
  14. Pegas, P.N.; Evtyugina, M.G.; Alves, C.A.; Nunes, T.; Cerqueira, M.; Franchi, M.; Pio, C.; Almeida, S.M.; Freitas, M.C. Outdoor/indoor air quality in primary schools in Lisbon: A preeliminary study. Quim. Nova 2010, 33, 1145–1149. [Google Scholar] [CrossRef]
  15. Yoon, C.; Lee, K.; Park, D. Indoor air quality differences between urban and rural preschools in Korea. Environ. Sci. Pollut. Res. 2011, 18, 333–345. [Google Scholar] [CrossRef] [PubMed]
  16. Cyprowski, M.; Buczyńska, A.; Szadkowska-Stańczyk, I. Indoor allergens in settled dust from kindergartens in city of Łódź, Poland. Int. J. Occup. Med. Environ. Health 2013, 26, 890–899. [Google Scholar] [CrossRef] [PubMed]
  17. Branco, P.T.B.S.; Alvim-Ferraz, M.C.M.; Martins, F.G.; Sousa, S.I.V. Indoor air quality in urban nurseries at Porto city: Particulate matter assessment. Atmos. Environ. 2014, 84, 133–143. [Google Scholar] [CrossRef]
  18. Gładyszewska-Fiedoruk, K. Correlations of air humidity and carbon dioxide concentration in the kindergarten. Energy Build. 2013, 62, 45–50. [Google Scholar] [CrossRef]
  19. Latif, M.T.; Yong, S.M.; Saad, A.; Mohamad, N.; Baharudin, N.H.; Mokhtar, M.B.; Tahir, N.M. Composition of heavy metals in indoor dust and their possible exposure: A case study of preschool children in Malaysia. Air Qual. Atmos. Heal. 2014, 7, 181–193. [Google Scholar] [CrossRef]
  20. Sousa, S.I.; Ferraz, C.; Alvim-Ferraz, M.C.; Vaz, L.G.; Marques, A.J.; Martins, F.G. Indoor air pollution on nurseries and primary schools: Impact on childhood asthma—Study protocol. BMC Public Health 2012, 12. [Google Scholar] [CrossRef] [PubMed]
  21. Wichmann, J.; Lind, T.; Nilsson, M.A.M.; Bellander, T. PM2.5, soot and NO2 indoor-outdoor relationships at homes, pre-schools and schools in Stockholm, Sweden. Atmos. Environ. 2010, 44, 4536–4544. [Google Scholar] [CrossRef]
  22. Salvi, S. Health effects of ambient air pollution in children. Paediatr. Respir. Rev. 2007, 8, 275–280. [Google Scholar] [CrossRef] [PubMed]
  23. Santamouris, M.; Synnefa, A.; Asssimakopoulos, M.; Livada, I.; Pavlou, K.; Papaglastra, M.; Gaitani, N.; Kolokotsa, D.; Assimakopoulos, V. Experimental investigation of the air flow and indoor carbon dioxide concentration in classrooms with intermittent natural ventilation. Energy Build. 2008, 40, 1833–1843. [Google Scholar] [CrossRef]
  24. Polish-European Standard. In Ambient Air. Standard Gravimetric Measurement Method for the Determination of the PM10 or PM2.5 Mass Concentration of Suspended Particulate Matter; Polish-European Standard: Warsaw, Poland, 2014.
  25. Dz, U. Regulation of the Minister of Environment of 13 September 2012,No. 1031—The Levels of Certain Substances in the Ambient Air; Minister of Polish Law: Warsaw, Poland, 2012. [Google Scholar]
  26. WHO. Air Quality Guidelines for Particulate Matter, Ozone, Nitrogen Dioxide and Sulfur Dioxide; World Health Organization: Geneva, Switzerland, 2006. [Google Scholar]
  27. Air Quality Guidelines; World Health Organization: Geneva, Switzerland, 2000.
  28. American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). Standard 62.1—2013 Ventilation for Acceptable Indoor Air Quality; ASHRAE: Atlanta, GA, USA, 2013. [Google Scholar]
  29. Ventilation for Non-residential Buildings. Performance Requirements for Ventilation and Room-conditioning Systems; Polish-European Standard: Warsaw, Poland, 2008.
  30. Common Information to European Air Quality Index; DCMR: Schiedam, Netherlands, 2012.
  31. Rogula-Kozłowska, W.; Klejnowski, K.; Rogula-Kopiec, P.; Ośródka, L.; Krajny, E.; Błaszczak, B.; Mathews, B. Spatial and seasonal variability of the mass concentration and chemical composition of PM2.5 in Poland. Air Qual. Atmos. Heal. 2014, 7, 41–58. [Google Scholar] [CrossRef] [PubMed]
  32. Rogula-Kozłowska, W.; Kozielska, B.; Klejnowski, K. Hazardous compounds in urban PM in the central part of Upper Silesia (Poland) in winter. Arch. Environ. Prot. 2013, 39, 53–65. [Google Scholar] [CrossRef]
  33. Nunes, R.A.O.; Branco, P.T.B.S.; Alvim-Ferraz, M.C.M.; Martins, F.G.; Sousa, S.I.V. Particulate matter in rural and urban nursery schools in Portugal. Environ. Pollut. 2015, 202, 7–16. [Google Scholar] [CrossRef] [PubMed]
  34. Blondeau, P.; Iordache, V.; Poupard, O.; Genin, D.; Allard, F. Relationship between outdoor and indoor air quality in eight French schools. Indoor Air 2005, 15, 2–12. [Google Scholar] [CrossRef] [PubMed]
  35. Gładyszewska-Fiedoruk, K. Analysis of stack ventilation system effectiveness in an average kindergarten in north-eastern Poland. Energy Build. 2011, 43, 2488–2493. [Google Scholar] [CrossRef]
  36. Połednik, B. Aerosol particle concentrations and indoor air parameters in school classrooms. In Management of Indoor Air Quality; Dudzińska, M.R., Ed.; CRC Press: London, UK, 2011; pp. 31–38. [Google Scholar]
  37. Dumała, S.M.; Dudzińska, M.R. Microbiological indoor air quality in Polish schools. Annu. Set Environ. Prot. 2013, 15, 231–244. [Google Scholar]
  38. Griffiths, M.; Eftekhari, M. Control of CO2 in a naturally ventilated classroom. Energy Build. 2008, 40, 556–560. [Google Scholar] [CrossRef]
  39. Mumovic, D.; Palmer, J.; Davies, M.; Orme, M.; Ridley, I.; Oreszczyn, T.; Judd, C.; Critchlow, R.; Medina, H.A.; Pilmoor, G.; et al. Winter indoor air quality, thermal comfort and acoustic performance of newly built secondary schools in England. Build. Environ. 2009, 44, 1466–1477. [Google Scholar] [CrossRef]
  40. Mendes, A.; Aelenei, D.; Papoila, A.L.; Carreiro-Martins, P.; Aguiar, L.; Pereira, C.; Neves, P.; Azevedo, S.; Cano, M.; Proença, C.; et al. Environmental and ventilation assessment in child day care centers in Porto: The envirh project. J. Toxicol. Environ. Health 2014, 77, 931–943. [Google Scholar] [CrossRef] [PubMed]
  41. Carreiro-Martins, P.; Viegas, J.; Papoila, A.L.; Aelenei, D.; Caires, I.; Araújo-Martins, J.; Gaspar-Marques, J.; Cano, M.M.; Mendes, A.S.; Virella, D.; et al. CO2 concentration in day care centres is related to wheezing in attending children. Eur. J. Pediatr. 2014, 173, 1041–1049. [Google Scholar] [CrossRef] [PubMed]
  42. Branco, P.T.B.S.; Alvim-Ferraz, M.C.M.; Martins, F.G.; Sousa, S.I.V. Children’s exposure to indoor air in urban nurseries-part I: CO2 and comfort assessment. Environ. Res. 2015, 140, 1–9. [Google Scholar] [CrossRef] [PubMed]

Share and Cite

MDPI and ACS Style

Mainka, A.; Zajusz-Zubek, E. Indoor Air Quality in Urban and Rural Preschools in Upper Silesia, Poland: Particulate Matter and Carbon Dioxide. Int. J. Environ. Res. Public Health 2015, 12, 7697-7711. https://doi.org/10.3390/ijerph120707697

AMA Style

Mainka A, Zajusz-Zubek E. Indoor Air Quality in Urban and Rural Preschools in Upper Silesia, Poland: Particulate Matter and Carbon Dioxide. International Journal of Environmental Research and Public Health. 2015; 12(7):7697-7711. https://doi.org/10.3390/ijerph120707697

Chicago/Turabian Style

Mainka, Anna, and Elwira Zajusz-Zubek. 2015. "Indoor Air Quality in Urban and Rural Preschools in Upper Silesia, Poland: Particulate Matter and Carbon Dioxide" International Journal of Environmental Research and Public Health 12, no. 7: 7697-7711. https://doi.org/10.3390/ijerph120707697