TRACE — Supplementary Materials | Revision R1 v05 | Energies, manuscript energies-4680020
Manuscript title: Waste Heat Recovery Limits for Energy-Efficient Climate Control in Mobile Working Machines
Corresponding author: Karol Durczak

PACKAGE CONTENTS (matching the manuscript TRACE_Energies_R1_v05.docx)
Table S1 — S1_Provenance/Table_S1_Source_settings_and_evidence_labels.csv
    64 test identifiers, published regeneration inlet setpoints, evidence provenance and matching status.
Table S2 — S2_Psychrometrics/Table_S2_Derived_psychrometric_descriptors.csv
    Reconstructed process/regeneration diagnostics for 64 cases; not measured cabin cooling power or a closed wheel balance.
Table S3 — S3_Regeneration/Table_S3_Conditional_heating_requirements.csv
    64 nominal 60 C calculated coil demands and conditional bounds for the 30 exact matches.
Table S4 — S3_Regeneration/Table_S4_External_test_T6_intervals.csv
    Four regeneration outlet-temperature intervals from experiments separate from the original 64 cases.
Table S5 — S4_Reproduction/Table_S5_Descriptive_summary_audit.csv
    Recalculated descriptive summaries.
Table S6 — S3_Regeneration/Table_S6_Figure6_exact_30_matched_tests.csv
    Figure 6 source values for exactly 30 matched tests (nominal markers and external-temperature scenario segments).
Table S7 — S4_Reproduction/Table_S7_Figure7_schematic_conditions.csv
    Figure 7 conceptual screening inequalities; NOT measured engine operating points.
Table S8 — S4_Reproduction/Table_S8_Balance_diagnostics.csv
    64-case moisture-indicator ratios and state-5-to-7 versus state-5-to-6 power comparisons.
Table S9 — S4_Reproduction/Table_S9_Hypothetical_joint_perturbation_envelopes.csv
    64 illustrative, simultaneous lower/upper input-perturbation scenarios; NOT confidence/coverage intervals.
Figure 3 — S2_Psychrometrics/Figure_3_Psychrometric_64_points.png
    Psychrometric plot: observed workbook states and separate published regeneration-inlet settings. State 6 is not plotted.
Code S1 — S4_Reproduction/Code_S1_Recalculate_TRACE.py
    Reproduce nominal heating calculations and matched conditional temperature intervals.
Code S2 — S4_Reproduction/Code_S2_Hypothetical_Sensitivity.py
    Additional sensitivity demonstration for Table S9. Code S2 supplements but does not replace Code S1.
SHA256_manifest.csv — file integrity hashes for all files except the manifest itself.

RUNNING THE CODE
From the extracted ZIP root:
    python S4_Reproduction/Code_S1_Recalculate_TRACE.py
    python S4_Reproduction/Code_S2_Hypothetical_Sensitivity.py
Code S1 uses Python 3 and pandas; Code S2 uses only Python's standard library. Input datasets are included in this archive.

SCIENTIFIC AND EVIDENCE QUALIFICATIONS
- Original source: Romero-Lara et al., Energy Conversion and Management 310 (2024) 118486, DOI: 10.1016/j.enconman.2024.118486.
- The original RACU workbook, paper PDF, and private correspondence are NOT included in this archive. Source-data redistribution permission has not been established. Derived test-level records also require provider/author rights review before public publisher deposit.
- All 64 source workbook records were checked in manuscript revision R1 v05; the regeneration-inlet temperature/humidity columns in that workbook are blank. Regeneration inlet values in these tables were obtained from published settings, not simultaneous state-5 measurements.
- The heating-coil outlet temperature T6 was not measured individually in the original 64 tests. T6 = 60 C is a nominal assumption. The intervals from separate experiments were assigned to 30 records only where both published T5 and w5 exactly matched; the other 34 were not extrapolated.
- Volumetric flows were reported as steady-state measured actual flows. Dry-air mass flow reconstruction uses the assumed air state at the volumetric section and reference pressure 101.325 kPa; those instrument-section conditions were not independently verified.
- A source-side engine installation, actual recovered heat, fuel savings, COP improvements, dynamic duty cycles, complete wheel balances and actual heater-water-side powers were NOT measured in these data.
- Table S8 comparisons are diagnostic consistency flags, not proof of conservation-law violations: they do not form a fully instrumented four-port wheel balance.
- Table S9 input perturbations assume p +/-1 kPa, airflow +/-5%, T5 +/-1 C, w5 +/-0.001 kg/kg, T6 +/-2 C. They are hypothetical and NOT a calibrated GUM uncertainty budget, nor 95% statistical intervals.
- Under T6=T5, a zero calculated heating requirement does not establish effective desiccant regeneration.
- The 64 operating points are experimental conditions, not 64 independent measurement replicates; descriptive min/median/max are not confidence bounds.

MANUSCRIPT ALIGNMENT
Main Figures 1-2 are conceptual; Figure 3 is psychrometric; Figure 4 is process diagnostics; Figure 5 is nominal heating requirements; Figure 6 uses Table S6; Figure 7 uses Table S7.
The manuscript refers to Tables S1-S9 and Code S1. Code S2 is provided for additional transparency of hypothetical sensitivities.

DATA RIGHTS / APPROVAL
This bundle is prepared for co-author review and possible resubmission. Before an unrestricted publisher upload, confirm authorization for distribution of derived test-level data with the original research-team data provider and obtain required co-author approval.