Next Article in Journal
Flow and Temperature Characteristics of a 15° Backward-Inclined Jet Flame in Crossflow
Next Article in Special Issue
Adaptive Damping Control Strategy of Wind Integrated Power System
Previous Article in Journal
Fatty Acids, Hydrocarbons and Terpenes of Nannochloropsis and Nannochloris Isolates with Potential for Biofuel Production
Previous Article in Special Issue
A Neural Network-Based Four Phases Interleaved Boost Converter for Fuel Cell System Applications
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Design and Analysis of a Repetitive Current Controller for a Single-Phase Bridgeless SEPIC PFC Converter

1
Department of Electrical Engineering, Konkuk University, Seoul 05029, Korea
2
Texas Instruments, 12500 TI Boulevard, Dallas, TX 75243, USA
*
Author to whom correspondence should be addressed.
Energies 2019, 12(1), 131; https://doi.org/10.3390/en12010131
Submission received: 16 November 2018 / Revised: 17 December 2018 / Accepted: 26 December 2018 / Published: 31 December 2018
(This article belongs to the Special Issue Intelligent Control in Energy Systems)

Abstract

:
This paper studies a repetitive controller design scheme for a bridgeless single-ended primary inductor converter (SEPIC) power factor correction (PFC) converter to mitigate input current distortions. A small signal modeling of the converter is performed by a fifth-order model. Since the fifth-order model is complex to be applied in designing a current controller, the model is approximated to a third-order model. Using the third-order model, the repetitive controller is designed to reduce the input current distortion. Then, the stability of the repetitive controller is verified with an error transfer function. The proposed controller performance is validated by simulation, and the experiment results show that the input current total harmonic distortion (THD) is improved by applying the proposed controller for an 800 W bridgeless SEPIC PFC converter prototype.

1. Introduction

Until now, many power conversion systems (PCS) are connected to grid and harmonic pollution becomes an issue [1,2]. General PCS needs AC-DC conversion to operate with the grid, and the easiest way is using a diode rectifier. However, it can decrease the power quality due to harmonics of the input current of the diode rectifier [3]. Thus, to improve the quality of the input current, the grid-tied power factor correction (PFC) converter can be applied. The PFC converter can achieve a unity power factor operation with the sinusoidal input current, which has low harmonics. Generally, the boost PFC converter is used, due to the simplicity, efficiency and low cost [4,5,6].
There are many systems using the PFC converter, such as switching mode power supply (SMPS) and LED applications, etc. [7,8,9]. These applications demand a low DC output voltage while the input voltage is relatively high. However, the general boost PFC converter only generates higher output voltage than the grid peak-voltage, and it needs two stages for step-down operation. It is difficult to expect the high efficiency because the number of PCS has been increased. In this case, the step-down PFC converter which has only one stage can be used. There are step-down PFC converters such as buck, buck-boost, Cuk and single-ended primary inductor converter (SEPIC) [10,11,12,13,14,15,16,17,18,19,20,21,22,23,24,25,26,27,28]. The buck PFC converter is simple as boost PFC converter with high efficiency, but it only can generate the lower voltage than the input voltage and does not create the input current around in zero-crossing point. On the other hand, the buck-boost, Cuk, and SEPIC have no limit to generate the input current and can operate in both step-up and step-down modes. So, the output voltage with wide range can be generated.
Recently, there have been continuing researches of the buck-boost, Cuk, and SEPIC PFC converters. The buck-boost PFC converter needs an input filter due to pulsating input current. On the contrary, the Cuk and SEPIC converters generate the continuous input current, and do not need an additional input filter which can decrease the efficiency of the system. However, the Cuk converter’s output voltage is inversed comparable table [19].
In [20,21,22], SEPIC and Cuk PFC converter topologies utilize the diode bridge at input side, which causes additional conduction losses. On the other hand, bridgeless SEPIC and Cuk PFC converter topologies are proposed in [23,24,25,26,27,28]. A Cuk PFC converter in [23,24] consists of 2 switches and 3 diodes. A SEPIC PFC converter in [25,26] has 2 switches and 3 diodes. The circuits using more switches have also been introduced in [27,28]. In this paper, a bridgeless SEPIC PFC converter with single switch and 5 diodes is utilized in Figure 1 [29]. Accordingly, the converter has low switching loss.
In general, the PFC converter has a unidirectional power transfer characteristic, because it is operated in unity power factor condition. Therefore, the PFC converter works in continuous conduction mode (CCM) and discontinuous conduction mode (DCM). The DCM operation is the cause of the input current distortion in low power condition. The input current distortion due to the DCM operation includes high-order harmonics, which are higher than the bandwidth of a typical current controller such as a proportional-integral (PI) controller or a proportional-resonant (PR) controller. To reduce the input current distortion, the current controller should be designed considering the plant model in DCM as well as in CCM [27,30,31]. In [27], the feed-forward is utilized in the SEPIC PFC converter for compensating the input current distortion. However, deriving an accurate DCM model is more difficult than a CCM model, which is relatively easy to interpret.
A repetitive controller can be applied to compensate the harmonic components caused by DCM operation. The repetitive controller has a high gain for the harmonics corresponding to multiples of the fundamental frequency [32,33,34,35]. Thus, if a stable repetitive controller design is guaranteed, the current distortion can be improved without the complicated analysis under DCM condition. In this paper, the design method of the current controller with repetitive controller is introduced. Also, a simplified third-order model of the SEPIC PFC converter is proposed.
This paper is organized as follows. Section 2 provides an analysis of the operating modes and the transfer function of the bridgeless SEPIC PFC converter. In Section 3, the proposed current controller design is described. The results of the simulations and the experiments are presented in Section 4 and Section 5 to verify the performance of the proposed current controller.

2. Bridgeless SEPIC PFC Converter with RC Damping Circuits

2.1. Circuit Structure and Mode Analysis

Figure 1 shows the bridgeless SEPIC PFC converter dealt in this paper. A RC damping circuit is equipped to suppress the high-order resonance of the converter which will be described in a later section. Compared to a traditional SEPIC DC–DC converter, the bridgeless SEPIC PFC converter contains the blocking diodes, D1 and D2, and the freewheeling diodes, Dp and Dn. With this configuration, only the single switching device Sc can be utilized for both positive and negative input voltage cycles.
Figure 2 represents the operation mode analysis of the bridgeless SEPIC PFC converter under a positive input voltage cycle. In Figure 2a, the current conduction paths are indicated when Sc turns on. In this case, Dn, D2, and Do are biased reversely. In this case, four paths are existent. Path 1 consists of the input source, L1, D1, Sc, and Dp. In this path, the input energy is stored in L1. Through path 2, C1 is charged by the energy stored in Lo. The RC damping circuit existing in this path dampens the resonant peak caused by C1, L1, and Lo. So, it can increase the stability of the circuit in the control viewpoint. For path 3, the energy exchange occurs between C1, C2, and L2. Again, C1 is charged while C2 is discharged. Unlike Lo, the input source does not contribute charging of the energy for L2. In this interval, the load Ro is supplied by Co via path 4. When Sc is opened, the current conduction paths change as shown in Figure 2b. In this case, Do turns on, and D1, D2, Sc, and Dn are blocked and the energy stored in L1, L2, C1, C2, and Lo is transferred to the load side including Co and Ro. Similarly, the analyses for negative input voltage cycles which are not discussed here can be also performed.

2.2. Control Model Derivation of the Bridgeless SEPIC PFC Converter

Figure 3 illustrates the equivalent circuits of the bridgeless SEPIC PFC converter with the damping circuit according to the switching operations. Since paths 3 and 7 are the leakage current paths and the leakage current is very smaller than the input current, it can be ignored. So, the operation of the converter is basically identical to traditional SEPIC PFC converters except the RC damping circuit is included. In order to see the effect of the damping circuit and design the controller, the control-to-inductor current model for the SEPIC PFC converter is derived.
When Sc is turned on, the following equations can be obtained. At this moment, the voltages of L1 and Lo are derived as follows:
V i n = L 1 d i L 1 d t
v C 1 = L o d i L o d t
The capacitor currents iC1, iCo and iCd are represented as follows:
i L o v C 1 v C d R d = C 1 d v C 1 d t
v C 1 v C d R d = C d d v C d d t
v C o R o = C o d v C o d t = V o R o
When Sc is turned off, the voltages of L1 and Lo are expressed as below:
V i n v C 1 v C o = L 1 d i L 1 d t
v C o = L o d i L o d t
and the currents of C1, Cd and Co are written as:
i L 1 v C 1 v C d R d = C 1 d v C 1 d t
v C 1 v C d R d = C d d v C d d t
i L 1 + i L o V C o R o = C o d v C o d t
Using Equations (1)–(5), then state–space matrix for Sc on time can be rewritten as follows:
A 1 = [ 0 0 0 0 0 0 0 1 L o 0 0 0 1 C o 1 R d C 1 1 R d C 1 0 0 0 1 R d C d 1 R d C d 0 0 0 0 0 1 R o C o ]   B 1 = [ 1 L 1 0 0 0 0 ]
and, the state–space matrix for Sc off time can be derived as below:
A 2 = [ 0 0 1 L 1 0 1 L 1 0 0 0 0 1 L o 1 C 1 0 1 R d C 1 1 R d C 1 0 0 0 1 R d C d 1 R d C d 0 1 C o 1 C o 0 0 1 R o C o ]   B 2 = [ 1 L 1 0 0 0 0 ]
x = [ i L 1 i L o v C 1 v C d v C o ] u = [ V i n ] x ˙ = [ d i L 1 d t d i L o d t d v C 1 d t d v C d d t d v C o d t ]
x ( s ) d ( s ) = ( s I A ) 1 { ( A 1 A 2 ) X + ( B 1 B 2 ) V i n }
The control-to-inductor current model can be obtained by Equations (11)–(14) as a fifth-order model. Similarly, the control-to-inductor current model without the RC damping also can be derived as a fourth-order model [29]. Figure 4 compares the control models of the bridgeless SEPIC PFC converters with the RC damping and without damping in frequency domain with parameters in Table 1. The model with the RC damping has only one resonant frequency in 800 Hz and the resonance at higher frequency is damped. On the contrary, the model without the RC damping has two resonance points in about 800 Hz and 5 kHz with high Q factor. This second resonance point with high frequency which is over than the current control bandwidth cannot be controlled and oscillates the system current unexpectedly. Therefore, the RC damping should be included to damp the second resonant peak.

2.3. Control Model Approximation of the Bridgeless SEPIC PFC Converter

The control-to-inductor current model with the RC damping is the fifth-order model. Since the original undamped model is the fourth model, it became more complexed than the original undamped model. Thus, it is difficult to analyze the frequency response of the controller with the fifth model so, approximation needs to be adapted to design the controller easily. Since the capacitance of C1 and Cd is much lower value than the other components, the multiple of C1 and Cd is sufficiently small to be ignored. Similarly, the multiple of the L1 and Lo is low value as Cd or C1, so C1L1Lo and CdL1Lo also can be substituted with zero. With these processes, the approximate model can be represented as follows:
G i d ( s ) = i g ( s ) d ( s ) = N 1 s 3 + N 2 s 2 + N 3 s + N 4 D 1 s 3 + D 2 s 2 + D 3 s + D 4
N 1 = C o L o R o { ( C 1 + C d ) ( V C 1 + V C o ) + C d R d D ( I L 1 + I L o ) } N 3 = L o D ( I L 1 + I L o ) + D ( C d R d + C o R o ) ( V C 1 + V C o ) + C d R d R o D ( I L 1 + I L o ) N 3 = L o D ( I L 1 + I L o ) + D ( C d R d + C o R o ) ( V C 1 + V C o ) + C d R d R o D ( I L 1 + I L o ) N 4 = D ( V C 1 + V C o ) + R o D ( I L 1 + I L o )
D 1 = C d C o R d R o { L o ( 1 2 D ) + D 2 ( L 1 + L o ) } D 2 = R o ( L 1 D 2 + L o D 2 ) ( C 1 + C d + C o ) + L 1 R o ( 1 2 D ) ( C 1 + C d ) + C d R d { L o ( 1 2 D ) + D 2 ( L 1 + L o ) } D 3 = L o ( 1 2 D ) + D 2 ( L 1 + L o ) + C d R d R o D 2 D 4 = R o D 2 D = 1 D
The frequency responses of the original fifth-order model and the approximated third-order model in buck and boost modes are represented in Figure 5. As can be seen, the third-order model is very well matched with the fifth-order model until 600 Hz. Where the frequency is beyond 600 Hz, the fifth-order model contains the damped resonance and phase delay, which do not appear in the third-order model. However, the third-order model is enough to design the current controller, because the current control bandwidth is not very high.

3. Proposed Current Controller

3.1. Traditional Current Controller Design

In order to control the bridgeless SEPIC PFC converter, a digital controller is implemented. Therefore, the approximated Gid(s) is transformed on the z-domain and delays due to unit calculation and digital pulse-width modulation (PWM) update should be also considered [36]. The z-domain control-to-inductor current model Gid(z) is derived as follows:
G i d ( z ) = z 1 G i d ( s ) | s = ( z 1 ) / T s
where Ts is the sampling period. The digital delay is represented by a unit delay.
The controller structure for regulating the current is shown in Figure 6. The input current reference ig* and the input current ig are input to the controller as absolute values. The duty reference dref is generated by the current controller Gcc(z) and the feed-forward duty dff. The feed-forward duty compensates for the disturbance caused by the input voltage [37], and is calculated as below:
d f f = V o | v g | + V o
where vg is the input voltage, and Vo is the output voltage.
For the stable current controller design, the frequency response of the open-loop gain Ti(z) consisting of Gcc(z) and Gid(z) should be analyzed. The open-loop gain Ti,P(z) and Ti,PI(z) of a proportional (P) controller and a proportional-integral (PI) controller are obtained as:
T i , P ( z ) = K p G i d ( z )
T i , P I ( z ) = ( K p + K i T s z z 1 ) G i d ( z )
where Kp is a proportional gain, and Ki is an integral gain. Since the approximated Gid(s) is consistent with the original fifth-order model up to about 600 Hz, the controller is designed accordingly. Figure 7 shows the frequency response of Ti,P(z) and Ti,PI(z) when Kp and Ki are selected as 0.01 and 60, respectively. In the buck mode, the crossover frequency of Ti,P(z) is 269 Hz, which is the bandwidth of the controller. The phase margin Фpm at the crossover frequency is 96.7 deg. For Ti,PI(z), the crossover frequency is 530 Hz and the phase margin is 45.3 deg. Thus, both controllers designed are stable in the buck mode. Also, Ti,p(z) and Ti,PI(z) of the boost mode are stable, but the crossover frequency is wider than the buck mode. As a result, characteristic of the controller can be superior in the boost mode.

3.2. Repetitive Controller Design

The repetitive controller has excellent performance in eliminating periodic errors [32,33,34,35]. The proposed current controller is shown in Figure 8, which consists of the repetitive controller and the P controller in parallel. The repetitive controller is composed of repetitive controller gain Krp, the number of samples N, the number of samples for phase leading L, and stabilization filter q(z). The transfer function of the repetitive controller is derived as below:
G r p ( z ) = d r p i e r r = K r p z L z N q ( z )
The number of samples N of the repetitive controller is determined by the fundamental frequency fr of the current reference to be controlled and the sampling frequency fs as follows:
N = f s f r
As shown in Figure 6, the current controller regulates the absolute value of the input current. Thus, compared with the frequency of the input current reference, the fundamental frequency of the repetitive controller is doubled. The number of samples for phase leading L is chosen as 2 to compensate for the digital delay of 1.5 Ts. The stabilization filter q(z) is used to ensure the stability of the repetitive controller for the very high order harmonics that cannot be regulated [32]. In general, the following zero-phase delay low pass filter is selected as q(z):
q ( z ) = 0.25 z 1 + 0.5 + 0.25 z
The remaining parameter of the repetitive controller is Krp, which determines the stability of the repetitive controller. In order to select Krp, the transfer function of the input current reference to error Ge(z) should be considered, and it is obtained as:
G e ( z ) = i e r r i g * = G e p ( z ) G e r p ( z )
where Gep(z) and Gerp(z) are expressed as below:
G e p ( z ) = 1 1 + T i , P ( z )
G e r p ( z ) = z N q ( z ) z N H ( z )
where H(z) is defined as follows:
H ( z ) = q ( z ) K r p z L G i d ( z ) 1 + T i , P ( z )
For Ge(z) to be stable, all poles must be located within the unit circle in the z-domain. If the P controller is designed to be stable, the poles of Gep(z) are in the unit circle. It can be ensured by selecting an appropriate Kp through the open-loop gain analysis as described above. Therefore, in order for Ge(z) to be stable, the stability of Gerp(z) must be guaranteed. According to the small gain theorem, Gerp(z) is stable if the magnitude of H(z) is less than 1 [35]. Figure 9 shows the root trajectories of H(z) depending on Krp up to the Nyquist frequency in buck and boost modes. When Krp is 0.021, Gerp(z) is unstable because the root trajectories of H(z) deviate from the unit circle in both modes. When Krp is 0.02, the magnitude of H(z) is smaller than 1 in buck mode, but not in boost mode. Therefore, Krp must be less than 0.02 for Ge(z) to be stable in both modes. The frequency response of Ge(z) is illustrated in Figure 10 when Krp is 0.01. Since the fundamental frequency is 120 Hz, it can be seen that the errors of the multiples of fundamental frequency are removed.

4. Simulation Results

In order to verify the performance of the proposed controller, the simulation studies have been performed using the simulation software package PSIM. All parameters used in the simulation are shown in Table 1.
Figure 11 and Figure 12 show the input current and the current error when operating in buck mode and boost mode at the full load condition under 800 W and light load condition under 100 W.
Before t = 0.2 s, the input current is regulated with the PI controller. At t = 0.2 s, the PI controller is substituted with the repetitive controller in parallel with P controller. In Figure 11, before applying the repetitive controller, the magnitude of the current error is less than 1 A. However, after applying the repetitive controller, the magnitude of the current error is limited to 0.5 A. The current errors considerably decrease after t = 0.2 s in both load conditions. Especially, under the light load condition, the distortion of the input current is significantly reduced. Also, the total harmonic distortion (THD) of the input current is improved from 4.3% to 2.8% at the full load condition and from 41.7% to 12.2% at light load condition.
Figure 12 depicts the input current and the current error when operating in boost mode at the full load condition under 800 W and light load condition under 100 W. In boost mode, after applying the repetitive controller the magnitude of the input current error is similar with that in buck mode. The THD of the input current under heavy and light load conditions improved 4.4% to 4.3% and 45.8% to 34.8%, respectively. In boost mode, the input current ripple is larger than in buck mode, because the voltage across L1 is higher due to output voltage according to Equation (6). So, the THD of the input current is higher than in buck mode.

5. Experimental Results

The parameter values for hardware are the same values in Figure 1, and a TMS320F28335 digital signal processor (DSP) of Texas Instruments (Dallas, TX, USA) was adopted to implement the digital controller. The bridgeless SEPIC PFC converter consists of a silicon carbide (SiC) MOSFET C2M004120D and four SiC schottky diodes C4D20120D, C3D16065A which are manufactured from Cree. The input voltage of the converter is supplied by Programmable AC power source model 61704. The SEPIC PFC prototype system has been tested from 100 W to 800 W in both buck and boost mode. The output voltages of buck and boost mode are 80 V and 220 V each.
Figure 13 and Figure 14 illustrate the experimental results without the repetitive controller and with the repetitive controller. Figure 13 shows the input current and the current error under 100 W load condition in buck mode and in boost mode. In Figure 13a, without the repetitive controller, the input current is regulated in phase with the input voltage. However, there is the current distortion near the zero-crossing point of the input current, and the peak-to-peak value of the current error is less than 1.8 A. On the other hand, with the repetitive controller the current error is reduced to 0.39 A and the waveform of the input current is significantly improved in Figure 13b. Figure 13c,d shows the experimental results in boost mode without and with the repetitive controller, respectively. In boost mode, the magnitude of current error is 1.53 A without the repetitive controller, but only 0.47 A is measured by applying the repetitive controller.
Figure 14 represents the input current and the current error under 800 W load condition in buck mode and boost mode. Figure 14a,c shows that the PI controller works well, and the addition of repetitive controller can be seen to reduce both size of current error and the input current THD as shown in Figure 14b,d. In Figure 14a that is buck mode operation, the current error is 1.35 A but after adding the repetitive controller, the current error is changed to 1.32 A as shown in Figure 14b. Similarly, Figure 14c which is the boost mode shows the current error magnitude of 1.94 A. But in Figure 14d, when the repetitive controller is applied, the current error was read as 1.12 A. Accordingly, Figure 13 and Figure 14 show that the proposed repetitive control method improves the input current quality.
Under various load conditions, the input current THD comparisons between the conventional PI controller and the proposed control scheme are shown in Figure 15. Figure 15a shows the buck operation mode and Figure 15b shows the boost operation mode in the bridgeless SEPIC PFC converter. It also shows that the proposed repetitive controller has much improved THD than the conventional PI controller.

6. Conclusions

The general PFC converters have been studied to boost the output voltage. On the other hand, it only can operate in boost mode, not in buck mode. To step down the output voltage, the general PFC converters must operate with the DC–DC converters. However, the SEPIC PFC converter can operate in buck and boost mode itself, without another system. In this paper, the bridgeless SEPIC PFC converter with RC damping topology has been discussed. The operation modes of the SEPIC converter and the control-to-inductor current model are described in detail. Also, the approximation of the current control model was proceeded, and it has been used to design and to analyze the stability of the current controller. By using this approximation model, the repetitive control scheme was evaluated with the error transfer function. The repetitive control parameters were derived by these analyses and the implementation of the digital controller is also discussed. The simulation and the experimental results verified the repetitive controller performance in 100 W to 800 W load conditions in buck mode and boost mode. As a result, the THDs of the input current are significantly decreased by the proposed repetitive controller in both buck and boost modes. Also, the experimental result shows that the controller based on simplified model is well designed.

Author Contributions

J.K., S.H., and W.C. implemented the system, performed the experiments, and wrote this paper. H.K. and Y.C. assisted with the idea development and the paper writing.

Funding

This work was supported by the “Human Resources Program in Energy Technology” of the Korea Institute of Energy Technology Evaluation and Planning (KETEP), granted financial resource from the Ministry of Trade, Industry & Energy, Republic of Korea (No. 20174030201660) and the “Human Resources Program in Energy Technology” of the Korea Institute of Energy Technology Evaluation and Planning (KETEP), granted financial resource from the Ministry of Trade, Industry & Energy, Republic of Korea (No. 20184030202270).

Conflicts of Interest

The authors declare no conflict interest.

References

  1. Choi, W.; Lee, W.; Han, D.; Sarlioglu, B. New Configuration of Multifunctional Grid-Connected Inverter to Improve Both Current-Based and Voltage-Based Power Quality. IEEE Trans. Ind. Appl. 2018, 54, 6374–6382. [Google Scholar] [CrossRef]
  2. Yao, Z.; Xiao, L. Control of Single-Phase Grid-Connected Inverters with Nonlinear Loads. IEEE Trans. Ind. Electron. 2013, 60, 1384–1389. [Google Scholar] [CrossRef]
  3. Ismail, E.H. Bridgeless SEPIC Rectifier with Unity Power Factor and Reduced Conduction Losses. IEEE Trans. Ind. Electron. 2009, 56, 1147–1157. [Google Scholar] [CrossRef]
  4. Musavi, F.; Edington, M.; Eberle, W.; Dunford, W.G. Control Loop Design for a PFC Boost Converter with Ripple Steering. IEEE Trans. Ind. Appl. 2013, 49, 118–126. [Google Scholar] [CrossRef]
  5. Lee, J.; Chae, H. 6.6-kW Onboard Charger Design Using DCM PFC Converter with Harmonic Modulation Technique and Two-Stage DC/DC Converter. IEEE Trans. Ind. Electron. 2014, 61, 1243–1252. [Google Scholar] [CrossRef]
  6. Xie, X.; Zhao, C.; Zheng, L.; Liu, S. An Improved Buck PFC Converter with High Power Factor. IEEE Trans. Power Electron. 2013, 28, 2277–2284. [Google Scholar] [CrossRef]
  7. Tian, G.; Qi, W.; Yan, Y.; Jiang, Y.Z. High power factor LED power supply based on SEPIC converter. Electron. Lett. 2014, 50, 1866–1868. [Google Scholar] [CrossRef]
  8. Wang, Y.; Huang, J.; Shi, G.; Wang, W.; Xu, D. A Single-Stage Single-Switch LED Driver Based on the Integrated SEPIC Circuit and Class-E Converter. IEEE Trans. Power Electron. 2016, 31, 5814–5824. [Google Scholar] [CrossRef]
  9. Ma, H.; Lai, J.; Feng, Q.; Yu, W.; Zheng, C.; Zhao, Z. A Novel Valley-Fill SEPIC-Derived Power Supply without Electrolytic Capacitor for LED Lighting Application. IEEE Trans. Power Electron. 2012, 27, 3057–3071. [Google Scholar] [CrossRef]
  10. Jang, Y.; Jovanović, M.M. Bridgeless High-Power-Factor Buck Converter. IEEE Trans. Power Electron. 2011, 26, 602–611. [Google Scholar] [CrossRef]
  11. Foroozeshfar, R.; Adib, E.; Farzanehfard, H. New single-stage, single-switch, soft-switching three-phase SEPIC and Cuk-type power factor correction converters. IET Power Electron. 2014, 7, 1878–1885. [Google Scholar] [CrossRef]
  12. Darwish, A.; Holliday, D.; Ahmed, S.; Massoud, A.M.; Williams, B.W. A Single-Stage Three-Phase Inverter Based on Cuk Converters for PV Applications. IEEE J. Emerg. Sel. Top. Power Electron. 2014, 2, 797–807. [Google Scholar] [CrossRef]
  13. Yang, J.; Do, H. Bridgeless SEPIC Converter with a Ripple-Free Input Current. IEEE Trans. Power Electron. 2013, 28, 3388–3394. [Google Scholar] [CrossRef]
  14. Diab, M.S.; Elserougi, A.; Massoud, A.M.; Abdel-Khalik, A.S.; Ahmed, S. A Four-Switch Three-Phase SEPIC-Based Inverter. IEEE Trans. Power Electron. 2015, 30, 4891–4905. [Google Scholar] [CrossRef]
  15. Costa, P.J.S.; Font, C.H.I.; Lazzarin, T.B. Single-Phase Hybrid Switched-Capacitor Voltage-Doubler SEPIC PFC Rectifiers. IEEE Trans. Power Electron. 2018, 33, 5118–5130. [Google Scholar] [CrossRef]
  16. Costa, P.J.S.; Font, C.H.I.; Lazzarin, T.B. A Family of Single-Phase Voltage-Doubler High-Power-Factor SEPIC Rectifiers Operating in DCM. IEEE Trans. Power Electron. 2017, 32, 4279–4290. [Google Scholar] [CrossRef]
  17. Lee, S.; Do, H. Zero-Ripple Input-Current High-Step-Up Boost–SEPIC DC–DC Converter with Reduced Switch-Voltage Stress. IEEE Trans. Power Electron. 2017, 32, 6170–6177. [Google Scholar] [CrossRef]
  18. Moradpour, R.; Ardi, H.; Tavakoli, A. Design and Implementation of a New SEPIC-Based High Step-Up DC/DC Converter for Renewable Energy Applications. IEEE Trans. Ind. Electron. 2018, 65, 1290–1297. [Google Scholar] [CrossRef]
  19. Chiang, S.J.; Shieh, H.; Chen, M. Modeling and Control of PV Charger System with SEPIC Converter. IEEE Trans. Ind. Electron. 2009, 56, 4344–4353. [Google Scholar] [CrossRef]
  20. Kamnarn, U.; Chunkag, V. Analysis and Design of a Modular Three-Phase AC-to-DC Converter Using CUK Rectifier Module with Nearly Unity Power Factor and Fast Dynamic Response. IEEE Trans. Power Electron. 2009, 24, 2000–2012. [Google Scholar] [CrossRef]
  21. Kwon, J.; Choi, W.; Lee, J.; Kim, E.; Kwon, B. Continuous-conduction-mode SEPIC converter with low reverse-recovery loss for power factor correction. IEE Proc.—Electr. Power Appl. 2006, 153, 673–681. [Google Scholar] [CrossRef]
  22. Chiu, H.; Lo, Y.; Chen, J.; Cheng, S.; Lin, C.; Mou, S. A High-Efficiency Dimmable LED Driver for Low-Power Lighting Applications. IEEE Trans. Ind. Electron. 2010, 57, 735–743. [Google Scholar] [CrossRef] [Green Version]
  23. Liu, Y.; Sun, Y.; Su, M. A Control Method for Bridgeless Cuk/Sepic PFC Rectifier to Achieve Power Decoupling. IEEE Trans. Ind. Electron. 2017, 64, 7272–7276. [Google Scholar] [CrossRef]
  24. Fardoun, A.A.; Ismail, E.H.; Sabzali, A.J.; Al-Saffar, M.A. New Efficient Bridgeless Cuk Rectifiers for PFC Applications. IEEE Trans. Power Electron. 2012, 27, 3292–3301. [Google Scholar] [CrossRef]
  25. Mahdavi, M.; Farzanehfard, H. Bridgeless SEPIC PFC Rectifier with Reduced Components and Conduction Losses. IEEE Trans. Ind. Electron. 2011, 58, 4153–4160. [Google Scholar] [CrossRef]
  26. Sabzali, A.J.; Ismail, E.H.; Al-Saffar, M.A.; Fardoun, A.A. New Bridgeless DCM Sepic and Cuk PFC Rectifiers with Low Conduction and Switching Losses. IEEE Trans. Ind. Appl. 2011, 47, 873–881. [Google Scholar] [CrossRef]
  27. Liao, Y.; Jhu, J. Analysis and implementation of a bridgeless sepic AC/DC converter with power factor correction and extended gain. In Proceedings of the 2017 IEEE Applied Power Electronics Conference and Exposition (APEC), Tampa, FL, USA, 26–30 March 2017; pp. 416–423. [Google Scholar]
  28. Onal, Y.; Sozer, Y. Bridgeless SEPIC PFC converter for low total harmonic distortion and high power factor. In Proceedings of the 2016 IEEE Applied Power Electronics Conference and Exposition (APEC), Long Beach, CA, USA, 20–24 March 2016; pp. 2693–2699. [Google Scholar]
  29. Koh, H.; Cho, Y.; Lai, J.; Chen, R.; Zheng, C. Z-domain modeling and control design of single-switch bridgeless SEPIC PFC converter with damping circuit. In Proceedings of the 2013 Twenty-Eighth Annual IEEE Applied Power Electronics Conference and Exposition (APEC), Long Beach, CA, USA, 17–21 March 2013; pp. 2744–2748. [Google Scholar]
  30. Clark, C.W.; Musavi, F.; Eberle, W. Digital DCM Detection and Mixed Conduction Mode Control for Boost PFC Converters. IEEE Trans. Power Electron. 2014, 29, 347–355. [Google Scholar] [CrossRef]
  31. Youn, H.; Park, J.; Park, K.; Baek, J.; Moon, G. A Digital Predictive Peak Current Control for Power Factor Correction with Low-Input Current Distortion. IEEE Trans. Power Electron. 2016, 31, 900–912. [Google Scholar] [CrossRef]
  32. Yang, S.; Wang, P.; Tang, Y.; Zagrodnik, M.; Hu, X.; Tseng, K.J. Circulating Current Suppression in Modular Multilevel Converters with Even-Harmonic Repetitive Control. IEEE Trans. Ind. Appl. 2018, 54, 298–309. [Google Scholar] [CrossRef]
  33. Cho, Y.; Lai, J. Digital Plug-In Repetitive Controller for Single-Phase Bridgeless PFC Converters. IEEE Trans. Power Electron. 2013, 28, 165–175. [Google Scholar] [CrossRef]
  34. Cho, Y. Dual-buck residential photovoltaic inverter with a high-accuracy repetitive current controller. Renew. Energy 2017, 101, 168–181. [Google Scholar] [CrossRef]
  35. Yang, S.; Wang, P.; Tang, Y.; Zhang, L. Explicit Phase Lead Filter Design in Repetitive Control for Voltage Harmonic Mitigation of VSI-Based Islanded Microgrids. IEEE Trans. Ind. Electron. 2017, 64, 817–826. [Google Scholar] [CrossRef]
  36. Kumar, M.; Gupta, R. Time-Domain Analysis of Sampling Effect in DPWM of DC–DC Converters. IEEE Trans. Ind. Electron. 2015, 62, 6915–6924. [Google Scholar] [CrossRef]
  37. Shayestehfard, A.; Mekhilef, S.; Mokhlis, H. IZDPWM-Based Feedforward Controller for Grid-Connected Inverters Under Unbalanced and Distorted Conditions. IEEE Trans. Ind. Electron. 2017, 64, 14–21. [Google Scholar] [CrossRef]
Figure 1. Topology of the bridgeless SEPIC PFC converter with the RC damping circuits. SEPIC: single-ended primary inductor converter; PFC: power factor correction.
Figure 1. Topology of the bridgeless SEPIC PFC converter with the RC damping circuits. SEPIC: single-ended primary inductor converter; PFC: power factor correction.
Energies 12 00131 g001
Figure 2. Operation modes of the bridgeless SEPIC PFC converter under positive voltage cycles: (a) when Sc is turned on; (b) when Sc is turned off.
Figure 2. Operation modes of the bridgeless SEPIC PFC converter under positive voltage cycles: (a) when Sc is turned on; (b) when Sc is turned off.
Energies 12 00131 g002aEnergies 12 00131 g002b
Figure 3. Equivalent circuits of the bridgeless SEPIC PFC converter with the damping circuit: (a) when Sc is turned on; (b) when Sc is turned off.
Figure 3. Equivalent circuits of the bridgeless SEPIC PFC converter with the damping circuit: (a) when Sc is turned on; (b) when Sc is turned off.
Energies 12 00131 g003aEnergies 12 00131 g003b
Figure 4. Frequency responses of the RC damped and the undamped models.
Figure 4. Frequency responses of the RC damped and the undamped models.
Energies 12 00131 g004
Figure 5. Frequency responses of the third- and the fifth-order RC damped models: (a) Buck mode; (b) Boost mode.
Figure 5. Frequency responses of the third- and the fifth-order RC damped models: (a) Buck mode; (b) Boost mode.
Energies 12 00131 g005
Figure 6. Current controller structure.
Figure 6. Current controller structure.
Energies 12 00131 g006
Figure 7. Frequency response of Ti(z): (a) Buck mode; (b) Boost mode.
Figure 7. Frequency response of Ti(z): (a) Buck mode; (b) Boost mode.
Energies 12 00131 g007
Figure 8. Proposed current controller.
Figure 8. Proposed current controller.
Energies 12 00131 g008
Figure 9. Root trajectories of H(z): (a) Buck mode; (b) Boost mode.
Figure 9. Root trajectories of H(z): (a) Buck mode; (b) Boost mode.
Energies 12 00131 g009
Figure 10. Frequency response of Ge(z).
Figure 10. Frequency response of Ge(z).
Energies 12 00131 g010
Figure 11. Simulation results applying repetitive controller at 0.2 s in buck mode: (a) Input current and current error at load = 800 W; (b) Input current and current error at load = 100 W.
Figure 11. Simulation results applying repetitive controller at 0.2 s in buck mode: (a) Input current and current error at load = 800 W; (b) Input current and current error at load = 100 W.
Energies 12 00131 g011
Figure 12. Simulation results applying repetitive controller at 0.2 s in boost mode: (a) Input current and current error at load = 800 W; (b) Input current and current error at load = 100 W.
Figure 12. Simulation results applying repetitive controller at 0.2 s in boost mode: (a) Input current and current error at load = 800 W; (b) Input current and current error at load = 100 W.
Energies 12 00131 g012
Figure 13. Experimental results under the 100 W condition in buck/boost mode under vg = 120 Vrms, Vo = 80 V(buck)/Vo = 220 V(boost): (a) without the repetitive controller in buck mode; (b) with the repetitive controller in buck mode; (c) without the repetitive controller in boost mode; (d) with the repetitive controller in boost mode.
Figure 13. Experimental results under the 100 W condition in buck/boost mode under vg = 120 Vrms, Vo = 80 V(buck)/Vo = 220 V(boost): (a) without the repetitive controller in buck mode; (b) with the repetitive controller in buck mode; (c) without the repetitive controller in boost mode; (d) with the repetitive controller in boost mode.
Energies 12 00131 g013
Figure 14. Experimental results under the 800 W condition in buck/boost mode under vg = 120 Vrms, Vo = 80 V(buck)/Vo = 220 V(boost): (a) without the repetitive controller in buck mode; (b) with the repetitive controller in buck mode; (c) without the repetitive controller in boost mode; (d) with the repetitive controller in boost mode.
Figure 14. Experimental results under the 800 W condition in buck/boost mode under vg = 120 Vrms, Vo = 80 V(buck)/Vo = 220 V(boost): (a) without the repetitive controller in buck mode; (b) with the repetitive controller in buck mode; (c) without the repetitive controller in boost mode; (d) with the repetitive controller in boost mode.
Energies 12 00131 g014aEnergies 12 00131 g014b
Figure 15. Input current total harmonic distortion comparison results at different load conditions: (a) THDs in buck mode; (b) THDs in boost mode.
Figure 15. Input current total harmonic distortion comparison results at different load conditions: (a) THDs in buck mode; (b) THDs in boost mode.
Energies 12 00131 g015
Table 1. System Parameters.
Table 1. System Parameters.
ParametersValues
Switching frequency (fsw)72 kHz
Sampling frequency (fs)24 kHz
Input root mean square (RMS) voltage (vg)120 V/60 Hz
Output voltage (Vo) (buck/boost) 80 V/220 V
Input filter inductance (L1, L2)1 mH
Output inductance (Lo)1 mH
Damping resistance (Rd)60 Ω
Energy transfer capacitance (C1, C2)0.47 µF
Damping capacitance (Cd)2.2 µF
Output capacitance (Co)2.6 mF

Share and Cite

MDPI and ACS Style

Kim, J.; Han, S.; Cho, W.; Cho, Y.; Koh, H. Design and Analysis of a Repetitive Current Controller for a Single-Phase Bridgeless SEPIC PFC Converter. Energies 2019, 12, 131. https://doi.org/10.3390/en12010131

AMA Style

Kim J, Han S, Cho W, Cho Y, Koh H. Design and Analysis of a Repetitive Current Controller for a Single-Phase Bridgeless SEPIC PFC Converter. Energies. 2019; 12(1):131. https://doi.org/10.3390/en12010131

Chicago/Turabian Style

Kim, Jinwoo, Sanghun Han, Wontae Cho, Younghoon Cho, and Hyunsoo Koh. 2019. "Design and Analysis of a Repetitive Current Controller for a Single-Phase Bridgeless SEPIC PFC Converter" Energies 12, no. 1: 131. https://doi.org/10.3390/en12010131

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop