Development and Calibration of a Multizone CONTAM Model for Indoor PM2.5 Dynamics in Central Asian Social Housing Under High Ambient Pollution
by
Mainur Kurmanbekova
Mainur Kurmanbekova
,
Jiangtao Du
Jiangtao Du *
and
Steve Sharples
Steve Sharples
School of Architecture, University of Liverpool, Liverpool L69 7ZN, UK
*
Author to whom correspondence should be addressed.
Submission received: 3 September 2026
/
Revised: 30 September 2026
/
Accepted: 1 October 2026
/
Published: 3 October 2026
Featured Application
The calibrated model can evaluate retrofit and ventilation strategies to reduce indoor PM2.5 exposure in the studied social housing apartment and, with appropriate adaptation and calibration, in similar polluted urban settings.
Abstract
Indoor air quality in Central Asian social housing remains understudied despite high ambient air pollution and growing concern over housing-related health inequalities. This study developed and calibrated a multizone CONTAM model to simulate hourly indoor PM2.5 dynamics in a representative, naturally ventilated, occupied social housing apartment in Almaty, Kazakhstan, during the winter heating season. The model included measured outdoor PM2.5 concentrations, local meteorological data, construction drawings, literature-derived leakage values, and occupancy schedules based on household interviews. Calibration was performed iteratively across 360 model versions, and performance was evaluated using ASTM D5157-19 model-evaluation criteria. The final calibrated model met NMSE and FB (NMSE = 0.21, FB = 0.08) criteria with FS just outside the |FS| ≤ 0.50 limit (FS = −0.51), but not the correlation, slope or intercept criteria (r = 0.86, M = 0.66, b = 43% of the mean observed concentration). Baseline simulations showed significant spatial and seasonal variation in PM2.5 concentrations. During winter, simulated average PM2.5 concentrations were 41.81 µg/m3 in the living room and 220.59 µg/m3 in the kitchen, with cooking peaks exceeding 1000 µg/m3. Warmer season simulations indicated weaker stack-driven ventilation and greater interzonal pollutant transfer. These findings show that calibrated multizone modelling can characterize PM2.5 transport in occupied social housing and provide a basis for evaluating retrofit and policy interventions to reduce PM2.5 exposure among vulnerable populations.
Share and Cite
MDPI and ACS Style
Kurmanbekova, M.; Du, J.; Sharples, S.
Development and Calibration of a Multizone CONTAM Model for Indoor PM2.5 Dynamics in Central Asian Social Housing Under High Ambient Pollution. Appl. Sci. 2026, 16, 9829.
https://doi.org/10.3390/app16199829
AMA Style
Kurmanbekova M, Du J, Sharples S.
Development and Calibration of a Multizone CONTAM Model for Indoor PM2.5 Dynamics in Central Asian Social Housing Under High Ambient Pollution. Applied Sciences. 2026; 16(19):9829.
https://doi.org/10.3390/app16199829
Chicago/Turabian Style
Kurmanbekova, Mainur, Jiangtao Du, and Steve Sharples.
2026. "Development and Calibration of a Multizone CONTAM Model for Indoor PM2.5 Dynamics in Central Asian Social Housing Under High Ambient Pollution" Applied Sciences 16, no. 19: 9829.
https://doi.org/10.3390/app16199829
APA Style
Kurmanbekova, M., Du, J., & Sharples, S.
(2026). Development and Calibration of a Multizone CONTAM Model for Indoor PM2.5 Dynamics in Central Asian Social Housing Under High Ambient Pollution. Applied Sciences, 16(19), 9829.
https://doi.org/10.3390/app16199829
Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details
here.
Article Metrics
Article Access Statistics
For more information on the journal statistics, click
here.
Multiple requests from the same IP address are counted as one view.