Next Article in Journal
Computational Fluid Dynamics Modelling and Simulation of an Inclined Horizontal Axis Hydrokinetic Turbine
Previous Article in Journal
Economic Feasibility of Wave Energy Farms in Portugal
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Design and Implementation of Novel Multi-Converter-Based Unified Power Quality Conditioner for Low-Voltage High-Current Distribution System

School of Electrical Engineering, Southeast University, Nanjing 210096, China
*
Author to whom correspondence should be addressed.
Energies 2018, 11(11), 3150; https://doi.org/10.3390/en11113150
Submission received: 30 September 2018 / Revised: 3 November 2018 / Accepted: 11 November 2018 / Published: 14 November 2018
(This article belongs to the Section F: Electrical Engineering)

Abstract

:
This paper introduces a novel multi-converter-based unified power quality conditioner (MCB-UPQC). Three optimization methods are proposed based on the traditional UPQC: (1) The shunt converter is substituted with multi-modular parallel converters. Hence, the reactive power and harmonic currents can be increased greatly, which are suitable for low-voltage high-current distribution systems. (2) The series converters consist of three H-bridge inverters, and each of the H-bridge inverters is controlled separately. The control strategy is easier to achieve and can improve the control performance of voltage regulation under unbalanced voltage sag or swell. (3) A three-phase four-leg (3P4L) converter is connected to the common DC bus of the proposed UPQC to connect the renewable energy and energy storage system. The detailed mathematical models of shunt and series converters are analyzed, respectively. A multi-proportional resonant (PR) controller is presented in the voltage regulation and reactive power compensation control algorithms. The simulation results verify the feasibility of the control algorithms. Finally, the experimental platform is established, and the experimental results are presented to verify the validity and superiority of the proposed topology and algorithms.

1. Introduction

1.1. Motivation

The power system has greatly evolved and has been popularized since the 21st Century [1]. The characteristics of the power system have also changed. With the development of science and technology, the electronic loads have increased largely [2]. A great amount of harmonic loads has been employed in the manufacturing industry, entertainment centers and financial enterprises, which can inject plenty of harmonic currents into the grid [3,4,5]. Furthermore, large numbers of single-phase loads are connected to the distribution system [6]. Therefore, the unbalanced voltage is generated by an unreasonable connection [7,8,9]. Under this circumstance, the power quality is greatly affected and deteriorated. Reasonable governance measures should be taken to improve the power quality. With the growing severity of the energy crisis, renewable energy sources (RES) have attracted much attention in recent years [10]. The proportion of RES to the overall electricity power in the world has increased from 5–20% from 2012–2016 in China [11]. However, the utilization of renewable energy depends on the proportion that is interconnected with the power system. As a result, improving the power quality and improving the absorptive capacity of renewable energy have become quite significant issues nowadays.
Due to the technological advancements in power electronics, the power quality has the opportunity to be greatly improved by power electronic devices [12,13]. The static var compensator (SVC), static var generator (SVG), active power filters (APF) and static synchronous compensator (STATCOM) can be used to filter out harmonics in the power system and compensate the reactive power [14,15,16]. The dynamic voltage regulator (DVR) can compensate the voltage sag or swell [17,18]. However, these power electronic devices can only improve the power quality partially. The unified power quality conditioner (UPQC) composed of shunt and series back to back converters is the combination of all the devices mentioned above [19].

1.2. Literature Review

Many scholars have conducted extensive research on UPQC. In [20], a two-stage algorithm was proposed to select the minimum ratings of the shunt converter and series converter of the UPQC in order to obtain the maximum utilization rates of the power converters in the UPQC. The work in [21] introduced a UPQC without series transformers, controlled by algorithms based on the active and non-active currents together with PLL circuits. In [22], a single-phase unified power quality conditioner based on the modular multilevel matrix converter (M3C) was presented. The M3C-UPQC is comprised of four identical multilevel converter arms and associated filtering inductors. In [23], the phenomena of the variation in the rating of the UPQC system with the variation in displacement angle between source and load voltages had been studied by formulating the generalized VA loading equations of UPQC systems.
The research on UPQC has mainly focused on the control algorithms and topologies for the moment. However, most of the literature only analyzed and optimized the algorithms unilaterally and has not presented an overall control method for UPQC. Moreover, although the topologies of UPQC are optimized and proposed in great quantity, researchers have seldom performed the analysis of the specific applications and detailed experimental verifications of the proposed topologies. In [24], a new reduced switch UPQC system topology that comprises ten switches was proposed. Although a carrier-based double-zero sequence injection scheme was developed to maintain the linear modulation range and uniform switching frequency, the control algorithm had not been presented clearly. The work in [25] presented a current source unified power quality conditioner (CS-UPQC). A fault current limiting scheme was also presented, which limited the fault current effectively by utilizing the large DC link inductor of the CS-UPQC. However, there was no experimental verification in the paper to verify the topology and control method.

1.3. Contribution and Paper Structure

On account of the situation mentioned above, a multi-converter-based (MCB)-UPQC is proposed in this paper. To increase the compensating current of UPQC, the structure of the traditional UPQC is optimized in this paper. The shunt converter is replaced by three converters connected in parallel both on the AC and DC side. Therefore, the compensation current and power are triple that previously achieved. The series converter of each phase is constituted by an H-bridge. The parallel converters and H-bridge are back to back connected to a common DC bus. Furthermore, a three-phase four-leg (3P4L) converter is connected to the common DC bus. As a result, the renewable energy interface is provided by the output of the 3P4L converter. With the help of the DC bus and the renewable energy interface, the renewable DC and AC sources can be connected to the grid through the proposed UPQC.
Compared with the UPQC mentioned before, the MCB-UPQC has the following features: (1) A multi-converter connected in parallel is introduced in the shunt converter. (2) The series converters are connected to the load without the series transformer independently in each phase. (3) The renewable energy interface of the MCB-UPQC can connect the microgrid and energy storage system. Benefiting from these characteristics, the control algorithms of the proposed MCB-UPQC are simpler than before, and the difficulty of the hardware implementation is reduced. The MCB-UPQC has a wider application in distribution systems and microgrids.
This paper gives a comprehensive analysis of the proposed MCB-UPQC, which is designed for a low-voltage high-current distribution system. The topology, control strategy, parameters and hardware design of the proposed UPQC are presented. Additionally, a prototype is built for verification. Finally, simulation and experimental results prove the correctness of the topology and the control strategy of the proposed UPQC.

2. System Description

The topology of the UPQC is shown in Figure 1. It consists of the following parts: three shunt converters, three series H-bridge converters and a renewable energy interface.
As shown in Figure 1, three identical converters (Converters 1, 2 and 3) are shunt connected to the distribution system by a three-winding transformer. The structure of the converters is parallel both on the AC and DC side. Besides, if the power rate or current level is still insufficient, the number of converters can be increased to benefit from the parallel structure without changing the hardware structure. However, the following steps are required when introducing more converters: (1) The parameters of the control algorithms in shunt converters should be altered with the number of converters. (2) A greater communication line is needed between the controller and converters. The series converters consist of three H-bridge inverters (H-bridges A, B and C). The output of each H-bridge is connected to the grid in series using inductor and capacitor (LC) filters.
The renewable energy interface is comprised of a 3P4L inverter. This provides a DC interface ( U d c ) for the DC sources or DC loads and an AC interface ( u a , u b , u c , N u ) for the AC sources. Furthermore, the 3P4L inverter can connect AC or DC loads directly. e a , e b , e c are the main power transmission interfaces for the LV AC distributed network.
In conclusion, compared with the traditional UPQC, the following advantages can be observed in the proposed novel UPQC as:
  • Due to the parallel structure, the control algorithms of each converter are easier than for the cascade converter or multilevel module converter (MMC).
  • The power rate and compensation current are promoted.
  • Renewable energy and microgrid absorptive capabilities are achieved by the common DC bus and renewable energy interface.

3. Control Algorithms of UPQC

The control strategy is the key to the UPQC, and the performance of the controller will affect the equipment stability. Therefore, the most important procedure for debugging the prototype is accurately designing the control strategy. The control algorithms of the converter in the UPQC are discussed in this section. The control algorithms of the shunt converter, the series converter and the renewable energy interface are analyzed in detail in the following subsection.

3.1. Control Algorithm of Series Converters

The function of the series converters is to regulate the load voltage. By controlling the output voltage, the series converters can dynamically compensate the output voltage of the UPQC dynamically. Since the structure of the series converter in each phase is the same, the control algorithm of each converter is identical. Figure 2 shows the equivalent diagram of the series converter in Phase A.
In Figure 2, V s a is the switch side voltage of the converter, u e a is the grid voltage, i a is the current in Phase A, C f and u c a are the capacitance and voltage of the filter capacitor, respectively, and L f and i L a are the inductance and current of the filter inductor, respectively. The mathematical model of the structure can be derived as Equation (1):
d d t i L a u c a = 1 C f 1 L f V s a u c a R f i L a i L a i a
The open loop transfer function diagram of the control object of the series converters is shown in Figure 3.
Thus, the open loop transfer function can be written as:
G 0 ( s ) = 1 C f L f s 2 + R f C f s + 1
Based on the analysis above, the proposed control algorithm of series converters is shown in Figure 4.
The control algorithm is divided into two sections, the reference voltage of the capacitor is calculated in the detection section. A simplified calculation method is proposed in the detection section. Firstly, a α β coordinate is constructed using an all-pass filter. After the phase locking loop, the reference voltage can be calculated with F 1 and V r m s . Equation (3) is the transfer function of the all-pass filter.
G 1 ( s ) = ω f s ω f + s
where ω f = 2 π f = 100 π , and F 1 is calculated in Equation (4):
F 1 : V a r e f = 2 cos θ V r m s V b r e f = ( 2 2 cos θ + 6 2 sin θ ) V r m s V c r e f = ( 2 2 cos θ 6 2 sin θ ) V r m s
V r m s = 220 is the root mean square of the output voltage. The simulation result of the detection section is shown in Figure 5. Before 0.05 s, the grid voltage sag is 25%, and between 0.05 s and 0.1 s, the grid voltage sag is zero. However, between 0.1 s and 0.15 s, the grid voltage increases by 25%. As shown in the waveform, the detection section can precisely track the phase of the grid voltage and rapidly calculate the value of the compensation voltage.
Typically, a proportional resonant (PR) controller is used to control AC signals instead of a PI controller, since a PR controller has zero state error for AC signals. The transfer function of a normal PR controller is shown in Equation (5).
G p r ( s ) = K p + K r s s 2 + ω 0 s
It has an infinite gain at resonant frequency. However, the bandwidth of the controller is too small for digital realization. In the control section, a quasi-PR controller (q-PRc) is adopted. The bandwidth of the controller is increased, which means the stability of system is improved. Furthermore, it is necessary to suppress the selected order harmonic voltage to improve the power quality. A multi q-PRc is adopted at the selected order resonant frequency. The transfer function can be written as Equation (6):
G p r q ( s ) = K p + n = 1 , 3 , 5 . . . 2 K r ω c s s 2 + 2 ω c s + ( n ω 0 ) 2
Figure 6 shows the Bode diagram of the PR controller. Compared with a PR controller, the bandwidth at resonant frequency of the q-PRc is much wider. Parameters of controller are given as follows: K p = 0 . 25 , K r = 1000 , ω c = 5 , ω 0 = 100 π .
The eigenvalue and time-delay analysis should be considered in designing the controller [26]. However, the time-delay analysis and discretization are neglected due to the content and length of this paper.

3.2. Control Algorithm of Shunt Converters

Parallel converters have good characteristics with a higher power level and a higher conversion efficiency, which is far more flexible than a single converter. However, the L g , R g variations may result in interactions between converters, in which the circulating current is one of their major concerns. The circulating current will lead to current distortion and output harmonics in parallel converters. To overcome this problem, the circulating current-suppressing method should be considered in the control algorithms [27]. In this paper, we assume that the filters of each converter are identical; therefore, the circulating current is ignored.
The equivalent diagram of a shunt converter is shown in Figure 7. The functions of the shunt converter include controlling the DC side voltage, reactive power compensation and harmonic current suppression. To achieve these functions, the controller should be designed appropriately. When designing the traditional double closed loop of a shunt converter, a complex calculation process, multi-coordinate transformation and decoupling control are involved. These steps increase the difficulty of converter control. In this paper, a two degrees of freedom (TDF) quasi-PR controller is proposed to control the shunt converter.
Converter 1 is analyzed as an example. i g a , i g b and i g c are the phase currents of the converter; u g a , u g b and u g c are the phase voltages of the converter; i a , i b and i c are the load currents of the main winding. Equation (7) is the mathematical model in the synchronous rotating frame (SRF).
C d u d c d t = k = a , b , c i g k s k i L L d i g k d t + R i g k = u g k u d c ( s k 1 3 j = a , b , c s j )
To establish the TDF control strategy, Equation (7) can be derived into the α β coordinate as:
C d u d c d t = k = α , β i g k s k i L L d i g α d t + R i g α = u g α u d c s α L d i g β d t + R i g β = u g β u d c s β
Let v α = u d c s α , v β = u d c s β , and as Section 3.1 shows, the current control loop can use the q-PR controller. The control equations of the shunt converters under the proposed TDF are shown in Equation (9):
v α = G p r q ( s ) ( i α * i g α ) + u g α v β = G p r q ( s ) ( i β * i g β ) + u g β
Furthermore, a current component should be added into the current loop for the purpose of reactive power compensation and harmonic current suppression. The detection section and control section are shown in Figure 8.
In Figure 8, i q is the reactive current of the load current, while i α h and i β h are the harmonic currents of the load current. The current common harmonic current detection method is the instantaneous reactive power algorithm. The harmonic current detection algorithms presented in this paper are optimized based on it, as shown in Figure 9.
A PI controller is adapted to control the DC side voltage. Since there are three shunt converters, the current added into the current loop should be divided by three in each converter. Compared with the double closed loop of the PI controller, the proposed algorithm is simpler, and fewer calculations are required.
To verify the stability of the controller and appropriateness of the design parameters, the open loop transfer function of the current control loop is shown in Equation (10):
G ( s ) = K p ( s 2 + ω e 2 ) + K i s ( s 2 + ω e 2 ) ( s L + R L )
Figure 10 shows the root locus diagram of Equation (10). The q-PR controller has similar system stability as the PI controller. According to Figure 10, the values of k p and k i are easy to set. In this paper, the parameters of the q-PR controller are: K p = 4 , K i = 800 .
In the actual operation process of the three-phase converter, the parameters of the filters will change with the environment. These changes will bring greater perturbation to the control system. Therefore, it is necessary to consider the influence of robustness under the fluctuation of the parameters. The bode diagram of the control system transfer function under parameter fluctuation is shown in Figure 11.
With the variation of the filter inductance in the shunt converter, the controller has a great gain at the resonant frequency point, which is 50 Hz. The designed control algorithms can adapt to parameter perturbation in a wide range; therefore, the effect of parameters fluctuation on system stability is effectively suppressed. The proposed control algorithms have a strong robustness.

3.3. Control Algorithm of the Renewable Energy Interface

As mentioned above, the renewable energy interface is comprised of a three-phase four-leg inverter, which is connected to the common DC bus. In this subsection, a control algorithm based on the virtual synchronous generator (renewable energy interface) of the 3P4L inverter is presented. By simulating frequency regulation, voltage control, interference and excitation in the renewable energy interface, the control strategy can solve the difficulty of regulating the voltage and current when connecting to the renewable energy. Furthermore, we improve the control strategy of the renewable energy interface by introducing the voltage and current loop to increase the dynamic performance. Figure 12 shows the control algorithm of the proposed strategy.
The renewable energy interface can correspond to a synchronous generator [28,29]. According to the features of synchronous generators [30], the control algorithm can be easily designed. Equation (11) shows the relationship between the active power, frequency, reactive power and voltage.
P r e f + D p ( ω r e f ω ) P = J ω r e f d ω d t Q r e f + D q ( U r e f U ) Q = K d E d t θ = ω d t
where P r e f , Q r e f , P and Q are the reference active power, reference reactive power, actual active power and actual reactive power, respectively. D p and D q are the droop coefficients of power. ω r e f is rated angular frequency, while ω is actual angular frequency. E is the RMS voltage of the bridge arm. θ is the phase of the grid voltage.
From Equation (11), the three main control algorithms of VSG are presented in Figure 11. Figure 13a shows the active power control algorithm; Figure 13b shows the reactive power control algorithm; and Figure 13c shows the frequency and phase synchronous control algorithm of the renewable energy interface.
To increase the output dynamic stability of the renewable energy interface, a double closed voltage and current loop is used in the control strategy. Furthermore, a 3D-SVPWM strategy is used for the 3P4L converter. There are 16 switch states of eight switches in the converter, in which 16 effective switch vectors are constituted. Let pmean that the top IGBTs of each bridge arm are open and the bottom IGBTs are closed; nmeans that the top IGBTs are closed and the bottom IGBTs are open. In the α β γ coordinate system, a hexagon column can be constructed as shown in Figure 14.
Based on the research mentioned above, the whole control diagram of the 3P4L converter in the renewable energy interface is shown in Figure 15.
The reactive power controller, active power controller and frequency and phase synchronous controller are presented in Figure 11. With the proposed control algorithms in the renewable energy interface, the following functions can be implemented: (1) The renewable energy interface can connect AC loads directly; (2) The renewable energy can be connected to the grid by the proposed UPQC.
Compared with the traditional PI control methods of UPQC, the proposed control algorithms of MCB-UPQC based on the PR controller are divided into three parts, and each of the controllers is independent. The proposed q-PRc is easier to implement and more stable. Plenty of calculations of the coordinate transformation are removed for digital processing. Renewable energy connection is achieved by the control algorithms of the renewable energy interface.

4. Simulation and Experimental Verification

4.1. Simulation Results

In this section, a series of simulations is performed to verify the performance of the proposed UPQC. The simulations are carried out using MATLAB/Simulink. The parameters of the simulation model are shown in Table 1.
The factors affecting the design parameters of the filter include the power level, rated voltage, rated current, switch frequency and volume and heat dispersion of the prototype. Considering these factors and the design equation in [31], the filter parameters in the proposed UPQC are as shown in Table 1.
Figure 16 shows the simulation results of the shunt converter. At 0.1 s, the proposed control algorithm is used, and with the help of q-PRc, the voltage of DC side can be regulated to the reference value rapidly. Furthermore, the output current, which is aiming to compensate the reactive power, is switch on at 0.2 s.
To verify the prompt response to the reactive power, Figure 17 shows the difference between the reference current and actual values, and the results show that the shunt converter has a good performance in compensating the reactive power.
Figure 18 presents the simulation results of reactive power compensation and power factor correction. Before 0.1 s, the phase of the input voltage is ahead of the current. After 0.1 s, the shunt converters start to compensate the reactive power of the gird. The results show that the converters can compensate the reactive power within 0.02 s. The power factor of the grid is corrected to around 0.99. The performance of the controller is reasonable.
Figure 19 shows the voltage regulation ability of the series converter. The input voltage has a sag of 20% between 0.15 s and 0.18 s and of 100% between 0.12 s and 0.16 s. The results verify that the control algorithms proposed have a good performance in the voltage regulation.
Figure 20 is the dynamic synchronizing process of the microgrid interface. After 0.3 s, the output voltage of the renewable energy interface is the same as the grid voltage in the amplitude and phase. The results show that the renewable energy interface can connect to the grid within 0.3 s.

4.2. Experimental Results

In order to verify the correction of the proposed topology and control algorithms of UPQC, a 200-kVA platform of the proposed UPQC was designed and built. The structure of UPQC and the hardware in each module was exactly identical to Figure 1. The experimental platform of the proposed UPQC is shown in Figure 21. The control system adopted a master-slave structure. A TI 28346 DSP and FPGA were used in the master controller to achieve the communication between the converters and protection control. The IGBT and switches in each converter were controlled by the slave controller with a 28335 DSP. The switch frequency was 10k Hz in shunt converters and 15k Hz in series converters.
The filters consisted of the filter inductance of the shunt converters and the inductor, capacitor and inductor (LCL)filters of the series converters. Each back to back module consisted of a shunt converter and an H-bridge converter. The control circuits were assembled in the modules. The voltage regulator could adjust the input voltage to create the voltage sag or swell.

4.2.1. Experimental Results of Shunt Converters

Figure 22a shows the DC side voltage waveforms in each shunt converter. t 1 is the time bypassing the current-limiting resistance. t 2 is the time initiating the PWM rectification based on the multi q-PR controller. The results show that within 50 ms, the DC voltage could be regulated to the reference value of 800 V.
Figure 22b shows the steady state and transient state of the reactive power compensation of the shunt converter. As shown in Figure 7, u g a b and u g b c are the line voltages of the shunt converter; u d c is the DC side voltage of the shunt converter; u s a b , u s b c are the line voltages of the input voltage; i g a , i g b and i g c are the phase currents of the shunt converter. t 1 is the time at which the PWM rectification is initiated, and t 2 is the time at which the compensation is initiated. The experimental results verify that:
  • U d c was stable during the compensation.
  • The converter had a perfect var control ability according to the compensation current detected.
  • Benefiting from the three shunt converters, the compensation power increased to three-times that of one converter.
Figure 23 shows the harmonic compensation of the shunt converter. The experimental results in (a) and (b) verify that the control algorithm based on q-PRc had a decent performance in terms of compensating the harmonic current. Compared with (c) and (d), the total harmonic distortion of the input current (THDi)after compensation was 3.8%, which is compliant with the standards.

4.2.2. Experimental Results of Series Converters

To regulate the output voltage of the proposed UPQC, a control algorithm based on q-PRc was proposed in Figure 24.
The experimental results are shown in Figure 24. The grid voltage decreased 10% at t 1 and t 2 , respectively, and increased 10% at t 3 and t 4 . Furthermore, the output voltage of the proposed UPQC e a , e b and e c remained stable.
Although the shunt and series converters are controlled separately, the compensation ability when the current and voltage compensation are operating at the same time should be verified. Figure 25 shows the experimental results under the condition that the current and voltage compensation are both activated.
The grid voltage had a 10% sag both at t 1 and t 2 . The compensation current was stable the whole time. Additionally, the load voltage was stable due to the compensation of the H-bridge converters.

4.2.3. Experimental Results of the Renewable Energy Interface

Figure 26 is the experimental results of the dynamic synchronization process of the renewable energy interface.
V g r i d is the voltage of renewable energy; V i n v e r t e r is the output voltage of the renewable energy interface. After the action of the synchronous controller, the inverter voltage tracks the grid voltage gradually. After eight cycles, the frequency, phase and amplitude accuracy reached the requirements. The inverter voltage and the grid voltage coincided, and the interface was connected to the renewable energy sources.
Figure 27 shows the experimental waveforms of renewable energy interface in off-grid mode. The results verify that the transient state and steady state of inverter were quite stable.
Figure 28 shows the whole process of switching the operation mode from grid-connection to off-grid.
The load was switched on at t 1 , and the power of load was supplied by the grid, which was 6 kW. At t 2 , the output power of the renewable energy interface was set to 3 kW. The power of the load was supplied by both the grid and the renewable energy interface. At t 3 , the output power of the renewable energy interface was set to 6 kW, and the waveforms showed that the power was supplied by the inverter since the grid current was 0 A.

5. Discussion

The objective of this paper is to introduce a novel MCB-UPQC for a low-voltage high-current distribution system and a microgrid. To evaluate the topology and control algorithms of the MCB-UPQC, both the simulation and experimental results are presented. The software and hardware design of the proposed MCB-UPQC are analyzed and implemented. Although there are many switches and filters in the MCB-UPQC, structuralization and modularization are adopted in the proposed design of MCB-UPQC. It is suitable for application in the power grid.

6. Conclusions

Increasingly, equipment based on power electronics has been developed for application in the network, among which UPQC plays a significant role. However, UPQC can only compensate the power quality. To optimize the traditional UPQC, a novel UPQC based on a multi-converter parallel with a common DC bus is proposed in this paper. With the help of parallel converters, voltage regulation and current harmonic compensation can both be achieved to improve the power quality for a low-voltage high-current distribution system, and the renewable energy interface also benefits from the DC/AC converter. The control algorithms based on a multi-quasi-PR controller are proposed in both the shunt converters and the series converters. Considering the large numbers of modules in the UPQC, the proposed control algorithms have a reduced calculation time and are easier to achieve. Finally, the simulation results verify the feasibility of the control algorithms. Finally, the experimental platform is established, and the experimental results are presented to verify the validity and superiority of the proposed topology and algorithms.

Author Contributions

Conceptualization, B.Y.; Data curation, K.L.; Funding Acquisition, J.Z.; Methodology, B.Y.; Project Administration, J.Z.; Software, S.Z.; Validation, S.Z.; Writing-Original Draft, B.Y.; Writing-review and Editing, K.L.

Funding

This work was supported in part by grants from National Natural Science Foundation of China (Grant Number 51877042) and the Jiangsu Planned Projects for Postdoctoral Research Funds (Grant Number 2018K002B).

Conflicts of Interest

The authors declare no conflict of interest.

Nomenclature

U s a , U s b , U s c Input voltage of the distribution system
u e a , u e b , u e c Output voltage of the three-winding transformer
u g a , u g b , u g c Input voltage of the shunt converter
u d c Voltage of the common DC bus
i a , i b , i c Output current of the transformer
i g a , i g b , i g c Output current of the shunt converter
e a , e b , e c Load voltage
u a , u b , u c , u n Output voltage of the 3P4L converter
L g , C g Filter inductance and DC capacitor of the shunt converter
L f , C f Filters of the H-bridge inverters
L f 1 , L f 2 , C f e LCL filters of the switch side in the 3P4L converter
P r e f , Q r e f Reference active and reactive power
P , Q Actual active and reactive power
ω r e f , ω Rated and actual angular frequency
D p , D q Droop coefficient of power
U r e f , U Reference and actual voltage of the filter capacitor in the 3P4L converter
u i n t e r Output voltage of the 3P4L converter
u g r i d Output voltage of renewable energy
UPQCUnified power quality controller
SVCStatic synchronous compensator
SVGStatic var generator
APFActive power filters
STATCOMStatic synchronous compensator
DVRDynamic voltage regulator
3P4LThree-phase four-leg
SRFSynchronous rotating frame
TDFTwo degrees of freedom
q-PRcQuasi-PR controller
SVPWMSpace vector pulse width modulation
VSGVirtual synchronous generator

References

  1. Primadianto, A.; Lu, C.N. A Review on Distribution System State Estimation. IEEE Trans. Power Syst. 2017, 32, 3875–3883. [Google Scholar] [CrossRef]
  2. Garces, A.A. Linear Three-Phase Load Flow for Power Distribution Systems. IEEE Trans. Power Syst. 2016, 31, 827–828. [Google Scholar] [CrossRef]
  3. Pejovic, P.; Janda, Z. An improved current injection network for three-phase high-power-factor rectifiers that apply the third harmonic current injection. IEEE Trans. Ind. Electron. 2000, 47, 497–499. [Google Scholar] [CrossRef]
  4. Xiao, X.; Zheng, X.; Wang, Y.; Xu, S.; Zheng, Z. A Method for Utility Harmonic Impedance Estimation Based on Constrained Complex Independent Component Analysis. Energies 2018, 11, 2247. [Google Scholar] [CrossRef]
  5. Zhang, Y.; Roes, M.G.L.; Hendrix, M.A.M.; Duarte, J.L. Voltage Harmonic Suppression by Means of Grid-Connected Converters Using only Local Measurements. Energies 2018, 11, 2515. [Google Scholar] [CrossRef]
  6. Jayatunga, U.; Perera, S.; Ciufo, P.; Agalgaonkar, A.P. Voltage Unbalance Emission Assessment in Interconnected Power Systems. IEEE Trans. Power Deliv. 2013, 28, 2383–2393. [Google Scholar] [CrossRef] [Green Version]
  7. Ghijselen, J.A.L.; Bossche, A.P.M. Exact voltage unbalance assessment without phase measurements. IEEE Trans. Power Syst. 2005, 20, 519–520. [Google Scholar] [CrossRef]
  8. Paranavithana, P.; Perera, S.; Koch, R.; Emin, Z. Global Voltage Unbalance in MV Networks Due to Line Asymmetries. IEEE Trans. Power Deliv. 2009, 24, 2353–2360. [Google Scholar] [CrossRef] [Green Version]
  9. Kim, Y.J. Development and Analysis of a Sensitivity Matrix of a Three-Phase Voltage Unbalance Factor. IEEE Trans. Power Syst. 2018, 33, 3192–3195. [Google Scholar] [CrossRef] [Green Version]
  10. Tolba, M.; Rezk, H.; Diab, A.A.Z.; Al-Dhaifallah, M. A Novel Robust Methodology Based Salp Swarm Algorithm for Allocation and Capacity of Renewable Distributed Generators on Distribution Grids. Energies 2018, 11, 2556. [Google Scholar] [CrossRef]
  11. Lu, G.; Zhang, N. The effects of electric heating load on renewable energy generation utilization: Case study in North China. In Proceedings of the IEEE Conference on Energy Internet and Energy System Integration (EI2), Beijing, China, 26–28 November 2017. [Google Scholar]
  12. Liu, Y.; Steurer, M.; Ribeiro, P. A novel approach to power quality assessment: real time hardware-in-the-loop test bed. IEEE Trans. Power Deliv. 2005, 20, 1200–1201. [Google Scholar] [CrossRef]
  13. Rahmani, S.; Hamadi, A.; Al-Haddad, K.; Dessaint, L.A. A Combination of Shunt Hybrid Power Filter and Thyristor-Controlled Reactor for Power Quality. IEEE Trans. Ind. Electron. 2014, 61, 2152–2164. [Google Scholar] [CrossRef]
  14. Wu, J.C.; Jou, H.L.; Feng, Y.T.; Hsu, W.P.; Huang, M.S.; Hou, W.J. Novel Circuit Topology for Three-Phase Active Power Filter. IEEE Trans. Power Deliv. 2007, 22, 444–449. [Google Scholar] [CrossRef]
  15. Peng, F.Z.; Lai, J.S. Dynamic performance and control of a static VAr generator using cascade multilevel inverters. IEEE Trans. Ind. Appl. 1997, 33, 748–755. [Google Scholar] [CrossRef]
  16. Rao, P.; Crow, M.L.; Yang, Z. STATCOM control for power system voltage control applications. IEEE Trans. Power Deliv. 2000, 15, 1311–1317. [Google Scholar] [CrossRef]
  17. Xiao, S.; Qiu, W.; Miller, G.; Wu, T.X.; Batarseh, I. An Active Compensator Scheme for Dynamic Voltage Scaling of Voltage Regulators. IET Power Electron. 2009, 24, 307–311. [Google Scholar] [CrossRef]
  18. Jothibasu, S.; Mishra, M.K. A Control Scheme for Storageless DVR Based on Characterization of Voltage Sags. IEEE Trans. Power Deliv. 2014, 29, 2261–2269. [Google Scholar] [CrossRef]
  19. Khadkikar, V.; Chandra, A. UPQC-S: A Novel Concept of Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Utilizing Series Inverter of UPQC. IET Power Electron. 2011, 26, 2414–2425. [Google Scholar] [CrossRef]
  20. Ye, J.; Gooi, H.B.; Wu, F. Optimal Design and Control Implementation of UPQC Based on Variable Phase Angle Control Method. IEEE Trans. Ind. Inform. 2018, 14, 3109–3123. [Google Scholar] [CrossRef]
  21. Monteiro, L.F.; Aredes, M.; Pinto, J.G.; Exposto, B.F.; Afonso, J.L. Control algorithms based on the active and non-active currents for a UPQC without series transformers. IET Power Electron. 2016, 9, 1985–1994. [Google Scholar] [CrossRef]
  22. Xu, Q.; Ma, F.; Luo, A.; He, Z.; Xiao, H. Analysis and Control of M3C-Based UPQC for Power Quality Improvement in Medium/High-Voltage Power Grid. IEEE Trans. Power Electron. 2016, 31, 8182–8194. [Google Scholar] [CrossRef]
  23. Ambati, B.B.; Khadkikar, V. Optimal Sizing of UPQC Considering VA Loading and Maximum Utilization of Power-Electronic Converters. IEEE Trans. Power Deliv. 2014, 29, 1490–1498. [Google Scholar] [CrossRef]
  24. Abdul, M.R.; Amit, V.S.; Vinod, K.; Zeineldin, H.H. A Novel Ten-Switch Topology for Unified Power Quality Conditioner. IET Power Electron. 2016, 31, 6937–6946. [Google Scholar]
  25. Guo, W.Y.; Xiao, L.Y.; Dai, S.T. Control and design of a current source united power quality conditioner with fault current limiting ability. IET Power Electron. 2013, 6, 1755–4535. [Google Scholar] [CrossRef]
  26. Baghaee, H.R.; Mirsalim, M.; Gharehpetian, G.B.; Talebi, H.A. A generalized descriptor-system robust H∞ control of autonomous microgrids to improve small and large signal stability considering communication delays and load nonlinearities. INT J. Elec. Power. 2017, 92, 63–82. [Google Scholar] [CrossRef]
  27. Yang, B.; Zhao, Z.H.; Liu, M.X.; Zhao, J.F. Research on zero-sequence circulating current of PCS in MW energy storage system. In Proceedings of the IEEE International Conference on Power System Technology (POWERCON), Wollongong, Australia, 28 September–1 October 2016; pp. 1–5. [Google Scholar]
  28. Pochetjamroen, G.; Ise, T. Power Control of Low Frequency AC Transmission Systems Using Cycloconverters with Virtual Synchronous Generator Control. Energies 2017, 10, 34. [Google Scholar] [CrossRef]
  29. Cao, Y.J.; Wang, W.Y.; Li, Y.; Tan, Y.; Chen, C.; He, L.; Hager, U.; Rehtanz, C. A Virtual Synchronous Generator Control Strategy for VSC-MTDC Systems. IEEE Trans. Energy Convers. 2018, 33, 750–761. [Google Scholar] [CrossRef]
  30. Ma, Y.; Lin, Z.; Yu, R.; Zhao, S. Research on Improved VSG Control Algorithm Based on Capacity-Limited Energy Storage System. Energies 2018, 11, 677. [Google Scholar] [CrossRef]
  31. Liu, Y.T.; Lai, C.M. LCL Filter Design with EMI Noise Consideration for Grid-Connected Inverter. Energies 2018, 11, 1646. [Google Scholar] [CrossRef]
Figure 1. Topology of the proposed multi-converter parallel-based UPQC.
Figure 1. Topology of the proposed multi-converter parallel-based UPQC.
Energies 11 03150 g001
Figure 2. Equivalent diagram of H-bridge A in series converters.
Figure 2. Equivalent diagram of H-bridge A in series converters.
Energies 11 03150 g002
Figure 3. Control object structure diagram of H-bridge A.
Figure 3. Control object structure diagram of H-bridge A.
Energies 11 03150 g003
Figure 4. The proposed control algorithm of series converters.
Figure 4. The proposed control algorithm of series converters.
Energies 11 03150 g004
Figure 5. Simulation result of the detection section in the series converter.
Figure 5. Simulation result of the detection section in the series converter.
Energies 11 03150 g005
Figure 6. Bode diagram of the controller of series converters.
Figure 6. Bode diagram of the controller of series converters.
Energies 11 03150 g006
Figure 7. Equivalent diagram of shunt converters.
Figure 7. Equivalent diagram of shunt converters.
Energies 11 03150 g007
Figure 8. Control algorithm of the shunt converter. PR, proportional resonant controller.
Figure 8. Control algorithm of the shunt converter. PR, proportional resonant controller.
Energies 11 03150 g008
Figure 9. Harmonic detection algorithm.
Figure 9. Harmonic detection algorithm.
Energies 11 03150 g009
Figure 10. Root locus diagram of the current loop in the shunt converter.
Figure 10. Root locus diagram of the current loop in the shunt converter.
Energies 11 03150 g010
Figure 11. Frequency response considering parameter variation of the filter.
Figure 11. Frequency response considering parameter variation of the filter.
Energies 11 03150 g011
Figure 12. Schematic of the 3P4L inverter.
Figure 12. Schematic of the 3P4L inverter.
Energies 11 03150 g012
Figure 13. Control algorithm of the renewable energy interface: (a) active power control algorithm; (b) reactive power control algorithm; (c) frequency and phase synchronous control algorithm.
Figure 13. Control algorithm of the renewable energy interface: (a) active power control algorithm; (b) reactive power control algorithm; (c) frequency and phase synchronous control algorithm.
Energies 11 03150 g013
Figure 14. Vector diagram of 3D-SVPWM switch state.
Figure 14. Vector diagram of 3D-SVPWM switch state.
Energies 11 03150 g014
Figure 15. Control structure of the renewable energy interface.
Figure 15. Control structure of the renewable energy interface.
Energies 11 03150 g015
Figure 16. Simulation results of DC side voltage and reactive power compensation in the shunt converters.
Figure 16. Simulation results of DC side voltage and reactive power compensation in the shunt converters.
Energies 11 03150 g016
Figure 17. Simulation results of the difference between the reference current and actual values.
Figure 17. Simulation results of the difference between the reference current and actual values.
Energies 11 03150 g017
Figure 18. Simulation results of reactive power compensation and power factor correction. (a) Input voltage and input current in Phase A; (b) input voltage and output current in Phase A; (c) input current of the grid; (d) power factor of the grid.
Figure 18. Simulation results of reactive power compensation and power factor correction. (a) Input voltage and input current in Phase A; (b) input voltage and output current in Phase A; (c) input current of the grid; (d) power factor of the grid.
Energies 11 03150 g018
Figure 19. Dynamic voltage compensation simulation results of the series converter.
Figure 19. Dynamic voltage compensation simulation results of the series converter.
Energies 11 03150 g019
Figure 20. The dynamic synchronizing process of the renewable energy interface.
Figure 20. The dynamic synchronizing process of the renewable energy interface.
Energies 11 03150 g020
Figure 21. Experimental platform of the proposed UPQC.
Figure 21. Experimental platform of the proposed UPQC.
Energies 11 03150 g021
Figure 22. Experimental results of the shunt converters: (a) Experimental waveforms of the common DC bus; (b) Reactive power compensation of the shunt converter.
Figure 22. Experimental results of the shunt converters: (a) Experimental waveforms of the common DC bus; (b) Reactive power compensation of the shunt converter.
Energies 11 03150 g022
Figure 23. Harmonic compensation waveforms: (a) compensation and grid current waveform; (b) compensation and road current waveform; (c) THDbefore compensation; (d) THD after compensation.
Figure 23. Harmonic compensation waveforms: (a) compensation and grid current waveform; (b) compensation and road current waveform; (c) THDbefore compensation; (d) THD after compensation.
Energies 11 03150 g023
Figure 24. Voltage regulation waveform of the series converters.
Figure 24. Voltage regulation waveform of the series converters.
Energies 11 03150 g024
Figure 25. Experimental result of the compensation module.
Figure 25. Experimental result of the compensation module.
Energies 11 03150 g025
Figure 26. Dynamic synchronization process of renewable energy interface.
Figure 26. Dynamic synchronization process of renewable energy interface.
Energies 11 03150 g026
Figure 27. Off-grid mode waveforms: (a) initiate inverter program; (b) load switching on.
Figure 27. Off-grid mode waveforms: (a) initiate inverter program; (b) load switching on.
Energies 11 03150 g027
Figure 28. Grid-connection and off-grid switchover waveforms.
Figure 28. Grid-connection and off-grid switchover waveforms.
Energies 11 03150 g028
Table 1. Parameters of the filter.
Table 1. Parameters of the filter.
ParametersLabelValueUnit
Filter inductance of the shunt converter L g 2mH
DC capacitor in each shunt converter C g 4400 μ F
Filter inductance of the H-bridge L f 0.2mH
Filter capacitor of the H-bridge C f 400 μ F
Filter inductance of the switch side in the 3P4L converter L f 1 3.2mH
Filter inductance of the grid side in the 3P4L converter L f 2 0.8mH
Filter capacitor of the 3P4L converter C f e 10 μ F
Voltage of the common DC bus U d c 800V
Proportional integral parameter K p 4/
Proportional integral parameter K i 800/

Share and Cite

MDPI and ACS Style

Yang, B.; Liu, K.; Zhang, S.; Zhao, J. Design and Implementation of Novel Multi-Converter-Based Unified Power Quality Conditioner for Low-Voltage High-Current Distribution System. Energies 2018, 11, 3150. https://doi.org/10.3390/en11113150

AMA Style

Yang B, Liu K, Zhang S, Zhao J. Design and Implementation of Novel Multi-Converter-Based Unified Power Quality Conditioner for Low-Voltage High-Current Distribution System. Energies. 2018; 11(11):3150. https://doi.org/10.3390/en11113150

Chicago/Turabian Style

Yang, Bin, Kangli Liu, Sen Zhang, and Jianfeng Zhao. 2018. "Design and Implementation of Novel Multi-Converter-Based Unified Power Quality Conditioner for Low-Voltage High-Current Distribution System" Energies 11, no. 11: 3150. https://doi.org/10.3390/en11113150

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop