Next Article in Journal
Comparative Analysis of High Frequency Signal Injection Based Torque Estimation Methods for SPMSM, IPMSM and SynRM
Previous Article in Journal
Nonlinear Characteristics Compensation of Inverter for Low-Voltage Delta-Connected Induction Motor
Previous Article in Special Issue
Partial Discharge Analysis under High-Frequency, Fast-Rise Square Wave Voltages in Silicone Gel: A Modeling Approach
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Surface Discharges and Flashover Modelling of Solid Insulators in Gases

by
Mohammed El Amine Slama
1,*,
Abderrahmane Beroual
2 and
Abderrahmane (Manu) Haddad
1
1
Advanced High Voltage Engineering Centre, School of Engineering. Cardiff University, Queen’s Buildings The Parade, Cardiff, Wales CF24 3AA, UK
2
Laboratoire Ampère, University of Lyon, 36 Avenue Guy de Collongues, 69130 Ecully, France
*
Author to whom correspondence should be addressed.
Energies 2020, 13(3), 591; https://doi.org/10.3390/en13030591
Submission received: 25 October 2019 / Revised: 26 November 2019 / Accepted: 9 December 2019 / Published: 28 January 2020
(This article belongs to the Special Issue High Voltage Engineering and Applications)

Abstract

:
The aim of this paper is the presentation of an analytical model of insulator flashover and its application for air at atmospheric pressure and pressurized SF6 (Sulfur Hexafluoride). After a review of the main existing models in air and compressed gases, a relationship of flashover voltage based on an electrical equivalent circuit and the thermal properties of the discharge is developed. The model includes the discharge resistance, the insulator impedance and the gas interface impedance. The application of this model to a cylindrical resin-epoxy insulator in air medium and SF6 gas with different pressures gives results close to the experimental measurements.

1. Introduction

In order to optimize the insulation level for high-voltage components (air insulated substations (AIS), gas insulated substations (GIS) and gas insulated lines (GIL), breakers, overhead lines…), a special attention is given to creeping or surface discharges because of the thermal effects and the faults that they can produce by sparking or flashover. Then, the knowledge of the parameters characterizing this kind of discharge is essential to understand the complexity of the mechanisms involved in their development. Thus, it is fundamental to acquire such information to enable building a mathematical model that can help in optimizing the insulation efficiency.
This paper aims to carry out a review of existing models of creeping discharges and to propose an analytical approach for the calculation of flashover voltage of solid insulators in gases under lightning voltage stress.

2. Review of Surface Discharges and Flashover Models in Gases

From the insulation viewpoint, the triple junction (metal-gas-solid) constitutes the weakest point in high-voltage equipment. Indeed, when the electric field reaches a critical value, partial discharges (PDs) can be initiated in the vicinity of this region. The increase of the voltage leads these PDs to develop and to transform into surface discharges (creeping discharges) that propagate over the insulator up to flashover [1,2,3,4]. In the case of GIS and GIL, the worst case is when insulators (spacer, post-type insulator) are contaminated by metallic particles on their surfaces [5,6].
The physical mechanisms responsible for the surface discharge propagation are still not well known because of the complexity of the phenomena and the interaction of different factors, such as the interaction between the discharges, nature of gas and the proprieties of the solid insulating material, gas pressure, surface charges and pollution (metallic particle), geometrical parameters (insulator shape, electrodes form…), etc. Fundamental studies have been conducted to understand the inception and propagation of creeping discharges in various gases [7,8,9,10,11,12,13,14]. It appears from the reported results that the phenomena start with corona discharges that evolves into ramified streamers. When the streamer discharge reaches a certain length, a leader channel with streamers at its head appears.
The creeping discharge propagation dynamics in SF6 (sulfur hexafluoride) has been investigated by many researchers [7,8,9,10,11]. Okubo et al. [8] reported that the creeping discharge has the same dynamics as in air (Figure 1). Tenbohlen and Schröder [9] analysed the surface discharge under lightning impulse (LI) voltage with different electrical charges deposition on the insulator surface. Figure 1 illustrates the current waveform from the inception to flashover with different electrical charges on the insulator surface. From Figure 1, some similarities with discharge current propagating in air [13] can be noted: the current increases with the leader elongation until the discharge reaches the critical length. Then, the final jump occurs causing the full flashover.
Hayakawa et al. [7] analysed the mechanism of impulse creeping discharge propagation on charged PMMA (poly-methyl methacrylate) surface. Their results showed that the discharge propagation is influenced by the charged surface and can be explained by the streamer propagation and streamer-to-leader transition based on the precursor mechanism. On the other hand, according to Okubo et al. [8], Beroual [3] and Beroual et al. [10,11], the creeping discharge propagation depends on the specific capacitance of the solid insulator. The permittivity, the conductivity and the geometry of the insulator affect the propagation of the surface discharge [10,11,12].
Modelling and calculation of flashover voltage is not an easy task because of the interaction of different parameters, such as gas pressure and its chemical constitution, physicochemical properties of the solid insulator, nature and distribution of the surface charges, etc. Different models have been proposed in order to compute the inception voltage of creeping discharges and flashover voltage of insulator in air at atmospheric pressure [2,3,13,14]. Figure 2 depicts the different evolution steps of creeping discharge on the insulator.
According to Reference [2], the corona inception voltage depends on the equivalent capacitance of the system. It can be calculated with the following relationship [2]:
U i n c e p t i o n = A C a
The second step is the appearance of streamers (Figure 2a). The streamers voltage inception is given by [2]:
U s t r e a m e r = B C b
According to Toepler [3], the maximum (critical) length of the discharge that leads to flashover is:
l max = k C 2 U 5 d u d t 4
Then, if the voltage is increased, the discharge will be irreversible and propagates until flashover. In this case, the flashover voltage Ufov can be calculated as well:
U f o v = D C d
where:
  • C is the equivalent capacitance,
  • A, B and D are parameters that depend on the geometry and the material of insulator, the kind of the discharge and the experimental conditions (gas, pressure, temperature, humidity, electrodes shape, voltage waveform…), respectively. Terms a, b and d are empirical parameters the values of which vary in the range 0.2–0.44.
These models are empirical and involve only the capacitance of the insulator.
In the case of SF6, Laghari [15] proposed a relationship of flashover voltage based on the efficiency coefficient that represents the ratio of the flashover voltage for uniform electrical gradient distribution to the voltage breakdown of the same gap without an insulator with the same configuration of insulator as well:
V f o v = 12.4 ln ( V b ) k 1 k 2 ln ( ε r ) ε r V b
where,
V b = c o n s t + ( E p ) c r i p d
Vb is the breakdown voltage calculated according to Paschen law. k1 and k2 are parameters that depend on the roughness and the contact nature between the insulator and the electrodes. εr is the permittivity of the insulator.
Hama et al. [16] proposed a semi-empirical relationship of flashover voltage based on the mechanism leader/precursor:
V f o v = X L e a d e r D p o l V L e a d e r + V L e a d e r
where XLeader and VLeader are the length and the voltage of the leader discharge respectively, and Dpol is a coefficient that is dependent on the polarity of the applied voltage, the reduced critical electrical gradient and the shape of the electrodes, with:
D p o l = c o n s t × ( E p ) c r i × ϕ ( R y é l e c t r o d e s )
The application of this model shows results close to the experimental measurements, but it is limited to the shape of the used insulators and the experimental conditions.
In the following, we recall the main principles of an analytical static model based on the electrical equivalent circuit and thermal discharge temperature we previously developed [1,13].

3. Principal of Circuit Model

Surface discharges are like spark (streamer/leader) discharges, i.e., a hot leader column and a streamers zone at its head [8,9,13,17]. Based on Figure 3, the voltage along the discharge can be written as follows:
Vd = Vl + Vs = xlEl + xsEs = xd rd I
where Vd, Vl and Vs are the voltages of the discharge, the leader channel and the streamers, respectively. xl, xs, El and Es are respectively the length and the electrical gradient of the leader channel and the streamers. xd, rd, and I are respectively the discharge length, the discharge resistance and the current.
The discharge resistance can be deduced from Equation (9):
r d = x l E l + x s E s x d I
where xd = xs + xl.
According to Equation (10), creeping discharge can be considered as a resistance and it can be assumed that the discharge channel is a uniform cylinder.
Many researchers published photos of surface discharges indicating that there are two regions: the main luminous discharge (leader + streamer head) and less luminous branches, as illustrated in Figure 4 and Figure 5 [10,18]. So, the presence of those less luminous discharges can be represented as a resistor in parallel to the insulator surface. On the other hand, several research investigations demonstrate the existence of a dark current in high-pressurized gases that contribute to increase the insulator conductivity [19]. These currents contribute to the appearance of the second region (called luminous plasma), as depicted in Figure 4 and Figure 5.

3.1. Parameters of the Circuit

The proposed model is constituted by an equivalent electrical circuit representing the electrical discharge, in series with the unbridged gap. The gap (the distance between the head of discharge and the opposite electrode) consists of a gas layer and of the solid dielectric at the interface (Figure 6). The gas layer is assumed to be equal to the diameter of the discharge channel. This model was developed elsewhere [13] in the case of air at atmospheric pressure and represents the instant when the discharge reaches a maximum length (called critical length) before the final jump [13]. In the following, the same approach [13] will be adopted with the assumption that the LI (lightning impulse) voltage waveform can be considered as a quart-cycle of sine signal with a frequency about 0.3 MHz.
The electrical Equation describing this circuit is:
V = R d ( x ) I + [ Z g ( x ) / / Z i ( x ) ] I
where,
Z g ( X ) = R g ( x ) / / C g ( x ) = R g ( x ) 1 + j ω R g ( x ) C g ( x ) = r g ( L x ) 1 + ( r g c g ω ) 2 j r g 2 c g ω ( L x ) 1 + ( r g c g ω ) 2 2 Z i ( X ) = R i ( x ) / / C i ( x ) = R i ( x ) 1 + j ω R i ( x ) C i ( x ) = r i ( L x ) 1 + ( r i c i ω ) 2 j r i 2 c i ω ( L x ) 1 + ( r i c i ω ) 2 2
and
R d ( x ) = r d x = x ρ d s d ;
C i ( X ) = c i L x = ε i s i L x ; C g ( X ) = c g L x = ε g s g L x ; R i ( x ) = r i ( L x ) = ρ i L x s i ; R g ( x ) = r g ( L x ) = ρ g L x s g
rd is the linear resistance of the discharge channel. ri, rg, ci, cg, εI, εg, ρi, and ρg, are respectively the linear resistance, capacitance, the permittivity and the resistivity, respectively of the solid insulator and the unbridged gap. sd is the cross-section of the discharge channel, si and sg are respectively the cross-sections of the solid insulator and the layer of the unbridged gap. ω is the pulsation (ω = 2πf, f being the frequency).
Then, the equivalent impedance of the system will be:
Z e q ( x ) = r d x + r g r i α g α i G 1 ( L x ) + j r g r i α g α i G 2 ( L x )
Let us put:
τ g = ρ g ε g ω = r g c g ω τ i = ρ i ε i ω = r i c i ω
Product τi2 >> 1 and τg2 >> 1, then:
{ α i τ i 2 α g τ g 2
The terms G1 and G2 are:
G 1 = z 1 z 3 + z 4 G 2 = z 2 z 3 + z 4
where,
{ z 1 = ( r g τ g 2 + r i τ i 2 ) ( 1 τ g τ i ) + ( r g τ g + r i τ i ) ( τ g + τ i ) z 2 = ( r g τ g + r i τ i ) ( 1 τ i ) ( r g τ g 2 r i τ i 2 ) ( τ g + τ i ) z 3 = ( r g τ g 2 + r i τ i 2 ) 2 z 4 = ( r g τ g + r i τ i ) 2
The square of the modulus of the equivalent impedance is:
| Z e q | 2 = γ x 2 + 2 L x [ r d ( r d r g r i τ g 2 τ i 2 G 1 ) γ ]
where,
γ = ( r d r g r i τ g 2 τ i 2 G 1 ) 2 + ( r g r i τ g 2 τ i 2 G 2 ) 2
According to Reference [20], when the discharge length increases, the equivalent impedance decreases:
d | Z e q | 2 d x 0
By differentiating Equation (18) with respect to x, we get:
d | Z e q | 2 d x = 2 γ x + 2 L [ r d ( r d r g r i τ g 2 τ i 2 G 1 ) γ ] 0
Then,
x L 1 [ r d γ τ g 2 τ i 2 ( r g r i G 1 τ g 2 τ i 2 r d ) ]
Flashover of the solid dielectric occurs when Equation (22) is equal to zero, i.e., when the discharge length is equal to the total creeping (leakage) distance. This Equation can be considered as “the flashover condition”. Therefore, the maximum (or critical) length of the discharge corresponding to flashover is:
x c r i = L γ α g α i [ γ τ g 2 τ i 2 r d ( r d τ g 2 τ i 2 G 1 ) ] = L n
where,
n = 1 γ τ g 2 τ i 2 [ γ τ g 2 τ i 2 r d ( r d r g r i G 1 ) ]
where 0 < n < 1.
The worst case can be derived from Equation (12), it corresponds to:
r d γ τ g 2 τ i 2 ( r g r i G 1 τ g 2 τ i 2 r d ) 0
The term r d γ τ g 2 τ i 2 is always positive, then:
r g r i G 1 τ g 2 τ i 2 r d
Equation (26) can be written as:
τ g 2 τ i 2 G 1 r d r g r i = K 1
where,
0 < K ≤ 1
or:
r d K G 1 r g r i τ g 2 τ i 2
Condition (28) indicates that the discharge propagates when the ratio K is less than or equal to 1. This corresponds to the propagation criterion in which the discharge length is sufficient for causing the final jump, provoking flashover [13].
On the other hand, the power loss per unit length pd in the discharge channel is:
p d = r d I 2
By combining Equations (30) and (26), it yields:
I = p d r d
The square of the modulus of the voltage—Equation (11) is:
| V | 2 = | I | 2 | Z e q | 2
By substituting Equations (23), (24) and (30) in Equation (18), it yields:
| Z e q | 2 = β L 2 ( r g r i τ g 2 τ i 2 ) 2
with:
β = K 2 G 1 2 n 2 + ( G 1 2 + G 2 2 ) ( 1 n ) 2 + 2 K 2 G 1 n ( 1 n )
By substituting Equations (31) and (33) in Equation (32), the Equation of flashover voltage will be deduced as:
V F O V = L τ g τ i p d r g r i r d β .

3.2. Thermal Conductivity and Discharge Resistance

According to the solution proposed by Frank-Kamenetski [21,22], the energy dissipated by thermal conduction within the discharge channel is:
P d = 16 π λ d K B W i T 2
By combining Equations (36) and (30), the final Equation of flashover voltage will be:
V F O V = 4 L τ g τ i T π K B W i λ d r g r i r d β
In the case of air at atmospheric pressure, the thermal conductivity is calculated according to the following Equation [23]:
λ ( θ ) = λ a 1 + A a ( 1 v a ) v a
where λa, va and Aa are the thermal conductivity, volume fraction and kinetic gas coefficient for air, respectively.
Also, the discharge resistance in air at atmospheric pressure is given by [24]:
r d ( T ) = r 0 d exp ( W i 2 K B T ) .
where r0d is a constant in the range of operating temperatures of the discharge. Wi represents the first ionization energy of the different species constituting the discharge channel and KB is the Boltzmann constant.
In the case of SF6, both discharge resistance and discharge thermal conductivity are functions simultaneously of gas pressure and plasma temperature [25,26].
λ d = Γ ( T , p ) σ d = Σ ( T , p )
According to Pinnekamp and Niemeyer [27], and Niemeyer et al. [28], the temperature of the leader discharge is between 2400 K and 2800 K. On the other hand, based on the transport parameters data of SF6 published in the literature [25,26], the thermal conductivity was plotted as a function of gas pressure (Figure 7) and the discharge resistance against gas pressure (Figure 8) for a range of temperatures between 2500 K and 3500 K. From these figures, numerical empirical formulae of the discharge thermal conductivity and discharge resistance against pressure for a given temperature was deduced:
σd = A.p−m
λd = a0 + …+anpn
where p is the gas pressure and a and A are empirical parameters.

4. Application

To validate the proposed model, first the model was applied for the calculation of the flashover voltage of cylindrical epoxy insulators in air at atmospheric pressure. The second application will be for the same kind of insulator in SF6 gas medium. The computed flashover voltages are compared with the experimental data reported by other researchers, as in References [12,13,15,29]. Table 1 gives the characteristics of the used insulator in the computations.
The lightning impulse voltage frequency is calculated based on the following Equation [30]:
f = 0.35 / TR
TR is the rising time of the voltage front equal to 1.2 µs.

4.1. Air at Normal Atmospheric Conditions

Figure 9 illustrates the results of the application of the proposed model in air at atmospheric pressure. The model is compared with the experimental data of Reference [13], a previous model developed earlier [1] and Toepler’s model. The temperature of discharge was taken between 1800 K and 2000 K, which corresponds to a leader phase on the insulator surface [13]. The resistance of air ranges from 1023 to 1025 Ω/cm, its dielectric constant being equal to 1. The effect of humidity and roughness are neglected.
By comparing flashover voltage given by Equation (36) and the other models, we can remark that the computed values are close to the measured ones and follow the same trend. According to this result, we can deduced that the impedance of the interface between the head of the discharge and the opposite electrode plays affects the result (Figure 9). It contributes to the breakdown process before the final jump of the discharge (flashover), as described in Reference [12]. The maximum deviation is 18.2% and the average deviation is less than 5%.

4.2. SF6 at Variable Pressure

In the case of SF6, we use Equations (41) and (42), to compute the flashover voltage and its dependency on the gas pressure and temperature. The temperature of the discharge was taken between 2500 K and 3500 K.
A specific consideration for the resistance of the gas at the interface is required in the case of pressurised SF6. In fact, experimental results concerning flashover of solid insulators on pressurised gases suggest that the discharge tends to stick to the insulator surface when the gas pressure increases [8,12]. On the other hand, according to Figure 4 and Figure 5, the gap between the discharge’s head and the ground electrode appears like an ionized cylinder. Knowing that the attachment of the pressurised gas also increases with pressure, it can be deduced that the resistance of the interface between the discharge head and the grounding electrode depends on the gas pressure as well.
Based on the data reported in the literature [25,26], the resistance of the interface can be represented as a cylindrical plasma with a temperature between 1000 K and 1500 K. In this range of temperature, the plasma resistivity increases with the gas pressure, as depicted in Figure 10. As can be observed in this figure, the assumption of a plasma with a temperature varying between 1200 K and 1400 K is a good approximation, since the resistivity is increasing with pressure for all temperatures. The dielectric constant being equal to 1 and the effects of surface charge accumulation and humidity are not considered.
Figure 11 illustrates the comparison of the calculated flashover voltage with the data of Slama et al. [12] for insulator 2 of Table 1. It can be observed that the calculated flashover voltages are close to the measured values, indicating that flashover voltage tends to be stable with the pressure increase. The maximum deviation is 8.2% and the average deviation is around 4.5%.
A comparison of the calculated flashover voltage with the data of Reference [29] obtained with insulator 3, is depicted in Figure 12. In this work, Moukengué and Feser [29] present results of flashover voltages as a function of gas pressure for different tests: one for a single impulse shot and the second for five impulse shots. It is noted that the calculated flashover voltages are close to the experimental measured values. The maximum deviation is 8.2% and the average deviation is around 6.5%.
Figure 13 shows the comparison of the results using the developed model and the data of Reference [15] with insulator 4. Again, it is observed that the calculated flashover voltages are close to the experimental ones and the maximum deviation is 10% and the average deviation is less than 4%.

5. Conclusions

In this paper, a model was developed for surface discharges and flashover voltage in air at atmospheric pressure and compressed SF6. The proposed analytical model is based on the equivalent electrical circuit representing the discharge along the insulator surface and the thermal properties of the discharge by assuming that the area between the discharge head and the ground electrode as a cylindrical plasma.
The proposed model was first applied for air at atmospheric pressure to validate it against existing models and data. It was noticed that the simulated results are very close to the experimental ones. Thus, the impedance of the interface between the head of the discharge and the opposite electrode significantly affects the result. It contributes to the breakdown process before the final jump of the final discharge that is flashover. In the case of SF6, the application of this model to various configurations taken from the literature shows that the computed flashover voltage magnitudes are close to the measured values and exhibit similar trends.
The proposed model constitutes a first step for developing a tool for flashover prediction in ambient air and for the design of the solid insulation in GIS and GIL filled with SF6.

Author Contributions

Conceptualization, M.E.A.S., A.B. and A.M.H.; methodology, M.E.A.S., A.B. and A.M.H.; validation, M.E.A.S., A.B. and A.M.H.; formal analysis, M.E.A.S., A.B. and A.M.H.; investigation, M.E.A.S.; writing—original draft preparation, M.E.A.S.; writing—review and editing, M.E.A.S., A.B. and A.M.H.; visualization, M.E.A.S., A.B. and A.M.H. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Acknowledgments

The authors would like to thank Sylvain Nichele, Alain Girodet and Paul Vinson from SuperGrid Institute (France) for their help.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Slama, M.E.A.; Beroual, A.; Girodet, A.; Vinson, P. Characterization and Mathematical Modelling of Surface Solid Insulator in Air. In Proceedings of the International Symposium on High Voltage Engineering, Plzen, Czech Republic, 24–28 August 2015. [Google Scholar]
  2. Al-Arainy, A.B.; Malik, N. Experiments in High Voltage Engineering King, Saud University; Academic Publishing and Press: Riyadh, Saudi Arabia, 2014. [Google Scholar]
  3. Beroual, A. Creeping Discharges at Liquid/solid and Gas/Solid Interfaces: Analogies and Involving Mechanisms. In Proceedings of the IEEE 20th International Conference on Dielectric Liquids (ICDL), Roma, Italy, 23–27 June 2019. [Google Scholar]
  4. Toepler, M. Über die physikalischen Grundgesetze der in der Isolatorentechnik auftretenden elektrischen Gleiterscheinungen. Archiv Elektrotechnik 1921, 10, 157–185. [Google Scholar] [CrossRef]
  5. Cookson, A.H. Review of high-voltage gas breakdown and insulators in compressed gas. IET 1981, 128, 303–312. [Google Scholar] [CrossRef]
  6. Sudarshan, T.S.; Dougal, R. Mechanisms of surface flashover along solid dielectrics in compressed gases: A Review. IEEE Trans. Electr. Insul. 1986, 21, 727–746. [Google Scholar] [CrossRef]
  7. Hayakawa, N.; Ishida, Y.; Nishiguchi, H.; Hikita, M.; Okubo, H. Mechanism of impulse creepage discharge propagation on charged dielectric surface in SF6 gas. IEEJ Trans. Power Energy 1996, 116-B, 600–606. [Google Scholar] [CrossRef] [Green Version]
  8. Okubo, H.; Kanegami, M.; Hikita, M.; Kito, Y. Creepage Discharge Propagation in Air and SF6 Gas Influenced by Surface Charge on Solid Dielectrics. IEEE Trans. Dielectr. Electr. Insul. 2004, 1, 204–304. [Google Scholar]
  9. Tenbohlen, S.; Schröder, G. Discharge Development over Surfaces in SF6. IEEE Trans. Dielectr. Electr. Insul. 2000, 7, 241–246. [Google Scholar] [CrossRef]
  10. Beroual, A.; Coulibaly, M.-L.; Aitken, O.; Girodet, A. Investigation on creeping discharges propagating over epoxy resin and glass insulators in presence of different gases and mixtures. Eur. Phys. J. Appl. Phys. 2011, 56, 30802–30809. [Google Scholar] [CrossRef] [Green Version]
  11. Beroual, A.; Coulibaly, M.-L.; Aitken, O.; Girodet, A. Effect of micro-fillers in PTFE insulators on the characteristics of surface discharges in presence of SF6, CO2 and SF6 –CO2 mixture. IET Gener. Transm. Distrib. 2012, 6, 951–957. [Google Scholar] [CrossRef]
  12. Slama, M.E.A.; Beroual, A.; Girodet, A.; Vinson, P. Barrier effect on Surface Breakdown of Epoxy Solid Dielectric in SF6 with Various Pressures. In Proceedings of the Conference on Electrical Insulation and Dielectrics Phenomena, Toronto, ON, Canada, 23 October 2016. CEIDP 2016. [Google Scholar]
  13. Slama, M.E.A.; Beroual, A.; Girodet, A.; Vinson, P. Creeping Discharge and Flashover of Solid Dielectric in Air at Atmospheric Pressure: Experiment and Modelling. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 2949–2956. [Google Scholar] [CrossRef] [Green Version]
  14. Douar, M.A.; Beroual, A.; Souche, X. Creeping discharges features propagating in air at atmospheric pressure on various materials under positive lightning impulse voltage—Part 2: Modelling and computation of discharges’ parameters. IET Gener. Transm. Distrib. 2018, 6, 1429–1437. [Google Scholar] [CrossRef]
  15. Laghari, R. Spacer Flashover in Compressed Gases. IEEE Trans. Electr. Insul. 1985, EI-20, 83–92. [Google Scholar] [CrossRef]
  16. Hama, H.; Inami, K.; Yoshimura, M.; Nakanishi, K. Estimation of Breakdown Voltage of Surface Flashover Initiated from Triple Junction in SF6 Gas. IEEJ 1996, 116. [Google Scholar] [CrossRef]
  17. Waters, R.T.; Haddad, A.; Griffiths, H.; Harid, N.; Sarkar, P. Partial-arc and Spark Models of the Flashover of Lightly Polluted Insulators. IEEE Trans. Dielectr. Electr. Insul. 2010, 17, 417–424. [Google Scholar] [CrossRef]
  18. Kessler, J.E.M. Isoliervermögen Hybrider Isoliersysteme in Gasisolierten Metallgekapselten Schaltanlagen (GIS). Ph.D. Thesis, Technische Universität München, Munich, Germany, 2011. [Google Scholar]
  19. Zavattoni, L. Conduction phenomena through gas and insulating solids in HVDC GIS, and consequences on electric field distribution. Ph.D. Thesis, University of Grenoble, Grenoble, France, 2014. [Google Scholar]
  20. Dhahbi-Megriche, N.; Beroual, A.; Krähenbühl, L. A New Proposal Model for Polluted Insulators Flashover. J. Phys. D Appl. Phys. 1997, 30, 889–894. [Google Scholar] [CrossRef]
  21. Fridman, A.; Nester, S.; Kennedy, L.A.; Saveliev, A.; Mutaf-Yardimci, O. Gliding arc discharge. Prog. Energy Combust. Sci. 1999, 25, 211–231. [Google Scholar] [CrossRef]
  22. Fridman, A. Plasma Chemistry; Cambridge University Press: Cambridge, UK, 2008. [Google Scholar]
  23. McElhannon, W.; McLaughlim, E. Thermal Conductivity of Simple Dense Fluid Mixtures. In Proceedings of the Fourteenth International Conference on Thermal Conductivity, Storrs, CT, USA, 2–4 June 1975; Klemens, P.G., Clen, T.K., Eds.; [Google Scholar]
  24. Slama, M.E.A.; Beroual, A.; Hadi, H. Analytical Computation of Discharge Characteristic Constants and Critical Parameters of Flashover of Polluted Insulators. IEEE Trans. Dielectr. Electr. Insul. 2010, 17, 1764–1771. [Google Scholar] [CrossRef]
  25. Zhong, L.; Rong, M.; Wang, X.; Wu, J.; Han, G.; Lu, Y.; Yang, A.; Wu, Y. Compositions, thermodynamic properties, and transport coefficients of high temperature C5F10O mixed with CO2 and O2 as substitutes for SF6 to reduce global warming potential. AIP Adv. 2017, 7, 075003. [Google Scholar] [CrossRef] [Green Version]
  26. Assael, M.J.; Koini, I.A.; Antoniadis, K.D.; Huber, M.L.; Abdulagatov, I.M.; Perkins, R.A. Reference Correlation of the Thermal Conductivity of Sulfur Hexafluoride from the Triple Point to 1000 K and up to 150 MPa. J. Phys. Chem. Ref. Data 2012, 41, 023104. [Google Scholar] [CrossRef] [Green Version]
  27. Niemeyer, L.; Pinnekamp, F. Leader discharges in SF6. J. Phys. D: Appl. Phys. 1983, 16, 1031–1045. [Google Scholar] [CrossRef]
  28. Wiegart, N.; Niemeyer, L.; Pinnekamp, F.; Boeck, W.; Kindersberger, J.; Morrow, R.; Zaengl, W.; Zwicky, I.; Gallimberti, M.; Boggs, S.A. Inhomogeneous Field Breakdown in GIS—The Prediction of Breakdown Probabilities and Voltages: Parts I, II, and III. IEEE Trans. Power Deliv. 1988, 3, 923–946. [Google Scholar] [CrossRef]
  29. Moukengué lmano, A.; Feser, K. Flashover behavior of conducting particle on the spacer surface in compressed N2, 90%N2+10%SF6 and SF6 under lightning impulse stress. In Proceedings of the International Symposium on Electrical Insulation (ISEI 2000), Anaheim, CA, USA, 2–5 April 2000. [Google Scholar]
  30. Ianovici et, M.; Morf, J.-J. Compatibilité Électromagnétique; Presses Polytechniques et Universitaires Romandes: Lausanne, Suisse, 1979. [Google Scholar]
Figure 1. Instantaneous current and voltage during flashover at the surface of cylindrical epoxy insulator according to Reference [9].
Figure 1. Instantaneous current and voltage during flashover at the surface of cylindrical epoxy insulator according to Reference [9].
Energies 13 00591 g001
Figure 2. Steps of creeping discharges according to Reference [2].
Figure 2. Steps of creeping discharges according to Reference [2].
Energies 13 00591 g002
Figure 3. Illustration of leader column and streamers head of a discharge at the surface of an insulator.
Figure 3. Illustration of leader column and streamers head of a discharge at the surface of an insulator.
Energies 13 00591 g003
Figure 4. Surface discharge at the surface of insulator in SF6 with 3 bars under LI+ according to Reference [10].
Figure 4. Surface discharge at the surface of insulator in SF6 with 3 bars under LI+ according to Reference [10].
Energies 13 00591 g004
Figure 5. Surface discharge at the surface of a coated electrode in SF6 with 1 bar under LI+ according to Reference [18].
Figure 5. Surface discharge at the surface of a coated electrode in SF6 with 1 bar under LI+ according to Reference [18].
Energies 13 00591 g005
Figure 6. Insulator cylindrical model with a discharge channel and the corresponding equivalent electrical circuit.
Figure 6. Insulator cylindrical model with a discharge channel and the corresponding equivalent electrical circuit.
Energies 13 00591 g006
Figure 7. Discharge thermal conductance of discharge versus variation with pressure with for different temperatures.
Figure 7. Discharge thermal conductance of discharge versus variation with pressure with for different temperatures.
Energies 13 00591 g007
Figure 8. Discharge resistance variation versus pressure with different temperatures at 2500 and 3000 K, respectively.
Figure 8. Discharge resistance variation versus pressure with different temperatures at 2500 and 3000 K, respectively.
Energies 13 00591 g008
Figure 9. Comparison between calculated and measured flashover voltage versus creepage distance in air at atmospheric pressure for insulator 1.
Figure 9. Comparison between calculated and measured flashover voltage versus creepage distance in air at atmospheric pressure for insulator 1.
Energies 13 00591 g009
Figure 10. Resistivity of the SF6 plasma at non-thermal regime versus gas pressure et different temperatures.
Figure 10. Resistivity of the SF6 plasma at non-thermal regime versus gas pressure et different temperatures.
Energies 13 00591 g010
Figure 11. Comparison between calculated and measured flashover voltage versus gas pressure for insulator 2 with 60 mm length and 25 mm diameter.
Figure 11. Comparison between calculated and measured flashover voltage versus gas pressure for insulator 2 with 60 mm length and 25 mm diameter.
Energies 13 00591 g011
Figure 12. Comparison between calculated and measured flashover voltage versus gas pressure for a cylindrical epoxy insulator 4 with 45 mm length and 25 mm diameter.
Figure 12. Comparison between calculated and measured flashover voltage versus gas pressure for a cylindrical epoxy insulator 4 with 45 mm length and 25 mm diameter.
Energies 13 00591 g012
Figure 13. Comparison between calculated and measured flashover voltage versus gas pressure for a cylindrical epoxy insulator with 10 mm length and 30 mm diameter.
Figure 13. Comparison between calculated and measured flashover voltage versus gas pressure for a cylindrical epoxy insulator with 10 mm length and 30 mm diameter.
Energies 13 00591 g013
Table 1. Characteristics of used insulators from literature used in modelling.
Table 1. Characteristics of used insulators from literature used in modelling.
InsulatorMaterialDiameterLength Reference GasPressure
1Epoxy2560[13]AirAtmospheric
2Epoxy2560[12]SF6Variable
3Epoxy2545[29]SF6Variable
4Epoxy3010[15]SF6Variable

Share and Cite

MDPI and ACS Style

Slama, M.E.A.; Beroual, A.; Haddad, A. Surface Discharges and Flashover Modelling of Solid Insulators in Gases. Energies 2020, 13, 591. https://doi.org/10.3390/en13030591

AMA Style

Slama MEA, Beroual A, Haddad A. Surface Discharges and Flashover Modelling of Solid Insulators in Gases. Energies. 2020; 13(3):591. https://doi.org/10.3390/en13030591

Chicago/Turabian Style

Slama, Mohammed El Amine, Abderrahmane Beroual, and Abderrahmane (Manu) Haddad. 2020. "Surface Discharges and Flashover Modelling of Solid Insulators in Gases" Energies 13, no. 3: 591. https://doi.org/10.3390/en13030591

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop