Next Article in Journal
Electrical Damping Assessment and Stability Considerations for a Highly Electrified Liquefied Natural Gas Plant
Next Article in Special Issue
Increasing the Sensitivity of the Method of Early Detection of Cyber-Attacks in Telecommunication Networks Based on Traffic Analysis by Extreme Filtering
Previous Article in Journal
Frequency-Domain Nonlinear Modeling Approaches for Power Systems Components—A Comparison
Previous Article in Special Issue
Global Harmonic Parameters for Estimation of Power Quality Indices: An Approach for PMUs
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

A Study on Application of Recloser Operation Algorithm for Mixed Transmission System Based on Travelling Wave Method

1
Department of Electrical and Computer Engineering, Sungkyunkwan University, Suwon 16419, Korea
2
Korea Railroad Research Institute, Uiwang 16105, Korea
*
Author to whom correspondence should be addressed.
Energies 2020, 13(10), 2610; https://doi.org/10.3390/en13102610
Submission received: 14 April 2020 / Revised: 15 May 2020 / Accepted: 17 May 2020 / Published: 20 May 2020

Abstract

:
Recently, the operation of a mixed transmission system has increased due to rapid urbanization and the purpose of a good view. Therefore, a proper protection scheme for a mixed transmission system is required. Generally, when a fault occurs on a transmission line, auto reclosing is performed for the purpose of improving the continuity of service by clearing the fault and restoring the power system. However, the auto reclosing scheme should be applied to a mixed transmission system carefully because the mixed transmission system involves underground cable sections. When a fault occurs in the underground cable section, it is mostly a permanent fault. If auto reclosing is performed on a permanent fault condition, it may cause excessive overcurrent and switching surge, which can generate a serious impact on the whole transmission system and even cause an explosion. Due to this, many utilities worldwide do not allow auto reclosing or only apply it very restrictively on a mixed transmission system based on their practice. However, there is no clear guidance or standard related to auto reclosing on a mixed transmission system. Therefore, in this paper, an application of a recloser operation algorithm is proposed. Based on the proposed algorithm, reclosers can work properly and protect the transmission system. To verify the proposed algorithm, simulations were conducted using the ElectroMagnetic Transient Program (EMTP).

1. Introduction

These days, due to rapid urbanization, there has been an increase in the requirement for a good view and efficient use of space and as a result, the application of underground cables is increasing. Additionally, as DC systems are widely used, this requires the need for the application of underground cables. As a result, a mixed power system that consists of an overhead line section and underground cable section is in wide operation. Therefore, as the portion of underground cable becomes larger in the whole power system, the need for a proper protection scheme to protect the mixed power system has also increased.
In the auto reclosing procedure, circuit breakers open to isolate the fault from the main system and close to restore the system, according to the command of the protective relay. In this way, auto reclosing can improve the continuity of service when a transient fault occurs on the power system. For this reason, many utilities have adopted an auto reclosing scheme and operate a recloser in their power system [1,2,3].
However, in a mixed transmission system, to adopt an auto reclosing scheme, there are some considerations regarding the characteristics of underground cables. In underground cables, faults are mostly permanent in nature, so there are many risks associated with auto reclosing. If auto reclosing is performed on a permanent fault, switching surges and overcurrent are generated across the whole system. These phenomena may affect power equipment such as generator, transformer, cable, etc., in particular, if a cable is exposed to this kind of phenomena, the cable insulation can be broken down and can even generate explosions, according to the type of cable. Therefore, to operate a recloser in a mixed transmission system, a proper operation algorithm is required with special considerations. It must include a special protection scheme to discriminate between faults in the overhead line section versus the underground cable section. In fact, in some documents, it is mentioned that an auto reclosing scheme on a mixed transmission system should consider the fault location whether the fault is on an overhead line section or underground cable section [4,5,6,7,8]. However, many utilities operate reclosers according to their practice, which may not consider this kind of factor [9,10,11,12].
To detect and locate the fault in the transmission system, many studies have been conducted. To detect and locate faults, generally, the impedance-based method or travelling wave-based method are used [13,14]. Among these methods, the travelling wave-based method consists of the single ended method and double ended method [15]. While the single ended method observes and uses information from only one terminal of the line, the double ended method uses information from both terminals of the line. So, in case of the double ended method, the synchronism problem is important and has to be considered [16,17]. In [18], Lee proposed a fault locator based travelling wave using a global positioning system (GPS). Additionally, in [19], Naidu proposed a selective auto-reclosing scheme for a multi-terminal mixed system using synchrophasor measurements. To provide synchronized measurements, a synchrophasor based on GPS was used. In [20], Hong proposed a fault location method using pattern analysis based travelling wave theory and signal processing. In [21], Han and Crossley proposed a hybrid method that consisted of the impedance method and travelling wave method. The multiple zone quadrilateral impedance relay model and double ended travelling wave fault locator were used to calculate the fault location precisely and the hybrid method was verified using the PSCAD/EMTDC (Power System Computer Aided Design/Electromagnetic Transients program including DC) simulator by J. Han in [21].
By Lin, Abur and Hamidi, in [22,23,24], various research related to fault location in a general transmission system based on the travelling wave method was conducted. Lin, in [22], proposed a single ended travelling wave method based on the Lipschitz exponent. In that study, to obtain the Lipschitz exponent of the second transient wave-front signal, wavelet transform and the least square method were used. Furthermore, by Abur and Hamidi, in [23,24], wavelet transform, which applies a different mother wavelet, was utilized to calculate the fault location. However, in these studies, different signal processing methods were applied to detect and locate the fault, so time to process the signal is required. It can also cause an inefficiency when the recloser operates on a mixed transmission line. By Lin, in [25], to improve the fault location accuracy of the travelling wave method, the universal wavefront positioning correction method was proposed. By Mardiana, in [26], a travelling wave related to high frequency transient voltage was introduced to calculate the fault location for the ground fault. By Lopes, in [27], an innovative fault location method based on two terminal travelling waves was proposed where only the fault location formulation was utilized to calculate the fault location instead of applying the signal processing method. Han, in [28], introduced the empirical mode decomposition (EMD) concept to a single-pole adaptive reclosure. EMD is a one type of data analysis method and its concept is to decompose the signal into a set of functions.
Although research related to fault detection and location have matured deeply, the application of these methods to the practical operation of a power device has not been developed sufficiently. In other words, for a practical recloser operation, research related to a simpler method that is easy to adjust on the recloser should be considered.
In this paper, we propose a novel recloser operation algorithm that considers the faulted section on a mixed transmission system by using travelling wave theory. The proposed algorithm includes functions such as fault detection, fault location, and transferring the reclosing signal to provide a proper reclosing procedure on a mixed transmission system. In Section 2, conventional recloser operation principles and preceding research related to fault detection/location method in mixed transmission system are introduced. In Section 3, the principle of the proposed algorithm based on travelling wave theory and the concept of the proposed algorithm are introduced. In Section 4, to verify the proposed algorithm, the simulation results are presented. Finally, in Section 5, we present our conclusions.

2. Conventional Recloser Operation Principles

A mixed transmission system consists of overhead lines and underground cables. As referred to in the Introduction, when a fault occurs on a mixed transmission system, an auto reclosing scheme has to be applied carefully by considering which section is at fault (overhead line or underground cable). Therefore, the utilities in many countries operate a recloser, according to their own operation principle, but is based on practice. For this reason, there are no specific standards or guidelines for applying an auto reclosing scheme in a mixed transmission system. In Table 1, the auto reclosing principles adopted by the utilities in some countries are presented, and shows that each auto reclosing principle is different to each other because it follows the practice of each individual utility.
As shown in Table 1, the recloser operation principles of many utilities are different from each other, and confirms that there are no specific standards or guidelines for performing reclosing behavior on a mixed transmission system. It is common that auto reclosing is allowed only for overhead line faults, but for underground cable faults, auto reclosing is generally prohibited, except for cases in which the length of the underground cable section is relatively shorter than the overhead line section.

3. Proposed Recloser Operation Algorithm for Mixed Transmission System

In this paper, the proposed algorithm provides a proper recloser operation for a fault that considers whether the faulted section is an overhead line or underground cable on a mixed transmission system when using the travelling wave of voltage. As shown in Figure 1, there are three types of mixed transmission systems. In Figure 1a, the first configuration is Case 1, which consists of an overhead line section and underground cable section, assumed as “OL + UC (Overhead Line + Underground Cable)”. The second configuration (Figure 1b) is Case 2, which consists of three sections located in a row, assumed as “OL + UC + OL (Overhead Line + Underground Cable + Overhead Line)”. The last configuration (Figure 1c) is Case 3, which consists of an underground cable, overhead line, and underground cable, assumed as “UC + OL + UC (Underground Cable + Overhead Line + Underground Cable)”. In each case, Tref including Tref1, Tref2 is the reference value to distinguish the faulted section on the mixed transmission system. T r e f can be calculated and set by the utility based on the characteristics of the target system. The essential characteristics of the system are line length and velocity of travelling wave in each section.
T r e f can be calculated using Equation (1) and can be considered as the required time that the travelling wave propagates on the whole section (overhead line or underground cable). Therefore, T r e f can be preset by the utilities because they know the line length and the velocity of the travelling wave in their system, depending on the characteristics of the conductor.
T r e f = L / v
where T r e f is a reference value to distinguish the faulted section; L is the length of overhead line or underground cable; and v is the propagation velocity of the travelling wave on the overhead line or underground cable depending on characteristic of conductor.
T s a m p l e , presented in Figure 1, is the arrival time that the travelling wave propagates from the fault point to the measuring point, which is the sending end. If the fault occurs on a mixed transmission system, then the travelling wave propagates and reaches at the measuring point. Then, the voltage of the measuring point will fluctuate. Assume the time when this voltage fluctuation occurs as T s a m p l e . Using T s a m p l e , the proposed algorithm calculates the difference between the fault occurring time and T s a m p l e . Assume this difference as T . Next, the proposed algorithm compares the T with T r e f , so it can finally distinguish the faulted section according to the condition of the mixed transmission system.
The detailed conditions for each configuration of a mixed transmission system to distinguish the faulted section are mentioned in the following sub-sections.

3.1. Configuration: (OL + UC)

Considering configuration (a) in Figure 1, if a fault occurs on an overhead line section, T , which is measured at the end of the line is smaller than T r e f . In contrast, if the fault occurs on an underground cable section, T is larger than T r e f . This relation is presented as follows:
T r e f = L 1 / v 1
where T r e f is a reference value that the travelling wave propagates on an overhead line; L 1 is the length of the overhead line; and v 1 is the propagation velocity of the travelling wave on the overhead line.
Then,
T T r e f :   Overhead   line   fault
T > T r e f :   Underground   cable   fault

3.2. Configuration: (OL + UC + OL)

Considering configuration (b) in Figure 1, if a fault occurs on the overhead line section, T is smaller than T r e f 1 or larger than T r e f 2 . In contrast, if a fault occurs on the underground cable section, T is larger than T r e f 1 and smaller than T r e f 2 . This relation is presented as follows:
T r e f 1 = L 1 / v 1 ,   T r e f 2 = T r e f 1 + L 2 / v 2
where T r e f 1 is a reference value that the travelling wave propagates on an overhead line located in front of the underground cable; T r e f 2 is a reference value that the travelling wave propagates on the overhead line and underground cable; L 1 is the length of the overhead line located in front of the underground cable; v 1 is the propagation velocity of the travelling wave on the overhead line located in front of the underground cable; L 2 is the length of underground cable; and v 2 is the propagation velocity of the travelling wave on the underground cable.
Then,
T T r e f 1   o r   T T r e f 2 :   Overhead   line   fault
T r e f 1 < T < T r e f 2 :   Underground   cable   fault

3.3. Configuration: (UC + OL + UC)

Considering configuration (c) in Figure 1, if a fault occurs on the overhead line section, T is larger than T r e f 1 and smaller than T r e f 2 . In contrast, if a fault occurs on the underground cable section, T is smaller than T r e f 1 or larger than T r e f 2 . This relation is presented as follows:
T r e f 1 = L 1 / v 1 ,   T r e f 2 = T r e f 1 + L 2 / v 2
where T r e f 1 is a reference value that the travelling wave propagates on the underground cable located in front of the overhead line; T r e f 2 is a reference value that the travelling wave propagates on the underground cable and overhead line; L 1 is the length of the underground cable located in front of the overhead line; v 1 is the propagation velocity of the travelling wave on the underground cable located in front of overhead line; L 2 is the length of the overhead line; and v 2 is the propagation velocity of travelling wave on overhead line.
Then,
T r e f 1 < T < T r e f 2 :   Overhead   line   fault
T T r e f 1   o r   T T r e f 2 :   Underground   cable   fault
Based on these conditions, the proposed algorithm can distinguish the faulted section on a mixed transmission system. Figure 2 presents the flow chart of the proposed algorithm. In this algorithm, “OC” represents the (OL + UC) configuration, “OCO” represents the (OL + UC + OL) configuration, and “COC” represents the (UC + OL + UC) configuration, respectively. Additionally, to detect fault occurrence and voltage fluctuation, V is used. When the travelling wave due to the fault arrives at the measuring point, voltage fluctuation, which exceeds the range of voltage variation in the steady state, is caused. Based on the result of the comparison between the fault occurrence time and voltage fluctuation time, the proposed algorithm distinguishes the faulted section and provides a proper reclosing signal for the recloser.

4. Simulation and Verification

4.1. Simulation Conditions

To verify the proposed algorithm, three types of AC 154 kV mixed transmission systems were modeled as shown from Figure 3, Figure 4 and Figure 5. Each system represents three configurations: (OL + UC), (OL + UC + OL), and (UC + OL + UC), respectively. In each case, the total length of overhead line was 10 km and the underground cable was 2.4 km. In addition, the actual conductor data of ACSR 410 mm2 and XLPE 2000 mm2 were used to represent the overhead line and underground cable section, respectively. Both sections were modeled by the Bergeron model of ATP because of the necessity of the consideration related high frequency phenomena. For the underground cable section, crossbonding was applied every 400 m. With a sampling frequency equal to 30.72 kHz (512 samples/cycle), bus voltage at the sending end was observed. Table 2 shows the simulation conditions. Additionally, according to the characteristics of the used conductors, the propagation velocity of the travelling wave on the overhead line was calculated as 2.8 × 108 m/s, and as 1.68 × 108 m/s for the underground cable. Based on these data, the reference values T r e f , T r e f 1 , T r e f 2 were preset as shown in Table 3.
As shown in Figure 3, in the case of the (OL + UC) configuration, a 10 km overhead line was placed in front of the underground cable. In this case, only T r e f exists. Using the propagation velocity of the travelling wave on the overhead line which equals to 2.8 × 108 m/s, the reference value T r e f can be calculated as follows:
T r e f = 10   k m / ( 2.8 × 10 8   m / s ) = 35.71   μ s
According to Equations (3) and (4), when the fault occurs, if the measured T is smaller than 35.71 μs, therefore, the faulted section is the overhead line.
The detailed conditions for each configuration of the mixed transmission system to distinguish the faulted section are mentioned in the following sub-sections.
As shown in Figure 4, in the case of the (OL + UC + OL) configuration, 2.4 km of underground cable section was placed between two overhead line sections with a length of 5 km. In this case, two reference values ( T r e f 1 , T r e f 2 ) are required because there are two transition points that connect the overhead line and underground cable. Therefore, T r e f 1 and T r e f 2 can be calculated as follows:
T r e f 1 = 5   k m / ( 2.8 × 10 8   m / s ) = 17.9   μ s
T r e f 2 = T r e f 1 + 2.4   k m / ( 1.68 × 10 8   m / s ) = 32.19   μ s
According to Equations (6) and (7), when the fault occurs, if the measured T is smaller than 17.9 μs or larger than 32.19 μs, the faulted section is the overhead line.
As shown in Figure 5, in the case of the (UC + OL + UC) configuration, 10 km of the overhead line section was placed between two underground cable sections with lengths of 1.2 km. In this case, two reference values ( T r e f 1 , T r e f 2 ) are also required. In this case, T r e f 1 and T r e f 2 can be calculated as follows:
T r e f 1 = 1.2   k m / ( 1.68 × 10 8   m / s ) = 7.1   μ s
T r e f 2 = T r e f 1 + 10   k m / ( 2.8 × 10 8   m / s ) = 42.81   μ s
According to Equations (9) and (10), when the fault occurs, if the measured T is larger than 7.1 μs and smaller than 42.81 μs, then the faulted section is the overhead line.

4.2. Simulation Results and Verification

For the above three configurations of a mixed transmission system, various fault points were applied along the whole mixed system. After a fault occurrence, the measured T of each case were as presented in Table 4, Table 5 and Table 6. Furthermore, based on T , the results of the recloser operation are also shown in Table 4, Table 5 and Table 6.
In the case of the (OL + UC) configuration, T r e f equaled 35.71 μs, as shown in Table 3. When a fault occurred on an overhead line section, the measured T was smaller than 35.71 μs in all cases. As a result, the recloser received an auto reclosing signal and then conducted a reclosing procedure according to the proposed algorithm. In the case of the (OL + UC + OL) configuration, T r e f 1 and T r e f 2 were equal to 17.9 μs and 32.19 μs, respectively. When a fault occurred on the overhead line section, the measured T shown in Table 5 was smaller than 17.9 μs or larger than 32.19 μs. Only for these cases was the auto reclosing signal transferred to the recloser. In the case of the (UC + OL + UC) configuration, T r e f 1 and T r e f 2 were equal to 7.1 μs and 42.81 μs, respectively. When a fault occurred on the overhead line section, the measured T shown in Table 6 was larger than 7.1 μs and smaller than 42.81 μs. Auto reclosing was allowed only for this T range and the results shown in Table 6 verified this. As shown in Table 4, Table 5 and Table 6, the proposed algorithm operated the recloser successfully for various conditions. In other words, the proposed algorithm could distinguish the faulted section on a mixed transmission system and operated the recloser only for the overhead line fault in all cases. To support clear understanding about the results, voltage waveform of an example case and detailed code of the proposed algorithm are presented in Appendix A and Appendix B, respectively.

4.3. Setting for Different Conditions and Results

The proposed algorithm was verified only for specific conditions that used conductors, which were ACSR (Aluminum Conductor Steel Reinforced) and XLPE (Cross Linked Polyethylene). However, there are many conductor types that can be used in a mixed transmission system. Therefore, in this section, how to apply the proposed algorithm to different conditions is discussed.
The oil-filled (OF) cable is one of the most widely used conductors in underground cables, but because it is filled with oil, it carries the risks of explosion and fire when exposed to overvoltage or overcurrent. Therefore, it is especially important to prevent auto reclosing when the fault occurs on an OF cable section. To apply the proposed algorithm to a mixed transmission system that includes an OF cable section, there is a need to set the reference values considering the characteristics of an OF cable. The XLPE cable has a propagation velocity of travelling wave equal to 1.68 × 108 m/s, and an OF cable has one equal to 1.324 × 108 m/s. Therefore, due to the difference in the propagation velocity, when an OF cable is used, the reference values have to be set properly. In Table 7, the settings of the reference values considering an OF 2000 mm2 cable are shown.
Using these values, simulations were conducted to verify the proposed algorithm in a mixed transmission system that included an OF cable section. Table 8, Table 9 and Table 10 present the results of the recloser operation on a mixed system including the OF cable section, according to the configuration. As shown in Table 8, Table 9 and Table 10, the proposed algorithm could distinguish the faulted section in a mixed transmission system that includes an OF cable section and operate the recloser only for overhead line faults in all cases.
In this way, utilities who operate mixed transmission systems can apply the proposed algorithm through proper reference values that consider their system conditions (system configuration, cable type), thus avoiding improper recloser operation.

5. Conclusions

In this paper, a novel recloser operation algorithm on a mixed transmission system was proposed using the travelling wave. In a mixed transmission system, proper auto reclosing has to be applied because some risks such as explosion, fire, and insulation breakdown can occur by reclosing for underground cable faults. Therefore, in this paper, the proposed algorithm distinguished the faulted section using voltage waveform caused by the travelling wave and there was no need for any signal processing. Thus, the proposed algorithm can provide a simple, fast, and correct recloser operation command. Moreover, utilities can easily apply the proposed algorithm to their recloser according to their system condition. Additionally, if the discontinuity problem at a converter station and a transition point fault case can be overcome through advanced study, the proposed method can also be applied to an AC/DC hybrid system. What is new, compared to the existing methods, and why the proposed approach is needed are summarized as follow.
  • Simple and convenient to use: The proposed approach uses instantaneous voltage information, which is sampled data by PT (Potential Transformer) on buses, and did not apply signal processing. Thus, there are no requirements for additional devices and the signal processing procedure when utilities try to apply the proposed algorithm on their recloser.
  • Cost efficiency: As above-mentioned, except PTs, additional equipment (including GPS or computation device) is not required to apply the proposed approach. Additionally, because the function of the proposed algorithm performs simple subtraction and comparison, it has a low computation time. Thus, the proposed approach has a low computation cost. In addition, because the proposed algorithm is based on a single ended method, which differs from existing approaches that are mostly based on a double ended method, it requires a relatively smaller number of devices.
  • Expansion ability: The proposed approach uses the characteristics of various conductors that consist of a mixed transmission line. According to the type of conductor, characteristics including the propagation speed of the travelling wave are changed. By considering the propagation speed of the travelling wave and setting proper reference values ( T r e f , T r e f 1 , T r e f 2 ), the proposed algorithm can be applied to any type of conductors. Furthermore, a mixed transmission line is operated under many different topologies. In this paper, only three types (OL + UC, OL + UC + OL, UC + OL + UC) were considered, but this can be expanded to many topologies (OL + UC + OL + UC, OL + UC + UC + OL, and so on) by adding more reference values.

Author Contributions

Conceptualized the proposed algorithm and investigated this study. Also, he drafted the original article and revised it according to review process: S.-H.S. Also conceptualized and validated the proposed algorithm also, he reviewed and edited the first draft: G.-J.C. This study was carried out under the supervision and management of C.-H.K. He also conceptualized the proposed algorithm and reviewed this article. All authors have read and agreed to the published version of the manuscript.

Funding

This research was supported by the National Research Foundation of Korea (NRF) grant funded by the Korea government (MSIP), grant number No. 2018R1A2A1A05078680.

Conflicts of Interest

The authors declare no conflicts of interest.

Nomenclature

Variables
TrefA reference value to distinguish the faulted section
TsampleThe arrival time that travelling wave propagates from fault point to measuring point
∆TThe difference between fault occurring time and Tsample
Llength of overhead line or underground cable
vpropagation velocity of travelling wave
Abbreviations
OLOverhead line
UCUnderground cable
OCOverhead line + Underground cable
OCOOverhead line + Underground cable + Overhead line
COCUnderground cable + Overhead line + Underground cable

Appendix A

Figure A1 shows the recloser operation results according to the proposed algorithm when a fault occurs on a mixed transmission system that has an (OL + UC + OL) configuration. Figure A1 also shows the voltage waveform when a single line to ground fault (a phase) is injected in the overhead line section (9.9 km point of whole system). In the case of Figure A1, the fault is distinguished as an overhead line fault by the proposed algorithm, thus based on this result, the recloser conducts reclosing behavior at 0.6 s. In contrast, in the case of an underground cable fault, the recloser did not conduct reclosing behavior by the proposed algorithm.
Figure A1. Example of a recloser operation result by the proposed algorithm when a fault occurs on an overhead line in the (OL + UC + OL) configuration.
Figure A1. Example of a recloser operation result by the proposed algorithm when a fault occurs on an overhead line in the (OL + UC + OL) configuration.
Energies 13 02610 g0a1

Appendix B

In Figure A2, the pseudo-code of the proposed algorithm is shown. In step 1, the maximum value of the voltage difference between the sampled voltage in steady-state is obtained. In the next step, after a fault occurs, the proposed algorithm detects the voltage variation resulting from the travelling wave. In step 3, the proposed algorithm transfers the trip signal to the recloser. Finally, in last step, the proposed algorithm compares the T r e f with T , and then transfers the reclosing signal or prevents reclosing, according to the fault location.
Figure A2. The pseudo-code of the proposed algorithm.
Figure A2. The pseudo-code of the proposed algorithm.
Energies 13 02610 g0a2

References

  1. Korea Electric Power Research Institute. A Study on the Optimization of Reclosing Scheme on Transmission and Distribution Line; Korea Electric Power Corp.: Daejeon, Korea, 1998. [Google Scholar]
  2. Cho, G.J.; Park, J.K.; Sohn, S.H.; Chung, S.J.; Gwon, G.H.; Oh, Y.S.; Kim, C.H. Development of a Leader-End Reclosing Algorithm Considering Turbine-Generator Shaft Torque. Energies 2017, 10, 622. [Google Scholar]
  3. Seo, H.C. New Adaptive Reclosing Technique in Unbalanced Distribution System. Energies 2017, 10, 1004. [Google Scholar] [CrossRef] [Green Version]
  4. Granizo Arrabé, R.; Platero Gaona, C.A.; Álvarez Gómez, F.; Rebollo López, E. Novel Auto-Reclosing Blocking Method for Combined Overhead-Cable Lines in Power Networks. Energies 2016, 9, 964. [Google Scholar] [CrossRef] [Green Version]
  5. IEEE Guide for Automatic Reclosing of Circuit Breakers for AC Distribution and Transmission Lines; IEEE Standard C37.104-2012; IEEE: New York, NY, USA, 2012.
  6. EPRI. EPRI Underground Transmission Systems Reference Book; The Green Book: Palo Alto, CA, USA, 2012; pp. 2–20, 2–21, 16–22, 16–23. [Google Scholar]
  7. Louredo, N.H.G.R.; Filho, E.K.; Lopes, J.C.R.; Vale, P.A.M. Overhead to Underground Transmission Line Coupling-Technical Recommendations to Brazilian Utilities; CIGRE B1-107; CIGRE: Paris, France, 2012. [Google Scholar]
  8. The Protective Relay Subcommittee. Considerations for Transmission Reclosing Practices in the MRO Area; Midwest Reliability Organization: Roseville, MN, USA, 2009. [Google Scholar]
  9. Jung, C.K.; Park, H.S.; Kang, J.W.; Wang, X.; Kim, Y.K.; Lee, J.B. Development of Fault Location Algorithm and Its Verification Experiments for HVDC Submarine Cables. J. Electr. Eng. Technol. 2012, 7, 859–868. [Google Scholar] [CrossRef] [Green Version]
  10. Gilany, M.; Din, E.S.T.E.; Aziz, M.M.A.; Ibrahim, D.K. An accurate scheme for fault location in combined overhead line with underground power cable. In Proceedings of the IEEE Power Engineering Society General Meeting, San Francisco, CA, USA, 12–16 June 2005. [Google Scholar]
  11. Spoor, D.; Zhu, J.G. Improved single-ended traveling-wave fault-location algorithm based on experience with conventional substation transducers. IEEE Trans. Power Deliv. 2006, 21, 1714–1720. [Google Scholar] [CrossRef] [Green Version]
  12. CIGRE WG B1.19. General Guidelines for the Integration of a New Underground Cable System in the Network; CIGRE: Paris, France, 2004. [Google Scholar]
  13. Thomas, D.W.P.; Christopoulos, C.; Carvalho, R.J.O.; Pereira, E.T. Single and double ended travelling-wave fault location on a MV system. In Proceedings of the Eighth IEE International Conference on Developments in Power System Protection, Amsterdam, The Netherlands, 5–8 April 2004. [Google Scholar]
  14. Bains, T.P.S.; Sidhu, T.S.; Xu, Z.H.; Voloh, I.; Zadeh, M.R.D. Impedance-based fault location algorithm for ground faults in series-capacitor-compensated transmission lines. IEEE Trans. Power Deliv. 2018, 33, 189–199. [Google Scholar] [CrossRef]
  15. Ji, L.; Tao, X.; Fu, Y.; Fu, Y.; Mi, Y.; Li, Z. A New Single Ended Fault Location Method for Transmission Line Based on Positive Sequence Superimposed Network During Auto-Reclosing. IEEE Trans. Power Deliv. 2019, 34, 1019–1029. [Google Scholar] [CrossRef]
  16. Salim, R.H.; Resener, M.; Filomena, A.D.; Oliveira, K.R.C.; Bretas, A.S. Extended Fault-Location Formulation for Power Distribution Systems. IEEE Trans. Power Deliv. 2009, 24, 508–516. [Google Scholar] [CrossRef]
  17. Naidu, O.; Pradhan, A.K. A Traveling Wave-Based Fault Location Method Using Unsynchronized Current Measurements. IEEE Trans. Power Deliv. 2019, 34, 505–513. [Google Scholar] [CrossRef]
  18. Lee, H.; Mousa, A.M. GPS travelling wave fault locator systems: Investigation into the anomalous measurements related to lightning strikes. IEEE Trans. Power Deliv. 1996, 11, 1214–1223. [Google Scholar] [CrossRef]
  19. Naidu, O.; Yalla, P.; George, N. Auto-reclosing Protection Scheme for Multi-Terminal Mixed Lines Using Synchrophasor Measurements. In Proceedings of the International Conference on Smart Grid Synchronized Measurements and Analytics, College Station, TX, USA, 21–23 May 2019. [Google Scholar]
  20. Hong, Y.J.; Qingzhang, C.; Dan, W. Traveling wave fault location based on wavelet and improved singular value difference spectrum. In Proceedings of the 2017 International Conference on Circuits, Devices and Systems, Chengdu, China, 5–8 September 2017. [Google Scholar]
  21. Han, J.; Crossley, P.A. Fault location on a mixed overhead and underground transmission feeder using a multiple-zone quadrilateral impedance relay and a double-ended travelling wave fault locator. In Proceedings of the 12th IET International Conference on Developments in Power System Protection, Copenhagen, Demark, 31 March–3 April 2014. [Google Scholar]
  22. Lin, S.; He, Z.Y.; Li, X.P.; Qian, Q.Q. Travelling wave time-frequency characteristic-based fault location method for transmission lines. IET Gener. Transm. Distrib. 2012, 6, 764–772. [Google Scholar] [CrossRef]
  23. Abur, A.; Magnago, F.H. Use of time delays between modal components in wavelet based fault location. Int. J. Electr. Power Energy Syst. 2000, 22, 397–403. [Google Scholar] [CrossRef]
  24. Hamidi, R.J.; Livani, H. Traveling-wave-based fault-location algorithm for hybrid multi terminal circuits. IEEE Trans. Power Deliv. 2017, 32, 135–144. [Google Scholar] [CrossRef]
  25. Lin, X.; Zhao, F.; Wu, G.; Li, Z.; Weng, H. Universal Wavefront Positioning Correction Method on Traveling-Wave-Based Fault-Location Algorithms. IEEE Trans. Power Deliv. 2012, 27, 1601–1610. [Google Scholar] [CrossRef]
  26. Mardiana, R.; Motairy, H.A.; Su, C.Q. Ground Fault Location on a Transmission Line Using High-Frequency Transient Voltages. IEEE Trans. Power Deliv. 2011, 26, 1298–1299. [Google Scholar] [CrossRef]
  27. Lopes, F.V.; Dantas, K.M.; Silva, K.M.; Costa, F.B. Accurate two terminal transmission line fault location using traveling waves. IEEE Trans. Power Deliv. 2018, 33, 873–880. [Google Scholar] [CrossRef]
  28. Lan, H.; Ai, T. Application of EMD on single-pole adaptive reclosure of transmission. Dianli Xitong Baohu yu Kongzhi/Power Syst. Prot. Control 2010, 38, 35–39. [Google Scholar]
  29. Power System Protection Team. A Study on Establishment of Operating Practices Adequacy for Reclosing Relay in Transmission Line; Korea Power Exchange: Naju, Korea, 2013. [Google Scholar]
Figure 1. The concept of the proposed algorithm considering three configurations of mixed transmission system: (a) Overhead Line + Underground Cable (OL + UC) configuration; (b) Overhead Line + Underground Cable + Overhead Line (OL + UC + OL) configuration; (c) Underground Cable + Overhead Line + Underground Cable (UC + OL + UC) configuration.
Figure 1. The concept of the proposed algorithm considering three configurations of mixed transmission system: (a) Overhead Line + Underground Cable (OL + UC) configuration; (b) Overhead Line + Underground Cable + Overhead Line (OL + UC + OL) configuration; (c) Underground Cable + Overhead Line + Underground Cable (UC + OL + UC) configuration.
Energies 13 02610 g001
Figure 2. Proposed recloser operation algorithm on a mixed transmission system.
Figure 2. Proposed recloser operation algorithm on a mixed transmission system.
Energies 13 02610 g002
Figure 3. One-line diagram of the modeled system for the (OL + UC) configuration.
Figure 3. One-line diagram of the modeled system for the (OL + UC) configuration.
Energies 13 02610 g003
Figure 4. One-line diagram of the modeled system for the (OL + UC+ OL) configuration.
Figure 4. One-line diagram of the modeled system for the (OL + UC+ OL) configuration.
Energies 13 02610 g004
Figure 5. One-line diagram of the modeled system for the (UC + OL+ UC) configuration.
Figure 5. One-line diagram of the modeled system for the (UC + OL+ UC) configuration.
Energies 13 02610 g005
Table 1. Auto reclosing principles adopted by utilities on a mixed transmission system [29].
Table 1. Auto reclosing principles adopted by utilities on a mixed transmission system [29].
NationVoltage LevelAuto Reclosing Principle
South Korea(1) 154 kV(1-1) Auto reclosing allowed: when portion of underground cable <30% (total system)
(1-2) Auto reclosing prohibited: when “OF (Oil-Filled) cable” is used
(2) 345 kV(2) Auto reclosing prohibited: when underground cable section exists
Brazil138 kV, 230 kVAmong the total ‘12′ mixed system,
(1) Auto reclosing allowed: ‘9′ systems
(2) Auto reclosing allowed only for overhead line fault: ‘2′ systems
(3) Auto reclosing prohibited: ‘1′ system
Japan(1) <154 kV(1) Auto reclosing allowed: when following conditions are met
-Short circuit current < 1000 A, Fault clearing time <1 s,
-Fire prevention measure is applied to exposed part of cable and adjacent cable,
-Length of underground cable < 1 km, Length of underground cable <1/3 of overhead line length,
-Fault will not affect the other cable
(2) >154 kV(2-1) Auto reclosing allowed: when following conditions are met
-Length of underground cable <1 km, Length of underground cable <1/3 of overhead line length,
-Fault will not affect the other cable
(2-2) Auto reclosing prohibited: when underground cable fault occurs
Canada(1) 60~345 kV(1) Auto reclosing allowed: only for overhead line fault or according to portion of overhead line
(2) >500 kV(2) Auto reclosing prohibited
Sweden132 kV(1) Auto reclosing allowed: when overhead line section is enough long or only for overhead line fault
(2) Auto reclosing prohibited: when overhead line section is short
Table 2. Simulation conditions.
Table 2. Simulation conditions.
Fault TypeSampling FrequencyTotal line Length
(1) Single line to ground fault
(2) 3-phase fault
30.72 kHz
(512 samples/cycle)
(1) Overhead line: 10 km
(2) Underground cable: 2.4 km
Table 3. Reference values Tref, Tref1, and Tref2.
Table 3. Reference values Tref, Tref1, and Tref2.
Configuration
(OL + UC)
Configuration
(OL + UC + OL)
Configuration
(UC + OL + UC)
(1) Tref: 35.71 μs(1) Tref1: 17.9 μs
(2) Tref2: 32.19 μs
(1) Tref1: 7.1 μs
(2) Tref2: 42.81 μs
Table 4. Results of the reclosing operation using the proposed algorithm on the (OL + UC) configuration.
Table 4. Results of the reclosing operation using the proposed algorithm on the (OL + UC) configuration.
Obtained △T and Result of Comparison with Tref
Fault Position△T (μs)Recloser Operation Signal
Single Line to Ground Fault3-Phase Fault
Overhead line2 km7.20027.2002Auto Reclosing Allowed (△T< Tref)
4 km14.293214.2932
6 km21.401021.4010
8 km28.598328.5983
10 km35.706235.7062
Underground cable10.4 km37.896637.8966Auto Reclosing Prevented (△T > Tref)
10.8 km40.206340.2063
11.2 km42.605442.5011
11.6 km44.900244.7959
12 km47.299347.195
Table 5. Results of the reclosing operation using the proposed algorithm on the (OL + UC + OL) configuration.
Table 5. Results of the reclosing operation using the proposed algorithm on the (OL + UC + OL) configuration.
Obtained △T and Result of Comparison with Tref
Fault Position△T (μs)Recloser Operation Signal
Single Line to Ground Fault3-Phase Fault
Overhead line1 km3.59423.5942Auto Reclosing Allowed (△T < Tref1)
3 km10.702010.7020
5 km17.899317.8993
Underground cable5.4 km20.104620.1046Auto Reclosing Prevented (Tref1 < △T and △T < Tref2)
5.8 km22.399422.3994
6.2 km24.798524.6942
6.6 km27.093327.0039
7 km29.403029.4030
7.4 km31.697831.6978
Overhead line7.9 km33.605133.5008Auto Reclosing Allowed (Tref2 < △T)
9.4 km38.895038.8950
10.9 km44.304144.1998
12.4 km49.594049.5940
Table 6. Results of the reclosing operation using the proposed algorithm on the (UC + OL + UC) configuration.
Table 6. Results of the reclosing operation using the proposed algorithm on the (UC + OL + UC) configuration.
Obtained △T and Result of Comparison with Tref
Fault Position△T (μs)Recloser Operation Signal
Single Line to Ground Fault3-Phase Fault
Underground cable0.4 km2.40212.4021Auto Reclosing Prevented (△T < Tref1)
0.8 km4.69684.6968
1.2 km7.00657.0065
Overhead line1.7 km8.70538.7053Auto Reclosing Allowed (Tref1 < △T and △T < Tref2)
3.2 km14.099514.0995
4.7 km19.404319.4043
6.2 km24.798524.7985
7.7 km30.103330.1033
9.2 km35.497535.4975
10.7 km40.802440.8024
11.2 km42.605442.6054
Underground cable11.6 km45.004544.9002Auto Reclosing Prevented (Tref2 < △T)
12 km47.299347.1950
12.4 km49.698449.5940
Table 7. Settings of the reference values Tref, Tref1, Tref2 considering an oil-filled (OF) cable.
Table 7. Settings of the reference values Tref, Tref1, Tref2 considering an oil-filled (OF) cable.
Settings for Reference Values in OF Cable System
Cable TypeConfiguration (OL + UC)Configuration (OL + UC + OL)Configuration (UC + OL + UC)
XLPE cable(1) Tref: 35.71 μs(1) Tref1: 17.9 μs
(2) Tref2: 32.19 μs
(1) Tref1: 7.1 μs
(2) Tref2: 42.81 μs
OF cable(1) Tref: 35.71 μs(1) Tref1: 17.9 μs
(2) Tref2: 36.03 μs
(1) Tref1: 9.06 μs
(2) Tref2: 44.77 μs
Table 8. Results of the reclosing operation on an OF cable system in configuration (OL + UC).
Table 8. Results of the reclosing operation on an OF cable system in configuration (OL + UC).
Configuration (OL + UC)
Fault Position△T (μs)Recloser Operation
Signal
Overhead line2 km7.2002Auto Reclosing Allowed (△T < Tref)
4 km14.2932
6 km21.4010
8 km28.5983
10 km35.7062
Underground cable10.4 km38.4927Auto Reclosing Prevented (Tref < △T)
10.8 km41.3984
11.2 km44.3041
11.6 km47.2993
12 km50.205
Table 9. Results of the reclosing operation on an OF cable system in configuration (OL + UC + OL).
Table 9. Results of the reclosing operation on an OF cable system in configuration (OL + UC + OL).
Configuration (OL + UC + OL)
Fault Position△T (μs)Recloser Operation Signal
Overhead line1 km3.5942Auto Reclosing Allowed (△T < Tref1)
3 km10.7020
5 km17.8993
Underground cable5.4 km20.7007Auto Reclosing Prevented (Tref1 < △T < Tref2)
5.8 km23.6064
6.2 km26.4972
6.6 km29.403
7 km32.3981
7.4 km35.3038
Overhead line7.9 km37.1963Auto Reclosing Allowed (Tref2 < △T)
9.4 km42.5011
10.9 km47.8953
12.4 km53.2001
Table 10. Results of the reclosing operation on an OF cable system in configuration (UC + OL + UC).
Table 10. Results of the reclosing operation on an OF cable system in configuration (UC + OL + UC).
Configuration (UC + OL + UC)
Fault Position△T (μs)Recloser Operation Signal
Underground cable0.4 km2.9981Auto Reclosing Prevented (△T< Tref1)
0.8 km5.9638
1.2 km8.7947
Overhead line1.7 km10.5977Auto Reclosing Allowed (Tref1 < △T < Tref2)
3.2 km15.9025
4.7 km21.2967
6.2 km26.6016
7.7 km31.9958
9.2 km37.3006
10.7 km42.6948
11.2 km44.3935
Underground cable11.6 km47.2993Auto Reclosing Prevented (Tref2 < △T)
12 km50.2944
12.4 km53.2001

Share and Cite

MDPI and ACS Style

Sohn, S.-H.; Cho, G.-J.; Kim, C.-H. A Study on Application of Recloser Operation Algorithm for Mixed Transmission System Based on Travelling Wave Method. Energies 2020, 13, 2610. https://doi.org/10.3390/en13102610

AMA Style

Sohn S-H, Cho G-J, Kim C-H. A Study on Application of Recloser Operation Algorithm for Mixed Transmission System Based on Travelling Wave Method. Energies. 2020; 13(10):2610. https://doi.org/10.3390/en13102610

Chicago/Turabian Style

Sohn, Seung-Hyun, Gyu-Jung Cho, and Chul-Hwan Kim. 2020. "A Study on Application of Recloser Operation Algorithm for Mixed Transmission System Based on Travelling Wave Method" Energies 13, no. 10: 2610. https://doi.org/10.3390/en13102610

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop