Next Article in Journal
SAPTM: Towards High-Throughput Per-Flow Traffic Measurement with a Systolic Array-Like Architecture on FPGA
Next Article in Special Issue
A Review and Comparison of Solid, Multi-Strands and Litz Style PCB Winding
Previous Article in Journal
End-to-End Noisy Speech Recognition Using Fourier and Hilbert Spectrum Features
Previous Article in Special Issue
Optimizing AC Resistance of Solid PCB Winding
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Bidirectional Operation Scheme of Grid-Tied Zeta Inverter for Energy Storage Systems

Division of Electronic Engineering, Jeonbuk National University, Jeonju 561-756, Korea
Electronics 2020, 9(7), 1159; https://doi.org/10.3390/electronics9071159
Submission received: 7 June 2020 / Revised: 14 July 2020 / Accepted: 16 July 2020 / Published: 17 July 2020
(This article belongs to the Special Issue Design and Optimization of High-Frequency Power Converter)

Abstract

:
The zeta inverter has been used for single-phase grid-tied applications. For its use of energy storage systems, this paper proposes the bidirectional operation scheme of the grid-tied zeta inverter. A shoot-through switching state is introduced, providing reliable bidirectional operation modes. A shoot-through duty cycle is utilized for the bidirectional grid current control of the inverter. The grid current is bidirectionally controlled by the shoot-through duty cycle, which enables the inverter to operate with seamless change of operation modes. Over the state-of-the art techniques using flyback and Cuk inverter topologies, the grid-tied zeta inverter using the proposed operation scheme provides advantages of high efficiency, low cost, and high reliability. The operation principle is presented by describing the operation mode and control method for the grid-tied zeta inverter. A 500 W prototype has been built and tested to verify its operation principle.

1. Introduction

Up to now, various single-phase isolated grid-tied inverters have been developed with renewable energy sources [1,2,3,4,5,6,7,8,9,10]. Among them, the grid-tied zeta inverter has been recently developed for high-efficiency inverter designs [7,8,9,10]. It has been gaining high attention due to its circuit count reduction design [9,10]. As the state-of-the art techniques, the grid-tied flyback inverter [1,2,3] and the grid-tied Cuk inverter [4,5,6] necessarily use a bidirectional switch along with the unfolding switching circuit at the grid side. It needs the additional gate driving circuit, which causes drawbacks for increasing the manufacturing cost and decreasing the power density for industrial uses. On the other hand, the grid-tied zeta inverter can solve the drawbacks of the current state-of-the art inverters because it does not use the bidirectional switch at the grid side [9,10]. It can reduce the circuit components and improve the power density. Furthermore, it can increase the power efficiency for reducing the switching loss by removing the bidirectional switch, compared to the previous bidirectional grid-tied inverters using flyback and Cuk inverter topologies. As the grid-tied zeta inverter operates in the continuous conduction mode [9], it has reduced conduction losses, compared to the inverters operating in the discontinuous conduction mode [7,8]. Furthermore, the grid-tied zeta inverter has improved its power efficiency [10] by using advanced switching techniques such as active clamp [11] and synchronous rectification [12].
One thing to remark is that its most applications have been mainly focused on photovoltaic power generations [7,8,9,10]. As a microinverter for photovoltaic modules, the grid-tied zeta inverter operates as an isolated dc-ac converter, supplying ac power from dc power source. However, for its use of energy storage systems, the grid-tied zeta inverter needs a bidirectional operation scheme. In the energy storage systems, the grid-tied zeta inverter should interface the grid with energy storage devices such as batteries [13] and ultracapacitors [14]. Nevertheless, any literatures have not been reported yet about the bidirectional operation of the grid-tied zeta inverter.
This paper proposes the bidirectional operation scheme of the grid-tied zeta inverter for energy storage systems. The operation principle is presented for its operation mode and control method. A shoot-through switching state [15] is intentionally introduced for the bidirectional operation of the inverter. The shoot-through is typically a forbidden switching state for isolated grid-tied inverters because of the breakdown of the full-bridge unfolding circuit [16,17]. In contrast, the shoot-through switching state provides reliable bidirectional operation modes for the grid-tied zeta inverter. A shoot-through duty cycle is utilized for the bidirectional grid current control of the inverter. The grid current can be bidirectionally controlled by the shoot-through duty cycle. A unified grid current controller can be implemented, which enables the grid-tied zeta inverter to have seamless change of operation modes [18,19].
In this paper, Section 2 presents the operation principle of the grid-tied zeta inverter. It describes the circuit configuration, operation mode, and control method. Section 3 discusses the experiment results to verify the operation principle for a 500 W prototype. Section 4 presents the concluding remark of the paper.

2. Proposed Inverter

2.1. Circuit Configuration

Figure 1 shows the circuit diagram of the grid-tied zeta inverter for energy storage systems. The grid-tied zeta inverter has a primary switch (SP), a high-frequency transformer (T), and a secondary switching circuit (CS, SS1, SS2, SS3, SS4, Lg). The dc voltage for the energy storage device is Vb. The grid voltage vg is defined as
v g = V g sin ω t .
The absolute peak value of vg is Vg. The angular frequency of vg is ω. An ideal transformer is modeled as T, which has the magnetizing inductor Lm with a negligible leakage inductor. Its turns ratio n is nS/nP. The primary winding turns is nP. The secondary winding turns is nS. The magnetizing inductor Lm is large enough so that its current iLm is continuous during constant switching period Ts. The filter inductor Lg is large enough so that the grid current ig is continuous during Ts. The secondary capacitor CS is large enough so that its voltage VCs is constant during Ts. The capacitor voltage VCs is considered to be |vg| as the secondary switching circuit gives the current path to fold vg.
All power switches are considered ideal with their intrinsic body diodes. A shoot-through switching state happens when series connected power switches are turned on simultaneously in the secondary switching circuit. One shoot-through switching state occurs when SS1 and SS2 are turned on simultaneously. Another shoot-through switching state occurs when SS3 and SS4 are turned on simultaneously. The LC network (Lm, CS) couples the secondary switching circuit to the grid, thus providing reliable power transfer operation that cannot be obtained in the traditional isolated grid-tied inverters.
The grid-tied zeta inverter has two operation modes: the inverter mode and the rectifier mode. In the inverter mode, it operates as an isolated dc-ac converter, supplying the energy storage device power into the grid. In the rectifier mode, it operates as an isolated ac-dc converter, supplying the grid power into the energy storage device.

2.2. Operation Mode

Figure 2 shows the circuit diagrams that describe the switching states in the inverter mode. Figure 2a,b show the switching circuit diagrams during Ts, respectively, for the positive grid voltage. The switches SS2 and SS3 are always turned on, and SS4 is always turned off. The switch SS1 operates complementary to SP with constant switching frequency fs (=1/Ts). There are four switching states in the inverter mode. It is a switching state 1 when SS1 is turned off and SP is turned on, as shown in Figure 2a. The magnetizing inductor Lm stores the energy from Vb. As the voltage across the secondary winding of T is nVb, the grid current ig increases linearly at the rate of dig/dt = nVb/Lg. As shown in Figure 2b, it is a switching state 2 when SS1 is turned on and SP is turned off. This is the shoot-through switching state that the energy stored in Lm is transferred to CS through CS, SS2, SS1, and the secondary winding of T. The grid current ig freewheels through Lg, vg, SS1, and SS3, decreasing at the rate of dig/dt = −vg/Lg.
Figure 2c,d show the switching circuit diagrams during Ts, respectively, for the negative grid voltage. The switches SS1 and SS4 are always turned on, and SS2 is always turned off. The switch SS3 operates complementary to SP with fs. It is a switching state 3 when SS3 is turned off and SP is turned on, as shown in Figure 2c. The magnetizing inductor Lm stores the energy from Vb. As the voltage across the secondary winding of T is nVb, the grid current ig decreases linearly at the rate of dig/dt = −nVb/Lg. As shown in Figure 2b, it is a switching state 4 when SS3 is turned on and SP is turned off. This is the shoot-through switching state that the energy stored in Lm is transferred to CS through CS, SS4, SS3, and the secondary winding of T. The grid current ig freewheels through Lg, vg, SS1, and SS3, increasing at the rate of dig/dt = vg/Lg.
Figure 3 shows the circuit diagrams to describe the switching states in the rectifier mode. Figure 3a,b show the switching circuit diagrams during Ts, respectively, for the positive grid voltage. The switches SS2 and SS3 are always turned on, and SS4 is always turned off. The switch SS1 operates complementary to SP with fs. There are four switching states in the rectifier mode. It is a switching state 1 when SS1 is turned on and SP is turned off, as shown in Figure 3a. This is the shoot-through switching state that the energy stored in CS is transferred to Lm through SS1, SS2, CS, and the secondary winding of T. The inductor Lg stores the energy from vg. The grid current ig increases linearly at the rate of dig/dt = vg/Lg. As shown in Figure 3b, it is a switching state 2 when SS1 is turned off and SP is turned on. When SP is turned on, Lm supplies its stored energy to Vb. As the voltage across Lm is Vb, ig decreases linearly at the rate of dig/dt = –nVb/Lg.
Figure 3c,d show the switching circuit diagrams during Ts, respectively, for the negative grid voltage. The switches SS1 and SS4 are always turned on, and SS2 is always turned off. The switch SS3 operates complementary to SP with fs. It is a switching state 3 when SS3 is turned on and SP is turned off, as shown in Figure 3c. This is the shoot-through switching state that the energy stored in CS is transferred to Lm through SS3, SS4, CS, and the secondary winding of T. The inductor Lg stores the energy from vg. The grid current ig decreases linearly at the rate of dig/dt = −vg/Lg. As shown in Figure 3d, it is a switching state 4 when SS3 is turned off and SP is turned on. When SP is turned on, Lm supplies its stored energy to Vb. As the voltage across Lm is Vb, ig increases linearly at the rate of dig/dt = nVb/Lg.
Assume that the shoot-through duty cycle is DST for Ts. Regardless of the operation modes, the on-time of SS1 is the shoot-through duty cycle for the positive grid voltage. For the negative grid voltage, the on-time of SS3 is the shoot-through duty cycle. Suppose that the on-time of SP is DSP for Ts. As DSP is complementary to DST for Ts, the following duty cycle relationship is obtained as
D S P + D S T = 1 .

2.3. Control Method

Regardless of the operation modes, the volt-second balance for Lg during Ts gives the following voltage Equation as
v g D S T T s n V b 1 D S T   T s = 0 .
By rearranging (3), we have the relation between vg and Vb as
V b v g = D S T n 1 D S T .
By (4) and the input-output power relation of Vb ib = vg ig, we have the relation between ib and ig as
i g i b = D S T n 1 D S T .
By the relation between ib and iLm, the following current equation is represented as
i b = 1 D S T i L m .
By (5) and (6), the relation between ig and iLm is represented as
n i b = D S T i L m .
For both operation modes, the following voltage equations can be obtained for Lm for one switching period Ts as
v g = L m i L m D S T T s .
n V b = L m i L m 1 D S T T s .
By (8) and (9), the average voltage for Lm during Ts can be represented with respect to the deviation ∆iLm of iLm as
v g D S T + n V b 1 D S T = L m Δ i L m T s .
From (10), DST can be represented as
D S T = n V b n V b + v g 1 n V b + v g L m Δ i L m T s .
By using (4) and (7), DST in (11) can be represented as
D S T = D N , S T + D C , S T = n V b n V b + v g L m Δ i g V b T s
where DN,ST is the nominal shoot-through duty cycle, and DC,ST is the controlled shoot-through duty cycle as
D N , S T = n V b n V b + v g = n V b n V b + V g sin ω t , D C , S T = L m Δ i g V b T s .
Suppose that vg is exactly measured with a phase-locked loop (PLL) [20]. The nominal shoot-through duty cycle DN,ST plays the role of providing the nominal voltage compensation. For both operation modes, the relation between DST and ig is nonlinear, as shown in (12). By using DN,ST for the nominal voltage compensator, the non-linear system in (12) is transformed to the first order linear system, which can be controlled by DC,ST.
As the same nominal and controlled shoot-through duty cycles can be defined for both operation modes, the bidirectional grid current control can be performed in a unified controller. This feature enables the grid-tied zeta inverter to have seamless change of operation modes. Figure 4 shows the bidirectional grid current control block diagram of the grid-tied zeta inverter. The operation mode is selected by the sign of I*g. The power level is decided by the peak magnitude of the grid current reference I*g. A grid current controller generates DC,ST to minimize the error between i*g and ig. The grid current controller can be designed by high performance grid current control techniques such as the proportional-resonant (PR) control [21] and the repetitive control [22].

2.4. Control Implementation

To regulate the grid current ig with low harmonic currents, DC,ST can be implemented by the PR control [21]. Its ideal transfer function CPR (s) is
C P R s = k p + k r s s 2 + ω 2
where kp and kr are PR control gains, respectively. Unfortunately, it is not able to implement the PR controller in (14) with an infinite gain. Therefore, the following non-ideal transfer function is used as
C P R s = k p + 2 k r ω c s s 2 + 2 ω c s + ω 2
where ωc is the angular frequency at the cutoff frequency of the controller. Also, additional harmonic compensators could be included to the PR controller for minimizing the harmonic currents for selective harmonic frequencies [23]. Its transfer function CHC (s) can be represented as
C H C s = h = 3 ,   5 ,   7 2 k r h ω c s s 2 + 2 ω c s + h ω 2
where h is the harmonic order and krh is the resonant control gain for each harmonic frequency. Since the third, fifth, and seventh harmonics are significant under the grid environment, the third to seventh harmonic compensators would be implemented.

3. Experiment Results

A 500 W prototype has been built for the grid-tied zeta inverter. Table 1 shows the key parameters and components of the prototype. The prototype includes the power and control circuits as well as the auxiliary circuits for gate driving circuits and stand-by power circuit. For the energy storage device, value-regulated lead acid batteries have been used. Four 12-V batteries are connected in series whose nominal voltage is 48 V. The PR control has been adopted for the grid current controller. Its digital implementation has been performed by a micro-controller dsPIC30F3011 (microchip). For the implementation of the transformer, a ferrite magnetic core (PQ5050) has been used with a bifilar winding technique so that the leakage inductance could be minimized.
Figure 5 shows the experiment waveforms for the grid voltage vg, the grid current ig, and the battery voltage Vb. Figure 5a shows the experiment waveforms for 500 W in the inverter mode. The grid current ig is in phase with vg. The grid-tied zeta inverter operates as an isolated dc-ac converter, supplying the battery power into the grid. The total harmonic distortion was measured as 3.1%. Figure 5b shows the experiment waveforms for 500 W in the rectifier mode. The grid current ig is 180° out of phase with vg. The grid-tied zeta inverter operates as an isolated ac-dc converter, supplying the grid power into the battery. The total harmonic distortion was measured as 3.3%. For both operation modes, the power factor was measured as 0.99. As shown in Figure 5, the grid-tied zeta inverter performs its bidirectional operation with high power quality.
Figure 6 shows the experiment waveforms for the operation mode changes. Figure 6a shows the experiment waveforms for vg and ig for 500 W from the inverter mode to the rectifier mode. Figure 6b shows the experiment waveforms for vg and ig for 500 W from the rectifier mode to the inverter mode. As shown in Figure 6, the grid current ig has been seamlessly changed as the inverter changes its operation mode. The grid-tied zeta inverter operates with seamless change of operation modes by the suggested control method.
Figure 7 shows the measured power efficiency curves. The digital power meter (WT-230, Yokogawa Electric, Tokyo, Japan) has been used for the calculation and the measurement of the power efficiency. The power efficiency has been calculated by dividing the output power by the input power. The uncertainty level for the measured power efficiency ranges from −0.05% to 0.05%. The uncertainty has been determined by residual measurement error.
The blue curve shows the power efficiency curve in the inverter mode. The grid-tied zeta inverter has shown the peak efficiency of 94.5% at 300 W. It has achieved the efficiency of 94.0% at 500 W. The red curve shows the power efficiency curve in the rectifier mode. The grid-tied zeta inverter has shown the peak efficiency of 94.3% at 260 W. It has achieved the efficiency of 93.9% at 500 W. As the inverter operates for entire load conditions, ranging from light load to full load, the prototype has been designed to achieve its peak efficiency around half of the rated load condition. The peak efficiency point can be mainly changed by the key circuit components such as the power switches and the reactive components.

4. Concluding Remark

This paper has proposed the bidirectional operation scheme of the grid-tied zeta inverter for energy storage systems. The operation principle has been presented for the operation mode and control method. A shoot-through switching state has been introduced, providing reliable bidirectional operation modes for the inverter. A shoot-through duty cycle has been utilized for the bidirectional grid current control. A unified grid current controller has been implemented, which enables the grid-tied zeta inverter to perform seamless change of operation modes. A 500 W prototype has been built and tested to verify its operation principle. The grid-tied zeta inverter has achieved the peak efficiency of 94.5% at 300 W and the efficiency of 94.0% at 500 W, respectively, in the inverter mode. It has achieved the peak efficiency of 94.3% at 300 W and the efficiency of 93.9% at 500 W, respectively, in the rectifier mode. The grid-tied zeta inverter with the proposed operation scheme can provide benefits such as high efficiency, low cost, and high reliability over the previous inverter techniques. It is expected that the proposed operation principle enables the grid-tied zeta inverter to be a next-generation inverter technique, which can reduce the manufacturing cost and provide high power efficiency for energy storage systems.
As a future research, several topics would be considered for renewable energy and smart grid integrations. In terms of control-level research, the output impedance of the inverter could be controlled. For power flow control, more research efforts should be made for parallel operation of inverters. In terms of circuit-level research, the use of gallium-nitride (GaN) power devices should be considered for the design of inverters. Along with the use of the advanced power devices, the use of high frequency switching device like planar transformers would facilitate developing high power density design of the inverters.

Author Contributions

W.-Y.C. managed the project, performed the experiments, analyzed the data, and wrote the manuscript. The Author has read and agreed to the published version of the manuscript.

Funding

This work was supported by the National Research Foundation of Korea (NRF) grant funded by the Korea government (MSIT) (2020R1F1A1048346). Also, this research was supported by “Research Base Construction Fund Support Program” funded by Jeonbuk National University in 2020.

Conflicts of Interest

The author declares no potential conflict of interest.

References

  1. Dong, M.; Tian, X.; Li, L.; Song, D.; Wang, L.; Zhao, M. Model-based current sharing approach for DCM interleaved flyback microinverter. Electronics 2018, 11, 1685. [Google Scholar]
  2. Feng, X.; Wang, F.; Wu, C.; Luo, J.; Zhang, L. Modeling and comparisons of aggregated flyback microinverters in aspect of harmonic resonances with the grid. IEEE Trans. Ind. Electron. 2019, 66, 276–285. [Google Scholar] [CrossRef]
  3. Lodh, T.; Pragallapati, N.; Agarwal, V. Novel control scheme for an interleaved flyback converter based solar PV microinverter to achieve high efficiency. IEEE Trans. Ind. Appl. 2018, 54, 3473–3482. [Google Scholar] [CrossRef]
  4. Han, B.; Lee, J.S.; Kim, M.S. Repetitive controller with phase-lead compensation for Cuk CCM inverter. IEEE Trans. Ind. Electron. 2018, 65, 2356–2367. [Google Scholar] [CrossRef]
  5. Han, B.; Lai, J.-S.; Kim, M.S. Bridgeless Cuk-derived single power conversion inverter with reactive-power capability. IEEE Trans. Power Electron. 2020, 35, 2629–2645. [Google Scholar] [CrossRef]
  6. Han, B.; Lai, J.-S.; Kim, M.S. Dynamic modeling and controller design of dual-mode Cuk inverter in grid-connected PV/TE applications. IEEE Trans. Power Electron. 2018, 33, 8887–8904. [Google Scholar] [CrossRef]
  7. Viero, R.C.; Lopez, H.F.M.; Zollmann, C.A.; dos Reis, F.S. Dynamic modeling of a sinusoidal inverter based on zeta converter working in DCM for PV arrays. In Proceedings of the Annual Conference on IEEE Industrial Electronics Society (IECON), Glendale, AZ, USA, 7–10 November 2010; pp. 439–444. [Google Scholar]
  8. Levin, G.H.; Flores, J.V.; Salton, A.; dos Reis, F.S. Internal model control of the zeta converter for the grid connection of photovoltaic panels. In Proceedings of the Brazilian Power Electronics Conference, Gramado, Brazil, 27–31 October 2013; pp. 666–671. [Google Scholar]
  9. Surapaneni, R.K.; Rathore, A.K. A single-stage CCM zeta microinverter for solar photovoltaic AC module. IEEE J. Emerg. Sel. Topics Power Electron. 2015, 3, 892–900. [Google Scholar] [CrossRef]
  10. Choi, W.Y.; Yang, M.K. High-efficiency design and control of zeta inverter for single-phase grid-connected applications. Energies 2019, 12, 974. [Google Scholar] [CrossRef] [Green Version]
  11. Liu, Y.C.; Chen, M.C.; Yang, C.Y.; Kim, K.A.; Chiu, H.J. High-efficiency isolated photovoltaic microinverter using wide-band gap switches for standalone and grid-tied applications. Energies 2018, 11, 569. [Google Scholar] [CrossRef] [Green Version]
  12. Liu, Y.C.; Chen, M.C.; Yang, C.Y.; Kim, K.A.; Chiu, H.J. Research on digital synchronous rectification for a high-efficiency dc-dc converter in an auxiliary power supply system of magnetic levitation. Energies 2020, 13, 51. [Google Scholar]
  13. Sandelic, M.; Sangwongwanich, A.; Blaabjerg, F. Reliability evaluation of PV systems with integrated battery energy storage systems: Dc-coupled and ac-coupled configurations. Electronics 2019, 8, 1059. [Google Scholar] [CrossRef] [Green Version]
  14. Fang, J.; Tang, Y.; Li, H.; Li, X. A battery/ultracapacitor hybrid energy storage system for implementing the power management of virtual synchronous generators. IEEE Trans. Power Electron. 2018, 33, 2820–2824. [Google Scholar] [CrossRef]
  15. Lai, R.; Wang, F.; Burgos, R.; Boroyevich, D.; Zhang, D.; Ning, P. A shoot-through protection scheme for converters built with SiC JFETs. IEEE Trans. Ind. Appl. 2010, 46, 2495–2500. [Google Scholar] [CrossRef]
  16. Caiza, D.L.; Kouro, S.; Flores-Bahamonde, F.; Hernandez, R. Unfolding PV microinverter current control: Rectified sinusoidal vs sinusoidal reference waveform. In Proceedings of the Annual Conference on IEEE Energy Conversion Congress and Exposition (ECCE), Portland, OR, USA, 7–10 September 2018; pp. 7094–7100. [Google Scholar]
  17. Hernandez-Vidal, R.; Renaudineau, H.; Kouro, S. Sub-module photovoltaic microinverter with cascaded flybacks and unfolding H-bridge inverter. In Proceedings of the Annual Conference on IEEE International Symposium on Industrial Electronics (ISIE), Edinburgh, UK, 19–21 June 2017; pp. 1035–1040. [Google Scholar]
  18. Kim, N.; Parkhideh, B. PV-battery series inverter architecture: A solar inverter for seamless battery integration with partial-power dc-dc optimizer. IEEE Trans. Energy Convers. 2019, 34, 478–485. [Google Scholar] [CrossRef]
  19. Dong, D.; Thacker, T.; Cvetkovic, I.; Burgos, R.; Boroyevich, D.; Wang, F.; Skutt, G. Modes of operation and system-level control of single-phase bidirectional PWM converter for microgrid systems. IEEE Trans. Smart Grid 2012, 3, 93–104. [Google Scholar] [CrossRef]
  20. Tan, G.; Zong, C.; Sun, X. Tan-Sun transformation-based phase-locked loop in detection of the grid synchronous signals under distorted grid conditions. Electronics 2020, 9, 674. [Google Scholar] [CrossRef] [Green Version]
  21. Zmood, D.N.; Holmes, D.G. Stationary frame current regulation of PWM inverters with zero steady-state error. IEEE Trans. Power Electron. 2003, 18, 814–822. [Google Scholar] [CrossRef]
  22. Jiang, S.; Cao, D.; Li, Y.; Liu, J.; Peng, F.Z. Low-THD, fast-transient, and cost-effective synchronous-frame repetitive controller for three-phase UPS inverters. IEEE Trans. Power Electron. 2012, 27, 2139–2149. [Google Scholar] [CrossRef]
  23. Pereira, L.F.A.; Flores, J.V.; Bonan, G.; Coutinho, D.F.; da Silva, J.M.G. Multiple resonant controllers for uninterruptible power supplies-a systematic robust control design approach. IEEE Trans. Ind. Electron. 2014, 61, 1528–1538. [Google Scholar] [CrossRef]
Figure 1. Circuit diagram of the grid-tied zeta inverter for energy storage systems.
Figure 1. Circuit diagram of the grid-tied zeta inverter for energy storage systems.
Electronics 09 01159 g001
Figure 2. Switching states in the inverter mode: (a) state 1 for the positive grid voltage; (b) state 2 for the positive grid voltage; (c) state 3 for the negative grid voltage; (d) state 4 for the negative grid voltage.
Figure 2. Switching states in the inverter mode: (a) state 1 for the positive grid voltage; (b) state 2 for the positive grid voltage; (c) state 3 for the negative grid voltage; (d) state 4 for the negative grid voltage.
Electronics 09 01159 g002
Figure 3. Switching states in the rectifier mode: (a) state 1 for the positive grid voltage; (b) state 2 for the positive grid voltage; (c) state 3 for the negative grid voltage; (d) state 4 for the negative grid voltage.
Figure 3. Switching states in the rectifier mode: (a) state 1 for the positive grid voltage; (b) state 2 for the positive grid voltage; (c) state 3 for the negative grid voltage; (d) state 4 for the negative grid voltage.
Electronics 09 01159 g003
Figure 4. Bidirectional grid current control block diagram of the grid-tied zeta inverter.
Figure 4. Bidirectional grid current control block diagram of the grid-tied zeta inverter.
Electronics 09 01159 g004
Figure 5. Experiment waveforms for the grid voltage vg, the grid current ig, and the battery voltage Vb: (a) waveforms in the inverter mode; (b) waveforms in the rectifier mode.
Figure 5. Experiment waveforms for the grid voltage vg, the grid current ig, and the battery voltage Vb: (a) waveforms in the inverter mode; (b) waveforms in the rectifier mode.
Electronics 09 01159 g005
Figure 6. Experiment waveforms for the operation mode changes: (a) waveforms from the inverter mode to the rectifier mode; (b) waveforms from the rectifier mode to the inverter mode.
Figure 6. Experiment waveforms for the operation mode changes: (a) waveforms from the inverter mode to the rectifier mode; (b) waveforms from the rectifier mode to the inverter mode.
Electronics 09 01159 g006
Figure 7. Measured power efficiency curves.
Figure 7. Measured power efficiency curves.
Electronics 09 01159 g007
Table 1. Key parameters and components.
Table 1. Key parameters and components.
SymbolQuantityValue
Vbbattery voltage48 V
vggrid voltage60 Hz/220 Vrms
fsswitching frequency50 kHz
Lmmagnetizing inductor60 μH
nPprimary winding turns15
nSsecondary winding turns64
CSsecondary capacitor1.0 μF
Lgfilter inductor2.0 mH
SPprimary swichIXFK150N30P3
SS1 ~ SS4secondary switchesUJC1206K

Share and Cite

MDPI and ACS Style

Choi, W.-Y. Bidirectional Operation Scheme of Grid-Tied Zeta Inverter for Energy Storage Systems. Electronics 2020, 9, 1159. https://doi.org/10.3390/electronics9071159

AMA Style

Choi W-Y. Bidirectional Operation Scheme of Grid-Tied Zeta Inverter for Energy Storage Systems. Electronics. 2020; 9(7):1159. https://doi.org/10.3390/electronics9071159

Chicago/Turabian Style

Choi, Woo-Young. 2020. "Bidirectional Operation Scheme of Grid-Tied Zeta Inverter for Energy Storage Systems" Electronics 9, no. 7: 1159. https://doi.org/10.3390/electronics9071159

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop