Next Article in Journal
Optimal Placement and Sizing of Renewable Distributed Generations and Capacitor Banks into Radial Distribution Systems
Previous Article in Journal
Energy Modelling and Automated Calibrations of Ancient Building Simulations: A Case Study of a School in the Northwest of Spain
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Comprehensive Reactive Power Support of DFIG Adapted to Different Depth of Voltage Sags

1
Sate Grid Hunan Electric Power Corporation Research Institute, Changsha, Hunan 410007, China
2
Department of Mechanical Engineering, University of Texas at Dallas, Richardson, TX 75080, USA
3
Electric Power Research Institute, Palo Alto, CA 94304, USA
4
School of Electrical Engineering, Wuhan University, Wuhan, Hubei 430072, China
*
Author to whom correspondence should be addressed.
Energies 2017, 10(6), 808; https://doi.org/10.3390/en10060808
Submission received: 9 May 2017 / Revised: 9 June 2017 / Accepted: 10 June 2017 / Published: 14 June 2017

Abstract

:
The low voltage ride-through (LVRT) capability of the doubly-fed induction generator (DFIG) significantly impacts upon the integration of wind power into the power grid. This paper develops a novel comprehensive control strategy to enhance the LVRT and reactive power support capacities of the DFIG by installing the energy storage system (ESS). The ESS is connected to the DC-link capacitor of the DFIG and used to regulate the DC-link voltage during normal or fault operations. The unbalanced power between the captured wind power and the power injected to the grid during the transient process is absorbed or compensated by the ESS. The rotor-side converter (RSC) is used to control the maximum power production and the grid-side converter (GSC) is used to control the reactive power before participating in the voltage support. When the supply voltage continues to drop, the rotor speed is increased by controlling the RSC to realize the LVRT capability and help the GSC further enhance the reactive power support capability. The capacity of the GSC is dedicated to injecting the reactive power to the grid. An auxiliary transient pitch angle controller is proposed to protect the generator’s over speed. Both RSC and GSC act as reactive power sources to further enhance the voltage support capability with serious voltage sags. Simulations based on a single-machine infinite-bus power system verify the effectiveness of the developed comprehensive control strategy.

1. Introduction

With the increasing penetration of wind power integrated into the power system [1,2,3,4], power system operators (PSOs) have enforced more stringent connection requirements on the doubly-fed induction generator (DFIG) based wind turbines [5]. One of these requirements is the low voltage ride-through (LVRT) capability of wind turbines, i.e., the ability of the power plant to remain connected to the grid during voltage sags [6,7].
Several research has been carried out to improve the LVRT capacity of DFIG. One common LVRT solution is to install a crowbar circuit across the rotor terminals to damp the over-current in the rotor circuit in order to protect the rotor-side converter (RSC) [8]. However, it is already recognized that the decoupled control of active and reactive power of the DFIG is temporarily unavailable during the crowbar protection. The DFIG actually works as a conventional induction generator absorbing a large amount of reactive power from the grid which further deteriorates the terminal voltage during the faults [9,10]. Therefore, the conservative crowbar protection should be the last choice to limit rotor currents [11,12].
In order to cure the drawbacks of the crowbar protection, some control strategies on the RSC and the grid-side converter (GSC) [13] have been adopted to protect the converters of DFIG. Typically, the control strategy proposed in [14] was used to accelerate the rotor to convert the excessive electric energy that could not be sent to the grid to kinetic energy. Thus, the surge of the rotor current as well as the DC-link voltage could be reduced. Nevertheless, this approach is limited due to the maximum allowable rotor speed, especially for the generator operating near the rated speed.
Many other advanced hardware aided methods, such as the series GSC [15,16], additional resistance circuits [17], dynamic voltage restorer (DVR) [18], energy storage system (ESS) [19,20], and electric vehicles [21,22], have been developed to tackle the LVRT operation. Among these hardware modification solutions, ESS is the most promising method. This is because ESS can help not only realize the uninterrupted operation in fault condition, but also smoothen the power output in the normal operation without using extra power electronic devices [23].
Another stringent requirement for wind turbines is the reactive power support by DFIG during the grid fault. In [24], the reactive power capability of DFIG under the steady state condition is investigated. A similar study has been reported in [25]. The GSC is reconfigured as a reactive power source during grid faults which has been proposed in [9] and [11]. However, the reactive power capability of disabled RSC has not been effectively used in these research. In [8], RSC is put in parallel with the GSC to inject the reactive power into the grid during grid faults. However, the reactive power capability is strictly limited, especially when the voltage drops to a low value. In [26], a coordinated voltage control scheme is present by using the RSC in collaboration with an on-load tap changer. However, it does not consider the GSC contribution. A coordinated reactive power control of the RSC and GSC is present in [27]. However, it only considers shallow voltage sags with the minimum remnant voltage of 0.6 p.u.. Another coordinated control of RSC and GSC is suggested in [13], where the GSC contributes to the reactive power control together with the RSC during large disturbances. However, the reactive power of GSC and RSC is limited since most of them are used to transfer the active power to the grid during grid faults.
In this paper, by installing ESS into the DFIG, a novel coordinated control strategy of LVRT capability and reactive power support capability adapted to different depth of voltage sags for DFIG-ESS is proposed to improve the dynamic performance of the DFIG-ESS system during the grid fault. The key point to realize the LVRT is to handle the excessive energy between the captured wind power and the power injected to the grid by the DFIG that cannot be transmitted into the grid during the transient process. Thus, the ESS connected to the DC-link capacitor of the DFIG is controlled to regulate the DC-link voltage during normal and fault operations. This is equivalent to absorb or compensate the unbalanced power. When the supply voltage suffers a low-level drop, RSC is used to control the maximum power production of the stator while the GSC operates to provide the reactive power before participating into the voltage support. As the supply voltage continues to drop, the rotor speed is increased by controlling the RSC to realize the LVRT capability, and helps the GSC further enhance the reactive power support capability. In the meanwhile, the whole capacity of GSC is dedicated to inject the reactive power into the grid. Moreover, an auxiliary transient pitch angle controller is used to protect the over speed of the generator. Both RSC and GSC act as reactive power sources to further enhance the voltage support capability when the supply voltage suffers a serious voltage sag.

2. Topology of DFIG Incorporated with ESS

The structure of a wind power generator integrated with the ESS is shown in Figure 1. In conventional configurations, the ESS and the switches connected to the DC-link are absent. The RSC is used to keep the maximum available wind power production and regulate the stator voltage, while the GSC is responsible for regulating the DC-link voltage.
If the stator and rotor copper losses are neglected, the amount and direction of the power flow through the rotor circuit can be approximately expressed as:
P r c = P w P s
where P w , P r c , and P s represent the captured wind power, rotor power, and stator power, respectively. Normally, the power flow flocking into the rotor circuit ( P r c ) equals 20–30% of the captured wind power ( P w ) during the normal operation at the super-synchronous operation. When the power grid is subject to a short-circuit fault, the transmitting capability of the active power P s is extremely restricted due to the decline of the supply voltage. Consequently, it can be seen from (1) that the large transient wind power flows into the DC-link capacitor through the rotor circuit due to the low response of the generator and wind turbine, especially when the DFIG suffers a serious voltage drop.
According to the reference direction of different power shown in Figure 1, the instantaneous dynamic response of the DC-link capacitor without ESS can be described as:
C v d c d v d c d t = P r c P g c = P r c e g d i g d = Δ P
where P g c is the instantaneous input power of the GSC. e g d and i g d are the d-axis components of the grid’s voltage and current, respectively.
For the traditional DFIG, the main task of GSC is to maintain the DC-link voltage and provide a path for the rotor power to/from the grid. Hence, the DC-link capacitor can be protected and the adequate voltage on the rotor can also be provided. However, it is difficult to realize that Δ P in (2) equals zero when e g d drops to a low value [28]. This is because the rotor power is large and the instantaneous power e g d i g d is small and determined by the current limitation of the converter semiconductor i g   max . Therefore, the excessive power Δ P cannot be transmitted to the grid.
It is noted that the DFIG dynamics are exasperated due to the excessive power that cannot be transmitted into the grid during the grid fault. The rotor control might be affected by the DC-link voltage fluctuation when the DFIG is running back to its normal operation [28]. Therefore, from the energy balance point of view, the key point of suppressing the over-current in the rotor and stator circuits as well as over-voltage in the DC-link is to reduce the power surplus between the captured wind power and the power injected into the grid provided by the DFIG [14].
By adding an ESS and its converter to the DC-link, Equation (2) can be re-expressed as:
P c = C V d c d V d c d t = P r c P b P g c
where P b is the power absorbed by the ESS.
By tuning appropriate control parameters of ESS, the left side of Equation (3) is zero, which means the DC-link voltage can be maintained as a constant value. Equation (3) can be represented as:
P b = P r c P g c = P w P s P g r i d P s = P w P g r i d
where P w and P g r i d represent the captured wind power and the active power injected to the grid by the DFIG, respectively.
It can be seen from Equations (3) and (4) that the ESS can regulate the DC-link voltage by absorbing or compensating the power from/to the rotor circuit during normal or fault operations. Therefore, there is little risk of over-voltage in the DC-link capacitor, even if the GSC is controlled to transfer zero active power to the grid. In addition, the difference between the absorbed power P g c and P r c is essentially equal to those between P w and P g r i d . Consequently, the excessive power flocking into the DFIG can be handled by the ESS, which is actually equivalent to regulate the transient DC-link voltage during grid faults. Furthermore, the oscillation of the current in the rotor and stator can be reduced since the variation of the DC-link voltage is suppressed. This will be verified by simulation results in Section 5. Therefore, the ESS connected to the DC-link can enhance the LVRT capacity of the DFIG during voltage dips.

3. Methodology of DFIG LVRT Enhancement with ESS

Modern grid codes require the wind turbine to remain in the continuous operation during voltage drops, which is termed as the low voltage ride through capability, as well as the voltage support capability by providing the reactive power into the grid [5,13]. For the traditional DFIG, there is not enough free capacity for GSC to participate into the voltage support, especially when the DFIG operates at the rated power production during grid faults. Therefore, the reactive power support capability of the DFIG is achieved by the RSC, which means the RSC changes to the reactive current priority. Consequently, the active power production of DFIG needs to be sacrificed for the sake of injecting reactive power. However, with increasing penetration levels of wind power integrated into the grid, the active power reduction of wind farms during grid disturbances may surpass the available reserve capability of the system, especially in islanded power systems. Consequently, the system security may be threatened due to a fall of the system frequency below the load shedding threshold [9]. Based on this knowledge, it is also important for wind turbines to deliver the active power as much as possible to the grid during the non-voltage drop.
The key point to suppress the over-current in the rotor and over-voltage in the DC-link voltage is to handle the power produced by wind turbines under fault conditions. Hence, the control system and hardware have to be modified to reduce the excessive power flow through the DFIG during fault conditions. It can be seen from (1) and (2) that the excessive power flocking into the rotor is determined by P w , P s , and P g c .
During the non-serious voltage drop, the RSC have the free capacity to maintain P s constant. This will be discussed in the Section 4. It can be seen from Equation (2) that P r c can be kept constant and the over-current is not induced in the rotor. ESS can regulate the bidirectional power balance between the GSC and RSC. Therefore, the GSC can be controlled to inject the reactive power into the grid for the voltage support according to the depth of voltage drops, while the RSC is controlled to keep the maximum power production to support the system frequency. As the terminal voltage drops to a low value, the regulation capability of P s is strictly restricted due to the limited capacity of the RSC. Consequently, the surplus power flow flocking into the rotor circuit may exceed the capacity of the RSC and result in the transient excessive current in the rotor circuit [29]. Moreover, the reactive power support capability is also restricted due to the low voltage dig. Therefore, a novel control strategy is presented to enhance the LVRT and further reactive power support capability of DFIG-ESS during voltage drops.
The captured wind power P w is given by:
P w = 0.5 C p λ , β ρ π R 2 V w 2
where C p is the power coefficient. V w is the wind speed. ρ is the air density. R is the radius of the rotor blade. β is the pitch angle. λ is the tip-speed ratio, and λ = 2 π f · ω r / p · G R · V w . ω r is the generator rotor speed. p is the pole number of the generator. f is the power system frequency. G R is the rear ratio. C p determines the “maximum power” that the wind turbine can absorb from the available wind power for a given wind turbine at a given wind speed. It is a function of the tip-speed ratio λ and the pitch angle β. A typical curve of C p is illustrated in Figure 2.
As can be seen in Figure 2a that the power coefficient C p reduces from C p a to C p b as the rotor speed of wind generators increases from ω r 1 to ω r 2 at a given β, which causes the reduction of the captured wind power P w . The generator speed acceleration can be achieved by reducing the electromagnetic torque with the proper control strategy of RSC. The dynamic response of the generator rotor can be described by Equation (6), where ω r and J are the generator rotor speed and the moment of inertia of the rotating mass connected to the rotor, respectively. T m and T e are the mechanical torque and electromagnetic torque, respectively.
T m T e = J d ω r d t
The increase of the rotor speed converts the partial wind power into the rotor inertia energy. The stored mechanical energy Δ E m ( t ) in the generator rotor at time t is relevant to the increase of the rotor speed, given by:
Δ E m t = 1 2 J ω r t 2 ω r t 0 2 , t > t 0
The acceleration of the rotor speed reduces the surplus power flowing to the rotor speed by reducing the captured wind power and convert partial captured wind power into the inertia energy in the rotor inertia, as shown in Equation (7). Under the stator-flux oriented reference frame, the decrease of T e causes the decrease of the q-axis active current in the rotor immediately [14]. Thus, the proposed control strategy of RSC reserves considerable potential reactive power capacity for the RSC to participate into the voltage-reactive power control, which will further enhance the voltage support capability during voltage drops.
When the supply voltage seriously drops (e.g., 0.1 p.u.), the grid code in UK [5] requires that the wind turbine must provide the maximum reactive current during serious grid faults to support the voltage. Thus, the whole capacity of RSC is dedicated to inject the reactive power to the grid. With this control strategy, the total amount of the reactive power from a large scale wind farm should be rather considerable, which probably leads to the favorable improvement of the voltage at the point of common coupling (PCC). Interestingly, if the voltage of the PCC is improved during the grid fault, it means that the stator voltage drop is reduced. Hence, the peak of the transient excessive power also declines [28].
However, the generator speed can accelerate quickly since T e reduces to zero. The acceleration of the rotor speed may increase the thrust and centrifugal force, when DFIG is operating at or close to the rated speed. When applied to the rotor construction, this may endanger the wind turbine mechanical system. Thus, the acceleration of the rotor speed is finite due to the maximum allowable rotor operation speed. Moreover, the mass stored inertia energy is large if the rotor speed increases far beyond to the prefault value. Once the stored energy is released in a very short time duration, the large over-current will be induced without any special control. Therefore, it is preferable to keep the rotor speed close to the prefault value.
As shown in Figure 2b, if the pitch angle increases from β 1 to β 2 , the C p curve will transfer from curve D1 to curve D2. Accordingly, the power coefficient C p reduces from C p b to C p d , which causes a perceptible reduction in the aerodynamic power extraction and mechanical torque. In addition to the increase of the rotor speed beyond the optimal value, an improved auxiliary pitch angle controller is proposed to reduce the captured wind power and suppress the over-speed of the rotor, when the amplitude of the supply voltage drop exceeds a certain threshold.

4. Reactive Power Control Strategy and Controller Design for DFIG-ESS

The transient response of DFIG-ESS varies with the different depth of voltage dips. Therefore, different control strategies can be designed for DFIG according to the depth of the voltage dip. The flow chart of the integrated LVRT and enhanced reactive power support scheme is shown in Figure 3. It can be seen from Figure 3 that the three-layer control strategy of DFIG is proposed according to the magnitude of the supply voltage during the fault period. Different control strategies of GSC, RSC, and pitch angle control are designed for different layers.
In Figure 3, ESS is responsible for the DC-link voltage regulation during the normal and fault operations. When the supply voltage drops below 0.9 p.u., the RSC is used to control the maximum power production of the stator, while the GSC operates at the reactive power before participating into the voltage support. As the voltage drops between 0.75 p.u. and 0.5 p.u., the GSC acts as a reactive power source to inject the reactive power to the grid. The RSC is controlled to realize the LVRT capability and helps the GSC further enhance the reactive power capability of the DFIG under fault conditions. When the supply voltage suffers a serious voltage drop (e.g., below 0.5 p.u.), the whole capacities of RSC and GSC are used to deliver the reactive power to the grid to boost the AC voltage. Furthermore, an auxiliary transient pitch angle controller is proposed to protect the rotor and realize the LVRT capability of DFIG.

4.1. Grid Faults Identification

In order to rapidly switch the normal controllers to the LVRT controllers, a good monitoring of the supply voltage dip is a crucial issue in the implementation of the proposed control strategy for the DFIG [30]. Different fast identification algorithms of grid voltage dip have been employed by several researchers [12,30]. In this paper, a sequence component decomposition method in [12], where its accuracy and fast identification of voltage variables under balance and unbalance conditions have been verified, is implemented in order to detect the magnitude of the supply voltage. The block diagram of this method is shown in Figure 4, where γ is the delay angle. The amplitude ( v s m + ) of the calculated positive sequence component of the stator voltage ( V s ) can be derived as:
v s m + = v s α + 2 + v s β + 2
where v s α + and v s β + are the α- and β-axis positive sequence components of the stator voltage V s , respectively.

4.2. Control Strategy of ESS

The ESS can be readily integrated into the design of the DFIG using a two-quarter IGBT-based DC/DC converter as described in Figure 5. The control objective of the ESS is to regulate the DC-link voltage by keeping the power balance between RSC and GSC to make a good performance for the DFIG during normal and fault operations. Figure 5 shows the overall vector control scheme of the ESS. The control strategy uses the cascade control, whereby slower outer control loops regulate d- and q-axis current reference set point and inner faster current loops regulate the current to track the reference current.

4.3. Controller and Reactive Power Control Strategy of GSC

The GSC can be free from managing the DC-link voltage since ESS is responsible for the DC-link voltage regulation. The control strategy used in [23] is applied here to modify the active power outer loop of the GSC, where the output active power of DFIG is regulated to the command value that comes from the system operator. It can also provide a limited reactive power support. Normally, the reference reactive power can be set to zero for the unity power factor operation for economic operations. The overall vector control scheme of the GSC during the normal operation is shown in Figure 6.
Based on Equation (4), the relation between the currents of RSC ( i o r ), GSC ( i o s ), and ESS ( i b ) can be derived as:
i b = i o r i o s = i o r 3 m 2 2 i g d
where m is the factor of the PWM modulation depth.
It is known from (9) that the ESS maintains the DC-link voltage constant. This is also equivalent to regulate the current balance between i o r and i o s . If the controller of ESS is fast enough, the DC-link voltage can be kept constant even if i o s or i g d reduces to zero. This reserves considerable potential reactive current capacity for GSC to participate in the voltage support during voltage sags. Therefore, it is proposed that the GSC can be contributed to the voltage support by injecting 4% reactive current for 1% supply voltage drop when the supply voltage falls below 0.9 p.u. to satisfy the requirement of grid codes, while the residual current capacity of GSC is used to deliver the active current to the grid. Figure 7 shows the coordinated control strategy of i g q and i g d for GSC during grid fault under the rated power active production condition as this is the most onerous situation that can be experienced by a wind turbine. The control strategy with a slight modification can meet the regulation of the other scenario.
Three different operation stages are observed in Figure 7. In Stage I, i g d increases from the initial value of 0.17 p.u., while i g q maintains zero to deliver its rated active power at the unity power factor as the supply voltage drops from 1 p.u. to 0.9 p.u.. As the supply voltage continues to drop below 0.9 p.u. in Stage II, i g q starts to linearly increase from 0.4 p.u. by 4% for each 1% reduction in the supply voltage magnitude. i g d must decrease so that the grid current is constrained within the limits of semiconductor switches to ensure I G 1 . Consequently, the active power output of GSC is partially sacrificed for the sake of the reactive power injection. Finally, when the supply voltage drops to 0.75 p.u., i g q equals to 1.0 p.u. and i g d reduces to zero, which means the GSC acts as a reactive power source and the power flowing into the rotor circuit is completely absorbed by the ESS.
For the GSC, the dynamic response of the outer power control loop is slower than that of the inner current control loop [28]. Thus, a single inner current control loop is proposed to provide a fast initial reactive current injection following the voltage drop which can help fulfill dynamic demanding requirements.

4.4. Controller and Reactive Power Control Strategy of RSC

In the normal mode, the RSC is used to extract the maximum available wind power and regulate the stator voltage (reactive power) in a decoupled manner. Accordingly, the block diagrams of the controllers are presented in Figure 8, where dual-loop controls of torque-current and reactive power-current are applied in q- and d-axis, respectively.
The independent control of the stator active power ( P s ) and reactive powers ( Q s ) can be achieved through regulating the q-axis current ( i r q ) and d-axis current ( i r d ) of rotor current, given by:
P s = V s × i r q Q s = V s i r d V s 2 ω 1 L s
Normally, i r q equals to 75% of the current capacity of the RSC when DFIG extracts rated power at the unity power factor, and P s can be kept constant by increasing i r q to compensate the voltage dip during fault conditions. Therefore, it is proposed here as shown in Figure 8 that the DFIG works at the rated power production when the magnitude of voltage remains between 0.75 p.u. and 1 p.u..
When the voltage drops below 0.75 p.u., the output power of the stator is seriously decreased since the current of RSC reaches its limitation. This leads to a significantly instantaneous imbalance power between the incoming power from the wind and the power flowing into the grid. It has been analyzed above that the key point to realize the LVRT is to reduce the imbalance power flocking into the DFIG during grid faults. The imbalance power can be reduced by decreasing the captured wind power, which can be achieved by increasing the generator speed to make the operation mode of DFIG shift to the non-optimal operation.
The electrical torque T e can be expressed as a function of q-axis current of RSC as shown in Figure 8, given by:
T e = L m Ψ s L s i r q
One can easily deduce that the reduction of electrical torque can be obtained by reducing the active current ( i r q ). The imbalance torque between the electrical torque T e and the mechanical torque T m causes the acceleration of the generator speed and consequently reduces the captured wind power. Besides, the increase of the rotor speed converts the partial wind energy into the rotor kinetic energy, which further reduces the imbalance power flow through the DFIG. Therefore, the transient over-current is not induced. DFIG can keep the continuous operation during gird faults. Moreover, the reduction of the i r q during fault condition reserves considerable potential reactive power capacity for the RSC to participate in the voltage control. It further enhances the voltage support capability of GSC which is limited as the voltage drops to a low value.
In order to meet the reactive power requirement by the stringent grid code, the RSC changes into the reactive current priority where the i r d increases by 4% for 1% drop of the supply voltage amplitude while i r q is reduced to make the rotor current constrained within the limits of the RSC. A single control loop is also applied for RSC to make a fast response. The block diagrams of RSC controllers during the fault transient are shown in Figure 9.
It can been seen from Figure 8 that the active power reduces to zero as the supply voltage drops to 0.5 p.u. and consequently T e also reduces to zero which causes the over-speed of the generator rotor and over-current in the stator after the fault clearance. This problem is addressed in the flowing subsection.

4.5. Pitch Angle Controller

Based on Equation (6), the relation between the angular rotor speed, the captured wind power, and output power of DFIG can be obtained:
ω r 2 = 2 J P w P g d t
This formulation shows that the generator speed decreases due to the decrease of P w . Compared to the generator speed, the increase of pitch angle has a more significant impact on the reduction of aerodynamic power extraction. Generally, the mechanical servo system is able to change the pitch angle of the blades at a rate around 10 / sec [31]. This indicates that the pitch angle can be only altered several degrees during the grid fault transient (0.6–1s). For a given wind speed, if the blade pitch angle increases from 0 degrees to 10 degrees, the power coefficient drops from 0.48 to around 0.20 in a second. Consequently, the captured wind power decreases around 30% [32].
For the conventional PI controller, the wind turbine blade pitch angle is not controlled until the upper generator speed or rated power is reached. Therefore, it cannot effectively help in the reduction of the captured wind power. It can be seen from Equation (12) that if the captured wind power is reduced as soon as possible, the maximum generator speed will be significantly decreased. Consequently, the maximum generator speed and the over-current after fault clearance are seriously suppressed. Therefore, an auxiliary improved pitch angle controller (as shown in Figure 10) is proposed. For this improved pitch angle controller, the turbine blade pitch angle is controlled at the instant of voltage dips, when the generator speed is below the rated speed.
The switcher works at position 1 in the normal operation to prevent over-rated power production under high speed winds. As the amplitude of the supply voltage is below a certain threshold (0.5 p.u.), the fault controller is triggered to change the switcher to position 2. Thus, the pitch angle increases at the maximum rate to the desired value which is obtained from the zero power block storing the pitch angle values corresponding to zero power output of the turbine over the whole range of wind speeds.

5. Case Studies

In this section, simulations are carried out on a single-machine-infinite-bus system (as shown in Figure 11) with a 1.5 MW DFIG based wind farm to validate the proposed method in enhancing the LVRT capability of the DFIG as well as supporting the terminal voltage during grid faults. Three different cases are studied as follows:
Case 1: examining the LVRT capability of the DFIG-ESS with the proposed control strategy during serious balanced voltage drops.
Case 2: evaluating the reactive power support capability of the DFIG-ESS during serious unbalanced voltage drops.
Case 3: evaluating the maximum power production of the DFIG-ESS during low-level voltage dips.
Case 4: investigating the reactive power support capability of DFIG-ESS during medium-level voltage dips.

5.1. Case 1: LVRT Capabilities of DFIG With Serious Balanced Voltage Drops

Besides the case where the proposed method (Method A) is used, the conventional crowbar protection (Method B) is also employed during grid faults to give comprehensive comparisons. For the crowbar protection, the resistor is chosen to be 0.5 p.u.. The crowbar threshold is set to 1.5 times of the rated current. Note that the DC-chopper which is usually installed with the crowbar circuit in the method B is not used here, in order to investigate the capability of the ESS in controlling the DC-link voltage.
The RSC is controlled to extract the rated power and maintain zero reactive power output of the stator during the normal operation, which is corresponding to the super-synchronous operation mode of DFIG. A three-phase 85% supply voltage drop of 625 ms duration is assumed to occur at Bus B at t = 2 s.
The transient behaviors of the DFIG with two different control strategies A and B with serious balanced voltage drops are depicted in Figure 12. It is observed that the transient behaviors in the case of Method A are better than those in the case of Method B. The rotor current and DC-link are suppressed below the crowbar threshold with Method A (see Figure 12a,f). The DFIG can keep the continuous operation without the interruption of the crowbar and participate into the voltage support by injecting the reactive power to the grid (see Figure 12c,e). However, the DFIG with Method A starts to draw the reactive power from the grid (see Figure 12c). This reactive power consumed by the DFIG further reduces the voltage of the DFIG stator terminals (0.1 p.u. as shown in Figure 12a). This is not acceptable when considering the grid codes [11]. Moreover, Method A can response much faster to increase the pitch angle than Method B. It indicates less unbalance power flow into rotor and less power stored in the rotor inertia energy. Consequently, the voltage on RSC, the maximum generator speed, and stator and rotor current after fault clearance in Method A are less than those in Method B.
The comparative analysis is investigated to evaluate the effectiveness of the X / R ratio of the 220 kV/500 kV transmission grid on the transient voltage support capability of DFIG by using the proposed control strategy. Table 1 compares the improvements of voltage profiles at bus D with different X / R ratios of the external grid impedance. As can be observed in Table 1, the voltage improvement at bus D increases to a high level with the X / R ratio at the fixed reactive power output of DFIG. Hence, the proposed control strategy of DFIG has a positive impact on the voltage improvement of the transmission grid during the fault period.

5.2. Case 2: Reactive Power Support Capabilities of DFIG With Serious Unbalanced Voltage Drops

This simulation case is performed to further verify the LVRT and reactive power support capabilities of DFIG by using the proposed control strategy. The LVRT capability of the fixed-speed induction generator (FSIG) nearby the DFIG is improved when the unbalanced serious voltage drop occurs. In Figure 11, a 1.5 MW FSIG is connected at bus B and the DFIG in this case presents a 12 MW wind farm. Under the normal operation, the FSIG speed is set as 1.01 p.u. with the active power output 0.4 p.u. and the reactive power absorption capability of 0.17 p.u. At time t = 7 s, a two-phase ground short circuit fault occurs with the duration of 300 ms at bus B. The voltage drops to about 0.6 p.u. The simulated transient behaviors of the FSIG when the DFIG-based wind farm is controlled by the proposed control strategy (Method A) are compared with those when the DFIG-based wind farm is controlled by the conventional design strategy (Method B), as shown Figure 13.
In Figure 13, the DFIG-based wind farm can deliver about 1.86 p.u. reactive power to the grid by using Method A, while the DFIG-based wind farm absorbs approximately 0.35 p.u. by using Method B [see Figure 13c]. Consequently, the terminal voltage with Method A is higher than that with Method B during the unbalanced grid faults [see Figure 13a]. The generator speed with Method B accelerates faster than that with Method A due to the larger torque difference between the electrical torque and mechanical torque [see Figure 13d–f]. It is observed the terminal voltage with Method B remains relatively low because of the high reactive power consumption by the FSIG after the fault [see Figure 13b]. Consequently, the electrical torque of FSIG is always smaller than the mechanical torque, and its speed continues to increase, which makes the voltage collapse [see Figure 13f]. Finally, the FSIG fails to ride through the unbalanced fault when the DFIG is controlled by Method B without the reactive power support during the fault period. In contrast, due to the lower acceleration of the generator speed and the higher initial voltage recovery with Method A, the electrical torque is larger than the mechanical torque [see Figure 13f]. Thus, the generator speed starts to decrease [see Figure 13d]. As a result, both the generator speed and terminal voltage of the FSIG [see Figure 13a] restore to the prefault values when the fault is cleared.

5.3. Case 3: Maximum Power Production of DFIG-ESS During Fault Period

This case is developed to assess the maximum power producing capability of the DFIG-ESS during fault period. The operation condition is the same as that in the previous case. The fault remnant voltage drops to 0.8 p.u. at t = 1.0 s.
The simulated responses of the DFIG-ESS with the proposed maximum power producing control strategy are shown in Figure 14. As the fault takes place, i r q increases from 0.83 p.u. to 1.02 p.u. to maximum the active power that can be exported from the DFIG to the grid. The excitation current i r d reduces from 0.33 p.u. to 0.27 p.u. since the supply voltage drops (see Figure 14c). The current of RSC is constrained within the current limitation (1.14 p.u.). Moreover, the electromagnetic torque is kept constant due to the increase of i r q . The generator speed does not accelerate during this period (see Figure 14d). In order to satisfy the grid codes requirement, the GSC injects 0.21 p.u. reactive current to the gird which accounts for 80% of the capacity of GSC. The active current of GSC reduces from 0.17 p.u. to 0.15 p.u.. Hence, the current carrying capacity of GSC does not exceed. Accordingly, the output active power of the GSC decreases from 0.17 p.u. to 0.13 p.u.. The reduction of the output power of GSC is quickly absorbed by the ESS in Figure 14d, which keeps the DC-link voltage stable (see Figure 14e).

5.4. Case 4: Reactive Power Support Capability of DFIG-ESS During Voltage Dips

This simulation test is used to further verify the reactive power support capability of DFIG-ESS during grid voltage sags. The operations of the RSC and GSC are the same as those in Case 2, and 625ms three phase fault with remnant voltage of 0.6 p.u. occurs on bus B. Figure 15 shows the system response of the DFIG-ESS with the reactive power support priority scheme.
Figure 15b shows the reactive power priority of the DFIG-ESS during voltage dips. It is obvious that the priority of the RSC gives the reactive current to support the supply voltage recovery upon the fault occurs. The reactive current increases from 0.33 p.u. to 0.90 p.u., while the active current decreases from 0.83 p.u. to 0.70 p.u.. The current of RSC is constrained within its limitation. As a result, the reactive power increases to 0.45 p.u. while the active power reduces from 0.83 p.u. to 0.45 p.u. (see Figure 15c). The reduction of active current causes the decrease of the electromagnetic torque, which results in the gradual increase of rotor speed from 1.20 to 1.22 p.u.. However, this is not serious. Furthermore, the GSC is acted as a reactive power source to boost the supply voltage (see Figure 15f,g), since the rotor power can be handled by the ESS (see Figure 15e).
Generally, the improvement of Method A in the nadir part of the voltage is very limited when the wind farm is simulated by only one DFIG. The provided reactive power is limited (see Figure 15a). However, it is very clear from Figure 15j that such voltage enhancement becomes increasingly obvious as the number of the DFIG in the wind farm increases. Therefore, the promising prospects of applying the proposed method to large scale wind farms are confirmed for voltage support during the grid faults.

6. Conclusions

This paper developed a novel comprehensive control strategy to enhance the low voltage ride-through (LVRT) and reactive power support capacities of the doubly-fed induction generator (DFIG) by installing the energy storage system (ESS). The reactive power supporting capability was also adapted to different depth of voltage sags for the DFIG-ESS to improve the dynamic performance during the grid fault. The ESS was connected to the DC-link capacitor of the DFIG and used to regulate the DC-link voltage during normal or fault operations. The unbalanced power between the captured wind power and the power injected to the grid during the transient process was absorbed or compensated by the ESS. The rotor-side converter (RSC) was used to control the maximum power production and the grid-side converter (GSC) was used to control the reactive power before participating into the voltage support. An auxiliary transient pitch angle controller was also developed to protect the over speed of generator. Both RSC and GSC acted as reactive power sources to further enhance the voltage support capability with serious voltage sags. Simulations based on a single machine-infinite bus power system verified that:
  • The LVRT capability of the DFIG-ESS was significantly improved by the developed control strategy in this paper, compared to the conventional crowbar method.
  • The maximum power production of DFIG-ESS was enhanced when a fault occurred. The excitation current was reduced due to the decrease of the supply voltage.
  • The reactive power increased to 0.45 p.u. while the active power reduced from 0.83 p.u. to 0.45 p.u. The GSC acted as a reactive power source to boost the supply voltage.

Acknowledgments

This work was supported by the Science and Technology Program of State Grid Hunan Electric Power Company (5216A516002C).

Author Contributions

Yangwu Shen and Mingjian Cui conceived and designed the methodology; Yangwu Shen and Bin Zhang performed the case studies and analysis; Yangwu Shen, Qin Wang, Feifan Shen, and Liqing Liang wrote the paper.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Hu, Y.; Li, Y.; Xu, M.; Zhou, L.; Cui, M. A chance-constrained economic dispatch model in wind-thermal- energy storage system. Energies 2017, 10, 326. [Google Scholar] [CrossRef]
  2. Wang, Q.; Martinez-Anido, C.B.; Wu, H.; Florita, A.R.; Hodge, B.M. Quantifying the economic and grid reliability impacts of improved wind power forecasting. IEEE Trans. Sustain. Energy 2016, 7, 1525–1537. [Google Scholar] [CrossRef]
  3. Cui, M.; Ke, D.; Gan, D.; Sun, Y. Statistical scenarios forecasting method for wind power ramp events using modified neural networks. J. Mod. Power Syst. Clean Energy 2015, 3, 371–380. [Google Scholar] [CrossRef]
  4. Cui, M.; Ke, D.; Sun, Y.; Gan, D.; Zhang, J.; Hodge, B.-M. Wind power ramp event forecasting using a stochastic scenario generation method. IEEE Trans. Sustain. Energy 2015, 6, 422–433. [Google Scholar]
  5. Tsili, M.; Papathanassiou, S. A review of grid code technical requirements for wind farms. IET Renew. Power Gener. 2009, 3, 308. [Google Scholar] [CrossRef]
  6. Morren, J.; de Haan, S. Ridethrough of wind turbines with doubly-fed induction generator during a voltage dip. IEEE Trans. Energy Convers. 2005, 20, 435–441. [Google Scholar] [CrossRef]
  7. Mullane, A.; Lightbody, G.; Yacamini, R. Wind-turbine fault ride-through enhancement. IEEE Trans. Power Syst. 2005, 20, 1929–1937. [Google Scholar] [CrossRef]
  8. Kasem, A.; El-Saadany, E.; El-Tamaly, H.; Wahab, M. An improved fault ride-through strategy for doubly fed induction generator-based wind turbines. IET Renew. Power Gener. 2008, 2, 201–214. [Google Scholar] [CrossRef]
  9. Meegahapola, L.G.; Littler, T.; Flynn, D. Decoupled-DFIG Fault ride-through strategy for enhanced stability performance during grid faults. IEEE Trans. Sustain. Energy 2010, 1, 152–162. [Google Scholar] [CrossRef]
  10. Lima, F.; Luna, A.; Rodriguez, P.; Watanabe, E.; Blaabjerg, F. Rotor voltage dynamics in the doubly fed induction generator during grid faults. IEEE Trans. Power Electron. 2010, 25, 118–130. [Google Scholar] [CrossRef]
  11. Liang, J.; Qiao, W.; Harley, R.G. Feed-forward transient current control for low-voltage ride-through enhancement of DFIG wind turbines. IEEE Trans. Energy Conv. 2010, 25, 836–843. [Google Scholar] [CrossRef]
  12. Rahimi, M.; Parniani, M. Transient performance improvement of wind turbines with doubly fed induction generators using nonlinear control strategy. IEEE Trans. Energy Conv. 2010, 25, 514–525. [Google Scholar] [CrossRef]
  13. Mohseni, M.; Islam, S.M. Transient control of DFIG-based wind power plants in compliance with the Australian grid code. IEEE Trans. Power Electron. 2012, 27, 2813–2824. [Google Scholar] [CrossRef]
  14. Yang, L.; Xu, Z.; Ostergaard, J.; Dong, Z.Y.; Wong, K.P. Advanced control strategy of DFIG wind turbines for power system fault ride through. IEEE Trans. Power Syst. 2012, 27, 713–722. [Google Scholar] [CrossRef]
  15. Flannery, P.; Venkataramanan, G. A fault tolerant doubly fed induction generator wind turbine using a parallel grid side rectifier and series grid side converter. IEEE Trans. Power Electron. 2008, 23, 1126–1135. [Google Scholar] [CrossRef]
  16. Yao, J.; Li, H.; Chen, Z.; Xia, X.; Chen, X.; Li, Q.; Liao, Y. Enhanced control of a DFIG-based wind-power generation system with series grid-side converter under unbalanced grid voltage conditions. IEEE Trans. Power Electron. 2013, 28, 3167–3181. [Google Scholar] [CrossRef]
  17. Yan, X.; Venkataramanan, G.; Wang, Y.; Dong, Q.; Zhang, B. Grid-fault tolerant operation of a DFIG wind turbine generator using a passive resistance network. IEEE Trans. Power Electron. 2011, 26, 2896–2905. [Google Scholar] [CrossRef]
  18. Ibrahim, A.O.; Nguyen, T.H.; Lee, D.C.; Kim, S.C. A fault ride-through technique of DFIG wind turbine systems using dynamic voltage restorers. IEEE Trans. Energy Convers. 2011, 26, 871–882. [Google Scholar] [CrossRef]
  19. Guo, W.; Xiao, L.; Dai, S. Enhancing low-voltage ride-through capability and smoothing output power of DFIG with a superconducting fault-current limiter-magnetic energy storage system. IEEE Trans. Energy Convers. 2012, 27, 277–295. [Google Scholar] [CrossRef]
  20. Abbey, C.; Joos, G. Supercapacitor energy storage for wind energy applications. IEEE Trans. Ind. Appl. 2007, 43, 769–776. [Google Scholar] [CrossRef]
  21. Zhang, J.; Cui, M.; Fang, H.; He, Y. Smart charging of EVs in residential distribution systems using the extended iterative method. Energies 2016, 9, 985. [Google Scholar] [CrossRef]
  22. Zhang, J.; He, Y.; Cui, M.; Lu, Y. Primal dual interior point dynamic programming for coordinated charging of electric vehicles. J. Mod. Power Syst. Clean Energy 2016. [Google Scholar] [CrossRef]
  23. Mishra, Y.; Mishra, S.; Li, F. Coordinated tuning of DFIG-based wind turbines and batteries using bacteria foraging technique for maintaining constant grid power output. IEEE Syst. J. 2012, 6, 16–26. [Google Scholar] [CrossRef]
  24. Engelhardt, S.; Erlich, I.; Feltes, C.; Kretschmann, J.; Shewarega, F. Reactive power capability of wind turbines based on doubly fed induction generators. IEEE Trans. Energy Convers. 2011, 26, 364–372. [Google Scholar] [CrossRef]
  25. Konopinski, R.; Vijayan, P.; Ajjarapu, V. Extended reactive capability of DFIG wind parks for enhanced system performance. IEEE Trans. Power Syst. 2009, 24, 1346–1355. [Google Scholar] [CrossRef]
  26. Cartwright, P.; Holdsworth, L.; Ekanayake, J.; Jenkins, N. Co-ordinated voltage control strategy for a doubly-fed induction generator (DFIG)-based wind farm. IEE Proc. Gener. Trans. Distrib. 2004, 151, 495. [Google Scholar] [CrossRef]
  27. Kayk, M.; Milanovi, J.V. Reactive power control strategies for DFIG-based plants. IEEE Trans. Energy Convers. 2007, 22, 389–396. [Google Scholar] [CrossRef]
  28. Yao, J.; Li, H.; Liao, Y.; Chen, Z. An improved control strategy of limiting the DC-link voltage fluctuation for a doubly fed induction wind generator. IEEE Trans. Power Electron. 2008, 23, 1205–1213. [Google Scholar]
  29. Foster, S.; Xu, L.; Fox, B. Coordinated reactive power control for facilitating fault ride through of doubly fed induction generator- and fixed speed induction generator-based wind farms. IET Renew. Power Gener. 2010, 4, 128. [Google Scholar] [CrossRef]
  30. Xiao, S.; Yang, G.; Zhou, H.; Geng, H. An LVRT control strategy based on flux linkage tracking for DFIG-based WECS. IEEE Trans. Ind. Electron. 2013, 60, 2820–2832. [Google Scholar] [CrossRef]
  31. Sun, T.; Chen, Z.; Blaabjerg, F. Flicker study on variable speed wind turbines with doubly fed induction generators. IEEE Trans. Energy Convers. 2005, 20, 896–905. [Google Scholar] [CrossRef]
  32. Kamel, R.M.; Chaouachi, A.; Nagasaka, K. Three control strategies to improve the microgrid transient dynamic response during isolated mode: A comparative study. IEEE Trans. Ind. Electron. 2013, 60, 1314–1322. [Google Scholar] [CrossRef]
Figure 1. Structure of the doubly-fed induction generator (DFIG)-energy storage system (ESS).
Figure 1. Structure of the doubly-fed induction generator (DFIG)-energy storage system (ESS).
Energies 10 00808 g001
Figure 2. A typical C p curve of DFIG.
Figure 2. A typical C p curve of DFIG.
Energies 10 00808 g002
Figure 3. Flow chart of the integrated low voltage ride-through (LVRT) and enhanced reactive power support scheme.
Figure 3. Flow chart of the integrated low voltage ride-through (LVRT) and enhanced reactive power support scheme.
Energies 10 00808 g003
Figure 4. Block diagram of the fast identification algorithm.
Figure 4. Block diagram of the fast identification algorithm.
Energies 10 00808 g004
Figure 5. Configuration and control block diagram of the bidirectional buck-boost DC/DC converter.
Figure 5. Configuration and control block diagram of the bidirectional buck-boost DC/DC converter.
Energies 10 00808 g005
Figure 6. Controllers of grid-side converter (GSC).
Figure 6. Controllers of grid-side converter (GSC).
Energies 10 00808 g006
Figure 7. The coordinated active and reactive current control strategy of GSC.
Figure 7. The coordinated active and reactive current control strategy of GSC.
Energies 10 00808 g007
Figure 8. Controllers of rotor-side converter (RSC).
Figure 8. Controllers of rotor-side converter (RSC).
Energies 10 00808 g008
Figure 9. The coordinated control strategy of the active and reactive current of RSC.
Figure 9. The coordinated control strategy of the active and reactive current of RSC.
Energies 10 00808 g009
Figure 10. Improved pitch angle controller.
Figure 10. Improved pitch angle controller.
Energies 10 00808 g010
Figure 11. Schematic diagram of the test system.
Figure 11. Schematic diagram of the test system.
Energies 10 00808 g011
Figure 12. Transient responses of the DFIG-ESS with Method A and B with serious balanced voltage drops: (a) terminal voltage; (b) rotor current; (c) reactive power output of the stator; (d) reactive current of the GSC; (e) total reactive power output of the DFIG; (f) DC-link voltage; (g) pitch angle; (h) rotor speed; (i) voltage of the RSC; and (j) active power of the ESS.
Figure 12. Transient responses of the DFIG-ESS with Method A and B with serious balanced voltage drops: (a) terminal voltage; (b) rotor current; (c) reactive power output of the stator; (d) reactive current of the GSC; (e) total reactive power output of the DFIG; (f) DC-link voltage; (g) pitch angle; (h) rotor speed; (i) voltage of the RSC; and (j) active power of the ESS.
Energies 10 00808 g012
Figure 13. Impacts of the reactive power support capability of DFIG-ESS to nearby FSIG-based wind farms during serious unbalanced voltage drops: (a) terminal voltage; (b) output reactive power of FSIG; (c) output reactive power of DFIG-ESS; (d) generator speed of FSIG; (e) electromagnetic torque and mechanical torque of FSIG with Method A; and (f) electromagnetic torque and mechanical torque of FSIG with Method B.
Figure 13. Impacts of the reactive power support capability of DFIG-ESS to nearby FSIG-based wind farms during serious unbalanced voltage drops: (a) terminal voltage; (b) output reactive power of FSIG; (c) output reactive power of DFIG-ESS; (d) generator speed of FSIG; (e) electromagnetic torque and mechanical torque of FSIG with Method A; and (f) electromagnetic torque and mechanical torque of FSIG with Method B.
Energies 10 00808 g013
Figure 14. Maximum power production of the DFIG-ESS during voltage dips: (a) terminal voltage; (b) current of RSC; (c) output power of the stator; (d) generator speed; (e) DC-link voltage; (f) active power of the ESS; (g) current of GSC; and (h) output power of the GSC.
Figure 14. Maximum power production of the DFIG-ESS during voltage dips: (a) terminal voltage; (b) current of RSC; (c) output power of the stator; (d) generator speed; (e) DC-link voltage; (f) active power of the ESS; (g) current of GSC; and (h) output power of the GSC.
Energies 10 00808 g014
Figure 15. Reactive power priority of the DFIG-ESS during voltage dips: (a) terminal voltage; (b) current of RSC; (c) output power of the stator; (d) electromagnetic and mechanical torques; (e) generator speed; (f) active power of the ESS; (g) current of GSC; (h) output power of the GSC; (i) DC-link voltage; and (j) terminal voltage with different amount of DFIG.
Figure 15. Reactive power priority of the DFIG-ESS during voltage dips: (a) terminal voltage; (b) current of RSC; (c) output power of the stator; (d) electromagnetic and mechanical torques; (e) generator speed; (f) active power of the ESS; (g) current of GSC; (h) output power of the GSC; (i) DC-link voltage; and (j) terminal voltage with different amount of DFIG.
Energies 10 00808 g015
Table 1. Voltage improvements at bus D with different X / R ratios of external grid impedance.
Table 1. Voltage improvements at bus D with different X / R ratios of external grid impedance.
X / R ratios of external grid impedance5.56.57.58.5
Voltage improvements at bus D (p.u.)0.0520.0600.0720.092

Share and Cite

MDPI and ACS Style

Shen, Y.; Cui, M.; Wang, Q.; Shen, F.; Zhang, B.; Liang, L. Comprehensive Reactive Power Support of DFIG Adapted to Different Depth of Voltage Sags. Energies 2017, 10, 808. https://doi.org/10.3390/en10060808

AMA Style

Shen Y, Cui M, Wang Q, Shen F, Zhang B, Liang L. Comprehensive Reactive Power Support of DFIG Adapted to Different Depth of Voltage Sags. Energies. 2017; 10(6):808. https://doi.org/10.3390/en10060808

Chicago/Turabian Style

Shen, Yangwu, Mingjian Cui, Qin Wang, Feifan Shen, Bin Zhang, and Liqing Liang. 2017. "Comprehensive Reactive Power Support of DFIG Adapted to Different Depth of Voltage Sags" Energies 10, no. 6: 808. https://doi.org/10.3390/en10060808

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop