Article

Fault Ride through Capability Augmentation of a DFIG-Based Wind Integrated VSC-HVDC System with Non-Superconducting Fault Current Limiter

by
Md Shafiul Alam
1,2,
Mohammad Ali Yousef Abido
1,*,
Alaa El-Din Hussein
1 and
Ibrahim El-Amin
1
1
Department of Electrical Engineering, King Fahd University of Petroleum & Minerals, Dhahran 31261, Saudi Arabia
2
Department of Electrical & Electronic Engineering, International Islamic University Chittagong, Chittagong 4318, Bangladesh
*
Author to whom correspondence should be addressed.
Sustainability 2019, 11(5), 1232; https://doi.org/10.3390/su11051232
Submission received: 27 January 2019 / Revised: 20 February 2019 / Accepted: 21 February 2019 / Published: 26 February 2019
(This article belongs to the Special Issue Advances in Renewable Energy Technologies for Sustainability)

Abstract

:
This paper proposes a non-superconducting bridge-type fault current limiter (BFCL) as a potential solution to the fault problems of doubly fed induction generator (DFIG) integrated voltage source converter high-voltage DC (VSC-HVDC) transmission systems. As the VSC-HVDC and DFIG systems are vulnerable to AC/DC faults, a BFCL controller is developed to insert sizeable impedance during the inception of system disturbances. In the proposed control scheme, constant capacitor voltage is maintained by the stator VSC (SVSC) controller, while current extraction or injection is achieved by rotor VSC (RVSC) controller. Current control mode-based active and reactive power controllers for an HVDC system are developed. Balanced and different unbalanced faults are applied in the system to show the effectiveness of the proposed BFCL solution. A DFIG wind-based VSC-HVDC system, BFCL, and their controllers are implemented in a real time digital simulator (RTDS). The performance of the proposed BFCL control strategy in DFIG-based VSC-HVDC system is compared with a series dynamic braking resistor (SDBR). Comparative RTDS implementation results show that the proposed BFCL control strategy is very efficient in improving system fault ride through (FRT) capability and outperforms SDBR in all cases considered.

1. Introduction

Due to the continuous depletion of fossil fuels as well as the perpetual escalation of energy demands, research on renewable energy resources has been a hot topic in recent years. The integration and planning of renewable energy has a great impact on the operation of the electric market [1,2,3]. Among several renewable energy resources, wind energy has drawn substantial attention from researchers due to its maximum power point tracking capability, high efficiency, self-regulating control of active and reactive power, and improved power quality [4,5]. Renewable energy resources, especially large-scale wind power based on doubly fed induction generator (DFIG) integration with the existing power grid is a challenging task for power engineers. Compared to other integration techniques, voltage source converter high-voltage DC (VSC-HVDC) has greater flexibility [6,7]. Additionally, since the VSC-HVDC system adopts an insulated-gate bipolar transistor (IGBT) switch instead of thyristor, it could prevent commutation failure due to grid fault. Hence, VSC-HVDC offers a better solution to the commutation problem in HVDC systems [8].
Although the HVDC system has several advantages; it is vulnerable to AC/DC faults in the system [9]. Due to disturbances, bulk power transmission is highly interrupted, causing power imbalance and instability in the system. Therefore, HVDC systems must be kept energized during faults. Various control techniques have been applied for VSCs to improve fault ride through (FRT) capability as well as transient stability [7,10]. In an HVDC system, for proper operation and control of the converters, DC link voltage must be regulated within permissible limits. Various DC link power dissipation techniques are presented in the literature [11] to keep the DC link voltage within expected limits during faults. These techniques involve a reduction in active power and the adjustment of wind turbine power, which depend on a fast communication route among the converter stations. DC link ripple reduction and a power oscillation damping method is presented with a negative sequence current controller [12]. Nevertheless, this method results in stresses on the mechanical system because of reduction of active power to zero from the sending terminal.
Electric power system reliability can be enhanced through the integration of several renewable energy resources [13,14,15,16]. However, disturbances in the grid may cause instability in such integrated systems. The integration of offshore wind turbines to grids through a medium-voltage DC transmission system is presented with a new magnetic linked converter [17]. The presented magnetic linked converter can eliminate the need for low frequency heavy transformers as well as solve isolation problems naturally. Among different wind energy integration techniques, DFIG is considered to be superior as its efficiency is high and the control of active and reactive powers can be decoupled [18,19,20].
The generated active and reactive powers are controlled by rotor-side converter (RSC), while DC link voltage and reactive power exchange with the grid are controlled by the grid-side converter (GSC) [21,22,23]. DFIG systems are vulnerable to grid faults due to the direct connection of the stator winding to the grid [24,25,26]. A new control technique for DFIG wind integration was presented whereby the continuation of the DFIG connection during a fault can be secured and the system stability can be improved under fault conditions [23].
Nowadays, it is imperative to maintain the security and stability of the power system, due to its complex structure. Fault current limiters (FCLs) are considered as an important candidate to be placed in power systems to augment stability and security. Generally, superconducting fault current limiter placement is dominant in AC power system [27,28,29,30]. A saturated iron-core superconducting fault current limiter (SISFCL) to improve distance protection of a 500 kV AC transmission line is presented [31]. Since SISFCL adds inductance to the transmission line, re-adjustment of distance relay settings was presented to achieve better coordination. In addition, a resistive-type superconducting FCL was presented [32]. However, it suffers from high current and high cost related to installation, operation, and maintenance. To overcome this problem, Nam et. al. [33] presented a hybrid resistive-type superconducting fault current limiter (SFCL) with thyristors where phase angle control of the thyristors is coordinated with SFCL to limit the fault current. However, this hybrid fault current limiting technique has been developed for small-scale system application. Further study and research on capability extension are needed for application in large-scale systems. Superconducting fault current limiting cables have been presented for protection purposes [34,35]. A systematic method for impedance selection of high-temperature superconducting cables under different fault conditions was developed [35]. Depending on fault current levels and relay operating times, the optimal impedance value is determined from the system protection perspective. Fault current limiting techniques with a series dynamic braking resistor (SDBR) are presented [36,37]. A controllable switch is connected in parallel with a resistive branch in SDBR. The switch can be turned off or on in a dynamic fashion to insert the resistance as a main current-limiting part in SDBR operation. However, the SDBR is sensitive to switching delay and has inadequate performance in restricting fault current and augmenting dynamic performance [38]. Furthermore, most of the FCLs have been examined and installed in AC power systems; however, their feasibility and placements have not been fully investigated in VSC-HVDC systems [39].
The non-superconducting bridge-type fault current limiter (BFCL) is a novel technology having promising competency to improve the dynamic stability of wind farms and power grids by inserting sizeable impedance during the inception of disturbances in the system [40,41,42,43,44,45]. However, determining the size of impedance of BFCL to restrict the fault current of DFIG wind-based HVDC systems is a challenging task. Also, the insertion of this determined impedance during fault conditions in the system needs proper fault detection and a BFCL operation strategy. Mainly, BFCL consists of some diodes, an IGBT switch, resistor, and inductor. Thanks to the non-superconducting nature of these elements [46], BFCL can easily be implemented in power system with less cost compared to other current-limiting devices. To sum up, there is gap in current studies examining and implementing low-cost BFCLs that needs to be filled by designing proper impedance as a prospective solution for fault impact mitigation of DFIG wind integrated HVDC systems.
This study proposes BFCL-based control for reducing the fault current, improving the fault ride through capability, and enhancing the transient stability of DFIG wind integrated VSC-HVDC systems. To the best of our knowledge, this non-superconducting BFCL has not been designed and examined for FRT capability enhancement of DFIG-based HVDC systems. In this work, the proper size of impedance of BFCL is designed and inserted under different fault conditions in HVDC systems. The proposed BFCL is also equated with SDBR to demonstrate its efficacy for reducing the fault current and improving the stability of VSC-HVDC systems with DFIG wind integration. Unlike other methods presented in the literature, the proposed BFCL-based protection scheme is superior for augmenting the FRT capability of DFIG wind farms integrated with VSC-HVDC systems. The following shortcomings in current studies are to be addressed as the main contributions of this research:
(a)
Excessive DC link voltage fluctuation
(b)
High fault current and oscillation in DFIG speed and active power
(c)
Improper size of BFCL impedance for DFIG-based HVDC systems

2. Bridge-Type Fault Current Limiter

Non-superconducting bridge-type fault current limiter (BFCL) is proposed to augment fault ride through capability of DFIG wind farm integration with VSC-HVDC. The construction, working principle, and proposed control strategy of BFCL are documented below.

2.1. BFCL Structure, Operation, and Design

As shown in Figure 1, BFCLs have two main parts [41,47]: shunt branch with resistor and inductor, and diode bridge with diodes, resistor, inductor, and IGBT switch. The shunt resistor, Rsh, and the inductor, Lsh, are the main current-limiting parts, the sizes of which need to be designed for the improvement of the dynamic performance of the system, while the DC resistor, RDC, and inductor, LDC, are chosen to have small values in order to have a very negligible impact on the system during normal operation. The main role of the BFCL is to inset the shunt branch impedance in series with the line under faulty conditions in order to limit the fault current.
The operation mode of BFCLs is controlled by proper control signal to the gate of the IGBT. For the system without fault mode, the objective is to bypass the shunt branch by short-circuiting the bridge part. Therefore, during normal conditions, the current passes through the D1-LDC-RDC-IGBT-D4 path for the positive half cycle of the line current, while the current passes through the D2-LDC-RDC-IGBT-D3 path for the negative half cycle of the line current. As a result, LDC and RDC carry the current, which is of a unified direction, and the LDC charges to the peak value of the line current. It is worth mentioning that LDC and RDC have small values and the voltage drops across them are inconsequential. In conclusion, the bridge acts as a short circuit and it bypasses the shunt branch of the BFCL under normal conditions. In the disturbance mode operation of the BFCL, the IGBT switch is turned off, and thus, the bridge part acts as an open circuit. Consequently, the line current is now forced to flow through the shunt branch, which restricts the current in fault mode operation.
In this work, sizeable impedance of the shunt branch is determined on the basis of the pre-fault active power flow through the line cable. The same amount of power flows through each line during normal operation. Each of the BFCLs placed in each line should absorb the same or a greater amount of power, which flows through the line in pre-fault conditions. Now, the power flow of each BFCL in post-fault conditions is presented by the following Equations [48]:
P B F C L P G 3
P B F C L = V P C C 2 R s h R s h 2 + X s h 2
where VPCC is the voltage at point of common coupling (PCC) and PG is the active power delivered to the grid. The simplification of Equations (1) and (2) gives the following equation:
R s h 3 V P C C 2 + 9 V P C C 4 4 P G 2 X s h 2 2 P G
Rsh must be a positive value. Thus, the term inside the root must be positive. This obligatory condition gives the following equation for determining the size of shunt branch reactance:
X s h < 1.5 V P C C 2 P G
A similar systematic method is adopted to determine the size of Rsh. Since the BFCL bridge part needs to be short-circuited during normal operation, with negligible impact, lower values of LDC and RDC are chosen on a trial-and-error basis so that the DC current flowing through them is smooth.

2.2. BFCL Control Strategy

The BFCL control signal is generated based on the detection of a fault in the system. Fault detection in AC/DC systems could be achieved by the amount of voltage dip or over-current at the point of common coupling (PCC) [49]. This work uses the amount of voltage dip to sense the fault, as shown in Figure 2.
A comparator circuit evaluates the voltage at PCC (VPCC) with a pre-defined threshold voltage (VT), which is arbitrarily chosen as 95% of the nominal VPCC. VT is chosen as 95% since the voltage below 0.95 p.u. is considered a worst-case scenario [50]. In normal conditions, VPCC is greater than VT. Therefore, the comparator provides a low signal output. The step voltage generation then provides a high-voltage signal to the gate of the IGBT and subsequently turns it on. Thus, the bridge part of the BFCL is short-circuited in this control mode. However, in faulty conditions, VPCC has a voltage dip and while it is below 95% of its nominal value, VT becomes higher than VPCC. A fault appearance signal is generated in the output of the comparator and based on this signal, low step voltage is produced, which turns off the IGBT. Accordingly, the bridge part of the BFCL is open-circuited and line current is forced to flow through the shunt branch. Now, insertion of the sizeable shunt branch impedance in the line restricts fault current and hence improves the dynamic performance of DFIG wind integrated VSC-HVDC systems. The current through LDC has a tendency to rise drastically during fault initiation. However, LDC limits this current and the IGBT switch is protected against high di/dt.

3. DFIG Wind System Modeling

In this study, a doubly fed induction generator (DFIG) is used for generating wind energy as it has better performance in variable speed wind systems [51]. Another benefit of DFIG is that only small amounts of power, usually 25 to 30% of the machine-rated power, is controlled by converters. Thus, the power loss is reasonably low in the converters compared to cases where converters have to exchange the entire amount of power. The DFIG wind integrated VSC-HVDC system shown in Figure 3 is modeled and implemented in a real time digital simulator (RTDS) to show the efficacy of the proposed non-superconducting BFCL control strategy. The HVDC system allows power flow from the wind farm to the utility grid. HVDC link voltage must be controlled to a specified value for the proper flow of the active power from the DFIG wind farm to the grid through the DC link. The proposed controller of the grid voltage source converter (GVSC) regulates the voltage of the DC link capacitor by controlling charging and discharging. The system components are modeled as follows.

3.1. Wind Turbine Modeling

Generally, the operating principle of a wind turbine is described by its mechanical power, given as [52]:
P t u r = 0.5 ρ A V w 3 C p ( λ , β )
where ρ is air mass density in kg/m3, A is turbine swept area = π r 2 , r is turbine radius, V w is turbine speed in m/s, Cp is the performance coefficient, β is the blade pitch angle, and λ is the tip speed ratio.
The tip speed ratio is given by the following equation.
λ = r ω t u r V w
where ω t u r is the turbine angular speed in rad/s. Power delivered by the wind turbine (Ptur) can be controlled by varying the performance coefficient. Variation of Cp is achieved by varying ω t u r and β since wind speed V w cannot be controlled. Cp is a highly nonlinear function of β and λ given by the equation below [53].
C p ( λ , β ) = 1 2 ( λ 0.022 β 2 5.6 ) e 0.17 λ

3.2. Doubly Fed Induction Generator (DFIG) Modeling

Wind energy is extracted and integrated to the grid with a doubly fed induction generator, which is basically a three phase wound-rotor induction machine. A mechanically coupled gear box is used to connect the wind turbine with the DFIG system. The stator side of the DFIG is directly connected to the PCC, as shown in Figure 3, while the DFIG rotor is connected to the PCC with an AC/DC/AC conversion system with voltage source converters (VSCs). A common DC bus of the VSCs contains a capacitor. Rotor voltage in d-q frame is given as [54]:
V d r = R r i d r + σ L r d i d r d t ω s l i p ( σ L r i q r )
V q r = R r i q r + σ L r d i q r d t + ω s l i p ( σ L r i d r + L m i m s )
where mutual inductance, L m = ( L o ) 2 L s ; leakage factor, σ = 1 ( L o ) 2 L r L s ; Rr is the rotor resistance; Lr is the rotor inductance; Ls is the stator inductance; Lo is the magnetizing inductance; and ωslip is the slip frequency, which is the difference between stator and rotor frequency.

4. Controller Design

The following subsections describe the design of the stator voltage source converter (SVSC), rotor voltage source converter (RVSC), wind turbine voltage source converter (WTVSC), and grid voltage source converter (GVSC) controllers in detail.

4.1. Control of Stator Voltage Source Converter (SVSC)

The stator-side converter consists of a two-level, six-pulse AC/DC VSC, the AC side of which is connected to the PCC and the DC side of which is connected to the capacitor. In the SVSC controller, the outer loop regulates DC bus voltage, while the inner loop controls current, as shown in Figure 4 [55].
The error between the measured DC capacitor voltage (Vcmes) and the reference voltage (Vcref) is processed by a proportional integral (PI) regulator. The output of the PI regulator provides the reference direct axis current (Idsref) to an inner current controller. The measured three-phase stator current is converted to d-q components using Park’s transformation and compared with corresponding reference currents then processed by inner PI current regulators. Output of the inner PI controllers is added with decoupling terms (Iqsω0Lsp and Idsω0Lsp) in which Lsp is the reactance between the SVSC terminal and the PCC. The stator-side converter consists of a two-level six-pulse AC/DC VSC, the AC side of which is connected to the PCC and the DC side of which is connected to a capacitor. In the SVSC controller, the outer loop regulates the DC bus voltage while the inner loop controls the current, as shown in Figure 4. The following subsections describe the design of the stator voltage source converter (SVSC), rotor voltage source converter (RVSC), wind turbine voltage source converter (WTVSC), and grid voltage source converter (GVSC) controllers in detail.

4.2. Control of Rotor Voltage Source Converter (RVSC)

The RVSC controller is developed in d-q frame to regulate powers, as in Figure 5. The base equations and symbol descriptions for the following controller are given in Section 3.2.
Figure 5 shows that the measured three-phase rotor current is converted to d-q components with a rotating reference frame (θslip), which is computed from the difference between the position of the stator flux (θs) and rotor flux (θr) vector [55]. Reactive reference rotor current (Iqrref) is provided by the optimal power point tracker, as shown in the above schematic diagram.

4.3. Control of Wind Turbine Voltage Source Converter (WTVSC)

The active power exchange between the wind farm and the grid is regulated by the WTVSC. Additionally, the reactive power interchange between the wind farm and the PCC can be controlled by the WTVSC in order to control AC voltage at the PCC. d-q components-based active and reactive powers are given as follows, as per instantaneous power theory [56].
P s = 3 2 [ V d I d + V q I q ]
Q s = 3 2 [ V d I q + V q I d ]
Phase-locked loop (PLL) is employed to measure grid angle and synchronize VSC with the grid in such a way that the quadrature axis voltage ( V q ) is zero. Thus, we get the following equations from the above two equations:
P s = 3 2 V d I d
Q s = 3 2 V d I q
Therefore, control of active and reactive power is achieved by simply controlling the direct axis and quadrature axis current, respectively, as below.
I d r e f = 2 3 V d P r e f
I q r e f = 2 3 V d Q r e f
By means of an a-b-c to d-q conversion technique, the following first-order differential equations and converter equations are obtained.
L d I d d t = L ω 0 I q R I d + V t d V d
L d I q d t = L ω 0 I d R I q + V t q V q
V t d = V D C 2 m d
V t q = V D C 2 m q
where md and mq are d-axis and q-axis modulating signals, respectively. Based on the above equations, the following controller has been developed for the WTVSC to control active and reactive powers.
As shown in Figure 6, inner current controllers control the active and reactive power with corresponding d-axis and q-axis currents, respectively. Both d-axis and q-axis currents are controlled by proportional integral (PI) controllers. Controller parameters for inner PIs are tuned by using the pole-zero cancellation technique. Implementation of a feed-forward filter (FFF) scheme removes undesirable start-up transient in VSC. The third harmonic injected pulse width modulation (PWM) method is adopted in this study as the required minimum DC bus voltage level is lower than classical PWM generation, which, in turn, increases system stability in the worst-case scenario [56]. In the third harmonic injected PWM technique, the squares of d-axis and q-axis signals are added together to generate the modulating signal (m). BFCL impedance is inserted by the control action during disturbances to keep the fault current within the limit, which eventually enhances transient stability of the DFIG-based HVDC system. Furthermore, the impact of fault current on wind turbine VSC is minimized by the proposed controller.

4.4. Control of Grid Voltage Source Converter (GVSC)

Control performance of the outer DC link voltage controller directly affects the system’s stability [57]. The GVSC controller employs a double control loop: an outer loop to control DC link voltage and an inner loop to control active and reactive power. The inner control loop for the GVSC is similar to the current control loop of the WTVSC and is presented in Figure 7. The main difference is that the reference active power (Pref2) for the GVSC is delivered by the outer DC voltage regulator, as shown in Figure 7.
In the outer voltage controller, the error between the measured DC voltage (VDCmes) and the reference DC voltage (VDCref) is processed by proportional integral (PI) controller. The outer PI parameters are obtained by employing the symmetrical optimum method [58]. The output of the outer PI is added to the amount of active power transferred from the wind farm to the grid for the active reference power generation of GVSC. Then, the d-axis reference current is generated and processed by the inner current control loop.

5. Results and Discussions

5.1. System Data

DFIG wind integrated VSC-HVDC with a BFCL system, as shown in Figure 3, is considered in this work to validate the proposed control strategies. The proposed fault current limiting device, the BFCL, is connected to both the wind power plant and the grid side of the system considered. The parameters of the HVDC system and the DFIG are listed in Table 1 and Table 2, respectively.

5.2. Controller Parameter Design

The pole-zero elimination method [59] is used to determine the parameters of the inner current controllers. In addition, the symmetrical optimum method [58] is used for parameter tuning of outer voltage controllers. Controller parameters obtained by these methods are listed in Table 3 for all proportional integral (PI) controllers.

5.3. RTDS Implementation

The test system of Figure 3 is implemented in a real time digital simulator (RTDS) to confirm the efficacy of the proposed BFCL in enhancing the system’s stability and improving the fault ride through capability. The proposed BFCL is also equated with the SDBR to demonstrate the augmentation of system performance to limit current during faults.
RTDS is a completely digital power system simulator working in real time. It comes with custom hardware with high-speed processor and software named RSCAD. The RTDS platform has been widely recognized by most of the electrical utilities, research institutes, protection equipment manufacturers, and educational institutions for the development and testing of power system equipment [60].
The RTDS rack is connected to the workspace computer with a network hub, as shown in Figure 8. The DFIG system and associated controllers are built in RSCAD software and compiled in the workspace computer. After successful compilation, codes are downloaded to the RTDS hardware to run the system in real time and observe the system’s behavior. Detailed RTDS implementation results are presented and discussed below.

5.4. Simulation Results

Initially, the system operates in its normal condition. Balanced 3LG and unbalanced 1LG disturbances are then applied separately at the point of common coupling. The duration of these faults is six cycles. Under each fault, three different simulation conditions are tested to show the effectiveness of the proposed BFCL control technique. These conditions are:
(i)
without FCL;
(ii)
with SDBR;
(iii)
with proposed BFCL.

5.4.1. Balanced Fault Applications

At the start, the VSCs are disconnected from the system and the DC link capacitors are discharged. When the capacitors are fully discharged, VSCs are connected to the system through an interface reactor and resistors. As a result, the capacitors are now gradually charged and reach a steady state value. The reference voltage is then step-changed to 35 kV and all the controllers are unblocked. Thus, the outer DC link voltage controllers of the GVSC regulate the DC link voltage to the reference value. At this level, the system is ready to apply different faults and observe the improvement of the system’s transient response with the proposed BFCL-based control technique.
Figure 9a shows that the speed of the DFIG fluctuates over a wide range without any auxiliary controller for a balanced 3LG fault. The implementation of SDBR reduces speed fluctuation by only 40%, as observed below. On the other hand, the proposed non-superconducting BFCL-control-based approach provides a greater speed oscillation damping performance, which is around 65%. Moreover, the settling time for speed oscillation is 9.5 seconds with the SDBR, which is significantly reduced to 5.8 seconds with the proposed technique. The DFIG speed oscillates during the entire simulation period without any auxiliary control techniques. In addition, the effectiveness of the proposed BFCL solution is clearly visualized in Figure 9b–d for an 3LG fault at the PCC, as the DFIG power oscillations, stator fault current, and DC link voltage fluctuations have been greatly reduced.
Improvement in HVDC system response with the proposed BFCL has also been observed. The DC capacitor voltage, grid active power, and grid current under the fault condition are shown in Figure 10. Figure 10a shows that the DC link voltage of HVDC is oscillating over the entire simulation period. The SDBR reduces voltage fluctuation by 26.6%, while the fluctuation is significantly suppressed, by 41.6%, with the proposed BFCL, as observed in Figure 10a. Reduction in grid power oscillation and fault current is shown in Figure 10b–c, where the superiority of the proposed BFCL is evident.

5.4.2. Unbalanced Fault Applications

An unbalanced single-line-to-ground (1LG) fault was applied at the PCC. Real time simulation in Figure 11 clearly shows the positive effect of the proposed BFCL in reducing system oscillation. Figure 11a shows the DFIG speed response of the system with a 1LG fault applied at the PCC. Without FCL, DFIG oscillates over a wide range and does not reach the steady state value within the entire simulation period. System performance is slightly improved with the SDBR. However, the proposed BFCL-based strategy keeps the DFIG speed oscillation within a narrow range during the fault. Time taken for DFIG speed to reach its reference value is also small for the proposed BFCL compared to without FCL and under SDBR conditions. A noteworthy reduction in fault current, power oscillation, and capacitor voltage fluctuation is observed and shown in Figure 11b–d.
Fault ride through capability of HVDC with the proposed BFCL is shown in Figure 12a–c. Without any fault current limiter, the DC link voltage of HVDC fluctuates exceedingly. With the application of the SDBR, fluctuation is reduced by 17.5%. Throughout the entire simulation period, the proposed BFCL keeps the DC link voltage within the permissible limit compared to the SDBR and without auxiliary controller. Line current and power profile improvement with the proposed control approach is shown in Figure 12b–c.

5.4.3. Index-Based Comparison

For a clearer perception of DFIG wind integrated VSC-HVDC system fault ride through capability enhancement with the proposed control-based BFCL, several performance indices are evaluated. These are based on the deviations in DC voltage, AC power, line current, and DFIG speed. The mathematical expressions for the above-mentioned indices are given as
D C v o l t = 0 T | Δ V D C | d t
A C p o w = 0 T | Δ P | d t
l i n e c u r r = 0 T | Δ i | d t
D F I G s p e e d = 0 T | Δ N | d t
where Δ V D C , Δ P , Δ i , and Δ N represent deviations of DC link voltage, active power flow, line current, and DFIG speed, respectively.
Performance indices for balanced and unbalanced disturbances are listed in Table 4 and Table 5, respectively.
The results in Table 4 and Table 5 show that the deviations in all indices considered are much smaller with the proposed BFCL control strategy. It can be concluded that the performance of the DFIG wind integrated VSC-HVDC system is substantially improved with the proposed BFCL.

5.4.4. BFCL Implementation Feasibility

Bridge-type fault current limiter (BFCL) implementation requires diodes, an IGBT, inductors, and resistors. Nowadays, due to the advancement of power electronic applications, IGBTs and diodes with high ratings are available on the market. Therefore, the assembling cost of BFCL can be calculated for implementation in real DFIG-based VSC-HVDC systems. Even though the actual cost of the practical implementation of BFCL is not yet known; it can be inferred from the components needed for implementing BFCL.

6. Conclusions

In this study, a non-superconducting BFCL-based control approach was demonstrated for augmenting the FRT capability of DFIG wind integrated VSC-HVDC systems. Depending on fault detection based on PCC voltage, the BFCL controller was designed to insert resistance and inductance during system faults. Stator VSC and rotor VSC controllers were proposed to control DC link capacitor voltage and power, respectively. Current control approaches based in VSC-HVDC transmission system controllers were developed to deliver DFIG power to the grid. The systems, including wind turbine, DFIG, converters, HVDC cable, and associated controllers, were implemented in RTDS. Symmetrical as well as unsymmetrical faults were applied at the PCC to demonstrate the augmentation of system performance with the proposed method. The main outcomes of this study can be highlighted as follows:
  • The proposed BFCL is a potential solution for restricting the fault current of DFIG wind-based VSC-HVDC during severe faults.
  • DFIG speed, DC link voltage, and power oscillations were reduced significantly with the proposed BFCL control scheme.
  • The superiority of the proposed BFCL-based control is demonstrated by comparing with the reported literature.

Author Contributions

All authors collaborated on this work. M.S.A. is the first author in this manuscript. All authors revised and approved the text for publication.

Funding

This research received no external funding.

Acknowledgments

The authors would like to acknowledge the support provided by the Deanship of Scientific Research, King Fahd University of Petroleum & Minerals, through the funded project # RG171002.

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

Abbreviations
BFCLBridge-type fault current limiter
DFIGDoubly fed induction generator
FFFFeed-forward function
FRTFault ride through
GSCGrid-side converter
HVDCHigh-voltage DC
IGBTInsulated-gate bipolar transistor
PCCPoint of common coupling
PIProportional integral
PLLPhase-locked loop
RSCRotor-side converter
RTDSReal time digital simulator
SDBRSeries dynamic braking resistor
VSCVoltage source converter
WTWind turbine
Subscripts
dDirect axis
GGrid
mMutual
mesMeasured
qQuadrature axis
rRotor
refReference
sStator
shShunt

References

  1. Javadi, M.; Marzband, M.; Akorede, M.F.; Godina, R. A Centralized Smart Decision-Making Hierarchical Interactive Architecture for Multiple Home Microgrids in Retail Electricity Market. Energies 2018, 11, 3144. [Google Scholar] [CrossRef]
  2. Valinejad, J.; Marzband, M.; Akorede, M.F.; Elliott, I.D.; Godina, R.; Carlos, J.; Matias, D.O.; Pouresmaeil, E. Long-Term Decision on Wind Investment with Considering Different Load Ranges of Power Plant for Sustainable Electricity Energy Market. Sustainability 2018, 10, 3811. [Google Scholar] [CrossRef]
  3. Valinejad, J.; Barforoshi, T.; Marzband, M. Investment Incentives in Competitive Electricity Markets. Appl. Sci. 2018, 8, 1978. [Google Scholar] [CrossRef]
  4. Daoud, M.I.; Massoud, A.M.; Abdel-Khalik, A.S.; Elserougi, A.; Ahmed, S. A flywheel energy storage system for fault ride through support of grid-connected VSC HVDC-based offshore wind farms. IEEE Trans. Power Syst. 2016, 31, 1671–1680. [Google Scholar] [CrossRef]
  5. Marzband, M.; Azarinejadian, F.; Savaghebi, M.; Pouresmaeil, E. Smart transactive energy framework in grid-connected multiple home microgrids under independent and coalition operations. Renew. Energy 2018, 126, 95–106. [Google Scholar] [CrossRef]
  6. Nanou, S.I.; Member, S.; Papathanassiou, S.A.; Member, S. Grid Code Compatibility of VSC-HVDC Connected Offshore Wind Turbines Employing Power Synchronization Control. IEEE Trans. Power Syst. 2016, 31, 5042–5050. [Google Scholar] [CrossRef]
  7. Erlich, I.; Feltes, C.; Shewarega, F. Enhanced voltage drop control by VSC-HVDC systems for improving wind farm fault ridethrough capability. IEEE Trans. Power Deliv. 2014, 29, 378–385. [Google Scholar] [CrossRef]
  8. Flourentzou, N.; Agelidis, V.G.; Demetriades, G.D. VSC-Based HVDC Power Transmission Systems: An Overview. IEEE Trans. Power Electron. 2009, 24, 592–602. [Google Scholar] [CrossRef]
  9. Van Hertem, D.; Ghandhari, M. Multi-terminal VSC HVDC for the European supergrid: Obstacles. Renew. Sustain. Energy Rev. 2010, 14, 3156–3163. [Google Scholar] [CrossRef]
  10. Feltes, C.; Wrede, H.; Koch, F.W.; Erlich, I. Enhanced fault ride-through method for wind farms connected to the grid through VSC-based HVDC transmission. IEEE Trans. Power Syst. 2009, 24, 1537–1546. [Google Scholar] [CrossRef]
  11. Bernal-Perez, S.; Ano-Villalba, S.; Blasco-Gimenez, R.; Rodriguez-D’Derlee, J. Efficiency and Fault Ride-Through Performance of a Diode-Rectifier- and VSC-Inverter-Based HVDC Link for Offshore Wind Farms. IEEE Trans. Ind. Electron. 2013, 60, 2401–2409. [Google Scholar] [CrossRef] [Green Version]
  12. Chaudhary, S.K.; Teodorescu, R.; Rodriguez, P.; Kjaer, P.C.; Gole, A.M. Negative sequence current control in wind power plants with VSC-HVDC connection. IEEE Trans. Sustain. Energy 2012, 3, 535–544. [Google Scholar] [CrossRef]
  13. Guerrero-Lemus, R.; González-Díaz, B.; Ríos, G.; Dib, R.N. Study of the new Spanish legislation applied to an insular system that has achieved grid parity on PV and wind energy. Renew. Sustain. Energy Rev. 2015, 49, 426–436. [Google Scholar] [CrossRef]
  14. Sichilalu, S.; Tazvinga, H.; Xia, X. Optimal control of a fuel cell/wind/PV/grid hybrid system with thermal heat pump load. Sol. Energy 2016, 135, 59–69. [Google Scholar] [CrossRef] [Green Version]
  15. Ding, M.; Xu, Z.; Wang, W.; Wang, X.; Song, Y.; Chen, D. A review on China׳s large-scale PV integration: Progress, challenges and recommendations. Renew. Sustain. Energy Rev. 2016, 53, 639–652. [Google Scholar] [CrossRef]
  16. Muttaqi, K.M.; Member, S.; Islam, R.; Member, S.; Sutanto, D.; Member, S. Future Power Distribution Grids: Integration of Renewable Energy, Energy Storage, Electric Vehicles, Superconductor, and Magnetic Bus. IEEE Trans. Appl. Supercond. 2019, 29, 1–5. [Google Scholar] [CrossRef]
  17. Islam, R.; Member, S.; Rahman, A. A New Magnetic-Linked Converter for Grid Integration of Offshore Wind Turbines Through MVDC Transmission. IEEE Trans. Appl. Supercond. 2019, 29, 1–5. [Google Scholar] [CrossRef]
  18. Charles, C.M.R.; Vinod, V.; Jacob, A. Field Oriented Control of DFIG Based Wind Energy System Using Battery Energy Storage System. Procedia Technol. 2016, 24, 1203–1210. [Google Scholar] [CrossRef] [Green Version]
  19. Weng, Y.-T.; Hsu, Y.-Y. Reactive power control strategy for a wind farm with DFIG. Renew. Energy 2016, 94, 383–390. [Google Scholar] [CrossRef]
  20. Kenan Döşoʇlu, M.; Arsoy, A.B. Transient modeling and analysis of a DFIG based wind farm with supercapacitor energy storage. Int. J. Electr. Power Energy Syst. 2016, 78, 414–421. [Google Scholar] [CrossRef]
  21. Wickramasinghe, A.; Perera, S.; Agalgaonkar, A.P.; Meegahapola, L. Synchronous mode operation of DFIG based wind turbines for improvement of power system inertia. Renew. Energy 2016, 95, 152–161. [Google Scholar] [CrossRef]
  22. Bossoufi, B.; Karim, M.; Lagrioui, A.; Taoussi, M.; Derouich, A. Observer backstepping control of DFIG-Generators for wind turbines variable-speed: FPGA-based implementation. Renew. Energy 2015, 81, 903–917. [Google Scholar] [CrossRef]
  23. Ostolaza, J.X.; Etxeberria, A.; Zubia, I. Wind farm node connected DFIG/back-to-back converter coupling transient model for grid integration studies. Energy Convers. Manag. 2015, 106, 428–439. [Google Scholar] [CrossRef]
  24. Chafouk, H.; Ouyessaad, H. Fault detection and isolation in DFIG driven by a wind turbine. IFAC Proc. Vol. 2015, 48, 251–256. [Google Scholar] [CrossRef]
  25. Khattara, A.; Bahri, M.; Aboubou, A.; Becherif, M.; Ayad, M.Y. Line-Fault Ride-Through (LFRT) Capabilities of DFIG Wind Turbine Connected to the Power System. APCBEE Procedia 2013, 7, 189–194. [Google Scholar] [CrossRef] [Green Version]
  26. Rolán, A.; Pedra, J.; Córcoles, F. Detailed study of DFIG-based wind turbines to overcome the most severe grid faults. Int. J. Electr. Power Energy Syst. 2014, 62, 868–878. [Google Scholar] [CrossRef] [Green Version]
  27. De Sousa, W.T.B.; Assis, T.M.L.; Polasek, A.; Monteiro, A.M.; de Andrade, R. Simulation of a Superconducting Fault Current Limiter: A Case Study in the Brazilian Power System With Possible Recovery Under Load. IEEE Trans. Appl. Supercond. 2016, 26, 1–8. [Google Scholar] [CrossRef]
  28. Jo, H.C.; Joo, S.K. Superconducting fault current limiter placement for power system protection using the minimax regret criterion. IEEE Trans. Appl. Supercond. 2015, 25. [Google Scholar] [CrossRef]
  29. Blair, S.M.; Elders, I.M.; Booth, C.D.; Burt, G.M.; McCarthy, J.; Singh, N.K. Superconducting fault current limiter application in a power-dense marine electrical system. IET Electr. Syst. Transp. 2011, 1, 93–102. [Google Scholar] [CrossRef] [Green Version]
  30. Yew, P.J.; Selamat, N.S.; Wai, S.K.; Ismail, A.B.; Hamid, N.A. Modeling of Resistive Type Superconducting Fault Current Limiter in Power System. J. Solid St. Sci. Technol. Lett. 2005, 12, 171–179. [Google Scholar]
  31. Li, B.; Li, C.; Guo, F. Application Studies on the Active SISFCL in Electric Transmission System and Its Impact on Line Distance Protection. IEEE Trans. Appl. Supercond. 2015, 25, 5600–5610. [Google Scholar] [CrossRef]
  32. Noe, M.; Hobl, A.; Tixador, P.; Martini, L.; Dutoit, B. Conceptual Design of a 24 kV, 1 kA Resistive Superconducting Fault Current Limiter. IEEE Trans. Appl. Supercond. 2012, 22, 5600304. [Google Scholar] [CrossRef]
  33. Nam, S.; Lee, J.; Lee, W.S.; Park, Y.G.; Song, S.; Jin, H.; Ko, T.K. Operational characteristics of a small-scale novel hybrid resistive-type SFCL with controlled power electronics. IEEE Trans. Appl. Supercond. 2015, 25. [Google Scholar] [CrossRef]
  34. Kojima, H.; Osawa, T.; Hayakawa, N. Fault current limitation coordination in power transmission system with Superconducting Fault Current Limiting Cables (SFCLC). IEEE Trans. Appl. Supercond. 2015, 25. [Google Scholar] [CrossRef]
  35. Jo, H.-C.; Kong, S.; Joo, S.-K. Impedance Selection of a Fault Current Limiting Superconducting Cable Under Fault Conditions in a Power System From a System Protection Perspective. IEEE Trans. Appl. Supercond. 2016, 26, 1–4. [Google Scholar] [CrossRef]
  36. Alam, M.S.; Abido, M.A.Y. Fault ride-through capability enhancement of voltage source converter-high voltage direct current systems with bridge type fault current limiters. Energies 2017, 10, 1898. [Google Scholar] [CrossRef]
  37. Alam, M.S.; Hossain, I.; Hossain, A.; Choudhory, S.H. Protection of Inverter-based Distributed Generation with Series Dynamic Braking Resistor: A Variable Duty Control Approach. In Proceedings of the 2018 10th International Conference on Electrical and Computer Engineering (ICECE), Dhaka, Bangladesh, 20–22 December 2018; IEEE: Piscataway, NJ, USA, 2018; pp. 253–256. [Google Scholar]
  38. Causebrook, A.; Atkinson, D.J.; Jack, A.G. Fault ride-through of large wind farms using series dynamic braking resistors. IEEE Trans. Power Syst. 2007, 22, 966–975. [Google Scholar] [CrossRef]
  39. Alam, M.S.; Abido, M.A.Y.; El-Amin, I. Fault Current Limiters in Power Systems: A Comprehensive Review. Energies 2018, 11, 1025. [Google Scholar] [CrossRef]
  40. Nourmohamadi, H.; Nazari-Heris, M.; Sabahi, M.; Abapour, M. A Novel Structure for Bridge-Type Fault Current Limiter: Capacitor Based Nonsuperconducting FCL. IEEE Trans. Power Electron. 2017, 33, 3044–3051. [Google Scholar] [CrossRef]
  41. Sadi, M.A.H.; Ali, M.H. A fuzzy logic controlled bridge type fault current limiter for transient stability augmentation of multi-machine power system. IEEE Trans. Power Syst. 2016, 31, 602–611. [Google Scholar] [CrossRef]
  42. Sadi, M.A.H.; Ali, M.H. Transient stability enhancement by bridge type fault current limiter considering coordination with optimal reclosing of circuit breakers. Electr. Power Syst. Res. 2015, 124, 160–172. [Google Scholar] [CrossRef]
  43. Fereidouni, A.; Masoum, M.A.S.; Hosseinimehr, T.; Moghbel, M. Performance of LR-type solid-state fault current limiter in improving power quality and transient stability of power network with wind turbine generators. Int. J. Electr. Power Energy Syst. 2016, 74, 172–186. [Google Scholar] [CrossRef]
  44. Hossain, M.K.; Ali, M.H. Transient stability augmentation of PV/DFIG/SG-based hybrid power system by parallel-resonance bridge fault current limiter. Electr. Power Syst. Res. 2016, 130, 89–102. [Google Scholar] [CrossRef]
  45. Naderi, S.B.; Jafari, M.; Tarafdar Hagh, M. Controllable resistive type fault current limiter (CR-FCL) with frequency and pulse duty-cycle. Int. J. Electr. Power Energy Syst. 2014, 61, 11–19. [Google Scholar] [CrossRef]
  46. Rashid, G.; Ali, M.H. Bridge-type fault current limiter for asymmetric fault ride-through capacity enhancement of doubly fed induction machine based wind generator. IEEE Energy Convers. Congr. Expos. 2014, 29, 1903–1910. [Google Scholar] [CrossRef]
  47. Jafari, M.; Naderi, S.B.; Hagh, M.T.; Abapour, M.; Hosseini, S.H. Voltage sag compensation of point of common coupling (PCC) using fault current limiter. IEEE Trans. Power Deliv. 2011, 26, 2638–2646. [Google Scholar] [CrossRef]
  48. Alam, M.S.; Abido, M.A.; Al-hamouz, Z.M. Model Predictive Control Approach for Bridge-Type Fault Current Limiter in VSC-HVDC System. Arab. J. Sci. Eng. 2018, 1–11. [Google Scholar] [CrossRef]
  49. Liu, X.; Wang, P.; Loh, P.C. A hybrid AC/DC microgrid and its coordination control. IEEE Trans. Smart Grid 2011, 2, 278–286. [Google Scholar] [CrossRef]
  50. Alam, M.S.; Razzak, A.; Islam, N.; Hossain, F.S. Transient Stability Enhancement Of Bangladesh East West Interconnected System Using Static VAR Compensator (SVC). Int. J. Eng. Res. Technol. 2013, 2, 730–733. [Google Scholar]
  51. Islam, R.; Guo, Y.; Zhu, J. A review of offshore wind turbine nacelle: Technical challenges, and research and developmental trends. Renew. Sustain. Energy Rev. 2014, 33, 161–176. [Google Scholar] [CrossRef] [Green Version]
  52. Alam, M.S.; Abido, M.A.Y. Fault Ride Through Capability Enhancement of a Large-Scale PMSG Wind System with Bridge Type Fault Current Limiters. Adv. Electr. Comput. Eng. 2018, 18, 43–50. [Google Scholar] [CrossRef]
  53. Slootweg, J.G.; Polinder, H.; Kling, W.L. Representing wind turbine electrical generating systems in fundamental frequency simulations. IEEE Trans. Energy Convers. 2003, 18, 516–524. [Google Scholar] [CrossRef] [Green Version]
  54. Pena, R.; Clare, J.C.; Asher, G.M. Doubly fed induction generator uising back-to-back PWM converters and its application to variable-speed wind-energy generation. IEE Proc. Power Appl. 1996, 143, 231–241. [Google Scholar] [CrossRef]
  55. Ali, M.H.; Hossain, M.M. Transient stability improvement of doubly fed induction generator based variable speed wind generator using DC resistive fault current limiter. IET Renew. Power Gener. 2015, 18, 803–809. [Google Scholar] [CrossRef]
  56. Yazdani, A.; Iravani, R. Voltage-Sourced Converters in Power Systems, 1st ed.; IEEE and Wiley Publisher: Hoboken, NJ, USA, 2010; ISBN 0470521562. [Google Scholar]
  57. Wang, Z.-D.; Li, K.-J.; Ren, J.-G.; Sun, L.-J.; Zhao, J.-G.; Liang, Y.-L.; Lee, W.-J.; Ding, Z.-H.; Sun, Y. A Coordination Control Strategy of Voltage-Source-Converter-Based MTDC for Offshore Wind Farms. IEEE Trans. Ind. Appl. 2015, 51, 2743–2752. [Google Scholar] [CrossRef]
  58. Preitl, S.; Precup, R.-E. An extension of tuning relations after symmetrical optimum method for PI and PID controllers. Automatica 1999, 35, 1731–1736. [Google Scholar] [CrossRef]
  59. Sajnekar, D.M.; Deshapande, S.B.; Mohril, R.M. Comparison of Pole Placement & Pole Zero Cancellation Method for Tuning PID Controller of A Digital Excitation. Int. J. Sci. Res. Publ. 2013, 3, 1–7. [Google Scholar]
  60. Baek, S.-M.; Park, J.-W. Nonlinear parameter optimization of FACTS controller via real-time digital simulator. IEEE Ind. Appl. 2012, 49, 2271–2278. [Google Scholar] [CrossRef]
Figure 1. Configuration of a non-superconducting bridge-type fault current limiter (solid arrow is for normal current flow and dashed arrow is for fault current flow path).
Figure 1. Configuration of a non-superconducting bridge-type fault current limiter (solid arrow is for normal current flow and dashed arrow is for fault current flow path).
Sustainability 11 01232 g001
Figure 2. Control strategy of bridge-type fault current limiter.
Figure 2. Control strategy of bridge-type fault current limiter.
Sustainability 11 01232 g002
Figure 3. Schematic diagram of a doubly fed induction generator (DFIG) wind integrated voltage source converter high-voltage DC (VSC-HVDC) system.
Figure 3. Schematic diagram of a doubly fed induction generator (DFIG) wind integrated voltage source converter high-voltage DC (VSC-HVDC) system.
Sustainability 11 01232 g003
Figure 4. Schematic diagram of the stator voltage source converter (SVSC) controller.
Figure 4. Schematic diagram of the stator voltage source converter (SVSC) controller.
Sustainability 11 01232 g004
Figure 5. Schematic diagram of the rotor voltage source converter (RVSC) controller.
Figure 5. Schematic diagram of the rotor voltage source converter (RVSC) controller.
Sustainability 11 01232 g005
Figure 6. Schematic diagram of the wind turbine voltage source converter (WTVSC) controller.
Figure 6. Schematic diagram of the wind turbine voltage source converter (WTVSC) controller.
Sustainability 11 01232 g006
Figure 7. Schematic diagram of the grid voltage source converter (GVSC) controller.
Figure 7. Schematic diagram of the grid voltage source converter (GVSC) controller.
Sustainability 11 01232 g007
Figure 8. Laboratory setup of the real time digital simulator.
Figure 8. Laboratory setup of the real time digital simulator.
Sustainability 11 01232 g008
Figure 9. Comparison of transient response of DFIG system balanced 3LG fault at the point of common coupling (PCC). (a) DFIG speed; (b) DFIG active power; (c) DFIG stator current; (d) DC link capacitor voltage of wind power plant. FCL: fault current limiter; BFCL: bridge-type fault current limiter.
Figure 9. Comparison of transient response of DFIG system balanced 3LG fault at the point of common coupling (PCC). (a) DFIG speed; (b) DFIG active power; (c) DFIG stator current; (d) DC link capacitor voltage of wind power plant. FCL: fault current limiter; BFCL: bridge-type fault current limiter.
Sustainability 11 01232 g009aSustainability 11 01232 g009b
Figure 10. Comparative transient response of HVDC subject to a balanced 3LG fault at the PCC. (a) HVDC DC link voltage; (b) grid active power; (c) grid current.
Figure 10. Comparative transient response of HVDC subject to a balanced 3LG fault at the PCC. (a) HVDC DC link voltage; (b) grid active power; (c) grid current.
Sustainability 11 01232 g010aSustainability 11 01232 g010b
Figure 11. Comparison of the transient response of the DFIG system for an unbalanced 1LG at the PCC. (a) DFIG speed; (b) DFIG active power; (c) DFIG stator current; (d) DC link capacitor voltage of wind power plant.
Figure 11. Comparison of the transient response of the DFIG system for an unbalanced 1LG at the PCC. (a) DFIG speed; (b) DFIG active power; (c) DFIG stator current; (d) DC link capacitor voltage of wind power plant.
Sustainability 11 01232 g011aSustainability 11 01232 g011b
Figure 12. Comparative transient response of HVDC subject to symmetrical fault at PCC. (a) HVDC DC link voltage; (b) grid active power; (c) grid current.
Figure 12. Comparative transient response of HVDC subject to symmetrical fault at PCC. (a) HVDC DC link voltage; (b) grid active power; (c) grid current.
Sustainability 11 01232 g012aSustainability 11 01232 g012b
Table 1. HVDC system parameters.
Table 1. HVDC system parameters.
ParameterValue
HVDC system power rating30 MVA
Grid voltage140 kV (L-L rms)
System frequency60 Hz
Transformer rating30 MVA
Transformer ratio140/18 kV (Delta/Y)
Transformer equivalent delta side leakage inductance110 mH
Resistor (R)88 mΩ
Inductor (L)8.5 mH
DC capacitor500 µF
DC bus voltage35 kV
BFCL shunt resistor10 mΩ
BFCL shunt inductor2 mH
SDBR resistor10 mΩ
Feed forward function (FFF)1/(1 + 7 × 10-6 s)
Table 2. DFIG system parameters.
Table 2. DFIG system parameters.
ParameterValue
Power rating2 MW
Stator voltage0.69 kV
Stator resistance0.001 Ω
Rotor resistance0.0013 Ω
Stator reactance0.0022 Ω
Magnetizing reactance0.941 Ω
Rotor reactance0.024 Ω
Rotor/stator turn ratio2.6377
Table 3. Controller Parameters.
Table 3. Controller Parameters.
NameKpKi
PIIDS0.30010
PIIQS0.30010
PIIDR1.38735.6
PIIQR1.38735.6
PIIDWVSC8.50088
PIIQWVSC8.50088
PIVDC0.103617.77
Table 4. DFIG wind-based HVDC system performance index improvement with the proposed method for balanced 3LG fault.
Table 4. DFIG wind-based HVDC system performance index improvement with the proposed method for balanced 3LG fault.
Index %Without FCLSDBRProposed BFCL
DFIGspeed80.817542.376314.2806
DCvolt [DFIG]0.0689020.057280.026487
DCvolt [HVDC]3.5861.79270.68626
ACpow [DFIG]52.179111.1190.6223
ACpow [GRID]49.97510.48771.0446
linecurr [Stator]0.730310.688260.63546
linecurr [Grid]1.37880.554280.38678
Table 5. DFIG wind-based HVDC system performance index improvement with the proposed method for unbalanced 1LG fault.
Table 5. DFIG wind-based HVDC system performance index improvement with the proposed method for unbalanced 1LG fault.
Index Parameters, %Without FCLSDBRProposed BFCL
DFIGspeed66.56121.64014.9367
DCvolt [DFIG]0.0520670.0350110.02854
DCvolt [HVDC]1.56770.562590.46095
ACpow [DFIG]8.03791.11630.43776
ACpow [GRID]7.61621.26490.76578
linecurr [Stator]0.730310.688260.63546
linecurr [Grid]1.37880.554280.38678

Share and Cite

MDPI and ACS Style

Alam, M.S.; Abido, M.A.Y.; Hussein, A.E.-D.; El-Amin, I. Fault Ride through Capability Augmentation of a DFIG-Based Wind Integrated VSC-HVDC System with Non-Superconducting Fault Current Limiter. Sustainability 2019, 11, 1232. https://doi.org/10.3390/su11051232

AMA Style

Alam MS, Abido MAY, Hussein AE-D, El-Amin I. Fault Ride through Capability Augmentation of a DFIG-Based Wind Integrated VSC-HVDC System with Non-Superconducting Fault Current Limiter. Sustainability. 2019; 11(5):1232. https://doi.org/10.3390/su11051232

Chicago/Turabian Style

Alam, Md Shafiul, Mohammad Ali Yousef Abido, Alaa El-Din Hussein, and Ibrahim El-Amin. 2019. "Fault Ride through Capability Augmentation of a DFIG-Based Wind Integrated VSC-HVDC System with Non-Superconducting Fault Current Limiter" Sustainability 11, no. 5: 1232. https://doi.org/10.3390/su11051232

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop